Vous êtes sur la page 1sur 9

ambient temperature, the load cycle, and

especially the degree of dirt, moisture, vibra-


tion, etc. The use of the law is rather in
Determination of Temperature Rise
estimating the effect of a temperature
change on insulation life, found by experi-
ence in particular conditions, than in esti- of Induction Motors
mating the life under totally new conditions.
Answering Mr. Wallau's statement that
our curve B, figure 1, is not an exact repre-
sentation of Mr. Montsinger's 1930 test
E. R. SUMMERS
ASSOCIATE AlEE
data, the curve does represent an over-all
a verage of experience, of which the particu-
lar tests reported by Mr. Montsinger are
only a part. The important conclusion is Synopsis: The American Standards for
H
The objects of this paper are (1) to
that the 105-degree-centigrade limiting hot- Rotating Electrical Machinery" (American
suggest revision of the present induction-
spot temperature for class A insulation has Standards Association) prescribe that the
temperature rise of motors shall be meas- motor standards to place temperature
been found generally satisfactory in indus-
trial service. ured by the thermometer method for measurements on a better basis, (2)
In reply to Mr. Kilgore's comment, the purposes of rating. Definite limiting values to present test data which illustrate the
curves in the paper are intended only to of temperature rise are established for each need for and justification of these revi-
cover general-purpose motors-that is, type of machine. The AlEE Standards
No. 1 fix conventional allowances of 15 sions, and (3) to suggest new temperature
200 horsepower and smaller at 450 rpm and
degrees centigrade, 10 degrees centigrade, ratings of motors on basis of using the
higher speeds. The starting torques are
assumed to correspond to the NEMA stand- and 5 degrees centigrade between the actual resistance method of determining tem-
ard of 150 per cent of full load torque for hottest-spot temperature and the highest perature rise.
four-pole motors. The 180 per cent value observable value of temperature as deter- AlEE Standards No. 1 dated April
for the 25-horsepower motor shown in figure mined by thermometer, resistance, and
embedded-detector methods, respectively. 1925) recognize three fundamental meth-
3 provides a reasonable margin over this 150
per cent guaranteed figure. This paper presents information on the ods of temperature determination which
Mr. Veinott points out the wide variation relations between the measured values of are defined respectively as the thermome-
in starting-current requirements of differ- temperature rise by different methods as ter, resistance, and embedded-detector
ent power companies and emphasizes the found in tests on several hundred induction
motors ranging from 10 to 1,000 horsepower
methods. Rules governing the inter-
importance of having such adequate stand- pretation of these different methods are
ards that the motor name-plate conveys a in rating. It is shown that, with modem
definite description of the motor's perform- motor construction, variations of 20 degrees quoted from paragraph 1-7 of the stand-
ance. This is very pertinent, as, under centigrade or more are sometimes obtained ards:
present conditions, many small motors are by the thermometer method on a given ma-
operated at loads greatly in excess of their chine depending on location of thermome- 1-7 Limiting Observable Temperatures
name-plate values, and this leads to a great ters or thermocouples, whereas the re- and Conventional Allowances. Limiting
deal of uncertainty about the proper control sistance measurements give relatively con- "observable" temperatures are deducted
and wiring. sistent values of temperature rise. from the limiting "hottest-spot" tempera-
There are two possible ways of procedure. It is therefore suggested that the stand- tures by subtracting therefrom a specified
One is to have a great number of special ards for temperature-rise measurements be number of degrees which, FOR PURPOSES
motors designed for particular services, revised, and that the resistance method be OF STANDARDIZATION, is the margin fixed
each with a name-plate horsepower and time adopted for all forms of enclosed or pro- between the limiting hottest spot and the
period of rating exactly representative of the tected machines which are not readily limiting observable temperatures.
expected motor performance. Such motors accessible for application of thermometers
on laminations, insulated windings, and This margin is designated as the uCONVEN-
would naturally have a low ratio of maxi- TIONAL ALLOWANCE."
mum to full-load torque and would have a other adjacent parts.
relatively low starting current per rated The specified differences (which may be
horsepower. The other procedure is to have designated the "Conventional Allowances")
a limited number of special motors of the by which the "observable" temperatures

T
foregoing closely rated types, and in addition E M P E R AT UR E rise is more fre- are, FOR PURPOSES OF STANDARDIZATION,
to have a standard general-purpose type of quently a limiting feature than is any assumed to be lower than the "hottest-spot"
motor suitable for operating under anyone temperatures, are as follows:
other single motor characteristic in de-
of a wide range of conditions. Such general- Thermometer Method-
purpose motors, however, would naturally termining the maximum horsepower rat-
15 degrees centigrade
be used at widely different values of horse- ings that may be obtained from a given
Resistance Method-
power, depending on the intermittency of induction-motor frame size. Depend- 10 degrees centigrade
load, the ambient temperature, the desired able heating data are of primary im-
life, and other conditions. If such motors Embedded-Detector Method~
portance) because the probable length of 5 degrees centigrade
are used, it is logical to give them a single
conservative rating, representing the output insulation life diminishes rapidly at ex-
the motor can always be relied upon to de- cessive winding temperatures. Proce- On the basis of the standard 105-
liver under severe conditions; and, in this dures for obtaining motor temperature degree-centigrade limiting "hottest-spot"
case, such motors will have relatively high measurements are not well standardized temperature, the maximum "observable"
starting and breakdown torques, high start- temperature must not exceed 90 degrees
ing currents, and considerable overload at the present time, and the reliability of
ability, which will be used in many applica- heating data cannot be satisfactorily centigrade by thermometer for class A
tions. The permissible starting current evaluated unless the fidelity and accu- insulation; and from this were derived
should, therefore, be based on the service- racy of testing methods are known. the present limiting ratings of 50 degrees
factor rating of the general-purpose motor, centigrade rise by thermometer above
to be consistent with the rules for closely Paper number 39-3, recommended by the AlEE the standard 40 degrees centigrade am-
rated special-purpose motors. committee on electrical machinery, and presented
In conclusion, I wish to point out again at the AlEE winter convention. New York, N. Y., bient for special-purpose open motors,
January 23-27, 1939. Manuscript submitted
that this paper is intended to give a better October 21, 1938; made available for preptinting
and 40 degrees centigrade rise combined
understanding of the range of possible ap- November 25, 1938. with a 1.15 service factor for general-
plication of a standard general-purpose E. R. SUMMERS is in the induction-motor depart- purpose open motors. The "conven-
motor which, without change in name plate, ment of the General Electric Company, Schenec-
is admirably fitted to a wide range of uses. tady, N. Y.
tional allowances" for "hottest-spots"

