DC Air Circuit Breakers

Moulded Case Circuit Breakers


&

www.terasaki.co.jp
CAT REF. ’15-I73E
TABLE OF CONTENTS

1.General ………………………………………1-1 5.Outline Dimensions …………………………5-1


Introduction ……………………………………………1-2 DC Air Circuit Breakers Outline Dimensions
General …………………………………………………1-3 AR216S, AR220S 3P…………………………………5-2
Selection Chart …………………………………………1-4 AR325S, AR332S 3P…………………………………5-4
AR325-NDH 4P ………………………………………5-6
2.Ratings and Specifications ………………2-1 AR440S 3P ……………………………………………5-8
Air Circuit Breakers for DC350V-800V ………………2-2 DC Moulded Case Circuit Breakers Outline Dimensions
Moulded Case Circuit Breakers for DC350V-600V …2-3 S160-SD, S160-GD, S160-SDN, S250-SD,
Moulded Case Circuit Breakers for DC750V-1000V…2-5 S250-GD, S250-SDN 3P ………………5-10
Switch-disconnectors for DC600V-1000V ……………2-7 S400-ND 3P …………………………………………5-11
S800-ND 3P …………………………………………5-11
3.Characteristics ………………………………3-1 S1000-ND 2P, 3P……………………………………5-12
Time/Current characteristic curves, XS1250ND 2P, 3P …………………………………5-13
Ambient Compensating Curves XS1600ND 2P, 3P …………………………………5-14
S160-SD, S160-GD, PVE160-SDL, XS2000ND 2P, 3P …………………………………5-15
S250-SD, S250-GD 3P ……………3-2 XS2500ND, XS3200ND 2P, 3P ……………………5-16
S400-ND, S800-ND 3P ………………………………3-3 PVE160-SDL 3P ……………………………………5-17
S1000-ND 2P, 3P ……………………………………3-3 PVS160-SDL, PVS250-SDL 3P ……………………5-18
XS1250ND, XS1600ND, XS2000ND 2P, 3P ………3-4 PVS160-SDL, PVS250-SDL,
XS2500ND, XS3200ND 2P, 3P ……………………3-5 PVS160-SNL, PVS250-SNL 4P …………5-18
PVS160-SDL, PVS250-SDL 3P, 4P ………………3-6 PVS160-SDH, PVS250-SDH,
PVS160-SDH, PVS250-SDH 4P ……………………3-6 PVS160-SNH, PVS250-SNH 4P ………5-19
PVS400-NDL 3P ……………………………………3-6 PVS400-NDL 3P ……………………………………5-20
PVS400-NDL, PVS400-NDH, PVS800-NDH 4P …3-7 PVS400-NDL, PVS400-NDH 4P …………………5-21
PVS800-NDL 3P, 4P …………………………………3-7 PVS400-NNL, PVS400-NNH 4P …………………5-21
PVS800-NDL 3P ……………………………………5-22
4.Mounting and Connection …………………4-1 PVS800-NDL, PVS800-NDH 4P …………………5-23
Connection of conductors to DC circuit breakers …4-2 PVS800-NNL, PVS800-NNH 4P …………………5-23
Insulation distance DC600V or less …………………4-7
Insulation distance DC750V-1000V
PVE160-SDL 3P ……………………………………4-8
PVS160-SDL 3P, PVS250-SDL 3P …………………4-9
PVS160-SDL 4P, PVS250-SDL 4P,
PVS160-SNL 4P, PVS250-SNL 4P ……4-10
PVS160-SDH 4P, PVS250-SDH 4P ………………4-11
PVS160-SNH 4P, PVS250-SNH 4P ………………4-12
PVS400-NDL 3P ……………………………………4-13
PVS400-NDL 4P, PVS400-NDH 4P ………………4-14
PVS400-NNL 4P, PVS400-NNH 4P ………………4-15
PVS800-NDL 3P ……………………………………4-16
PVS800-NDL 4P, PVS800-NDH 4P ………………4-17
PVS800-NNL 4P, PVS800-NNH 4P ………………4-18
1
1

General
General
Introduction ………………………………………………………………………1-2
General ……………………………………………………………………………1-3
Selection Chart …………………………………………………………………1-4

1-1
Introduction

In recent years, as part of the drive to reduce greenhouse gas emissions, significant attention is now
being directed towards the energy produced by large-scale photovoltaic (solar), wind, and biomass
energy power generation.
The total power generation capacity of facilities for these new energy sources is expected to exceed that
produced by nuclear energy by approximately 2030. To aid and support these new technologies,
Terasaki now offer a new, broad range of dedicated DC air circuit breakers and moulded case circuit
breakers. The new range of Terasaki DC circuit breakers are ideally suited for all types of industries,
buildings, as well as the information technology and communications sectors where highly reliable
sources of electric power are required.

