Vous êtes sur la page 1sur 27

VL to MCB Disc.

Discrimination limits (preliminary)


Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker - (line protection - thermal magnetic)


Downstream Miniature Circuit Breakers 3VL-160X 3VL-160 3VL-250 3VL-400 3VL-630
(Fixed/Fixed & Adj. / Fixed) (Adj./Adj. (Adj./Adj.) (Adj./Adj.) (Adj./Adj.)
In [A] 50 63 80 100 125 160 50 63 80 100 125 160 125 160 200 250 200 250 315 400 315 400-630
I>> [A] 600 600 1000 1000 1000 1600 500 630 800 1000 1250 1600 1250 1600 2000 2500 2000 2500 3150 4000 3150 4000-6300
Icn [kA] 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 45/70 45/70 45/70 45/70 45/70 45/70
100 100 100 100 100 100 100 100 100 100 100 100 100 100 100 100
Discrimination Limit [kA]
5SX2…-5 2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
A-Characteristics 10 30 6 4.7 4.7 6 6 6 6 2.5 4.7 6 6 6 6 6 6 6 6 6 6 6 6 6 6
16 48 6 4.7 4.7 6 6 6 6 2.3 4.7 6 6 6 6 6 6 6 6 6 6 6 6 6 6
32 96 6 3.6 3.6 6 6 6 6 1.8 3.6 4.8 6 6 6 6 6 6 6 6 6 6 6 6 6
40 120 6 2.5 2.5 6 6 6 6 1.5 2.5 3.1 6 6 6 6 6 6 6 6 6 6 6 6 6

5SX2…-8 2 40 6 6 6 6 6 6 6 4.2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
D-Characteristics 6 120 6 4.2 4.2 6 6 6 6 2.3 4.2 4.8 6 6 6 6 6 6 6 6 6 6 6 6 6
10 200 6 3.9 3.9 6 6 6 6 1.9 3.9 5.5 6 6 6 6 6 6 6 6 6 6 6 6 6
16 320 6 3.5 3.5 4.9 4.9 4.9 6 1.7 3.5 4.2 4.9 6 6 6 6 6 6 6 6 6 6 6 6
32 640 6 3.9 3.9 3.9 6 3.1 3.9 4.2 6 6 6 6 6 6 6 6 6 6 6
40 800 6 3.1 3.1 3.1 4.9 3.1 3.3 4.9 4 4.9 6 6 6 6 6 6 6 6
50 1000 6 4.8 2.9 4.8 4 4.8 6 6 6 6 6 6 6 6

5SX2…-6 6 30 6/10 6/10 6/10 6/10 6/10 6/10 6/10 3.2 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
5SX4…-6 10 50 6/10 6/10 6/10 6/10 6/10 6/10 6/10 2.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
B-Characteristics 13 65 6/10 5.1 5.1 6/10 6/10 6/10 6/10 2.3 5.1 6/8.2 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
16 80 6/10 5.1 5.1 6/10 6/10 6/10 6/10 2.3 5.1 6/8.2 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
20 100 6/10 5.1 5.1 6/10 6/10 6/10 6/10 2.3 5.1 6/8.2 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
25 125 6/10 3.5 3.5 5.5 5.5 5.5 6/10 2.1 3.5 4.6 5.5 6 6/10 6/9.6 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
32 160 6/10 3.5 3.5 5.5 5.5 5.5 6/10 2.1 3.5 4.6 5.5 6 6/10 6/9.6 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
40 200 6/10 2.4 2.4 3.3 3.3 3.3 6/6.7 1.8 2.4 2.8 3.3 4.5 6/6.7 6 6/6.7 6 6 6 6 6 6/10 6/10 6/10
50 250 6/10 2.4 2.4 3.3 3.3 3.3 5.8 2.4 2.8 3.3 4.3 5.8 5.1 5.8 6 6 6 6 6 6/10 6/10 6/10

5SX2…-7 0.5 5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
5SX4…-7 1 10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
C-Characteristics 1.5 15 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
2 20 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
3 30 6/10 6/9.5 6/9.5 6/10 6/10 6/10 6/10 2.5 6/9.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
4 40 6/10 6/9.5 6/9.5 6/10 6/10 6/10 6/10 2.5 6/9.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
6 60 6/10 6/9.5 6/9.5 6/10 6/10 6/10 6/10 2.5 6/9.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
8 80 6/10 4.2 4.2 6/10 6/10 6/10 6/10 2.3 4.2 6/7.9 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
10 100 6/10 4.2 4.2 6/10 6/10 6/10 6/10 2.3 4.2 6/7.9 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
13 130 6/10 4.2 4.2 6/10 6/10 6/10 6/10 2.1 4.2 5.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
16 160 6/10 4.2 4.2 6/10 6/10 6/10 6/10 2.1 4.2 5.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
20 200 6/10 4.2 4.2 6/10 6/10 6/10 6/10 2.1 4.2 5.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
25 250 6/10 3.4 3.4 5.4 5.4 5.4 6/8.8 1.9 3.4 4.5 5.4 5.7 6/8.8 6/8 6/9.1 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
32 320 6/10 3.4 3.4 5.4 5.4 5.4 6/8.8 1.9 3.4 4.5 5.4 5.7 6/8.8 6/8 6/9.1 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
40 400 6/10 2.2 2.2 2.8 2.8 2.8 4.8 1.4 2.2 2.6 2.8 3.1 4.8 3.6 4.8 6.5 6.5 6.5 6.5 6.5 6/10 6/10 6/10
50 500 6/10 2.1 2.1 2.8 2.8 2.8 4.8 2.1 2.5 2.8 3.1 4.8 3.6 4.8 6.2 6.2 6.2 6.2 6.3 6/10 6/10 6/10
63 630 6/10 1.5 1.5 1.5 3 1.5 2 3 2.5 3 4 4 4 4 4 6 6/10 6/10
5SX7…-7 63 630 10 1.5 1.5 1.5 3 1.5 2 3 2.5 3 4 4 4 4 4 6 6/10 6/10
C-Characteristics 80 800 10 1.5 1.5 1.5 2.5 1.5 1.5 2.5 1.5 2.5 3 3 3 3 3 6 6/8 6/10
100 1000 10 2 1.5 2 1.5 2 3 3 3 3 3 5 6 6/10
6/10
5SX7…-8 63 1200 10 2.5 2.5 2.5 4 4 4 4 4 6 6/8 6/10
D-Characteristics 80 1600 10 3 3 3 3 3 5 6 6/10
100 2000 10 2.5 2.5 3 5 6 6/10
Page 10
470034538.xls
Discrimination limits (preliminary) VL to MCB Disc..
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Downstream Miniature Upstream Circuit Breaker - (line protection - electronic)


Circuit-Breakers 3VL-160 3VL-250 3VL-400 3VL-630 3VL-800 3VL-1250 3VL-1600

In [A] 63 80 100 125 160 125 160 200 250 200 250 315 400 315 400-630 630-800 1000-1250 1600
I>> [A] 693 880 1100 1375 1760 1375 1760 2200 2750 2200 2750 3465 4400 3465 4400-6930 7500 13750 15000
Icn [kA] 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100
Discrimination Limit [kA]
5SX2…-5 2 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
A-Characteristics 10 30 6 4.7 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
16 48 6 4.7 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
32 96 6 3.6 4.6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
40 120 6 2.5 3.1 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

5SX2…-8 2 40 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
D-Characteristics 6 120 6 4.2 4.8 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
10 200 6 3.9 5.5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
16 320 6 3.5 4.2 4.9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
32 640 6 3.3 3.9 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
40 800 6 3.1 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
50 ### 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

5SX2…-6 6 30 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
5SX4…-6 10 50 6/10 6/6.6 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
B-Characteristics 13 65 6/10 5.1 6/8.2 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
16 80 6/10 5.1 6/8.2 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
20 100 6/10 5.1 6/8.2 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
25 125 6/10 3.5 4.6 5.5 6 6/10 6 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
32 160 6/10 3.5 4.6 5.5 6 6/10 6 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
40 200 6/10 2.4 2.8 3.3 6 6 6 6 6 6 6 6 6 6/10 6/10 6/10 6/10 6/10 6/10
50 250 6/10 2.4 2.8 3.3 5 6 5 6 6 6 6 6 6 6/10 6/10 6/10 6/10 6/10 6/10

5SX2…-7 0.5 5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
5SX4…-7 1 10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
C-Characteristics 1.5 15 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
2 20 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
3 30 6/10 6/9.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
4 40 6/10 6/9.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
6 60 6/10 6/9.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
8 80 6/10 4.2 6/7.9 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
10 100 6/10 4.2 6/7.9 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
13 130 6/10 4.2 5.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
16 160 6/10 4.2 5.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
20 200 6/10 4.2 5.5 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
25 250 6/10 3.4 4.5 5.4 6/8 6/9 6/8 6/9 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
32 320 6/10 3.4 4.5 5.4 6/8 6/9 6/8 6/9 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10 6/10
40 200 6/10 2.2 2.6 2.8 3.6 6/6.5 3.6 6/6.5 6/6.5 6/6.5 6/6.5 6/6.5 6/6.5 6/10 6/10 6/10 6/10 6/10 6/10
50 500 6/10 2.1 2.5 2.8 3.6 6/6.5 3.6 6/6.5 6/6.2 6/6.2 6/6.2 6/6.2 6/6.3 6/10 6/10 6/10 6/10 6/10 6/10

5SX7…-7 63 630 10 1.2 1.5 2 3 2 3 4 4 4 4 4 6 10 10 10 10 10


C-Characteristics 80 800 10 1.5 1.5 2.5 1.5 2.5 3 3 3 3 3 6 8 10 10 10 10
### ### 10 1.5 2 1.5 2 3 3 3 3 3 5 6 10 10 10 10

5SX7…-8 63 ### 10 2 2 4 4 4 4 4 6 8 10 10 10 10
D-Characteristics 80 ### 10 3 3 3 3 3 5 6 10 10 10 10
### ### 10 2.5 2.5 3 5 6 10 10 10 10
Page 10a Page 11a

470034538.xls
Discrimination limits (preliminary) Sheet3
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker - (line protection - thermal magnetic)


Downstream Circuit Breakers 3VL-160X 3VL-160 3VL-250
(Fixed & Adjustable) (Adj./Adj. (Adj./Adj.)
In [A] 50 63 80 100 125 160 50 63 80 100 125 160 125 160 200 250
I>> [A] 600 600 1000 1000 1000 1600 500 630 800 1000 1250 1600 1250 1600 2000 2500
Icn [kA] 40/70 40/70 40/70 40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
Discrimination Limit [kA]
3VU13 0.6 7 100 40/70 40/70 40/70 40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
1 12 100 40/70 40/70 40/70 40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
1.6 19 100 40/70 40/70 40/70 40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
2.4 29 100 40/70 40/70 40/70 40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
4 48 100 5 5 40/70 40/70 40/70 40/70 3 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
6 72 100 2.5 2.5 10 10 10 40/70 1.5 2.5 4 10 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
10 120 10 1.2 1.2 3 3 3 10 1.2 1.5 2.5 3 4 10 4 10 10 10
16 190 6 1.2 1.2 2 2 2 4 1 1.2 1.5 2 3 4 3 4 6 6
20 240 6 1.2 1.2 2 2 2 4 1 1.2 1.5 2 3 4 3 4 6 6
25 300 6 1.2 1.2 2 2 2 4 1 1.2 1.5 2 3 4 3 4 6 6

3VU16 1.6 19 100 40/70 40/70 40/70 40/70 40/70 40/70 40/70/100 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
2.4 29 100 40/70 40/70 40/70 40/70 40/70 40/70 3 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
4 48 100 2 2 12 12 12 40/70 1 2 5 12 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
6 72 100 1.1 1.1 2.5 2.5 2.5 5 0.8 1.1 1.8 2.5 3 5 3 5 10 6
10 120 100 1 1 1.6 1.6 1.6 3 0.7 1 1.4 1.6 2 3 2 3 4 5
15 190 100 1 1 1.5 1.5 1.5 3 0.7 1 1.2 1.5 2 3 2 3 3.5 4
25 300 100 1 1 1.4 1.4 1.4 2.5 1 1.2 1.4 1.5 2.5 1.5 2.5 3 3
32 380 100 1 1 1.3 1.3 1.3 2 1 1.2 1.3 1.5 2 1.5 2 3 3
40 480 35 1 1 1.3 1.3 1.3 2 1 1.2 1.3 1.5 2 1.5 2 3 3
50 500 35 1.2 1.2 1.2 2 1.1 1.2 1.5 2 1.5 2 3 3
63 600 35 1.2 1.2 1.2 2 1.1 1.2 2 2 3 3

3VF1231-1D… 10 120 100 4 4 40/70 40/70 40/70 40/70 2 4 7 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
15 190 100 2.5 2.5 3 3 3 7 1.5 2.5 3 3 4 7 4 7 10 10
20 240 100 1.5 1.5 2 2 2 4 1.2 1.5 2 2 2.5 4 2.5 4 6 6
32 380 100 1.5 1.5 2 2 2 3 1 1.5 2 2 2.5 3 2.5 3 4 4
40 480 42 1.2 1.2 2 2 2 3 1.2 1.5 2 2 3 2 3 4 4
50 500 30 1.5 1.5 1.5 3 1.5 1.5 2 3 2 3 4 4
56 672 42 1.5 1.5 1.5 3 1.5 1.5 2 3 2 3 4 4
63 760 22 2.5 1.5 2.5 1.5 2.5 3 3
65 780 30 2.5 1.5 2.5 1.5 2.5 3 3
80 960 22 2 1.5 2 1.5 2 3 3