SEPTEMBER 1939. VOL. 58 Summers-Determination of Temperature Rise TRANSACTIONS 459


standards approved on January 6, 1936 tion which either reduces or eliminates
(subsequently to adoption of AlEE entirely the accessibility of internal parts
Standards No.1) specifies that all tem- as illustrated by figure 1.
peratures of induction motors shall be To clarify this unsatisfactory situa-
determined by thermometer method. tion with respect to temperature meas-
ASA rules 2.055 and 2.063 relative to urements, testing methods should be
thermometer method are as follows: modified in accordance with changes in
motor construction, so that comparable
2.055-Thermometer Method of Temperature
'Determination Defined. This method con- results may be obtained when the same
sists in the determination of the tempera- machine is tested by two different or-
(1\)
ture by mercury or alcohol thermometers, ganizations. This paper recommends
by resistance thermometers, or by thermo- general recognition, adoption, and stand-
couples, any of these instruments being ardization of the resistance method.
applied to the hottest part of the machine
accessible to mercury or alcohol thermome- Results of many tests are presented to
ters. prove that the winding resistance gives a
2.063-Measurement of Machine Tempera- more reliable indication of actual insula-
tures. As far as practicable, temperature tion temperature than measurements
measurements shall be taken during the test, made with thermometers.
without making any change in the machine
which will affect the results, as well as im-
mediately after shutdown. The tempera- Some Specific Situations for Which
ture of totally enclosed motors (including the Present ASA Standards Are
totally enclosed fan-cooled motors) shall Inadequate
be obtained after shutdown by applying
the thermometer to the hottest part of the Specific test results and situations are
machine which can be made quickly ac-
cessible by removing covers. If the core presented to illustrate the inadequacy
and windings are not accessible such as in of the present ASA standards relative
(8) totally enclosed or totally enclosed fan- to heating tests.
cooled motors, holes must be provided
through any intervening structural parts to
permit the application of the thermometer 1. TOTALLY ENCLOSED

method. FAN-COOLED MOTORS

The highest measurements obtained shall Reliable winding temperature data


be the accepted values, usually are not obtained by thermome-
ters inserted through holes bored in the
The location of the hottest observable frame of an enclosed motor as directed by
point in a motor actually depends on a ASA rule 2.063.
number of factors such as the enclosing A test made on the totally enclosed
features if any, type of winding and insu- fan-cooled motor designated as X in
lation treatment, arrangement of fans appendix I and table I , where the stator
and air deflectors, number and size of winding was explored by placing 28
air ducts, relative proportions of compo- thermometers and thermocouples at dif-
nent losses, etc. No standardized ther- ferent points as indicated in figure 2,
mometer locations would be suitable for shows variations of 22 degrees centigrade
all types of motor construction. Conse- (27 degrees centigrade to 49 degrees
quently the test results by thermometer centigrade) in temperature rise, on the
method mayor may not be representa- surfaces accessible to thermometers. A
tive of actual maximum temperature rise maximum variation of 32 degrees centi-
depending on familiarity of testing per- grade (27 degrees centigrade to 59 degrees
(C)
sonnel with motor characteristics, and centigrade) is obtained by including the
Figure 1. Typical induction motors of also on whether a conscientious effort is inside surfaces of coil ends which are
modern construction which are not readily
made to locate the hottest observable accessible to thermocouples but not to
accessible for thermometer measurements
point in the machine. The term "ac- thermometers inserted through holes
(II) Totally enclosed fan-cooled wound-rotor cessible" is also subject to individual bored in the frame .
type, (8) spleshproo] type, and (C) vertical interpretation and cannot be sharply
motor for outdoor service defined. 2. MULTIWINDING MOTORS

A different arrangement of thermome- On multispeed motors having more


have generally been considered as five ters may occasion a wide disagreement in than one stator winding, thermometers
degrees centigrade less for totally en- test results when the same motor is usually cannot be placed on the under-
closed than for open motors because the tested by two different parties, and these neath winding. The lower-speed wind-
windings of the former are heated more variations are frequent sources of con- ing is almost invariably located inside
uniformly, and from this premise the troversy. The testing situation is be- next to the air gap. Because of reduced
maximum rating of 55 degrees centigrade coming increasingly complicated because ventilation this lower-speed winding usu-
rise by thermometer above a 40 degrees of the definite trend toward more en- ally has the higher temperature rise,
centigrade ambient was adopted for closing features in the design of induction especially on constant-horsepower and
totally enclosed motors. motors. A large percentage of modern constant-torque ratings. Thermometer
Paragraph 5.050 of the ASA C-50 motors now has a mechanical construe- measurements taken on the outside idle