DC Air Circuit Breakers

AR220S
Rated current 2000A
Rated breaking capacity DC600V 40kA

Possible reverse connection

DC Moulded Case Circuit Breakers

PVE160-SDL PVS160-SDL PVS250-SDH


Rated current 160A Rated current 160A Rated current 250A
Rated breaking capacity DC750V 3kA Rated breaking capacity DC750V 5kA Rated breaking capacity DC1000V 5kA

Possible reverse connection Possible reverse connection Possible reverse connection

1-2
General
1

General
DC power sources for the Uninterruptible Power Supply (UPS) market

Electrical and electronic equipment used in the advanced information and communications sectors requires a
highly reliable power source. Should a power failure occur, and to assist with continuity of electrical power, it is
standard practice to install an Uninterruptable Power Supply (UPS).
A data centre is where Internet servers and other systems for data communications, such as fixed, mobile, and IP
telephones are installed. At the data centre, AC power from the main system power source is sent to the UPS,
and is temporarily converted to DC power. A storage battery is then charged with this DC power, which is re-
converted back into AC power and then sent to the information equipment.

Building and Industrial power back-up

A UPS is typically required for critical power systems in department stores, hotels, hospitals, theaters, and office
buildings. For example, in semiconductor manufacturing plants that feature advanced automation as a part of
their production processes, UPS systems with large battery capacities are used to take measures against any
large-scale power outage affecting critical manufacturing facilities.

Photovoltaic power generation

Photovoltaic (or Solar) power generation, which is attracting attention as clean energy, ranges from simple
generation of up to several kilowatts for home use, to larger systems of 100 kilowatts or greater for industrial use.
In the "School New Deal" program, one of the governmental measures during the economic crisis, were for eco-
friendly modifications which advocated the use of photovoltaic power generation at schools. One example is a
power distribution system linked to a source of photovoltaic power generation. The current produced from the
photovoltaic solar cells is sent to a power conditioner via a diode with a DC circuit breaker in a junction box and
then converted into AC, which can then be supplied to a load via a distribution board.

Rationalization of use of electric power via large-capacity storage battery

Energy from new power sources such as wind and photovoltaic power generation do not have a stable output. A
lithium ion battery and a sodium-sulfur (NAS) battery can suppress such fluctuations by load leveling. The battery
is charged at night using a lower electrical power rate at night and discharged at daytime when the electrical
power usage rate is higher, and in addition, any new electrical power generated can also be saved. For this
purpose, large-capacity storage battery systems are used at wind and photovoltaic power generation facilities.
The use of these types of systems is expected to grow across all user sectors requiring large amounts of power,
plus as an additional measure against possible power outages.

1-3
All Air Circuit Breakers and Switch-disconnectors are possible to reverse the connection.
Moulded Case Circuit Breakers up to 1000A frame are possible to reverse the connection.

Selection Chart

Frame size (A)


Voltage
160 250 400 800

800V

Air Circuit Breakers

600V

PVS160-SDH PVS250-SDH PVS400-NDH PVS800-NDH


1000V 4P 4P 4P 4P
5kA/5kA 5kA/5kA 5kA/5kA 5kA/5kA

PVE160-SDL PVS160-SDL PVS250-SDL PVS400-NDL PVS800-NDL


3P 3P 3P 3P 3P
3kA/3kA 5kA/5kA 5kA/5kA 10kA/5kA 10kA/10kA
750V

PVS160-SDL PVS250-SDL PVS400-NDL PVS800-NDL


4P 4P 4P 4P
10kA/5kA 10kA/5kA 10kA/10kA 10kA/10kA

Moulded Case Circuit S160-SD S160-GD S250-SD S250-GD


600V 3P 3P 3P 3P
Breakers
5kA/5kA 10kA/5kA 5kA/5kA 10kA/5kA S400-ND S800-ND
3P 3P
15kA/15kA 20kA/10kA
S160-SD S160-GD S250-SD S250-GD
500V 3P 3P 3P 3P
7.5kA/7.5kA 15kA/7.5kA 7.5kA/7.5kA 15kA/7.5kA