3VL-125 16 300 40/70 1.3 1.3 1.3 1.9 1.2 1.3 1.3 1.9 1.3 1.9 2 2.5
for line protection 20 300 40/70 1.3 1.3 1.3 1.9 1.2 1.3 1.3 1.9 1.3 1.9 2 2.5
fixed & adj. settings 25 300 40/70 1.3 1.3 1.3 1.9 1.2 1.3 1.3 1.9 1.3 1.9 2 2.5
32 300 40/70 1.3 1.3 1.3 1.9 1.2 1.3 1.3 1.9 1.3 1.9 2 2.5
40 600 40/70 1 1 1 1.9 1 1 1 1.9 1 1.9 2 2.5
50 600 40/70 1 1 1 1.9 1 1 1 1.9 1 1.9 2 2.5
63 600 40/70 1 1 1 1.9 1 1 1 1.9 1 1.9 2 2.5
80 1000 40/70 1.5 1.5 1.5 2 2.5
100 1000 40/70 1.5 1.5 1.5 2 2.5
125 1000 40/70 1.5 1.5 1.5 2 2.5
160 1600 40/70 2 2.5

3VL-160 50 500 40/70/100 1.3 1.3 1.3 1.9 1.2 1.3 1.5 1.9 1.5 1.9 2 2.5
for line protection 63 630 40/70/100 1.3 1.3 1.3 1.9 1.3 1.5 1.9 1.5 1.9 2 2.5
adj. settings 80 800 40/70/100 1.3 1.3 1.3 1.5 1.3 1.5 1.5 1.5 1.5 2 2.5
100 1000 40/70/100 1.5 1.5 1.5 2 2.5
125 1250 40/70/100 1.5 1.5 1.5 2 2.5
160 1600 40/70/100 2.5

3VL-160 50 550 40/70 0.8 0.8 0.8 1.5 0.8 1 1.5 1 1.5 1.6 2.5
for motor protection 63 700 40/70 0.8 0.8 0.8 1.5 0.8 1 1.5 1 1.5 1.6 2.5
(electronic) 80 880 40/70 1.5 1 1.5 1 1.5 1.6 2.5
100 1100 40/70 2.5
160 1760 40/70

3VL-160 63 900 70 1.5 1 1.5 1 1.5 1.6 2.5


for starter 100 1500 70
combinations 160 2500 70

Page 14 Page 15

470034538.xls
Discrimination limits (preliminary) Sheet4
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker - (line protection - thermal magnetic)


Downstream Circuit Breakers 3VL-160X 3VL-160 3VL-250
(Fixed & Adjustable) (Adj./Adj. (Adj./Adj.)
In [A] 50 63 80 100 125 160 50 63 80 100 125 160 125 160 200 250
I>> [A] 600 600 1000 1000 1000 1600 500 600 800 1000 1250 1600 1250 1600 2000 2500
Icn [kA] 40/70 40/70 40/70 40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
Discrimination Limit [kA]
3VF3 50 500 40/70/100 1.3 1.3 1.3 1.9 1.2 1.3 1.5 1.9 1.5 1.9 2 2.5
for line protection 63 630 40/70/100 1.3 1.3 1.3 1.9 1.3 1.5 1.9 1.5 1.9 2 2.5
adjustable 80 800 40/70/100 1.3 1.3 1.3 1.9 1.3 1.5 1.9 1.5 1.9 2 2.5
100 1000 40/70/100 1.5 1.5 1.5 1.5 1.5 2 2.5
125 1250 40/70/100 1.5 1.5 1.5 2 2.5
160 1600 40/70/100 2 2.5

3VF3 16 400 40/70 1.3 1.3 1.3 1.9 1.2 1.3 1.5 1.9 1.5 1.9 2 2.5
for line protection 20 400 40/70 1.3 1.3 1.3 1.9 1.2 1.3 1.5 1.9 1.5 1.9 2 2.5
fixed settings 25 400 40/70 1.3 1.3 1.3 1.9 1.2 1.3 1.5 1.9 1.5 1.9 2 2.5
32 400 40/70/100 1.3 1.3 1.3 1.9 1.2 1.3 1.5 1.9 1.5 1.9 2 2.5
40 400 40/70/100 1.3 1.3 1.3 1.9 1.2 1.3 1.5 1.9 1.5 1.9 2 2.5
50 400 40/70/100 1.3 1.3 1.3 1.9 1.2 1.3 1.5 1.9 1.5 1.9 2 2.5
63 500 40/70/100 1.3 1.3 1.3 1.9 1.3 1.5 1.9 1.5 1.9 2 2.5
80 630 40/70/100 1.3 1.3 1.3 1.5 1.3 1.5 1.5 1.5 1.5 2 2.5
100 800 40/70/100 1.5 1.5 1.5 1.5 1.5 2 2.5
125 1000 40/70/100 1.5 1.5 1.5 2 2.5
160 1280 40/70/100 2 2.5
200 2400 40/70/100
225 2400 40/70/100

3VF3 80 1200 40/70 1.5 1.5 1.5 2 2.5


for motor protection 100 1500 40/70
160 2400 40/70
205 2600 40/70

3VF3 63 1000 70 1.5 1.5 1.5 2 2.5


for starter 100 1500 70 2 2.5
combinations 160 2400 70 2.5

3VF3 100 1500 70 2 2.5


isolating 160 2400 70 2.5
circuit-breakers
Page 14a Page 15a

470034538.xls
Discrimination limits (preliminary) Sheet5 3VF Mains - 3VL Branches
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker


Downstream Circuit Breakers 3VF3 3VF3 3VF4
adjustable fixed settings
In [A] 50 63 80 100 125 160 200 50 63 80 100 125 160 200 225 125 160 200 250
I>> [A] 500 630 800 1000 1250 1600 2000 400 500 630 800 1000 1280 2400 2400 1250 1600 2000 2500
Icn [kA] 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
Discrimination Limit [kA]
3VL-160X 16 300 40/70 1.2 1.3 1.5 1.9 2.5 0.6 0.8 1.3 1.5 3 3 1.3 1.5 2.8 3
for line protection 20 300 40/70 1.2 1.3 1.5 1.9 2.5 0.6 0.8 1.3 1.5 3 3 1.3 1.5 2.8 3
fixed & adj. settings 25 300 40/70 1.2 1.3 1.5 1.9 2.5 0.6 0.8 1.3 1.5 3 3 1.3 1.5 2.8 3
32 300 40/70 1.2 1.3 1.5 1.9 2.5 0.6 0.8 1.3 1.5 3 3 1.3 1.5 2.8 3
40 600 40/70 1.2 1.3 1.5 1.9 2.5 0.8 1.3 1.5 3 3 1.3 1.5 2.8 3
50 600 40/70 1.2 1.3 1.5 1.9 2.5 0.8 1.3 1.5 3 3 1.3 1.5 2.8 3
63 600 40/70 1.3 1.5 1.9 2.5 0.8 1.3 1.5 2.8 2.8 1.3 1.5 2.6 2.9
80 1000 40/70 1.3 1.5 1.9 2 1.3 1.5 2.8 2.8 1.5 2.6 2.9
100 1000 40/70 1.5 1.9 2 1 1.5 2.5 2.5 2.4 2.6
125 1000 40/70 1.9 2 1.5 2.5 2.5 2.4 2.6
160 1600 40/70 2.5 2.5 2.6

3VL-160 50 500 40/70/100 1.2 1.3 1.5 1.9 2.5 0.8 1.3 1.5 3 3 1.3 1.5 2.8 3
for line protection 63 630 40/70/100 1.3 1.5 1.9 2.5 0.8 1.3 1.5 3 3 1.3 1.5 2.6 2.9
fixed settings 80 800 40/70/100 1.3 1.5 1.9 2.5 1.3 1.5 3 3 1.5 2.6 2.9
100 1000 40/70/100 1.5 1.9 2 1.5 2.8 2.8 2.6 2.8
125 1250 40/70/100 1.9 2 2.8 2.8 2.6 2.8
160 1600 40/70/100 2 2.5 2.5 2.6

3VL-160 63 700 40/70


for line protection 80 880 40/70
(electronic) 100 1100 40/70
125 1375 40/70
160 1760 40/70

3VL-160 63 900 70 1.5 1.7 2 2.5 2.5 2 2.5


for starter 100 1500 70 2 2.5 2.5 2 2.5
combinations 160 2500 70

Page 14b Page 15b

470034538.xls
Sheet6
Discrimination limits (preliminary)
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker - (line protection - electronic)


Downstream Circuit Breakers
3VL-160 3VL-250
In [A] 63 80 100 125 160 125 160 200 250
I>> [A] 700 880 1100 1325 1760 1375 1760 2200 2750
Icn [kA] 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
Discrimination Limit [kA]
3VU13 0.6 7 100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
1 12 100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
1.6 19 100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
2.4 29 100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
4 48 100 5 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
6 72 100 2.5 4 10 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
10 120 10 1.2 2.5 3 4 10 5 10 10 10
16 190 6 1.2 1.5 2 3 4 3 4 6 6
20 240 6 1.2 1.5 2 3 4 3 4 6 6
25 300 6 1.2 1.5 2 3 4 3 4 6 6

3VU16 1.6 19 100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
2.4 29 100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
4 48 100 2 5 12 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
6 72 100 1.1 1.8 2.5 3 5 4 6 10 6
10 120 100 1 1.4 1.6 2 3 2.5 3 4 5
15 190 100 1 1.2 1.5 2 3 2 2.5 3.5 4
25 300 100 1 1.2 1.4 1.5 2.5 2 2.5 3 3
32 380 100 1 1.2 1.3 1.5 2 1.5 2 3 3
40 480 35 1 1.2 1.3 1.5 2 1.5 2 3 3
50 500 35 1.1 1.2 1.5 2 1.5 2 3 3
63 600 35 1.1 1.2 2 1.5 2 3 3

3VF1231-1D… 10 120 100 4 7 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
15 190 100 2.5 3 3 4 7 5 7 10 10
20 240 100 1.5 2 2 2.5 4 3 4 6 6
32 380 100 1.5 2 2 2.5 3 3 3 4 4
40 480 42 1.2 1.5 2 2 3 2.5 3 4 4
50 500 30 1.5 1.5 2 3 2 3 4 4
56 672 42 1.5 1.5 2 3 2 3 4 4
63 760 22 1.5 2.5 2 2.5 3 3
65 780 30 1.5 2.5 2 2.5 3 3
80 960 22 1.5 2 1.5 2 3 3

3VL-125 16 300 40/70 1.2 1.3 1.5 1.9 1.3 1.5 2.8 3
for line protection 20 300 40/70 1.2 1.3 1.5 1.9 1.3 1.5 2.8 3
fixed & adj. settings 25 300 40/70 1.2 1.3 1.5 1.9 1.3 1.5 2.8 3
32 300 40/70 1.2 1.3 1.5 1.9 1.3 1.5 2.8 3
40 600 40/70 1.2 1.3 1.5 1.9 1.3 1.5 2.8 3
50 600 40/70 1.2 1.3 1.5 1.9 1.3 1.5 2.8 3
63 600 40/70 1.3 1.5 1.9 1.3 1.5 2.6 2.9
80 1000 40/70 1.3 1.5 1.9 1.5 2.6 2.9
100 1000 40/70 1.5 1.9 2.4 2.6
125 1000 40/70 1.9 2.4 2.6
160 1500 40/70 2.6

3VL-160 50 500 40/70/100 1.2 1.3 1.5 1.9 1.3 1.5 2.8 3
for line protection 63 630 40/70/100 1.3 1.5 1.9 1.3 1.5 2.6 2.9
adj. settings 80 800 40/70/100 1.3 1.5 1.9 1.5 2.6 2.9
100 1000 40/70/100 1.5 1.9 2.6 2.8
125 1250 40/70/100 1.9 2.6 2.8
160 1600 40/70/100 2.6

3VL-160 63 693 40/70 2.3 2.5


for motor protection 80 880 40/70 2.3 2.5
100 1100 40/70
160 1760 40/70

3VL-160 63 900 40/70 1.5 1.7 2.4 2.6


for starter 100 1500 40/70 2.4 2.6
combinations 160 2500 40/70 2.6

Page14c Page15c

470034538.xls
Discrimination limits (preliminary) Sheet7
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker - (line protection - thermal magnetic)


Downstream Circuit Breakers 3VL-400 3VL-630 3VF5 3VF6 3VF7 3VF8

In [A] 200 250 315 400 315 400 500 630 200 250 315 400 315 400 500 630 800 800-1250 1600-2500
I>> [A] 2000 2500 3150 4000 3150 4000 5000 6500 2000 2500 3150 4000 3200 4000 5000 6300 6400 15000 20000
Icn [kA] 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
Discrimination Limit [kA]
3VU13 0.6 7 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
1 12 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
1.6 19 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
2.4 29 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
4 48 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
6 72 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
10 120 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
16 190 6 5 6 6 6 6 6 6 6 5 6 6 6 6 6 6 6 6 6 6
20 240 6 5 6 6 6 6 6 6 6 5 6 6 6 6 6 6 6 6 6 6
25 300 6 5 6 6 6 6 6 6 6 5 6 6 6 6 6 6 6 6 6 6