460 TRANSACTIONS Summers-r-Determination. of Temperature Rise ELECTRICAL ENGINEERING


winding may be from 10 degrees centi- seems most probable that this situation is 2. On open-type or partially enclosed
grade to 20 degrees centigrade lower than a result of variations in testing procedure splashproof (or dripproof) machines rated
2,200 volts or less, heating tests on 149
the actual temperature of inside active which may now occur under the present different motors as described in appendices
winding. Confirming tests are described standards. III and IV indicate about two degrees
in appendix II, and the test data are centigrade less average stator temperature
presented in table II. With the "sand- 5. EXPLOSION-PROOF MOTORS rise by the resistance method than by
wiched" type of coil construction, the thermometers (or thermocouples at loca-
Although the Underwriters do not tions which could have been reached by
inside winding may not be accessible for thermometers through holes in the frame)
either thermometers or thermocouples. actually forbid the boring of holes for searchingly applied in accordance with the
The ASA standards do not have any thermometers in explosion-proof motors, present ASA standards. (The 149 tests
satisfactory provisions for testing multi- such a practice is dangerous and un- include the stator temperature measure-
desirable; because any failure to plug ments on the 41 splashproof and 96 open
winding induction motors. On open as
a hole securely might result in an explo- motors of table III and on the 12 open
well as enclosed multiwinding motors, motors of table IV.)
only one winding is usually accessible for sion external to the motor after the
machine is placed in normal service. 3. Measurements taken on the 36 insu-
the thermometer method; consequently lated wound-rotors of table III show an
this criticism of the present standards The present standards as worded there- average temperature rise of 4.6 degrees
applies to all types of mechanical con- fore may create a potential hazard when centigrade (34 degrees centigrade-29.4
struction. tests are taken on explosion-proof ma- degrees centigrade) more by change in
chines. resistance than by thermometer. Lower
and in general less accurate values of tem-
:3. WOUND-RoTOR MACHINES WITH perature rise are obtained with thermome-
INACCESSIBLE ROTORS Summary of Test Results ters because: (a) thermometers cannot
No provisions are made in ASA stand- by Resistance Method , be placed on center of rotor laminations
in most cases, (b) the rotor must stop
ards for rotor temperature measure- turning before thermometers can be ap-
ments of totally enclosed wound-rotor To investigate and demonstrate the plied and they do not attain maximum in-
motors of the form shown in figure 1. dependability and consistency of the dication until after resistance readings are
With this construction the rotor winding resistance method of measuring tempera- taken, and (c) rotors of many motors are
ture rise, an analysis was made of ap- not readily accessible and good thermome-
-isusually the limiting feature, because its ter contacts cannot always be obtained.
temperature rise is commonly 10 de- proximately 300 heating tests on various
types of polyphase induction motors over 4. The resistance method is consistently
grees centigrade to 20 degrees centigrade reliable for all speeds and time ratings.
above that of the stator. On all forms the range of sizes from 10 to 1,000 horse-
In table III the results are segregated ac-
of totally enclosed as well as on most power. Temperature rises were meas- cording to motor poles over the range from
splashproof wound-rotor machines, the ured both by the resistance method and 2 to 12 poles for the continuous-rated
also by thermometers (or thermocouples). squirrel-cage motors. Heating runs of
insulated rotor winding is completely one hour or less are separated from the tests
inaccessible to the thermometer method The test results may be summarized as
of longer duration.
when outside enclosed collectors are used. follows:
5. The resistance method is dependable
The provision of paragraph 2.063 of ASA 1. On totally enclosed and totally enclosed over a wide range of motor load and line
standards for "applying the thermometer fan-cooled motors, the stator temperature voltage as demonstrated in appendix V,
to the hottest part of the machine which rise by resistance method is essentially the table V, and figure 4. Tests on a repre-
equivalent of that obtained by thermo- sentative 25-horsepower motor for differ-
can be made quickly accessible by re- couples applied at hottest part of winding ent conditions of operation show that the
moving covers" is certainly not appli- surface. On the basis of averages, the temperature rise by any method is approxi-
cable where it becomes necessary to thermocouples checked the resistance matelyproportional to the total motor losses.
practically disassemble the machine in method within 1.1 degrees centigrade (48
degrees centigrade--46.9 degrees centigrade) 6. Maximum differences of about ± ten
order to gain access to at least one end of degrees centigrade between the thermome-
for the 65 tests on totally enclosed fan-
the rotor winding. Such a major dis- cooled motors, and within 0.6 degrees ter and resistance methods have been ob-
assembly of large machines requires so centigrade (40.1 degrees centigrade-39.5 served in tests on individual machines.
The resistance method may definitely indi-
much time that subsequent temperature degrees centigrade) for the 26 tests on totally
cate either a higher or lower temperature
readings are of little significance. In enclosed motors which are tabulated in
than thermometers depending on mechani-
table III. To locate the hottest winding
field tests it may not be possible to dis- surface, some of the thermocouples were
cal construction of motor, the two extreme
assemble the motor. placed at points which were not accessible conditions being:
to thermometers inserted through holes in (a). Motors with improperly proportioned
4. GENERAL-PURPOSE MOTORS stator frame as explained in appendix III. ventilation may have local hot spots where
Although general-purpose motors with
open-type construction are more acces-
sible for application of thermometers on
the windings and laminations than the
types of machines cited in the preceding
paragraphs, nevertheless, there is con-
siderable variation in the results which
may be obtained by different parties due
to varying locations of thermometers. Figure 2. Location
Appendix IV and table IV present results of thermometers and
of tests made on motors of 12 different thermocouples on
motor X
manufacturers, and five of these machines
showed a temperature rise higher than (Refer to appendix I A- THERMOMETERS
the name-plate stamping. It, therefore, and table I) B- THERMO COUPLES

SEPTEMBER 1939, VOL. 58 Summers-Determination of Temperature Rise TRANSACTIONS 461


thermometer readings exceed resistance insufficient number of thermometers will reliable indication of act ual insulation
indication, but in many cases these hot be used to locate the hottest point acces- temperature than a few th erm ometer
spots are not located and explored by the
thermometer meth od .of test. sible to them. Wide varia tions in tem- readings taken at isolated points on the
perat ure may occur over a mot or sur- outside surfa ces of the coils.
(b) . High-voltage machines, especially
-l,OOO volts and above, usually (but not face th at appears to be uniform and sym- The relation between winding resist-
always) show a higher temperature rise by metrical. The element of "chance" is anc e and temperature is a specific, defi-
resistance than by thermom eter because of therefore alway s associated t o some ex- nite ph ysical law that is entirely div orced
the temperature drop in th e coil insula- tent with the thermometer method. from the element of chance which is
tion, in which case the resistance method is On splash proof and other types of par- inherently associated with the therm ome-
safer because it represents actual condi-
tions. t ially closed mot ors, thermometer read- ter method. The winding resistance can
ings ma y be as much as 10 degrees centi- be measured quickly, conveniently, and
Discussion grade below the temperature of the hot- at little cost . From the standpoint of
test surface th at might have been reached. comp arative tests, the precision of the
The t hermometer method, as com- M ot or K of tabl e IV in a ppe ndix IV is resis tance method is limited only by
monly used , is not a sufficiently definite cited as a specific example wherein the the accuracy of resistance readings and the
procedure for determining the tempera- actual maximum observ able tem perature measurements of initi al and am bient tem-
t ure rise of pa rtially or tot ally enclosed rise of 61 degrees centigrade by ther- peratures. Consequ ently it is believed
mot ors, becau se it is probable th at an mometer was 11 degrees centigrad e higher that a general ad opti on of the resistance
th an the manufacturer's name- plate rat- method will pr omote greater accuracy
ing of 50 degrees centigrade-presumably in testing, will assure the motor user of
becau se his test with thermomet ers did greater insulation life, will reduce con-
not locate the hottest spot . trovers y by making it possible for differ-
On totally enclosed ma chin es where it is ent orga nizations to obtain comparable
necessary t o drill a sepa ra te hole in the test results, and will pro vide the motor
frame for each thermometer, only a few user with a convenient method for taking
are likely to be used-somet imes only field tests.
one , and this incre ases th e probability Precedents have already been es-
th at the hottest part will not be located. t abli shed for recognizing the resistance
Furthermore when thermometers are method. The International Electrotech-
inserted in holes bored through inter- nical Commi ssion European Standards,
venin g parts, it is usually impossible to the United States Navy Specifications
cover the bulbs completely with pad s or 17MlO, and an increasing number of
putty as specified in paragraph 2.056 of comm ercial customers now either accept
ASA standa rds. If only th e end of or require the resistance method of te sting
thermometer bulb make s a point contact to prove temperature-rise guarantees.
with the winding or laminations, the Although the resistance method re-
reading may be influenced by the sur- quires accurate measuring devices and
(1\)
rounding air t o which the bulb is exposed. precision in te sting procedure, experience
As a pra ctical result of all th ese factors, indi cates that these difficultie s are min or
th e tre nd toward more encl osing features comp ar ed to the ben efits obtained when
i tToermibridge
ne ls
on mot ors has been accompan ied by in -
creasing variations in the te st results that
testing mot ors that do not have open-
type construction. Readily portable
are obtained by th e thermometer method. instruments have been developed and are
.M otor X of t able I in a ppendix I is a now av ailable which have an accuracy
striking exam ple. that is satisfactory for motor tempera-
As the present standa rds do not insure ture measurements. At least 95 per cent
reasonabl y accurate and consistent re- of the resistanc e data for th e heating
sults when various mot or t yp es are tested t est s included in t his rep ort were ob-
by different orga niza tions, it is th erefore tained with a portable-type double-
highly desira ble to ado pt a more con- bridge arrangement similar to that shown
venient , more definite , and less expensive in figure 3. The rem ainder of the read -
method of measuring temperatures which ings were tak en with the voltmeter-
will give an accuracy comp arable t o th at ammeter method by passing dir ect cur-
which can be obtai ned by a th orough rent through the winding. The portable
explora tion with th erm ometers. double-brid ge has proved very satisfac-
The test dat a point t o the desirability t ory in general testing work. It is
RQ.5istance to of standardizing on resistance meas ure- readil y carrie d, accurate, ru gged , has a
be measured ment s for th e det ermination of tem pera- wide range of measur ement, an d is not
t ure rise. For practically all t ypes of easily thrown out of calibration. A de-
mot or construction , t he resistan ce method scription of this genera l t ype of bridge
(8 ) gives results th at are essentia lly th e is given in an article entitled " T he
Figure 3. (A) Portable double bridge with equiva lent of a careful explora tion with Portable Double Brid ge" by L. O'Bry an
leads for stator resistance measurements and th erm ometers. T he resist an ce reveals in th e General Electric Review, volume
(8) prong-type contacts used on collector the average intern al temperature of the 34, 1931, page 752.
rings of wound rotors mot or winding and thereby gives a more In comm on with most indicating in-

462 TRANSACTIONS Summers-Determination of Temperature Rise ELECTRICAL ENGINEERING


struments, the probable per cent error good check on the accuracy of results is ob- that more accurate results will be ob-
of measurement decreases as the upper tained by having two different persons
tained by the resistance method than by
take readings with separate equipments.
end of bridge scale is approached. The two resistance readings should agree thermometers as commonly used.
Bridges covering a range from 0.0005 to within 0.4 per cent (or about one degree In actual practice over the past ten
4.4 ohms, and having a maximum prob- cen tigrade). years, however, the points of measure-
able error of 0.4 per cent in ohms (or 4. Take resistance readings every minute ment by the thermometer method have
about one degree centigrade) at most un- for about ten minutes after motor stops and
favorable part of scale that must be used, project the curve to zero time. 130
and a minimum probable error of 0.1 5. When taking "cold resistance" before
per cent at upper end of scale, have been the heat run, never assume that the motor 1'2.0
temperature is the same as the ambient. /
found suitable for temperature measure-
Always place thermometers directly on 110 I
ments of motors between 10 and 1,000 motor. The motor may have been moved -
"-RISE BY RESISTANCE / J
/
f---
K-EMBEDOED THERMOCOUPLE /
horsepower for which data are presented recently from another part of factory 100 - .a.-THERMOMETER ON
V/
~

in this paper. Bridges of this type can be where temperature was different, the ma- - -
LAMINATIONS I
chine may not have cooled off completely 90
C!J-TH[~~~~EJ~R ON 7 //
made with various scales and scale multi- ..;
from some previous manufacturing or EMBEOOED_ I - -
ltV
I / ./
pliers to adapt them to different horse- testing operation, or the ambient tempera- 080
THERMOCOUPLE V

power ranges of motors. Even though ture may have changed suddenly because
c!)
/ /17 /
II 0/"
&AI
o /
cumulative errors of 0.4 per cent in both of an open factory door. Accurate cold I '70
RESISTANCE: ---.
temperatures are just as important as ac-
W ~ '/ ~
the hot and cold resistance measurements (I)
/ /./ V
curate resistance readings. ~ 60
do cause an error of two degrees centi- w
a I~ V 1~1II

grade in temperature rise, this is small 6. Always take both hot and cold re- ::J
.... 50 '-JV' b(
sistance measurements between the same « I~ ~ /
compared to the error commonly made Q: THERMOMETER ~
two stator terminals or the same two rotor w
J'.J' /~ ON LAMINATIONS
when a thermometer is inserted through collector rings to avoid errors due to slight
~ 40
~A D'l!I THERMOMETER
bJ
a hole bored in the stator frame of an unbalance in phase resistances. If non- t-
30
j;,f I!J
ON WINDINGS ~-

enclosed motor. uniform heating is anticipated because of I.~I(


unbalanced power supply or unsymmetrical ,'(f/
Errors due to contact drop in current design, record resistance measurements of
10
lC~V
circuit are minimized by using four leads each phase separately. ~V
10
to connect the unknown resistance to ~
bridge terminals as shown in figure 3. Suggested Motor Temperature I/'
'2 3 4 5 E> .,
Leads Xl and X 2 carry the current which Ratings for Resistance Method TOTAL MOTOR LOSSES - KW
flows through the unknown resistance of Test Figure 4. Relations between total loues
whereas D I and D 2 are potential leads.
and temperature rise by different methods
The voltage between D I and D 2 does not If the resistance method of measuring of measurements for a typical is.horsepower
include the contact drops at Xl and X 2• temperature rise is accepted as standard, motor'
Part A of figure 3 shows the spring-type the question arises as to what tempera-
clips which are used for stator resistance (Refer to eppendix V dod table V)
ture ratings by resistance shall replace
measurements. The two contact sur- the present 40-degree-centigrade, 50-
faces of each clip are insulated from each degree-centigrade, and 55-degree-centi- not generally been the hottest surfaces.
other to provide separate voltage and grade ratings by thermometer for gen- Hence, it is probable that 50-degrees-
current contacts. eral-purpose, special-purpose, and totally centigrade rise by resistance is a close
Wound-rotor measurements are ob- enclosed motors, respectively. The con- approximation to the value that would be
tained with the contacts in part B of ventional "hottest-spot" allowance dif- found by test on many partially closed
figure 3. The sharp prongs Xl and DI ferentials in AlEE Standards No. 1 motors now rated 40-degrees-centigrade
are held firmly against one collector ring would suggest that all these ratings rise by thermometer. The original
while X 2 and D 2 are placed upon another should be increased 5 degrees centigrade 40-degree-centigrade rating was adopted
collector ring. Prongs D 1 and D 2 are for the resistance method-namely to in the standards on the assumption that
supported on flexible coil springs which 45 degrees centigrade, 55 degrees centi- thermometers gave values 15 degrees
depress under pressure and thereby per- grade, and 60 degrees centigrade. The centigrade below the actual "hottest-
mit all prongs to maintain contact even test data show that, for any normal low- spot" temperature; and when it is
though they are not held at right angles voltage induction motor, the resistance recognized that the resistance method
with collector-ring surfaces. method is practically the equivalent of gives test values that are approximately
The following fundamental precautions the thermometer method when thermome- within 5 degrees centigrade below the
will minimize testing errors and insure ters are searchingly applied to locate hottest spot in many (but not all)
dependable heating data by the resistance the hottest observable part of the ma- motors, an argument is presented for
method: chine. The two methods agree within adopting 50 degrees centigrade by re-
three degrees centigrade in most cases sistance to replace the 40-degree-centi-
1. Use a bridge which is accurate within 0.5 and seldom is the disagreement more grade rating by thermometer.
per cent on lowest part of scale that must be
than five degrees centigrade. The test To obtain confirming test data on the
used.
results therefore indicate that an increase differentials between the internal "hot-
2. Calibrate the bridge periodically and of not more than five degrees centigrade test-spot" and the limiting "observable"
keep the leads in good condition. Make
sure that contacts are clean, and check gal- should be made in the present motor temperatures by different methods of
vanometer when readings are taken. ratings to obtain the equivalent ratings measurement, thermocouples were dis-
by the resistance method. In fact, an tributed among the copper wires inside
3. The persons taking resistance measure-
ments should use all necessary precautions increase of even five degrees centigrade the stator slots when the random winding
to obtain and record accurate data. A must be justified partly on the grounds was Installed in a typical low-voltage