3VU16 1.6 19 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
2.4 29 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
4 48 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
6 72 100 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
10 120 100 4 6 10 20 45/70/100 45/70/100 45/70/100 45/70/100 4 6 10 20 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
15 190 100 3 4 6 10 12 45/70/100 45/70/100 45/70/100 3 4 6 10 12 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
25 300 100 2.5 3 5 8 8 45/70/100 45/70/100 45/70/100 2.5 3 5 8 8 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
32 380 100 2.5 3 4 6 8 20 35 35 2.5 3 4 6 8 20 35 35 35 35 35
40 480 35 2.5 3 4 6 8 20 35 35 2.5 3 4 6 8 20 35 35 35 35 35
50 500 35 2.5 3 4 6 8 15 35 35 2.5 3 4 6 8 15 35 35 35 35 35
63 600 35 2.5 3 4 6 8 15 12 35 2.5 3 4 6 8 15 12 35 35 35 35

3VF1231-1D… 10 120 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
15 190 100 10 7 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 10 7 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
20 240 100 5 4 5 10 45/70/100 45/70/100 45/70/100 45/70/100 5 4 5 10 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
32 380 100 4 3 4 8 20 45/70/100 45/70/100 45/70/100 4 3 4 8 20 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100
40 480 42 4 3 4 6 10 18 42 42 4 3 4 6 10 18 42 42 42 42 42
50 500 30 3 3 4 6 10 18 30 30 3 3 4 6 10 18 30 30 30 30 30
56 672 42 3 3 4 6 10 18 30 42 3 3 4 6 10 18 30 42 42 42 42
63 760 22 3 3 3 5 10 18 22 22 3 3 3 5 10 18 22 22 22 22 22
65 780 30 3 2.5 3 4 10 12 20 20 3 2.5 3 4 10 12 20 20 20 30 30
80 960 22 3 2.5 3 4 8 10 15 22 3 2.5 3 4 8 10 15 22 22 22 22

3VL-125 16 300 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70 40/70
for line protection 20 300 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70 40/70
fixed & adj. settings 25 300 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70 40/70
32 300 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70 40/70
40 600 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70 40/70
50 600 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70 40/70
63 600 40/70 2 2.3 2.5 3.4 4 5.6 6.4 6.4 2 2.1 2.5 3.4 4 5.6 6.4 8 8 40/70 40/70
80 1000 40/70 2 2.3 2.5 3.4 4 5.6 6.4 6.4 2 2 2.5 3.4 4 5.6 6.4 8 8 40/70 40/70
100 1000 40/70 2 2.3 2.5 3.4 4 5.6 6 6 2 2 2.5 3.4 4 5.6 6 8 8 40/65 40/70
125 1000 40/70 2 2.3 2.5 3.4 4 5.6 6 6 2 2 2.5 3.4 4 5.6 6 8 8 40/65 40/70
160 1500 40/70 2 2.3 2.5 3.4 4 5 6 6 2 2 2.5 3.4 4 5 6 8 8 40/65 40/70

3VL-160 50 500 40/70/100 2.2 2.3 3 3.4 4 5.6 6.4 6.4 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70/70 40/70/100
for line protection 63 630 40/70/100 2 2.1 2.5 3.4 4 5.6 6.4 6.4 2 2.1 2.5 3.4 4 5.6 6.4 8 8 40/70/70 40/70/100
adjustable 80 800 40/70/100 2 2 2.5 3.4 4 5.6 6.4 6.4 2 2 2.5 3.4 4 5.6 6.4 8 8 40/70/70 40/70/100
100 1000 40/70/100 2 2 2.5 3.4 4 5.1 5.5 5.5 2 2 2.5 3.4 4 5.1 5.5 8 8 40/70/70 40/70/100
125 1250 40/70/100 2 2 2.5 3.4 4 5.1 5.5 5.5 2 2 2.5 3.4 4 5.1 5.5 8 8 40/70/70 40/70/100
160 1600 40/70/100 3.4 4 5 5.5 5.5 2.5 3.4 4 5 5.5 6 6 40/65 40/70/100

3VL-160 63 693 40/70 1.7 1.7 2.5 3.4 4 5 6.3 6 1.7 1.7 2.5 3.4 4 5 6.3 6 6 40/70 40/70
for motor protection 80 880 40/70 1.7 1.7 2.5 3.4 4 5 6.3 6 1.7 1.7 2.5 3.4 4 5 6.3 6 6 40/70 40/70
100 1100 40/70 3.4 4 5 6 6 3.4 4 5 6 6 6 40/70 40/70
160 1760 40/70 3.4 4 5 6 6 3.4 4 5 6 6 6 40/70 40/70

3VL-160 63 900 70 2 2 2.5 3.4 4 6 7 8 2 2 2.5 3.4 4 6 7 8 8 50/70 70


for starter 100 1500 70 2.5 3.4 4 6 6.5 6 2.5 3.4 4 6 6.5 6 6 50/70 70
combinations 160 2500 70 3.4 4 5 6 6 3 4 5 6 6 6 50/70 70

3VL - 125 & 160 100 2500 70 2.5 3.4 4 6 6.5 6 2.5 3 4 6 6.5 6 6 50/70/70 70
circuit breaker 160 2500 70 2.5 3.4 4 5 6 6 3 4 5 6 6 6 50/70/70 70
switchs (CBS)
Page 16 & 16b Page 17 & 17b

470034538.xls
Discrimination limits (preliminary) Sheet8
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker


Downstream Circuit Breakers 3VL-400 (T/M) 3VL630 (T/M)

In [A] 200 250 315 400 315 400 500 630


I>> [A] 2000 2500 3150 4000 3200 4000 5000 6300
Icn [kA] 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100

3VF3 50 500 40/70/100 2.2 2.5 3.2 4 3.5 5 6 6.4


for line protection 63 630 40/70/100 2 2.5 3.2 4 3.5 5 6 6.4
adjustable 80 800 40/70/100 2 2.5 3.2 4 3.5 5 6 6.4
100 1000 40/70/100 1.8 2.3 2.5 3.4 3 5 6 6.4
125 1250 40/70/100 1.8 2.3 2.5 3.4 3 4 5 5.5
160 1600 40/70/100 1.8 2.3 2.5 3.4 3 4 5 5.5

3VF3 16 400 40/70 2 2.5 3.2 4 3.5 5 6 6.4


for line protection 20 400 40/70 2 2.5 3.2 4 3.5 5 6 6.4
fixed settings 25 400 40/70 2 2.5 3.2 4 3.5 5 6 6.4
32 400 40/70/100 2 2.5 3.2 4 3.5 5 6 6.4
40 400 40/70/100 2 2.5 3.2 4 3.5 5 6 6.4
50 400 40/70/100 2 2.5 3.2 4 3.5 5 6 6.4
63 500 40/70/100 2 2.5 3.2 4 3.5 5 6 6.4
80 630 40/70/100 2 2.5 3 3.6 3 4 6 6.4
100 800 40/70/100 1.7 2 2.5 3.6 3 4 4.5 6
125 1000 40/70/100 1.7 2 2.5 3.6 3 3.6 4.5 6
160 1280 40/70/100 1.7 2 2.5 3.6 3 3.6 4.5 6
200 2400 40/70/100 3.6 3 3.6 4.5 6
225 2400 40/70/100 3.6 3 3.6 4.5 6

3VF3 80 1200 40/70 1.7 2 2.5 3.4 3 3.6 5 6


for motor protection 100 1500 40/70 1.7 2 2.5 3.4 3 3.6 4.5 6
160 2400 40/70 2.5 3.4 3 3.6 4.5 6
205 2600 40/70 3.4 3 3.6 4.5 6

3VF3 63 1000 70 2 2 2.5 3.6 3 3.6 5 6.4


for starter 100 1500 70 2 2.5 3.6 3 3.6 5 6
combinations 160 2400 70 3.6 3 3.6 5 6

3VF3 100 1500 70 2 2.5 3.6 3 3.6 5 6


isolating 160 2400 70 3.6 3 3.6 5 6
circuit-breakers
Page 16a Page 17a
470034538.xls
Discrimination limits (preliminary) Sheet9
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker


Downstream Circuit Breakers 3VF5 3VF6 3VF7 3VF8 3WN1

In [A] 200 250 315 400 315 400 500 630 800 800-1250 1600-2500 315 400 500 630 800 1000
I>> [A] 2000 2500 3150 4000 3200 4000 5000 6300 6400 15000 20000 3780 4800 6000 7560 9600 12000
Icn [kA] 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100 65 65 80 80 80 80
Discrimination Limit [kA]
3VU13 0.6 7 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
1 12 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
1.6 19 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
2.4 29 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
4 48 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
6 72 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
10 120 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
16 190 6 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
20 240 6 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
25 300 6 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

3VU16 1.6 19 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
2.4 29 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
4 48 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
6 72 100 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 70 50/70/100 70/100 65 65 80 80 80 80
10 120 100 4 6 10 20 45/70/100 45/70/100 45/70/100 8 70 50/70/100 70/100 65 65 80 80 80 80
15 190 100 3 4 6 10 12 45/70/100 45/70/100 8 70 50/70/100 70/100 20 65 80 80 80 80
25 300 100 2.5 3 5 8 8 45/70/100 45/70/100 6 6 50/70/100 70/100 15 40 80 80 80 80
32 380 100 2.5 3 4 6 8 20 35 35 35 35 35 12 25 35 35 35 35
40 480 35 2.5 3 4 6 8 20 35 35 35 35 35 12 20 35 35 35 35
50 500 35 2.5 3 4 6 8 15 35 35 35 35 35 12 20 35 35 35 35
63 600 35 2.5 3 4 6 8 15 12 35 35 35 35 12 20 35 35 35 35

3VF1231-1D… 10 120 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65 65 80 80 80 80
15 190 100 10 7 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50 50 80 80 80 80
20 240 100 5 4 5 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 30 30 80 80 80 80
32 380 100 4 3 4 8 20 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 20 20 80 80 80 80
40 480 42 4 3 4 6 10 18 40/42/42 40/42/42 40/42/42 42 42 15 20 42 42 42 42
50 500 30 3 3 4 6 10 18 30 30 30 30 30 10 20 30 30 30 30
56 672 42 3 3 4 6 10 18 30 40/42/42 40/42/42 42 42 15 20 42 42 42 42
63 760 22 3 3 3 5 10 18 22 22 22 22 22 12 20 22 22 22 22
65 780 30 3 2.5 3 4 10 12 20 20 20 30 30 12 20 30 30 30 30
80 960 22 3 2.5 3 4 8 10 15 22 22 22 22 10 15 22 22 22 22

3VL-125 16 400 40/70 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70 40/65 7 10 15 28 40/50 40/80
for plant protection 20 400 40/70 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70 40/65 7 10 15 28 40/50 40/80
fixed settings 25 400 40/70 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70 40/65 7 10 15 28 40/50 40/80
32 400 40/70/100 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70/70 40/70/100 7 10 15 28 40/50/50 40/70/80
40 400 40/70/100 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70/70 40/70/100 7 10 15 28 40/50/50 40/70/80
50 400 40/70/100 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70/70 40/70/100 7 10 15 28 40/50/50 40/70/80
63 500 40/70/100 2 2.1 2.5 3.4 4 5.6 6.4 8 8 40/70/70 40/70/100 7 10 15 25 40/50/50 40/70/80
80 630 40/70/100 2 2 2.5 3.4 4 5.6 6.4 8 8 40/70/70 40/70/100 7 10 15 25 40/50/50 40/70/80
100 800 40/70/100 2 2 2.5 3.4 4 5.6 6 8 8 40/65 40/70/100 7 10 15 22 35 40/70/80
125 1000 40/70/100 2 2 2.5 3.4 4 5.6 6 8 8 40/65 40/70/100 7 10 15 22 35 40/70/80
160 1280 40/70/100 2 2 2.5 3.4 4 5 6 8 8 40/65 40/70/100 7 10 15 22 35 40/70/80

3VL-160 50 500 40/70/100 2.2 2.3 3 3.4 4 5.6 6.4 8.3 8.3 40/70/70 40/70/100 7 10 15 28 40/50/50 40/70/80
for plant protection 63 630 40/70/100 2 2.1 2.5 3.4 4 5.6 6.4 8 8 40/70/70 40/70/100 7 10 15 25 40/50/50 40/70/80
adjustable 80 800 40/70/100 2 2 2.5 3.4 4 5.6 6.4 8 8 40/70/70 40/70/100 7 10 15 25 40/50/50 40/70/80
100 1000 40/70/100 2 2 2.5 3.4 4 5.1 5.5 8 8 40/70/70 40/70/100 6.4 10 15 25 40/50/50 40/70/80
125 1250 40/70/100 2 2 2.5 3.4 4 5.1 5.5 8 8 40/70/70 40/70/100 6.4 10 15 25 40/50/50 40/70/80
160 1600 40/70/100 2.5 3.4 4 5 5.5 6 6 40/65 40/70/100 6.4 10 15 25 35 40/70/80