SEPTEMBER 1939_ VOL. 58 Summers-Determination of Temperature Rise TRANSACTIONS 463


25-horsepower motor as explained in allowance. Actually the internal tem- beyond the common mercury thermome-
appendix V. The hea ting tests on this peratures of an enclosed motor are ter with which everyone is familiar.
motor, which are presented in table V normally more uniform than in an open- Even if resistance measurements are
and figure 4, show that for the three type machine. Nevertheless, it is adopted as the standard method of test-
tests taken near normal load at 25.9, logical that some margin for hot spots ing and rating all types of motors,
26.4, and 25.8 horsepower, the corre- should be provided, because the resist- thermometers will still be needed for
sponding differentials between the re- ance method can give only the average measurements of initial and ambient
temperatures, bearing temperatures, for
determining when the motor has reached
Table I. Comparison of Two Totally Enclosed Fan-Cooled Motors of Different Manufacturers a constant temperature, and for ob-
(See Appendix I and Figure 2)
taining quick, approximate readings for
Pulley End
check purposes.
Front End

Test Results for Motor X Conclusions


*Position-inside coil periphery . . . . . . . . . . .. 1.... 2.... 3.... 4 10 11 12 13
Rise by thermocouple-degrees centigrade 54 54 54 53 58 58 58 59
To place motor specifications on a
Front End
more sound basis, and to assure the motor
*Position-outside coil periphery . . . . . . . . . . . . .. 5........ 6........ 7........ 8........ 9 buyer of more accurate and comparable
Rise by thermocouple-degrees centigrade 27 41 39 30 27
Rise by thermometer-degrees centigrade 39 .43 38 29 27 tern perature measurements, it is recom-
Pulley End mended that the resistance method of
determining temperature rise be adopted
*Position-outside coil periphery 14 15 16 17 18
Rise by thermocouple-degrees centigrade 47 .47 .47 48 49 as standard for all types of partially or
Rise by thermometer-degrees centigrade 46 46 48 48
totally enclosed induction motors, except
Front End Pulley End for large, high-voltage machines for which
Test Results for Motor Y the embedded-detector method should be
Inside coil periphery-degrees centigrade 50 50 51 51 49 51 51 50 retained.
Outside coil periphery-degrees centigrade 48 46 48 49 48 49 .49 .49
It is also recommended that general
Temperature rise by resistance, motor X, one minute after shutdown 51 degrees centigrade. industrial experience with respect to the
Thermometers in positions 5 and 16 were not embedded in putty.
present limits of temperature rise be
The other thermometers and all thermocouples were embedded in putty.
* Refer to figure 2 for locations of thermometers and thermocouples.
reviewed, especially as regards "hottest-
All above temperatures on motor Y were obtained with thermocouples. spot" allowances and differentials be-
Temperature rise by resistance, motor Y, .54 degrees centigrade. tween various methods of measurement,
so that the limits of temperature rise
ultimately specified by the resistance
sistance method and the internal "hot- winding temperature. It may, therefore,
method shall be in accord with the best
test-spot" were six degrees centigrade, be found desirable to accept 60 degrees
interests of motor users.
four degrees centigrade and five degrees centigrade instead of 65 degrees centi-
The test data herein presented indicate
centigrade, respectively-or an average grade rise by resistance for totally en-
that the new limits of rise by resistance
differential of five degrees centigrade as closed motors, unless the standardized
should be at least five degrees centigrade
compared to the present "conventional ambient temperature is reduced from
above the present thermometer ratings
allowance" of ten degrees centigrade in 40 degrees centigrade to 35 degrees centi-
for low-voltage machines with class A
paragraph 1-7 of AlEE Standards No.1. grade to be in closer agreement with pre-
insulation. However, additional data
From the point of view of retaining the vailing temperatures in the United States.
'and other considerations may indicate
same limiting "hottest-spot" tempera- The long standing and justifiable prece-
a ten-degree-centigrade increase to be
ture of 105 degrees centigrade for class A dent of rating open motors five degrees
logical, or may suggest separate tempera-
insulation as originally intended in the centigrade lower than enclosed machines
ture differentials for different voltage
standards, there is considerable justifi- may make it necessary to accept .55
ratings or types of motor construction.
cation for specifying 50 degrees centigrade degrees centigrade rise by resistance for
by resistance in place of 40 degrees centi- special-purpose open motors, and in turn
grade rise by thermometer in future 45 degrees centigrade for general-pur-
standards. Such a step, however, might pose open motors, if 60 degrees centi- Appendix I. Comparison of Two
not leave sufficient margin for the con- grade by resistance is adopted as the
Totally Enclosed Fan-Cooled
ventional limits of voltage and frequency temperature ceiling for totally enclosed
variation and for the 15 per cent service construction.
Motors of Different Manufacturers
factor which are now specified in the ASA Although the resistance method of
Comparative heating tests were made
standards for general-purpose motors. temperature measurement is particularly on two 75-horsepower totally enclosed fan-
Similarly.iff) degrees centigrade and 65 adapted to inaccessible motors of par- cooled motors having widely different con-
degrees centigrade rise by resistance may tially or totally closed construction, test struction features. These motors which
ultimately replace 50 degrees centi- results demonstrate that it is also very are designated as X and Y were made by
two different manufacturers. Both ma-
grade and 55 degrees centigrade bv satisfactory and dependable for open- chines had the same NEMA frame number,
thermometer for special-purpose and type motors. However it may be de- speed, and horsepower rating, but motor X
totally enclosed motors, respectively. sirable to retain the thermometer method had a name-plate rating of 40 degrees centi-
However, a 65-degree-centigrade rating in the standards for motors of entirely grade rise whereas motor Y was rated 55
for class A insulation based on a 40 open construction, because it is the degrees centigrade.
Figure 2 shows the locations of 28
degrees centigrade ambient would not simplest possible procedure, and re- thermometers and thermocouples which
provide any margin for "hottest-spot" quires no special measuring equipment were placed on the winding of motor X

464 TRANSACTIONS Summers-Determination of Temperature Rise ELECTRICAL ENGINEERING


through radial holes that were bored in the centigrade) whereas the corresponding varia- tions of test including winding locations
stator frame. One thermocouple was placed tion on motor Y is only 6 degrees centigrade and temperatures of both active and idle
adjacent to each of the ten thermometer (54 degrees centigrade-48 degrees centi- windings are tabulated for nine different
bulbs to obtain check readings. One of grade). The better uniformity of winding heating tests. Although a maximum dif-
the thermometer bulbs on each end of the temperatures on motor Y is a result of a ference of only 16 degrees centigrade
motor was not imbedded in putty in order different type of winding and a more effec- appears on table II, differences up to 20
to observe any difference in indication for tive internal ventilation system. Conse- degrees centigrade have been observed.
this reason. Eight of the thermocouples quently the thermometer method of ASA Two-winding wound rotors are not very
were placed on inside periphery of stator standards as usually applied would give common, but when such construction is
coil ends directly over the rotor end rings. results more nearly representative of maxi- used at least one of the windings is likely
The values of temperature rise obtained at mum insulation temperature on motor Y to be inaccessible on open motors, whereas
the different points for continuous opera- than on motor X. both are inaccessible to thermometer
tion at normal load are shown in table 1. The tests on these two motors indicate method on totally enclosed motors as well
By the thermometer method as defined in that the temperature-rise-by-resistance as on most splashproof motors.
ASA standards 2.055 and 2.063, the tem- method is much more dependable than When the "sandwiched" type of coil is
r-erature rise of motor X may be measured thermometer readings which are obtained used on a two-winding stator, the inner
as anything from 27 degrees centigrade to at a few points only. In this comparison winding is in middle of slot whereas the
49 degrees centigrade depending on the the motor rated 40 degrees centigrade by ou ter winding occupies both the top and
number and location of points where read- thermometer actually had higher insulation bottom positions. This inner winding is
ings are taken. The present standards do temperatures than the 55 degrees centigrade quite inaccessible to either thermocouples
not specify the amount of exploration that rated machine. If the resistance method or thermometers.
shall be made to locate the hottest point of test had been specified as standard, To avoid misleading data, the resistance
accessible to thermometers. In this par- motor X definitely could not have qualified method of temperature measurement is
ticular case the location and distribution of as a 40-degree-centigrade machine. recommended for all multiwinding motors.
thermometers is of much greater significance
than the details of how the bulbs are covered
with putty or pads. Appendix II. Multispeed Motors
By placing thermocouples on the inside Appendix III. Analysis of Heat-
periphery of coil ends in positions not With More Than One Winding
accessible to thermometers, higher values ing Data From Induction Motors
of temperature rise are obtained (53 degrees If a motor has more than one stator- Representing Various Types of
centigrade to 59 degrees centigrade). winding, surface temperature readings which Construction
The 51-degree-centigrade temperature are taken on the idle winding are of ques-
rise of motor X by resistance method is tionable value. I t is common practice to
only 2 degrees centigrade more than the place the winding with largest number of In order to present a comprehensive
maximum value of 49 degrees centigrade poles (and consequently the shortest end analysis of the fidelity of the resistance
that could be obtained by following the _connections) inside next to the air gap. method, a review was made of 264 heating
ASA rules. If the testing personnel had Even on open motors the underneath tests made over a period of three years
used only two thermometers in positions 5 winding usually cannot be reached with where temperature rises were measured by
and 9, the temperature rise by the ASA thermometers, and it is utterly impossible both the resistance and thermometer
rules would be measured as 27 degrees to reach the inside winding of an enclosed methods. The test data which are sum-
centigrade, or 22 degrees centigrade lower machine by inserting thermometers in marized in table III include a wide variety
than the value of 49 degrees centigrade holes bored through the stator frame. Be- of motors representing different horsepower
that might have been obtained. cause of reduced ventilation at lower speed, ratings, speeds, time ratings, electrical de-
signs, and mechanical forms of construc-
tion. With the exception of a few of the
wound-rotor measurements, each heating
Table II. Motors With Two Windings (Refer to Appendix II)
test was taken with a different motor. Ap-
proximately 70 per cent of the tests were
Symbol Motor Rating made on motors in NEMA frame sizes from
364 to 505, inclusive. The remaining 30
M-l. .. .4/6/8/12 poles-{)0/40/30/20 horsepower-l,800/1,200/900/600 rpm-three phase-440 volts per cent are for larger machines up to
M-2 .4/6/8/12 poles-7. 5/6.5/6/5 horsepower-l,800/1,200/900/600 rpm-three phase-440 volts 1,000 horsepower. Several tests are aver-
M-3 .4/6/8/12 poles-50/33/25/17 horsepower-l,800/1,200/900/600 rpm-three phase-220 volts aged for each form of motor construction in
Conditions of Test Temperature Rise-Degrees Centigrade order to minimize individual testing errors
and thereby obtain a truly representative
Motor Poles Horsepower Volts Active Winding Idle -Winding
indication of results that could be antici..
pated by a general application of the 're-
M -1 " {) 40 440 B 36 A 22 sistance method.·
M-l 12 20 440 B 27 A 19 All the surface temperature measure-
M -2 " 4......... 7. 5 440 A 23 B 20
M-2 f 6 6 ..5 440 B: . . 30 A 22 ments on the stator windings of the totally
M-2 8 6 440 A 31 B 24 enclosed and totally enclosed fan-cooled
M -2 12 . . . . . . . .. 5 440 B 45 A 30 motors of table III were obtained with
M-2 " 4 - 15 520 A 59 B 48 thermocouples which were well distributed
M-2 6 10 4.57 B 46 4 30
M-3 " 6 33 220 B 27 A 19 in order to locate the hottest point. The
testing procedure for the enclosed ma-
B-Indicates inaccessible underneath winding next to air gap. chines was carried beyond .the require-
A-Indicates outside winding farthest from air gap. ments of the ASA standards, because some
of the thermocouples were in locations that
could not have been reached by inserting
On motor Y the temperature rise by re- the inaccessible winding is likely to be the thermometers through holes in the frame.
sistance of 54 degrees centigrade is 5 degrees limiting feature of the motor with respect Consequently the recorded winding sur-
centigrade more than that obtained under to temperature rise on constant horsepower face temperatures were approximately three
the ASA rules, but is only 3 degrees centi- and constant torque ratings. degrees centigrade higher on the average
grade above the values measured with Table II shows thermocouple tempera- than could have been obtained by the ther-
thermocouples on inside coil periphery at tures on both active and idle windings of mometer method.
points inaccessible to thermometers. The three different four-speed motors having The data on the open motors of table III
variation in temperature measurements by two stator windings. Machines M-1 and were obtained by the thermometer method
all methods on motor X is 32 degrees centi- M-3 are of open-type construction, whereas as defined in the present standards. In
grade (59 degrees centigrade-27 degrees M-2 is totally enclosed fan-cooled. Condi- general, thermometers (or thermocouples)

SEPTEMBER 1939, VOL. 58 Summers-Determination of Temperature Rise TRANSACTIONS 465


Table III. Heating Data on Various Types of Induction Motors (See Appendix III)

Tempera-
ture Rise
of Hottest
Temperature Rise by Surface by Tempera-
Tempera- Thermometer Thermome- ture Rise
Number ture (or Thermocouple) ter (or by Resis-
Of Number Form Measure- §Average Degrees Centigrade Thermo- tance
Tests of of ments Length of couple)- Method-
Aver- Motor Mechanical Type of Taken Test in Wind- Lamina- Degrees Degrees
aged Poles Construction Motor on Hours ing tions Centigrade Centigrade