3VL-160 80 1200 40/70 1.7 1.7 2.5 3.4 4 5 6.3 6 6 40/70 40/70 7 10 15 22 35 40/70
for motor protection 100 1500 40/70 3.4 4 5 6 6 6 40/70 40/70 7 10 15 22 35 40/70
160 2400 40/70 3.4 4 5 6 6 6 40/70 40/70 7 10 15 22 35 40/70

3VL-160 63 1000 70 2 2 2.5 3.4 4 6 7 8 8 50/70 70 7.3 10 15 22 35 70


for starter 100 1500 70 2.5 3.4 4 6 6.5 6 6 50/70 70 6.9 10 15 22 35 70
combinations 160 2400 70 3 4 5 6 6 6 50/70 70 6.7 10 15 22 35 70

3VL-125 & 160 100 2500 70 2.5 3 4 6 6.5 6 6 70 70


isolating 160 2500 70 3 4 5 6 6 6 70 70
circuit-breakers
Page 16b Page 17b
470034538.xls
Discrimination limits (preliminary) Sheet10
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker (line protection - electronic)


Downstream Circuit Breakers 3VL-400 3VL630 3VL-800 3VL1250 3VL1600 3WN1

In [A] 200 250 315 400 315 400 500 630 630 800 800-1250 1600 315 400 500 630 800 1000
I>> [A] 2200 2750 3465 4400 3465 4400 5500 6300 6930 7500 12500 15000 3780 4800 6000 7560 9600 12000
Icn [kA] 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65 65 80 80 80 80
Discrimination Limit [kA]
3VU13 0.6 7 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65 65 80 80 80 80
1 12 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65 65 80 80 80 80
1.6 19 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65 65 80 80 80 80
2.4 29 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65 65 80 80 80 80
4 48 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65 65 80 80 80 80
6 72 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65 65 80 80 80 80
10 120 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
16 190 6 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
20 240 6 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6
25 300 6 5 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6

3VU16 1.6 19 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 65 65 80 80 80 80
2.4 29 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 65 65 80 80 80 80
4 48 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 65 65 80 80 80 80
6 72 100 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 65 65 80 80 80 80
10 120 100 4 6 10 20 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 65 65 80 80 80 80
15 190 100 3 4 6 10 12 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 20 65 80 80 80 80
25 300 100 2.5 3 5 8 8 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 15 40 80 80 80 80
32 380 100 2.5 3 4 6 8 20 35 35 35 35 35 35 12 25 35 35 35 35
40 480 35 2.5 3 4 6 8 20 35 35 35 35 35 35 12 20 35 35 35 35
50 500 35 2.5 3 4 6 8 15 35 35 35 35 35 35 12 20 35 35 35 35
63 600 35 2.5 3 4 6 8 15 12 12 35 35 35 35 12 20 35 35 35 35

3VF1231-1D… 10 120 100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/70 65 65 80 80 80 80
15 190 100 10 7 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/70 50 50 80 80 80 80
20 240 100 5 4 5 10 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/70 30 30 80 80 80 80
32 380 100 4 3 4 8 20 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/70 20 20 80 80 80 80
40 480 42 4 3 4 6 10 18 42 42 42 42 42 42 15 20 42 42 42 42
50 500 30 3 3 4 6 10 18 30 30 30 30 30 30 10 20 30 30 30 30
56 672 42 3 3 4 6 10 18 30 30 42 42 42 42 15 20 42 42 42 42
63 760 22 3 3 3 5 10 18 22 22 22 22 22 22 12 20 22 22 22 22
65 780 30 3 2.5 3 4 10 12 20 20 20 20 30 30 12 20 30 30 30 30
80 960 22 3 2.5 3 4 8 10 15 15 22 22 22 22 10 15 22 22 22 22

3VL-125 16 300 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 8 8.3 40/70 40/70 7 10 15 28 40/50 40/70
for line protection 20 300 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 8 8.3 40/70 40/70 7 10 15 28 40/50 40/70
fixed settings 25 300 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 8 8.3 40/70 40/70 7 10 15 28 40/50 40/70
32 300 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 8 8.3 40/70 40/70 7 10 15 28 40/50 40/70
40 600 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 8 8.3 40/70 40/70 7 10 15 28 40/50 40/70
50 600 40/70 2.2 2.3 3 3.4 4 5.6 6.4 6.4 8 8.3 40/70 40/70 7 10 15 28 40/50 40/70
63 600 40/70 2 2.1 2.5 3.4 4 5.6 6.4 6.4 7 8 40/70 40/70 7 10 15 25 40/50 40/70
80 1000 40/70 2 2 2.5 3.4 4 5.6 6.4 6.4 7 8 40/70 40/70 7 10 15 25 40/50 40/70
100 1000 40/70 2 2 2.5 3.4 4 5.6 6 6 7 8 40/65 40/70 7 10 15 22 35 40/70
125 1000 40/70 2 2 2.5 3.4 4 5.6 6 6 7 8 40/65 40/70 7 10 15 22 35 40/70
160 1500 40/70 2 2 2.5 3.4 4 5 6 6 7 8 40/65 40/70 7 10 15 22 35 40/70

3VL-160 50 500 40/70/100 2.2 2.3 3 3.4 4 5.6 6.4 6.4 8 8.3 40/70/70 40/70/70 7 10 15 28 40/50/50 40/70/80
for line protection 63 630 40/70/100 2 2.1 2.5 3.4 4 5.6 6.4 6.4 7 8 40/70/70 40/70/70 7 10 15 25 40/50/50 40/70/80
adjustable 80 800 40/70/100 2 2 2.5 3.4 4 5.6 6.4 6.4 7 8 40/70/70 40/70/70 7 10 15 25 40/50/50 40/70/80
100 1000 40/70/100 2 2 2.5 3.4 4 5.1 5.5 5.5 7 8 40/70/70 40/70/70 6.4 10 15 25 40/50/50 40/70/80
125 1250 40/70/100 2 2 2.5 3.4 4 5.1 5.5 5.5 7 8 40/70/70 40/70/70 6.4 10 15 25 40/50/50 40/70/80
160 1600 40/70/100 2.5 3.4 4 5 5.5 5.5 7 7.5 40/65 40/70/70 6.4 10 15 25 35 40/70/80

3VL-160 63 693 40/70 1.7 1.7 2.5 3.4 4 5 6.3 6.3 6 7.5 40/70 40/70 7 10 15 22 35 40/70
for motor protection 80 880 40/70 1.7 1.7 2.5 3.4 4 5 6.3 6.3 6 7.5 40/70 40/70 7 10 15 22 35 40/70
100 1100 40/70 3.4 4 5 6 6 6 7.5 40/70 40/70 7 10 15 22 35 40/70
160 1760 40/70 3.4 4 5 6 6 6 7.5 40/70 40/70 7 10 15 22 35 40/70

3VL3 63 900 70 2 2 2.5 3.4 4 6 7 7 7 7.5 50/70 50/70 7.3 10 15 22 35 70


for starter 100 1500 70 2.5 3.4 4 6 6.5 6.5 6 7.5 50/70 50/70 6.9 10 15 22 35 70
combinations 160 2500 70 3 4 5 6 6 6 7.5 50/70 50/70 6.7 10 15 22 35 70

3VL3 100 2500 70 2.5 3 4 6 6.5 6.5 6 7.5 50/70 50/70


isolating 160 2500 70 3 4 5 6 6 6 7.5 50/70 50/70
circuit-breakers
Page 16c Page 17c

470034538.xls
Discrimination limits (preliminary) 3WN to VL Disc...
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker


Downstream Circuit Breakers 3WN1 3WN6

In [A] 1250 1600 2000 2500 3200 4000 5000 6300 315 400 500 630 800 1000 1250 1600 2000 2500 3200
I>> [A] 15000 19200 24000 30000 37800 48000 60000 75600 4725 6000 7500 9450 12000 15000 18750 24000 24000 37500 48000
Icn [kA] 80 80 80 80 100 100 100 100 65 65 65 65 65 65 65 65 80 80 80
Discrimination Limit [kA]
3VL-160X 16 300 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 27 40/50 40/50 40/65 40/70 40/70 40/70
for line protection 20 300 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 27 40/50 40/50 40/65 40/70 40/70 40/70
fixed & adj. settings 25 300 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 27 40/50 40/50 40/65 40/70 40/70 40/70
32 300 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 27 40/50 40/50 40/65 40/70 40/70 40/70
40 600 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 27 40/50 40/50 40/65 40/70 40/70 40/70
50 600 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 27 40/50 40/50 40/65 40/70 40/70 40/70
63 600 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 25 40 40/50 40/65 40/70 40/70 40/70
80 1000 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 25 40 40/50 40/65 40/70 40/70 40/70
100 1000 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 22 33 35 40/65 40/70 40/70 40/70
125 1000 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 22 33 35 40/65 40/70 40/70 40/70
160 1500 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4.5 6.8 10 14 22 33 35 40/65 40/70 40/70 40/70

3VL-160 50 500 40/70/100 40/70/80 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4.5 6.3 10 14 27 40/65/65 40/65/65 40/65/65 40/70/80 40/70/80 40/70/80
for line protection 63 630 40/70/100 40/70/80 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4.5 6.3 10 14 25 40 40/65/65 40/65/65 40/70/80 40/70/80 40/70/80
adjustable 80 800 40/70/100 40/70/80 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4.5 6.3 10 14 25 40 40/65/65 40/65/65 40/70/80 40/70/80 40/70/80
100 1000 40/70/100 40/70/80 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4.5 6.3 10 14 24 40 40/65/65 40/65/65 40/70/80 40/70/80 40/70/80
125 1250 40/70/100 40/70/80 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4.5 6.3 10 14 24 40 40/65/65 40/65/65 40/70/80 40/70/80 40/70/80
160 1600 40/70/100 40/70/80 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4.5 6.3 10 14 20 35 35 40/65/65 40/70/80 40/70/80 40/70/80

3VL-160 63 693 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 5 6.9 10 15 20 35 40/65 40/65 40/70 40/70 40/70
for motor protection 80 880 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 5 6.9 10 15 20 35 40/65 40/65 40/70 40/70 40/70
100 1100 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 5 6.9 10 15 20 35 40/65 40/65 40/70 40/70 40/70
160 1760 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 5 6.9 10 15 20 35 40/65 40/65 40/70 40/70 40/70

3VL-160 63 900 70 70 70 70 70 70 70 70 70 5.4 7.2 10 15 20 35 65 65 70 70 70


for starter 100 1500 70 70 70 70 70 70 70 70 70 5 6.8 10 15 20 35 65 65 70 70 70
combinations 160 2500 70 70 70 70 70 70 70 70 70 5 6.6 10 15 20 35 65 65 70 70 70

3VL-125 & 160 100 2500 70 70 70 70 70 70 70 70 70 5.4 6.8 10 15 20 35 65 65 70 70 70


isolating 160 2500 70 70 70 70 70 70 70 70 70 5 6.6 10 15 20 35 65 65 70 70 70
circuit-breakers
Page 18 Page 19

470034538.xls
Discrimination limits (preliminary) VL to VF Disc..
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker (line protection - thermal magnetic)


Downstream Circuit Breakers 3VL-250 3VL400 3VL630
line protection
In [A] 125 160 200 250 200 250 315 400 315 400 500 630
I>> [A] 1250 1600 2000 2500 2000 2500 3150 4000 3200 4000 5000 6300
Icn [kA] 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100
Discrimination Limit [kA]
3VL-250 125 1250 40/70/100 1.5 1.8 2.3 2 2.5 3 4 3 4 5 6
for line protection 160 1600 40/70/100 1.8 2.3 2 2.5 3 4 3 4 5 6
200 2000 40/70/100 2.5 3 4 3 4 5 6
250 2500 40/70/100 3 4 3 4 5 6

3VL-250 200 2200 40/70/100 4 3 4 5 6


for line protection 250 2750 40/70/100 4 3 4 5 6
Electronic trip
3VL-250 200 2200 40/70 4 3 4 5 6
for motor protection 250 2750 40/70 4 3 4 5 6

3VL-250 125 2000 70 4 3 4 5 6


for starter 160 2500 70 4 3 4 5 6
combinations 250 3000 70 4 5 6

3VL-250 250 3000 70 4 4 5 6


cir.bkr.switch (CBS)
3VL-400 (T/M) 200 2000 45/70/100 3 4 3 4 5 6
for line protection 250 2500 45/70/100 3 4 5 6
315 3150 45/70/100 4 5 6
400 4000 45/70/100 6

3VL-400 315 3465 45/70/100 4 5


for line protection 400 4400 45/70/100 5
Electronic trip
3VL-400 315 3465 45/70 4 5
for motor protection 400 4400 45/70 5
Electronic trip
3VL-400 200 2500 70 3.4 4 5 6
for starter 250 4000 70 5 6
combinations 400 6000 70 6

3VL-400 400 6000 70


cir.bkr.switch (CBS)
3VL-630 (T/M) 315 3150 45/70/100 6
for line protection 400 4000 45/70/100 6
500 5000 45/70/100
630 6300 45/70/100

3VL-630 500 5500 45/70/100


for line protection 630 6930 45/70/100
Electronic trip
3VL-630 630 6930 45/70
for motor protection 5
3VL-630 315 4000 70
for starter 400 6000 70
combinations 500 6500 70
630 7000 70

3VL-630 630 7000 70


cir.bkr.switch (CBS)
3VL-800 630 6930 50/70/100
for line protection 800 7500 50/70/100

3VL-800 800 7500 70


cir.bkr.switch (CBS)
3VL-1250 800 8800 50/70/100
for line protection 1250 12500 50/70/100

3VL-1250 1250 15000 70


cir.bkr.switch (CBS)
3VL-1600 1600 15000 50/70/100
for line protection
3VL-1600 1600 15000 70
cir.bkr.switch (CBS)
Page 22

470034538.xls
Discrimination limits (preliminary) VF to VL Disc.
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Downstream Circuit Breakers 3VF5 3VF6 3VF7 3VF8 3WN1

In [A] 200 250 315 400 315 400 500 630 800 800-1250 1600-2500 315 400 500 630 800 1000
I>> [A] 2000 2500 3150 4000 3200 4000 5000 6300 6400 15000 20000 3780 4800 6000 7560 9600 12000
Icn [kA] 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50 50/70/100 70/100 65 65 65 65 65 65
Discrimination Limit [kA]
3VL-250 125 1250 40/70/100 2 2 2.5 3.5 3 3.5 4.5 5 5 33 40/65/65 5 7.5 10 14 22 33
for line protection 160 1600 40/70/100 2 2 2.5 3.5 3 3.5 4.5 5 5 33 40/65/65 5 7.5 10 13 22 33
200 2000 40/70/100 2.5 3.5 3 3.5 4.5 5 5 33 40/65/65 5 7.5 10 13 22 33
250 2500 40/70/100 2.5 3.5 3 3.5 4.5 5 5 33 40/65/65 5 7.5 10 13 22 33

3VL-250 200 2200 40/70/100 2.5 3.5 3 3.5 4.5 5 5 27 40/50 5 7.5 10 13 19 28
for line protection 250 2750 40/70/100 3.5 3 3.5 4.5 5 5 27 40/50 5 7.5 10 13 19 28
Electronic trip
3VL-250 200 2200 40/70 2.5 3.5 3 3.5 4.5 5 5 27 40/50 5 7.5 10 13 19 28
for motor protection 250 2750 40/70 3.5 3 3.5 4.5 5 5 27 40/50 5 7.5 10 13 19 28

3VL-250 125 2000 70 2.5 3.5 3 3.5 4.5 5 5 27 50 5 7.5 10 13 19 28


for starter 160 2500 70 3.5 3 3.5 4.5 5 5 27 50 5 7.5 10 13 19 28
combinations 250 3000 70 3.5 3.5 4.5 5 5 27 50 5 7.5 10 13 19 28

3VL-250 250 3000 40/70 3.5 3.5 4.5 5 5 27 40/50 5 7.5 10 13 19 28


cir.bkr.switch (CBS)
3VL-400 (T/M) 200 2000 45/70/100 2.6 3.5 3 3.5 4.5 5 5 20 45/65/65 5 7.5 10 13 20 30
for line protection 250 2500 45/70/100 2.5 3.5 3 3.5 4.5 5 5 20 45/65/65 5 7.5 10 13 19 28
315 3150 45/70/100 3.5 3.5 4.5 5 5 20 45/65/65 5 7.5 10 13 19 28
400 4000 45/70/100 5 20 45/65/65 5 7.5 10 13 19 28

3VL-400 315 3465 45/70/100 3.5 3.5 4.5 5 5 20 45/50 5 7.5 10 13 18 28


for line protection 400 4400 45/70/100 4.5 5 5 20 45/50 5 7.5 10 13 18 28
Electronic trip
3VL-400 315 3465 45/70 3.5 4.5 5 5 20 45/46 5 7.5 10 13 18 28
for motor protection 400 4400 45/70 20 45/46 5 7.5 10 13 18 2
Electronic trip
3VL-400 200 2500 70 3.5 3 3.5 4.5 5 5 20 46 5 7.5 10 13 18 28
for starter 250 4000 70 4.5 5 5 20 46 5 7.5 10 12 18 28
combinations 400 6000 70 5 20 46 7.5 10 12 18 28

3VL-400 400 6000 70 20 46 7 10 12 18 28


cir.bkr.switch (CBS)
3VL-630 (T/M) 315 3150 45/70/100 3.5 3.5 4.5 5 5 20 35 5 7 12 16 22
for line protection 400 4000 45/70/100 4.5 5 5 20 35 5 7 12 16 22
500 5000 45/70/100 20 35 7 12 16 22
630 6300 45/70/100 12 35 7 10 16 22

3VL-630 500 5500 45/70/100 12 20 6 10 10 15


for line protection 630 6930 45/70/100 12 20 10 10 15
Electronic trip
3VL-630 630 6930 45/70 12 20 10 10 15
for motor protection
3VL-630 315 4000 70 17 20 5 10 13 15
for starter 400 6000 70 17 20 10 13 15
combinations 500 6500 70 17 20 10 13 15
630 7000 70 17 20 10 13 15

3VL-630 630 7000 70 15 20 10 15


cir.bkr.switch (CBS)
3VL-800 630 6930 50/70/100 15 20 10 15
for line protection 800 7500 50/70/100 15 20 10 15

3VL-800 800 7500 70 15 20 10 15


cir.bkr.switch (CBS)
3VL-1250 800 8800 50/70/100 15 20 12
for line protection 1250 ### 50/70/100 20

3VL-1250 1250 ### 70 20


cir.bkr.switch (CBS)
3VL-1600 1600 ### 50/70/100 20
for line protection
3VL-1600 1600 ### 70 20
cir.bkr.switch (CBS)
Page 22a Page 23a

470034538.xls
Discrimination limits (preliminary) VL to VF Disc.
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker (line protection - electronic)


Downstream Circuit Breakers 3VL-400 3VL-630 3VL-800 3VL1250 3VL1600

In [A] 200 250 315 400 315 400 500 630 800 800-1250 1600
I>> [A] 2200 2750 3465 4400 3465 4400 5500 6930 7500 12500 15000
Icn [kA] 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100
Discrimination Limit [kA]
3VF4 125 1250 40/70/100 2 2.5 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15
for line protection 160 1600 40/70/100 2 2.5 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15
200 2000 40/70/100 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15
250 2500 40/70/100 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15

3VF4 125 2000 70 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15
for starter 160 2500 70 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15
combinations 200 3000 70 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15

3VF4 250 3000 40/70 4.5 3.4 4.5 5.5 6.8 7.5 12 15
isolating cir. bkr.
3VF5 200 2000 45/70/100 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15
for line protection 250 2500 45/70/100 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15
315 3150 45/70/100 4.5 4.5 5.5 6.8 7.5 12 15
400 4000 45/70/100 4.5 4.5 6.8 7.5 12 15

3VF5 315 4800 40/65 6.8 7.5 12 15


for motor protection
3VF5 200 3000 65 4.5 4.5 5.5 6.8 7.5 12 15
for starter 250 3800 65 4.5 4.5 5.5 6.8 7.5 12 15
combinations 315 4800 65 6.8 7.5 12 15

3VF5 315 4800 40/60 6.8 7.5 12 15


isolating cir. bkr.
3VF6 315 3150 45/70/100 4.5 4.5 5.5 6.8 7.5 12 15
for line protection 400 4000 45/70/100 4.5 5.5 6.8 7.5 12 15
500 5000 45/70/100 6.8 7.5 12 15
630 6300 45/70/100 6.8 7.5 12 15
800 6400 50 7.5 12

3VF6 500 7500 40/65 12 15


for motor protection
3VF6 315 4800 65 6.8 7.5 12 15
for starter 400 6000 65 6.8 7.5 12 15
combinations 500 7500 65 12 15

3VF6 500 7500 40/65 12 15


isolating cir. bkr.
3VF7 800 15000 50/70/100
for line protection 1250 15000 50/70/100

3VF7 800 15000 50/70


isolating cir. bkr. 1250 15000 50/70

3VF8 1600 20000 70/100


for line protection 2000 20000 70/100

3VF8 1600 20000 65


isolating cir. bkr. 2000 20000 65
Page 22b page 23b
470034538.xls
Discrimination limits (preliminary) 3WN to VL Disc.
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker


Downstream Circuit Breakers 3WN1 3WN6

In [A] 1250 1600 2000 2500 3200 4000 5000 6300 315 400 500 630 800 1000 1250 1600 2000 2500 3200
I>> [A] 15000 19200 24000 30000 37800 48000 60000 75600 4725 6000 7500 9450 12000 15000 18750 24000 24000 37500 48000
Icn [kA] 80 80 80 80 100 100 100 100 65 65 65 65 65 65 65 65 80 80 80
Discrimination Limit [kA]
3VL-250 125 1250 40/70/100 40/62 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4.3 6 7.5 10 13 16 25 40/45 40/70 40/70/80 40/70/80
for line protection 160 1600 40/70/100 40/62 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4 6 7.5 10 13 16 25 40/45 40/70 40/70/80 40/70/80
200 2000 40/70/100 40/62 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4 6 7.5 10 13 16 25 40/45 40/70 40/70/80 40/70/80
250 2500 40/70/100 40/62 40/70/80 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4 6 7.5 10 13 16 25 40/45 40/70 40/70/80 40/70/80

3VL-250 200 2200 40/70/100 40/50/50 40/70/70 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4 6 7.5 10 13 16 25 40/45 40/70 40/70/80 40/70/80
for line protection 250 2750 40/70/100 40/50/50 40/70/70 40/70/80 40/70/80 40/70/100 40/70/100 40/70/100 40/70/100 4 6 7.5 10 13 16 25 40/45 40/70 40/70/80 40/70/80
Electronic trip
3VL-250 200 2200 40/70 40/50 40/70 40/70 40/70 40/70/70 40/70/70 40/70/70 40/70/70 4 6 7.5 10 13 16 25 40/45 40/70 40/70 40/70
for motor protection 250 2750 40/70 40/50 40/70 40/70 40/70 40/70/70 40/70/70 40/70/70 40/70/70 4 6 7.5 10 13 16 25 40/45 40/70 40/70 40/70

3VL-250 125 2000 70 48 70 70 70 70 70 70 70 4 6 7.5 10 13 16 25 45 70 70 70


for starter 160 2500 70 48 70 70 70 70 70 70 70 4 6 7.5 10 13 16 25 45 70 70 70
combinations 250 3000 70 48 70 70 70 70 70 70 70 4 6 7.5 10 13 16 25 45 70 70 70

3VL-250 250 3000 40/70 40/48 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4 6 7.5 10 13 16 25 40/45 40/70 40/70 40/70
cir.bkr.switch (CBS)
3VL-400 (T/M) 200 2000 45/70/100 45/50 45/70/70 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 4 6 7 9 13 16 25 40 45/70/80 45/70/80 45/70/80
for line protection 250 2500 45/70/100 45/50 45/70/70 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 4 6 7 9 13 16 25 40 45/70/80 45/70/80 45/70/80
315 3150 45/70/100 45/50 45/70/70 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 4 6 7 9 13 16 25 40 45/70/80 45/70/80 45/70/80
400 4000 45/70/100 45/50 45/70/70 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 4 6 7 9 13 16 25 40 45/70/80 45/70/80 45/70/80

3VL-400 315 3465 45/70/100 45/50 45/70/70 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 4 6 7 9 12 16 25 40 45/70/80 45/70/80 45/70/80
for line protection 400 4400 45/70/100 45/50 45/70/70 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 4 6 7 9 12 16 25 40 45/70/80 45/70/80 45/70/80
Electronic trip
3VL-400 315 3465 45/70 40 45/70 45/70 45/70 45/70 45/70 45/70 45/70 4 6 7 9 12 16 25 40 45/70 45/70 45/70
for motor protection 400 4400 45/70 40 45/70 45/70 45/70 45/70 45/70 45/70 45/70 6 7 9 12 16 25 40 45/70 45/70 45/70
Electronic trip
3VL-400 200 2500 70 40 70 70 70 70 70 70 70 4 6 7 9 12 16 25 40 70 70 70
for starter 250 4000 70 40 70 70 70 70 70 70 70 6 7 9 12 16 25 40 70 70 70
combinations 400 6000 70 40 70 70 70 70 70 70 70 6 7 9 12 16 25 40 70 70 70

3VL-400 400 6000 70 40 70 70 70 70 70 70 70 6 7 9 12 16 25 40 70 70 70


cir.bkr.switch (CBS)
3VL-630 (T/M) 315 3150 45/70/100 32 45/55/55 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 4 6 7 9 10 15 20 32 45/50/50 45/70/80 45/70/80
for line protection 400 4000 45/70/100 32 45/55/55 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 6 7 9 10 15 20 32 45/50/50 45/70/80 45/70/80
500 5000 45/70/100 32 45/55/55 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 6 7 9 10 15 20 32 45/50/50 45/70/80 45/70/80
630 6300 45/70/100 32 45/55/55 45/70/80 45/70/80 45/70/100 45/70/100 45/70/100 45/70/100 7 10 15 20 32 45/50/50 45/70/80 45/70/80