17 " 2 #Fan cooled ....... Squirrel cage Stator 5.5 47.9 32.6 47.9 47.2
18. . . . . .. 4....... Fan cooled ....... Squirrel cage Stator 6.0 51.5 35.3 51.5 50.2
15 6 Fan cooled · Squirrel cage Stator 6.0 45.2 33.2 45.2 44.2
2 " 8....... Fan cooled · Squirrel cage Stator 7 .4 52.5....... 36.0 52.5 49.5
4 10 Fan cooled · Squirrel cage Stator 6. 7 45.5....... 34.8 45.5 45.0
2 12. . . . . .. Fan cooled · Squirrel cage Stator {).0 46.5....... 33.0 46.5 45.5
3. . . . . . . . . . . . . . .. Fan cooled · Squirrel cage Stator 1.0 44.0....... 31.7 44.0 43.0
2. . . . . . . . . . . . . . .. Fan cooled ....... Wound rotor Stator 4.7 54.0 30.5 54.0 52.0
2. . . . . . . . . . . . . . .. Fan cooled · Wound rotor Stator 1.0 39.0 28.0 39.0 37.0

Total 65. . . . . . . . . . . . . . .. Fan cooled .......................... Stator 48.0 33.5 48.0 46.9t Average

3 " 4 *Totally enclosed Squirrel cage Stator 8.8 51.7 *40.7 51.7 52.0
3 6 Totally enclosed Squirrel cage Stator 7.8 41.3 *35.3 41.3 40.0
2 8 Totally enclosed Squirrel cage Stator 9.2 52.5 *41. O 52.5 53.5
2 Totally enclosed Squirrel cage Stator .. ~ 0.5 36.5 *21.0 36.5 36.0
16. . . . . . . . . . . . . . .. Totally enclosed Wound rotor Stator 0.56 35.7 *23.1 35.7 36.8

Total 26 Totally enclosed Stator 39.5 27.8 39.5 40.1t Average

6 ......• 2....... Splashproof · Squirrel cage Stator 3.3 27.3 32.3 32.5 27.8
8. . . . . .. 4....... Splashproof · Squirrel cage Stator 4.0 27.3....... 29.4 30.0 28.1
7 6 Splashproof ....... Squirrel cage Stator 3.4 25.6 28.9 29.6 27.1
5. . . . . .. 8....... Splashproof · Squirrel cage Stator 4.9 31.0....... 33.8 34.0 34.8
5 10 Splashproof ....... Squirrel cage Stator 3.1 19.0 21.4 21.4 19.6
1. 12 Splashproof · Squirrel cage Stator 3.5 25.0 28.0 28.0 26.0
5. . . . . . . . . . . . . . .. Splashproof · Squirrel cage Stator 0.5 28.2 32.0 32.0 30.2
4 Splashproof · Wound rotor Stator 5.4 36.0....... 38.3 38.8 39.5

Total 41 Splashproof · Stator 27 .4. . . . . .. 30.5 30.8 29.0 t Average

25 2 Open · Squirrel cage Stator 4.0 23.9 30.1 30.7 28.6


14 4 Open ....... Squirrel cage Stator 3.7 21.9 26.9 26.9 22.7
8 6 Open ....... Squirrel cage Stator 3.7 21.1. 25.9 25.9 20.8
12 8 Open · Squirrel cage Stator 3.9 26.3 28.8 30.7 27.5
8 10 Open · Squirrel cage Stator 3.3 20.9 25.0 25.0 23.1
3 12 Open ....... Squirrel cage Stator 3.0 17.3 21.0 21.0 20.0
2 Open · Squirrel cage Stator 0.5 34.0 26.0 35.5 34.0
18 Open · Wound rotor Stator 4.0 26.3....... 30.3 30.2 30.4
6 Open ....... Wo~nd rotor Stator 0.75 31.0 30.0 31.7 32.7

Total 96. . . . . . . . . . . . . . .. Open · Stator 24.3 28.4 29.0 26. 9t Average

16 *Totally enclosed Wound rotor Rotor 0.56 31.1 26.6 31.5 37.1
4. . . . . . . . . . . . . . .. Splashproof Wound rotor Rotor 5.4 32.8....... 27.3 34.0 38.0
12 Open Wound rotor Rotor 4.0 24.0 23.1 25.2 28.9
4 . . . . . . . . . . . . . . .. Open Wound rotor Rotor 0. 75 28.8. . . . . .. 2'3. 7 28.8 33.0

Total 36 Wound rotor Rotor 28.7 25.2 29.4 34.0t Average


264-Total number of tests.

I Motors deslgnated as fan-cooled are also totally enclosed.


*Motors designated as totally enclosed are not cooled by external fan. Stator lamination temperatures were measured on outside of frame on totally enclosed
machines.
§All tests longer than one hour (a total of 208) were taken on continuous rated motors. The remaining 56 tests of one hour or less were taken on motors with short-
time ratings.
tAverages of temperatures are weighted in accordance with number of tests taken for each condition.

were distributed over laminations and mum value occurred before or after shut- gin between actual tests and the conven-
winding at ten or more points. All surface down). In each case a conscientious at- tional name-plate ratings for the different
measurements on wound rotors were made tempt was made to find the hottest observ- classes of motors.
with thermometers after shutdown. able spots on the machine. The average
Most of the data on splashproof ma- deceleration period was approximately' one-
chines were actually taken with thermo- half minute, from time load was removed Appendix IV. Comparison of 12
couples, but similar maximum values of until motor was stopped. Resistance meas-
temperature rise by surface measurements urements were obtained from one to two Open-Type Motors of Different
could have been obtained with thermome- minutes after motor stopped. (These time Manufacturers
ters if a sufficient number of holes had intervals were slightly greater for large, If

been bored in the motor frames. It will high-speed machines.) . Identical testing methods were used to
be noted that on both splashproof and The heating tests tabulated in table III determine the comparative temperature
open machines, the average temperature were not all made at the normal rated rises of 12 different low-voltage four-
rise of laminations exceeded that of the loads of the various motors. Tests on ma- pole, 50-cycle motors. Eleven of these
accessible parts of windings. Consequently chines of similar constructions but with machines were general-purpose open-type
the hottest part of many motors will not different ratings (such as 40 degrees centi- 25-horsepower motors rated 40 degrees
be reached if thermometers are placed on grade, 50 degrees centigrade, etc.) are centigrade rise, but one motor (designated
the windings only. averaged together. Consequently the aver- as K in table IV) was rated 50 degrees
Maximum observed temperatures are age values of temperature rise shown in this centigrade because it had some protective
tabulated (regardless of whether the maxi- table are not a direct indication of the mar- features. Each motor was made by a