3VL-630 500 5500 45/70/100 28 45 45 45/70/70 45/70/70 45/70/70 45/70/70 45/70/70 7 9 10 15 18 28 34 45/70/80 45/70/80
for line protection 630 6930 45/70/100 28 45 45 45/70/70 45/70/70 45/70/70 45/70/70 45/70/70 9 10 15 18 28 34 45/70/80 45/70/80
Electronic trip
3VL-630 630 6930 45/70 28 45 45 45/70 45/70 45/70 45/70/70 45/70/70 9 10 15 18 28 34 45/55 45/70
for motor protection
3VL-630 315 4000 70 28 40 45 70 70 70 70 70 7 9 10 15 18 28 34 55 70
for starter 400 6000 70 28 40 45 70 70 70 70 70 7 9 10 15 18 28 34 55 70
combinations 500 6500 70 28 40 45 70 70 70 70 70 7 9 10 15 18 28 34 55 70
630 7000 70 28 40 45 70 70 70 70 70 9 10 15 18 28 34 55 70

3VL-630 630 7000 70 28 40 45 70 70 70 70 70 9 10 15 18 28 34 55 70


cir.bkr.switch (CBS)
3VL-800 630 6930 50/70/100 15 20 25 30 35 45 45/60 45/70 9 10 15 18 22 24 35 45
for line protection 800 7500 50/70/100 15 20 25 30 35 45 45/60 45/70 9 10 15 18 22 24 35 45

3VL-800 800 7500 70 15 20 25 30 35 45 60 70 9 10 15 18 22 24 35 45


cir.bkr.switch (CBS)
3VL-1250 800 8800 50/70/100 15 20 25 30 35 45 50/60 50/70 10 15 18 22 24 35 45
for line protection 1250 12500 50/70/100 15 20 25 30 35 45 50/60 50/70 15 18 22 24 35 45

3VL-1250 1250 15000 70 20 25 30 35 45 60 70 18 22 24 35 45


cir.bkr.switch (CBS)
3VL-1600 1600 15000 50/70/100 20 25 30 35 45 50/60 50/70 18 22 22 35 45
for line protection
3VL-1600 1600 15000 70 20 25 30 35 45 60 70 18 22 22 35 45
cir.bkr.switch (CBS)
Page 24 Page 25

470034538.xls
Back-up protection values (preliminary) VL to MCB back up
Series-connected circuit-breakers - miniature circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker (line protection - electronic)


Downstream Miniature Circuit Breakers 3VL160 3VL250 3VL400 3VL630 3VL-800 3VL-1250 3VL-1600 3WN1/3WS1

In [A] 63 80 100 125 160 125 160 200 250 200 250 315 400 315…630 630-800 400…1250 1600 315…6300
I>> [A] 693 880 1100 1375 1760 1375 1760 2200 2750 2200 2750 3465 4400 3465..6930 7500 15000 15000 3780…75600
Icn [kA] 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65…100
Back-up protection values (kA)
5SX2...5 6 6kA/ 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
A -Characteristics 10 10kA 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
5SX2…6 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
5SX4…6 16 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
B - Characteristics 20 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
50 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

5SX2…7 0.5-2 6kA/ 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50
5SX4…7 3 10kA 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
C - Characteristics 4 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
6 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
8 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
16 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 10 10 10 10 10 10 8 8 8 8 8 8 8 8 8 8 8 8
50 10 10 10 10 10 10 8 8 8 8 8 8 8 8 8 8 8 8

5SX2…8 6 3 4.5 4.5 4.5 4 4 4


D - Characteristics 10 4.5 4.5 4.5 4 4 4
5SQ.6. 13 4.5 4.5 4.5 4 4 4
B - Characteristics 16 4.5 4.5 4.5 4 4 4
20 4.5 4.5 4.5 4 4 4
25 4.5 4.5 4.5 4 4 4
32 4.5 4.5 4.5 4 4 4
40 4.5 4.5 4.5 4 4 4

5SQ.7. 0.5-2 3kA 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6


C - Characteristics 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
6 4.5 4.5 4 4 4
8 4.5 4.5 4 4 4
10 4.5 4.5 4 4 4
13 4.5 4.5 4 4 4
16 4.5 4.5 4 4 4
20 4.5 4.5 4 4 4
25 4.5 4.5 4 4 4
32 4.5 4.5 4 4 4
40 4.5 4.5 4 4 4
50 4.5 4.5 4 4 4
63 4.5 4.5 4 4 4

Page 28 Estimates Only Must be confirmed by tests according to 947-2 (annex A) Page 29

470034538.xls
Back-up protection values (preliminary) 3VL to 3VF Backup
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker


Downstream Circuit Breakers 3VU16 3VF1231-1D 3VL160X 3VL160 3VL250 3VL400 3VL630 3VL800 3VL1250 3VL1600

In [A] 1.6/2.5 32/63 10 16 25 32 40 50 56 63 65 16-160 50-160 125-250 200-400 315-630 630-800 800-1250 1250-1600
I>> [A] 19/300 300/600 120 192 300 380 480 600 ### 760 780 300-1600 500-1600 1250-2500 2000-4000 3150-6300 7500 12500 15000
Icn [kA] 100 35 100 100 100 100 42 30 42 22 30 40/70 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100
Back-up protection values (kA)
3VU13 6 72 100
10 120 10 100 35 100 100 100 42 42 18 18 18 15/15 15/15/20 15/15/15
16 192 6 20 15 30 25 22 20 15 12 12 10/10 ### ###
20 240 6 15 25 22 18 15 12 10 10 10/10 ### ###
25 300 6 15 22 16 15 12 10 10 10/10 ### ###

3VU16 25 300 100


32 380 35 40/65 40/65/70 40/50/65
40 480 35 40/65 40/65/70 40/50/65
50 600 35 40/65 40/65/70 40/50/65
60 600 35 40/65 40/65/70 40/50/65

3VF1231-1D 32 380 100


40 480 42 70 . 40/70/100 40/65/70 45/65/65 45/65/65
50 600 30 40/70 40/70/100 40/65/70 45/65/65 45/65/65
56 672 42 70 . 40/70/100 40/65/70 45/65/65 45/65/65
63 760 22 40/70 40/70/100 40/65/70 45/65/65 45/65/65 30/30/30 30/30/30 30/30/30
65 760 22 40/70 40/70/100 40/65/70 45/65/65 45/65/65 30/30/30 30/30/30 30/30/30
80 960 22 40/70 40/70/100 40/65/70 45/65/65 45/65/65 30/30/30 30/30/30 30/30/30

3VL160X 16 300 40 70 . 70/100 70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100


… … 70 100 100 100 100 100 100 100
160 1600 ---

3VL-160 50 500 40 70/100 70/100 70/100 45/70/100 45/70/100 50/70/100 50/70/100


… … 70 100 100 100 100 100 100 100
160 1600 100

3VL-250 125 1250 40 70/100 70/100 45/70/100 40/65/100 50/70/100 50/70/100


… … 70 100 100 100 100 100 100
250 2500 100

3VL-400 200 2000 45 70/100 70/100 70/100 50/70/100 50/70/100


… … 70 100 100 100 100 100
400 4000 100

3VL-630 315 3200 45 70/100 70/100 50/70/100 50/70/100


… … 70 100 100 100 100
630 6300 100

3VL-800 630 7500 45 70/100 50/70/100 50/70/100


… 7500 70 100 100 100
800 7500 100

3VL1250 800 ### 50 70/100 70/100


… ### 70 100 100
1250 ### 100

3VL-1600 1250 ### 50 70/100


… ### 70 100
1600 ### 100

3VF3 50 400 40 70 70/100 70/100 70/100 45/70/100 45/70/100 50/70/100 65/65


… … 70 100 100 100 100 100 100
160 1600 100

3VF4 125 1250 40 70/100 45/70/100 45/65/100 50/65/65 65/65


… … 70 100 100 100
250 2500 100

3VF5 200 2000 45 45/70/100 45/70/100 50/65/65 65/65


… … 70 100 100
400 4000 100

3VF6 315 3200 45 50/65 65/65


… … 70
630 6300 100

Page 30/30a Estimates Only Must be confirmed by tests according to 947-2 (annex A) Page 31/31a

470034538.xls
Back-up protection values (preliminary) 3VU to 3VL
Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker


Downstream Circuit Breakers 3VU16 3VF1231-1D 3VF3 3VF4 3VF5 3VF6 3VF6 3VF7 3VF8

In [A] 1.6/2.5 32/63 10 16 25 32 40 50 56 63 65 50-160 125-250 200-400 315 400-630 400-1250 1600-2000
I>> [A] 19/300 300/600 120 192 300 380 480 600 672 760 780 400-1600 1250-2500 2000-4000 3200 4000-6300 15000 20000
Icn [kA] 100 35 100 100 100 100 42 30 42 22 30 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 50/70/100 70/100
Back-up protection values (kA)
3VU13 6 72 100
10 120 10 100 35 100 100 100 42 42 18 18 18 15/15/15
16 192 6 20 15 30 25 22 20 15 12 12 10/10/10
20 240 6 15 25 22 18 15 12 10 10 10/10/10
25 300 6 15 22 16 15 12 10 10 10/10/10

3VU16 25 300 100


32 380 35 40/65/65 40/50/50
40 480 35 40/65/65 40/50/50
50 600 35 40/65/65 40/50/50
60 600 35 40/65/65 40/50/50

3VF1231-1D 32 380 100


40 480 42 65/65 65/65 65/65 45/65/65
50 600 30 40/65/65 40/65/70 40/65/70 45/65/65
56 672 42 65/65 65/70 65/70 45/65/65
63 760 22 40/65/65 40/65/70 40/65/70 45/65/65
65 760 22 40/65/65 40/65/70 40/65/70 45/65/65 30/30/30 30/30/30 30/30
80 960 22 40/65/65 40/65/70 40/65/70 45/65/65

3VL160X 16 300 40 70/100 70/100 70/100 45/70/100 45/70/100 50/70 70


… … 70 100 100 100 100 100
160 1600 ---

3VL-160 50 500 40 70/100 70/100 70/100 45/70/100 45/70/100 50/70 70


… … 70 100 100 100 100 100
160 1600 100

3VL-250 125 1250 40 70/100 70/100 70/100 45/70/100 50/70 70


… … 70 100 100 100 100
250 2500 100

3VL-400 200 2000 45 70/100 70/100 50/65/65 70


… … 70 100 100
400 4000 100

3VL-630 315 3200 45 70/100 70 70


… … 70 100
630 6300 100

3VL-800 630 7500 45 70/100 70/100


… 7500 70 100 100
800 7500 100

3VL1250 800 12500 50 70/100 70/100


… 12500 70 100 100
1250 12500 100

3VL-1600 1250 15000 50 70/100


… 15000 70 100
1600 15000 100

Page 30b Estimates Only Must be confirmed by tests according to 947-2 (annex A) Page 31b

470034538.xls
3VU to 3VL

1600-2000

470034538.xls
3VL to 3VF

Discrimination limits (preliminary)


Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker (line protection - electronic)


Downstream Circuit Breakers 3VL-250 3VL400 3VL630 3VL-800 3VL1250 3VL1600 3WN1
line protection
In [A] 125 160 200 250 200 250 315 400 315 400 500 630 800 800-1250 1600 315 400 500 630 800 1000
I>> [A] 1375 1760 2200 2750 2200 2750 3465 4400 3465 4400 5500 6930 7500 12500 15000 3780 4800 6000 7560 9600 12000
Icn [kA] 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 65 65 80 80 80 80
Discrimination Limit [kA]
3VL-250 125 1250 40/70/100 1.5 2 2.5 2.2 2.7 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.4 7.5 10 14 22 33
for line protection 160 1600 40/70/100 2 2.5 2.2 2.7 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
200 2000 40/70/100 2.5 2.2 2.7 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
250 2500 40/70/100 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33

3VL-250 200 2200 40/70/100 2.7 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
for line protection 250 2750 40/70/100 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
Electronic trip
3VL-250 200 2200 40/70 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
for motor protection 250 2750 40/70 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33

3VL-250 125 2000 70 2.7 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
for starter 160 2500 70 3.4 4.5 3.4 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
combinations 250 3000 70 4.5 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 19 28

3VL-250 250 3000 40/70 3.4 4.5 4.5 5.5 6.8 7.5 12 15 5.3 7.5 10 13 19 28
cir.bkr.switch (CBS)
3VL-400 (T/M) 200 2000 45/70/100 2.7 3.4 4 3.4 4 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
for line protection 250 2500 45/70/100 3.4 4 3.4 4 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
315 3150 45/70/100 3.4 4 3.4 4 5.5 6.8 7.5 12 15 7.5 10 13 19 28
400 4000 45/70/100 5.5 6.8 7.5 12 15 10 13 19 28

3VL-400 315 3465 45/70/100 4 4 5.5 6.8 7.5 12 15 7.5 10 13 18 28


for line protection 400 4400 45/70/100 5.5 6.8 7.5 12 15 10 13 18 28
Electronic trip
3VL-400 315 3465 45/70 4 4 5.5 6.8 7.5 12 15 7.5 10 13 18 28
for motor protection 400 4400 45/70 5.5 6.8 7.5 12 15 10 13 18 28
Electronic trip
3VL-400 200 2500 70 4 3 4 5.5 6.8 7.5 12 15 5.3 7.5 10 13 22 33
for starter 250 4000 70 5.5 6.8 7.5 12 15 7.5 10 12 18 28
combinations 400 6000 70 7.5 12 15 12 18 28

3VL-400 400 6000 70 7.5 12 15 10 12 18 28


cir.bkr.switch (CBS)
3VL-630 (T/M) 315 3150 45/70/100 4 4 5.5 6.8 7.5 12 15 7.5 9 12 18 28
for line protection 400 4000 45/70/100 5.5 6.8 7.5 12 15 9 12 16 22
500 5000 45/70/100 6.8 7.5 12 15 12 16 22
630 6300 45/70/100 7.5 12 15 16 22

3VL-630 500 5500 45/70/100 6.8 7.5 12 15 10 13 17


for line protection 630 6930 45/70/100 12 15 13 17
Electronic trip
3VL-630 630 6930 45/70 12 15 13 17
for motor protection
3VL-630 315 4000 70 5.5 6.8 7.5 12 15 7.5 9 10 13 15
for starter 400 6000 70 7.5 12 15 10 13 15
combinations 500 6500 70 7.5 12 15 13 15
630 7000 70 12 15 13 15

3VL-630 630 7000 70 12 15 13 15


cir.bkr.switch (CBS)
3VL-800 630 6930 50/70/100 12 15 10 15
for line protection 800 7500 50/70/100 12 15 15

3VL-800 800 7500 70 12 15 15


cir.bkr.switch (CBS)
3VL-1250 800 8800 50/70/100 12 15
for line protection 1250 12500 50/70/100 15

3VL-1250 1250 15000 70


cir.bkr.switch (CBS)
3VL-1600 1600 15000 50/70/100
for line protection
3VL-1600 1600 15000 70
cir.bkr.switch (CBS)
Page 22c page 23c

470034538.xls
3VL4&5 to 3V4&6F

Discrimination limits (preliminary)


Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker (line protection - thermal magnetic)


Downstream Circuit Breakers 3VL-400 3VL-630

In [A] 200 250 315 400 315 400 500 630


I>> [A] 2000 2500 3150 4000 3200 4000 5000 6300
Icn [kA] 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100
Discrimination Limit [kA]
3VF4 125 1250 40/70/100 2 2.3 3 4 3 4 4.5 6
for line protection 160 1600 40/70/100 2 2.3 3 4 3 4 4.5 6
200 2000 40/70/100 2.3 3 4 3 4 4.5 6
250 2500 40/70/100 3 4 3 4 4.5 6

3VF4 125 2000 70 2.3 3 4 3 4 4.5 6


for starter 160 2500 70 3 4 3 4 4.5 6
combinations 200 3000 70 4 3 4 4.5 6

3VF4 250 3000 40/70 4 4 4.5 6


isolating cir. bkr.
3VF5 200 2000 45/70/100 3 4 3 4 4.5 6
for line protection 250 2500 45/70/100 3 4 3 4 4.5 6
315 3150 45/70/100 4 4 4.5 6
400 4000 45/70/100 6

3VF5 315 4800 40/65 6


for motor protection
3VF5 200 3000 65 4 4 4.5 6
for starter 250 3800 65 4.5 6
combinations 315 4800 65 6

3VF5 315 4800 40/60 6


isolating cir. bkr.
3VF6 315 3150 45/70/100 6
for line protection 400 4000 45/70/100 6
500 5000 45/70/100
630 6300 45/70/100
800 6400 50

3VF6 500 7500 40/65


for motor protection
3VF6 315 4800 65 6
for starter 400 6000 65
combinations 500 7500 65

3VF6 500 7500 40/65


isolating cir. bkr.
3VF7 800 15000 50/70/100
for line protection 1250 15000 50/70/100

3VF7 800 15000 50/70


isolating cir. bkr. 1250 15000 50/70

3VF8 1600 20000 70/100


for line protection 2000 20000 70/100

3VF8 1600 20000 65


isolating cir. bkr. 2000 20000 65
page 22d page 23d

470034538.xls
VL to VF Disc

Discrimination limits (preliminary)


Series-connected circuit-breakers - circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker (line protection - electronic)


Downstream Circuit Breakers 3VL-400 3VL630 3VL-800 3VL1250 3VL1600

In [A] 200 250 315 400 315 400 500 630 630 800 800-1250 1600
I>> [A] 2200 2750 3465 4400 3465 4400 5500 6300 6930 7500 12500 15000
Icn [kA] 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100
Discrimination Limit [kA]
3VF3 16 400 40/70 2.2 2.7 4 5 4 5 6 6.4 8.3 8.3 40/70 40/70
for line protection 20 400 40/70 2.2 2.7 4 5 4 5 6 6.4 8.3 8.3 40/70 40/70
fixed settings 25 400 40/70 2.2 2.7 4 5 4 5 6 6.4 8.3 8.3 40/70 40/70
32 400 40/70/100 2.2 2.7 4 5 4 5 6 6.4 8.3 8.3 40/70/70 40/70/70
40 400 40/70/100 2.2 2.7 4 5 4 5 6 6.4 8.3 8.3 40/70/70 40/70/70
50 400 40/70/100 2.2 2.7 4 5 4 5 6 6.4 8.3 8.3 40/70/70 40/70/70
63 500 40/70/100 2 2.7 4 5 4 5 6 6.4 8 8 40/70/70 40/70/70
80 630 40/70/100 2 2.7 4 5 4 5 6 6.4 8 8 40/70/70 40/70/70
100 800 40/70/100 2 2.4 3.5 4.5 3.5 4.5 5.5 6 8 8 40/65 40/70/70
125 1000 40/70/100 2 2.4 3.5 4.5 3.5 4.5 5.5 6 8 8 40/65 40/70/70
160 1280 40/70/100 2 2.4 3.5 4.5 3.5 4.5 5.5 6 8 8 40/65 40/70/70

3VF3 50 500 40/70/100 2.2 2.7 4 5 4 5 6 6.4 8.3 8.3 40/70/70 40/70/70
for line protection 63 630 40/70/100 2 2.7 4 5 4 5 6 6.4 8 8 40/70/70 40/70/70
adjustable 80 800 40/70/100 2 2.4 4 5 4 5 6 6.4 8 8 40/70/70 40/70/70
100 1000 40/70/100 2 2.4 3.5 4.5 3.5 4.5 5.5 6 8 8 40/70/70 40/70/70
125 1250 40/70/100 2 2.4 3.5 4.5 3.5 4.5 5.5 6 8 8 40/70/70 40/70/70
160 1600 40/70/100 3.5 4.5 3.5 4.5 5.5 6 6.5 7 40/65 40/70/70
200 2400 40/70/100 3.5 4.5 3.5 4.5 5.5 6 6.5 7 40/65 40/70/70
225 2400 40/70/100 3.5 4.5 3.5 4.5 5.5 6 6.5 7 40/65 40/70/70

3VF3 80 1200 40/70 1.7 2.5 4 5 4 5 6 4 7 7.5 40/70 40/70


for motor protection 100 1500 40/70 1.7 2.5 4 5 4 5 6 4 7 7.5 40/70 40/70
160 2400 40/70 4 5 4 5 6 4 7 7.5 40/70 40/70
205 2600 40/70 4 5 4 5 6 4 7 7.5 40/70 40/70

3VF3 63 1000 70 2 2.5 4 5 4 5 6.5 7 8 8.5 50/70 50/70


for starter 100 1500 70 2 2.5 3.5 4.5 3.5 4.5 6.5 6.5 7 7.5 50/70 50/70
combinations 160 2400 70 3.5 4.5 3.5 4.5 6 6.5 7 7.5 50/70 50/70

3VF3 100 1500 70 2 2.5 3.5 4.5 3.5 4.5 6.5 7 7 7.5 50/70 50/70
isolating 160 2400 70 3.5 4.5 3.5 4.5 6 6.5 7 7.5 50/70 50/70
circuit-breakers
Page 16d Page 17d

470034538.xls
VL to MCB Backup

Back-up protection values (preliminary)


Series-connected circuit-breakers - miniature circuit-breakers 400V, 50 Hz

Upstream Circuit Breaker - (line protection - thermal magnetic)


Downstream Miniature Circuit Breake 3VL-160X 3VL-160 3VL-250 3VL-400 3VL-630
(Fixed/Fixed) (Adj./Adj. (Adj./Adj.) (Adj./Adj.) (Adj./Adj.)
In [A] 50 63 80 100 125 160 50 63 80 100 125 160 125 160 200 250 200 250 315 400 315..630
I>> [A] 600 600 1000 1000 1000 1600 500 630 800 1000 1250 1600 1250 1600 2000 2500 2000 2500 3150 4000 3150..6300
Icn [kA] 40/70 40/70 40/70 40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100
Back-up protection values (kA)
5SX2...5 6 6kA/ 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
A -Characteristics 10 10kA 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
5SX2…6 13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
5SX4…6 16 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
B - Characteristics 20 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10
50 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10 10

5SX2…7 0.5-2 6kA/ 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50
5SX4…7 3 10kA 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
C - Characteristics 4 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35 35
6 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
8 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
13 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
16 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
20 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
25 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
32 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15 15
40 10 10 10 10 10 10 10 10 10 10 10 10 10 8 8 8 8 8 8 8 8
50 10 10 10 10 10 10 10 10 10 10 10 8 8 8 8 8 8 8 8

5SX2…8 6 3 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4


D - Characteristics 10 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
5SQ.6. 13 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
B - Characteristics 16 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
20 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
25 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
32 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
40 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4

5SQ.7. 0.5-2 3kA 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6 6


C - Characteristics 3 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4 4
6 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
8 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
10 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
13 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
16 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
20 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
25 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
32 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
40 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
50 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4
63 4.5 4.5 4 4 4 4 4.5 4.5 4.5 4 4 4 4 4

page 28a Estimates Only Must be confirmed by tests according to 947-2 (annex A) page 29a

470034538.xls
Preliminary Discrimination limits / Selektivitätsgrenzen

Series-connection circuit-breakers - circuit-breakers AC 400 V, 50 Hz


Reihenschaltung Leistungsschalter - Leistungsschalter bei AC 400 V, 50 Hz

Downstream circuit-breakers
Nachgeordnete Leistungsschalter 3VL1 VL160X 3VL1 VL160X 3VL2 VL160
fix therm/ fix mag (TM) adjustable therm/ fix mag (TM) adjustable therm/ adjustable mag (TM)
ETU
Tripping In (A) 16 20 25 32 40 50 63 80 100 125 160 20 25 32 40 50 63 80 100 125 160 50 63 80
Characteristics I > (A) 350 350 350 350 600 600 600 1000 1000 1000 1600 350 350 350 600 600 600 1000 1000 1000 1600 500 630 800
Icn (kA) 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70/100 40/70/100 40/70/100

5SQ B 6 3 1.2 1.2 1.2 1.2 2.5 2.5 2.5 2.6 2.6 2.6 3.0 1.2 1.2 1.2 2.5 2.5 2.5 2.6 2.6 2.6 3.0 1.2 2.5 2.5
(L) 10 3 0.8 0.8 0.8 0.8 1.5 1.5 1.5 1.9 1.9 1.9 2.5 0.8 0.8 0.8 1.5 1.5 1.5 1.9 1.9 1.9 2.5 0.8 1.5 1.7
13 3 0.7 0.7 0.7 1.2 1.2 1.2 1.5 1.5 1.5 2.0 0.7 0.7 0.7 1.2 1.2 1.2 1.5 1.5 1.5 2.0 0.7 1.2 1.3
16 3 0.7 0.7 1.2 1.2 1.2 1.5 1.5 1.5 2.0 0.7 0.7 1.2 1.2 1.2 1.5 1.5 1.5 2.0 0.7 1.2 1.3
20 3 0.7 1.2 1.2 1.2 1.5 1.5 1.5 2.0 0.7 1.2 1.2 1.2 1.5 1.5 1.5 2.0 0.7 1.2 1.3
25 3 1.0 1.0 1.0 1.2 1.2 1.2 2.0 1.0 1.0 1.0 1.2 1.2 1.2 2.0 0.7 1.0 1.1
32 3 1.0 1.0 1.2 1.2 1.2 2.0 1.0 1.0 1.2 1.2 1.2 2.0 0.7 1.0 1.1
40 3 1.0 1.2 1.2 1.2 1.5 1.0 1.2 1.2 1.2 1.5 1.0 1.1