466 TRANSACTIONS Summers-Determination of Temperature Rise ELECTRICAL ENGINEERING


different manufacturer. Complete test re- Table V. Continuous Heat Runs for Various Loads and Voltages (See Appendix V and
sults for continuous operation at rated Figure 4)
load are given in table IV.
The lamination and conductor tempera- (Motor Name-Plate Rating-Four Poles, 25 Horsepower, 220 Volts, Three Phase, 60 Cycles)
tures were obtained by surface measure-
ments with either thermometers or ther- Temperature Rise-
mocouples depending in each case on the Degrees Centigrade
accessibility of motor parts. However, Lamina- By
when thermocouples were used, they were Total Winding tions Embedded Re-
purposely placed in locations that could Volt- Horsepower Watts Motor Losses Ther- Ther- Thermo- sist-
age Load Input Amperes (Watts) mometer mometer couple ance
have been reached by thermometers if
holes had been bored through intervening
structural parts. Therefore the data in 220 0 966 24.6 966 9 14 16 11
table IV were obtained in accordance with 254 0 1,410 37 1,410 16 22 21. 17
187 0 740 19.4 740 6 10 10 8
rules 2.055 and 2.063 of the present ASA 220 25.9 21,900 66.5 2,591. 25 33 38 32
standards. Only the maximum observed 254 26.4 22,250 64.5 2,582 27 35 38 ......• 34
temperatures are recorded, but measure- 187 25.8 22,500 78.5 3,308 36 42 47 42
ments were made at many different points 220 32.3 27,800 83 3,729 37 47 53 50
on each machine. With the exception of 254 32 27,200 76 3,285 32 42 46 43
187 31.5 29,700 107 6,190 66 79 95 84
motor I, the resistance method does not 220 38.0 34,000 103 5,636 58 69 83 72
deviate from the maximum temperature 220 41. 9 39,200 120 7,976 91. 101. 121. 108
rise observed by surface measurements by
more than 3.5 degrees centigrade, and on
eight of the motors the agreement is within
2 degrees centigrade. ences in the extent of exploration with higher than the temperature by resistance
The tests on these 12 motors were made thermometers. for the heat runs taken near normal load.
successively by the same personnel, and the Figure 4 shows that the temperature rises
same dynamometer and metering equipment by all methods are approximately propor-
were used throughout. Therefore most of tional to the total motor losses. In general,
those controversial points were eliminated Appendix V. Temperature increasing differentials are obtained between
which usually arise when an attempt is Measurements for Various Condi- the temperature measurements by different
made to compare heating characteristics tions of Motor Load and Voltage methods as the motor losses are increased
of different motors. Since the motors repre- by overloading the machine.
sent a wide range of design proportions
and ventilation arrangements, the con- An open-type 25-horsepower motor rated
sistency of the temperature data obtained 220 volts at 1,800 rpm was selected for a
by the resistance method is highly signifi- series of 11 heat runs covering a wide range Bibliography
cant. of conditions from zero to 168 per cent of
Five of the 12 motors had a maximum normal load and from 85 to 115 per cent of 1. AMERICAN STANDARDS FOR ROTATING ELEC-
observable temperature rise by thermome- rated voltage. Temperatures were meas- TRICAL MACHINERY, ASA-C50-1936, approved
ured by thermocouples which were in- January 6, 1936; pages 23-7 and page 62.
serted in internal parts of stator slots when 2. GENERAL PRINCIPLES UPON WHICH TEM-
the random winding was installed, by ther- PERATURE LIMITS ARE BASED IN THE RATING OF
Table IV. Comparison of Open Motors of ELECTRICAL MACHINERY AND ApPARATUS, AlEE
mometers on windings and laminations, Standards No.1, April 1925, pages 5-6.
Different Manufacturers (Refer to Appendix and by resistance method as tabulated in
IV) 3. NEMA MOTOR AND GENERATOR STANDARDS,
table V for continuous heat runs at each publication number 38-49, May 1938; pages 35,
condition indicated. The laminations and 51, and 57-9.
Test Values of Temperature windings were readily accessible, and ther- 4. INDUCTION MOTORS AND MACHINES IN GEN-
Rise-Degrees Centigrade mometer readings were taken according to ERAL, AlEE Standards No.9, June 1927, pages
the ASA rules. 7-11.
For operation at rated voltage, the re- 5. TEST CODE FOR POLYPHASE INDUCTION MA-
sistance method indicated one degree cen ti- CHINES, AlEE Standards No. 500, August 1937;
pages 6-8, 12-14.
grade to three degrees cen tigrade lower
temperature than thermometers at normal 6. THE PORTABLE DOUBLE BRIDGE, L. O'Bryan.
General Electric Review, volume 34, December 1931,
load or less, but for extreme overloads the page 752.
temperature is higher by resistance, the
7. MEASUREMENT OF TEMPERATURE IN GENERAL-
A . . .. 40 41 38 41 41 maximum difference being seven degrees PURPOSE SQUIRREL-CAGE INDUCTION MOTORS,
B 40 42 34 42 41 centigrade at 168 per cent of rated load. C. P. Potter. AlEE TRANSACTIONS, volume 58,
C 40 34 37 37 37 Thermocouples were distributed through 1939. pages 468-78.
D 40 28 31 31 27 ..~
E 40 24.5 25. 5 25. 5 23. 5 the stator slots in order to locate the 8. RATING OF GENERAL-PURPOSE INDUCTION
F 40 34. 5 28. 5 34 . 5 32 hottest internal point in the motor, and the MOTORS, P. L. Alger and T. C. Johnson. AlEE
G 40 33 32 33 34 maximum temperatures observed are desig- TRANSACTIONS, volume 58, 1939, pages 445-59.
H 40 44 ., .. 37 44 45
I 40 47 34 47 41 nated as "embedded thermocouple" in 9. TEMPERATURE AND LIFE CHARACTERISTICS OF
table V and figure 4. In this random CLASS A INSULATION, J. J. Smith and J. A. Scott.
J 40 32 . 5 30. 5 32 . 5 30. 5 AlEE TRANSACTIONS, volume 58, 1939, pages 435-
*K 50 59 61 61 62 winding the embedded thermocouples are 44.
L 40 29 24 29 27 . 5 in close contact with the conductors, and
10. INTERNATIONAL ELECTROTECHNICAL COM-
Averages 37 . 4 34.4 38. 1. 36.8 are not separated from them by coil insula- MISSION, IEC SPECIFICATION FOR ELECTRICAL
* Motor K had some protective features. tion as in the case where embedded-detec- MACHINERY, FOURTH EDITION, 1935, pages 6-11
tors are placed between two formed coils and 17-27.
in the slot of a high-voltage motor. There-
ter that was higher than the name-plate fore these embedded thermocouples indi-
rating. These tests indicate that com- cate closely the theoretical "hottest spot"
parable results are not being obtained by of the winding which was located at the Discussion
different manufactures under the present middle of lamination stack. The "hottest
standards-presumably because of differ- spot" averaged five degrees centigrade For discussion, see page 472.

SEPTEMBER 1939, VOL. 58 Summers-r-Determination of Temperature Rise TRANSACTIONS 467

Vous aimerez peut-être aussi