C 0.5-2 3 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
(G,U) 3 3 1.2 1.2 1.2 1.2 2.3 2.3 2.3 2.5 2.5 2.5 3.0 1.2 1.2 1.2 2.3 2.3 2.3 2.5 2.5 2.5 3.0 1.2 2.3 2.4
4 3 1.2 1.2 1.2 1.2 2.3 2.3 2.3 2.5 2.5 2.5 3.0 1.2 1.2 1.2 2.3 2.3 2.3 2.5 2.5 2.5 3.0 1.2 2.3 2.4
6 3 1.2 1.2 1.2 1.2 2.3 2.3 2.3 2.5 2.5 2.5 3.0 1.2 1.2 1.2 2.3 2.3 2.3 2.5 2.5 2.5 3.0 1.2 2.3 2.4
8 3 0.8 0.8 0.8 0.8 1.4 1.4 1.4 1.9 1.9 1.9 2.5 0.8 0.8 0.8 1.4 1.4 1.4 1.9 1.9 1.9 2.5 0.8 1.4 1.6
10 3 0.8 0.8 0.8 0.8 1.4 1.4 1.4 1.9 1.9 1.9 2.5 0.8 0.8 0.8 1.4 1.4 1.4 1.9 1.9 1.9 2.5 0.8 1.4 1.6
13 3 0.7 0.7 0.7 1.0 1.0 1.0 1.5 1.5 1.5 2.0 0.7 0.7 0.7 1.0 1.0 1.0 1.5 1.5 1.5 2.0 0.7 1.0 1.2
16 3 0.7 0.7 1.0 1.0 1.0 1.5 1.5 1.5 2.0 0.7 0.7 1.0 1.0 1.0 1.5 1.5 1.5 2.0 0.7 1.0 1.2
20 3 0.7 1.0 1.0 1.0 1.5 1.5 1.5 2.0 0.7 1.0 1.0 1.0 1.5 1.5 1.5 2.0 0.7 1.0 1.2
25 3 1.0 1.0 1.0 1.2 1.2 1.2 2.0 1.0 1.0 1.0 1.2 1.2 1.2 2.0 0.7 1.0 1.1
32 3 1.0 1.0 1.2 1.2 1.2 2.0 1.0 1.0 1.2 1.2 1.2 2.0 0.7 1.0 1.1
40 3 1.0 1.2 1.2 1.2 2.0 1.0 1.2 1.2 1.2 2.0 1.0 1.1
50 3 1.2 1.2 1.2 2.0 1.2 1.2 1.2 2.0 1.1
63 3 1.2 1.2 1.2 2.0 1.2 1.2 1.2 2.0
3VL3 VL250 3VL4 VL400 3VL5 VL630 3VL6 VL800 3VL7 VL1250 3VL8 VL1600
adj. therm/ adj. mag (TM) adj. therm/ adj. mag (TM) adj. therm/ adj. mag (TM)
ETU ETU ETU ETU ETU ETU
100 125 160 125 160 200 250 200 250 315 400 315 400 500 630 630 800 1000 1250 1600
1000 1250 1600 1250 1600 2000 2500 2000 2500 3150 4000 3150 4000 5000 6300 7000 7500 11000 12500 15000
40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100

2.6 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.9 2.0 2.5 2.0 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.5 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.5 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.5 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.2 1.8 2.0 1.8 2.0 2.0 2.0 2.0 2.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.2 1.8 2.0 1.8 2.0 2.0 2.0 2.0 2.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.2 1.8 2.0 1.8 2.0 2.0 2.0 2.0 2.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0

3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.5 2.5 3.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.5 2.5 3.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
2.5 2.5 3.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.9 2.0 2.5 2.0 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.9 2.0 2.5 2.0 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.5 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.5 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.5 2.0 2.0 2.0 2.0 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.2 1.8 2.0 1.8 2.0 2.0 2.0 2.0 2.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.2 1.8 2.0 1.8 2.0 2.0 2.0 2.0 2.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.2 1.7 2.0 1.7 2.0 2.0 2.0 2.0 2.0 2.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.2 1.7 2.0 1.7 2.0 2.0 2.0 2.0 2.0 2.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
1.2 1.7 2.0 1.7 2.0 2.0 2.0 2.0 2.0 2.0 2.5 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0 3.0
Discrimination limits / Selektivitätsgrenzen

Series-connection circuit-breakers - circuit-breakers AC 400 V, 50 Hz


Reihenschaltung Leistungsschalter - Leistungsschalter bei AC 400 V, 50 Hz

Upstream circuit-breakers
Downstream circuit-breakers Vorgeordnete Leistungsschalter
Nachgeordnete Leistungsschalter 3VF22 3VL1 VL160X 3VL1 VL160X
fix therm/ fix mag (TM) fix therm/ fix mag (TM) adjustable therm/ fix mag (TM)

In (A) 16 20 25 32 40 50 63 80 100 125 16 20 25 32 40 50 63 80 100 125 160 16-20 20-25 25-32 32-40 40-50 50-63
I > (A) 3) 350 450 500 600 750 750 800 900 1000 1000 350 350 350 350 600 600 600 1000 1000 1000 1600 350 350 350 600 600 600
Icn (kA) 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
Discrimination limits (kA) / Selektivitätsgrenzen (kA)
3RV1.1 1 12 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
1,25 15 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
1,6 19 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
2 24 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
2,5 30 100 10 10 10 10 10 10 18/25 18/25 18/25 18/25 10 10 10 10 40/70 40/70 40/70 40/70 40/70 40/70 40/70 10 10 10 40/70 40/70 40/70
3,2 38 100 1.5 1.5 1.5 1.5 1.5 1.5 18/25 18/25 18/25 18/25 1.5 1.5 1.5 1.5 40/70 40/70 40/70 40/70 40/70 40/70 40/70 1.5 1.5 1.5 40/70 40/70 40/70
4 48 100 1.2 1.2 1.2 1.2 1.2 1.2 6 6 6 6 1.2 1.2 1.2 1.2 6 6 6 40/70 40/70 40/70 40/70 1.2 1.2 1.2 6 6 6
5 60 100 1 1 1 1 1 1 3 3 3 3 1 1 1 1 3 3 3 10 10 10 40/70 1 1 1 3 3 3
6,3 76 100 1 1 1 1 1 1 2.5 2.5 2.5 2.5 1 1 1 1 2.5 2.5 2.5 6 6 6 40/70 1 1 1 2.5 2.5 2.5
8 96 50 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 8 1.5 1.5 1.5
10 120 50 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 5 1.5 1.5 1.5
12 144 50 1.2 1.2 1.2 1.2 1.2 1.2 1.2 2 2 2 4 1.2 1.2 1.2

3RV1.2 1 12 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
1,25 15 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
1,6 19 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
2 24 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
2,5 30 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
3,2 38 100 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 18/25 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70 40/70
4 48 100 18/20 18/20 18/20 18/20 18/20 18/20 18/25 18/25 18/25 18/25 20 20 20 20 40/70 40/70 40/70 40/70 40/70 40/70 40/70 20 20 20 40/70 40/70 40/70
5 60 100 6 6 6 6 6 6 18/25 18/25 18/25 18/25 6 6 6 6 40/70 40/70 40/70 40/70 40/70 40/70 40/70 6 6 6 40/70 40/70 40/70
6,3 76 100 4 4 4 4 4 4 18/25 18/25 18/25 18/25 4 4 4 4 40/70 40/70 40/70 40/70 40/70 40/70 40/70 4 4 4 40/70 40/70 40/70
8 96 100 2 2 2 2 2 2 18/25 18/25 18/25 18/25 2 2 2 2 40/70 40/70 40/70 40/70 40/70 40/70 40/70 2 2 2 40/70 40/70 40/70
10 120 100 1 1 1 1 1 1 6 6 6 6 1 1 1 1 6 6 6 6 6 6 40/70 1 1 1 6 6 6
12,5 150 100 1 1 1 1 1 1 6 6 6 6 1 1 1 1 6 6 6 6 6 6 40/70 1 1 1 6 6 6
16 192 50 3 3 3 3 3 3 3 6 6 6 40/50 3 3 3
20 240 50 2.5 2.5 2.5 2.5 2.5 2.5 2.5 4 4 4 40/50 2.5 2.5 2.5
22 264 50 1.5 1.5 1.5 1.5 1.5 1.5 1.5 3 3 3 6 1.5 1.5 1.5
25 300 50 1.5 1.5 1.5 1.5 1.5 1.5 1.5 2.5 2.5 2.5 6 1.5 1.5 1.5

3RV1.3 16 192 50 4 4 4 4 4 4 4 40/50 40/50 40/50 40/50 4 4 4


20 240 50 2.5 2.5 2.5 2.5 2.5 2.5 2.5 6 6 6 40/50 2.5 2.5 2.5
25 300 50 2 2 2 2 2 2 2 4 4 4 10 2 2 2
32 384 50 1.2 1.2 1.2 1.2 1.2 1.2 1.2 2 2 2 5 1.2 1.2 1.2
40 480 50 1 1 1 1 1 1 1 2 2 2 4 1 1 1
45 540 50 0.8 0.8 0.8 0.8 0.8 0.8 0.8 1.5 1.5 1.5 3 0.8 0.8 0.8
50 600 50 1.5 1.5 1.5 3

3RV1.4 16 192 100 3 3 3 3 3 3 3 8 8 8 40 3 3 3


20 240 100 2 2 2 2 2 2 2 3 3 3 5 2 2 2
25 300 100 1.5 1.5 1.5 1.5 1.5 1.5 1.5 3 3 3 5 1.5 1.5 1.5
32 384 100 1.2 1.2 1.2 1.2 1.2 1.2 1.2 1.5 1.5 1.5 2.5 1.2 1.2 1.2
40 480 100 1 1 1 1 1 1 1 1.5 1.5 1.5 2.5 1 1 1
50 600 100 0.8 0.8 0.8 0.8 0.8 0.8 0.8 1.5 1.5 1.5 2 0.8 0.8 0.8
63 756 100 2
75 900 100 2
90 1080 100 1.5
100 1140 100
3VL2 VL160 3VL3 VL250 3VL4 VL400 3VL5 VL630 3VL6 VL800 3VL7 VL1250 3VL8 VL1600
adjustable therm/ adjustable mag (TM) adj. therm/ adj. mag (TM) adj. therm/ adj. mag (TM) adj. therm/ adj. mag (TM)
ETU ETU ETU ETU ETU ETU ETU
63-80 80-100 100-125 50 63 80 100 125 160 125 160 200 250 200 250 315 400 315 400 500 630 630 800 1000 1250 1600
1000 1000 1000 500 630 800 1000 1250 1600 1250 1600 2000 2500 2000 2500 3150 4000 3150 4000 5000 6300 7000 7500 11000 12500 15000
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100

40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 10 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 1.5 6 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
10 10 10 1.2 3 6 10 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
6 6 6 1.2 2.5 6 6 8 40/70/100 8 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
2.5 2.5 2.5 1 1.5 2.5 2.5 3 8 3 8 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50 50 50
2.5 2.5 2.5 1 1.5 2.5 2.5 3 5 3 5 10 10 8 8 10 45/50/50 10 45/50/50 45/50/50 45/50/50 50 50 50 50 50
2 2 2 1 1.2 1.5 2 2.5 4 2.5 4 8 8 6 6 8 45/50/50 8 45/50/50 45/50/50 45/50/50 50 50 50 50 50

40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 20 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 6 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
40/70 40/70 40/70 4 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
6 6 6 2 6 6 6 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
6 6 6 2 6 6 6 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
6 6 6 1.2 3 5 6 6 40/50/50 6 40/50/50 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50 50 50
4 4 4 1 2.5 3 4 4 40/50/50 4 40/50/50 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50 50 50
3 3 3 1 1.5 2 3 3 6 3 6 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50 50 50
2.5 2.5 2.5 0.8 1.5 2 2.5 3 6 3 6 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50 50 50

40/50 40/50 40/50 1.5 4 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50 50 50
6 6 6 1.2 2.5 4 6 6 40/50/50 6 40/50/50 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50 50 50
4 4 4 1 2 3 4 4 10 4 10 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50 50 50
2 2 2 0.8 1.2 1.5 2 2.5 5 2.5 5 40/50/50 40/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 45/50/50 50 50 50 50 50
2 2 2 1 1.5 2 2 4 2 4 8 8 4 4 6 8 6 8 45/50/50 45/50/50 50 50 50 50 50
1.5 1.5 1.5 0.8 1.5 1.5 2 3 2 3 6 6 3 3 4 8 4 8 45/50/50 45/50/50 50 50 50 50 50
1.5 1.5 1.5 1.5 1.5 2 3 2 3 6 6 3 3 4 8 4 8 45/50/50 45/50/50 50 50 50 50 50

8 8 8 3 3 5 8 10 40 10 40 40/70/100 40/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
3 3 3 2 2 3 3 4 5 4 5 40/70/100 40/70/100 12 12 30 30 30 30 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
3 3 3 1.5 1.5 2.5 3 3 5 3 5 11 12 5 5 8 12 8 12 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
1.5 1.5 1.5 1.2 1.2 1.2 1.5 2.5 2.5 2.5 2.5 10 10 5 5 6 10 6 10 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
1.5 1.5 1.5 1.2 1 1.5 1.5 2 2.5 2 2.5 4 4 205 2.5 4 6 4 6 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
1.5 1.5 1.5 1 0.8 1.5 1.5 2 2 2 2 4 4 4 4 4 6 4 6 45/70/100 45/70/100 50/70/100 50/70/100 50/70/100 50/70/100 50/70/100
1.5 2 1.5 2 3 3 3 3 3 5 3 5 12 30 30 30 50/70/100 50/70/100 50/70/100
1.2 2 1.2 2 3 3 2 2 3 4 3 4 12 15 15 15 50/70/100 50/70/100 50/70/100
1.2 1.5 1.2 1.5 2.5 2.5 2 2 3 4 3 4 12 12 12 12 50/70/100 50/70/100 50/70/100
2 2.5 2 2 3 4 3 4 10 12 12 12 50/70/100 50/70/100 50/70/100

Vous aimerez peut-être aussi