S160-SD S250-SD S400-ND S800-ND


350V 3P 3P 3P 3P
10kA/10kA 10kA/10kA 20kA/20kA 30kA/15kA

250V

PVS160-SNH PVS250-SNH PVS400-NNH PVS800-NNH


1000V 4P 4P 4P 4P

PVS160-SNL PVS250-SNL PVS400-NNL PVS800-NNL


Switch-disconnectors 800V 4P 4P 4P 4P

S160-SDN S250-SDN
600V 3P 3P

1-4
Reverse connection Reverse connection
Possible Not possible

1
1000 1250 1600 2000 2500 3200 4000

General
AR325-NDH
4P
30kA/30kA

AR216S AR220S AR325S AR332S AR440S


3P 3P 3P 3P 3P
40kA/40kA 40kA/40kA 40kA/40kA 40kA/40kA 40kA/40kA

XS1250ND XS1600ND XS2000ND XS2500ND XS3200ND


3P 3P 3P 3P 3P
S1000-ND 20kA/15kA 20kA/15kA 20kA/15kA 20kA/15kA 20kA/15kA
3P
20kA/10kA

XS1250ND XS1600ND XS2000ND XS2500ND XS3200ND


3P 3P 3P 3P 3P
50kA/25kA 50kA/25kA 50kA/25kA 50kA/25kA 50kA/25kA
S1000-ND
3P
30kA/15kA

S1000-ND XS1250ND XS1600ND XS2000ND XS2500ND XS3200ND


2P 2P 2P 2P 2P 2P
50kA/20kA 50kA/30kA 50kA/30kA 50kA/30kA 50kA/30kA 50kA/30kA

S160-SD
3P Number of poles
5kA/5kA

Icu Ics
1-5
2 Ratings and
Specifications 2

Ratings and Specifications


Air Circuit Breakers for DC350V-800V ………………………………………2-2
Moulded Case Circuit Breakers for DC350V-600V …………………………2-3
Moulded Case Circuit Breakers for DC750V-1000V ………………………2-5
Switch-disconnectors for DC600V-1000V …………………………………2-7

2-1
Air Circuit Breakers for DC350V-800V
Frame size (A) 1600 2000 2500 2500 3200 4000
Type AR216S AR220S AR325S AR325-NDH AR332S AR440S
Rated current(max.)〔In〕A 1600 2000 2500 2500 3200 4000
Number of poles 3 3 3 4 3 3
Rated insulation voltage〔Ui〕 V AC 1000 1000 1000 1000 1000 1000
Rated operational voltage〔Ue〕 V DC 600 600 600 800 600 600
Rated impulse withstand voltage〔U imp〕 kV 12 12 12 12 12 12
■Rated breaking cap, kA
JIS C 8201-2-1 Ann.1 Ann.2 DC 800V ― ― ― 30/30 ― ―
IEC 60947-2 600V 40/40 40/40 40/40 ― 40/40 40/40
Icu/Ics ①② 500V 40/40 40/40 40/40 ― 40/40 40/40
350V 40/40 40/40 40/40 ― 40/40 40/40
Rated short time withstand current〔Icw〕 kA 1s 40 40 40 30 40 40
Latching current kA 65 65 85 85 85 100
Total breaking time (s) 0.04 0.04 0.04 0.04 0.04 0.04
■Closing operation time
Spring charging time (s) max. 10 10 10 10 10 10
Close time (s) max. 0.08 0.08 0.08 0.08 0.08 0.08
■No. of operating cycles
Mechanical life with maintenance 30000 25000 20000 20000 20000 15000
without maintenance 15000 12000 10000 10000 10000 8000
Electrical life without maintenance DC 600V 1000 1000 500 500 500 500
■Outline dimension mm
Draw-out a 354 354 460 580 460 631
type b b 460 460 460 460 460 460
c 345 345 345 345 345 375
a c d d 40 40 40 40 40 53
Weight kg 76 79 105 125 105 139
Reverse connection Yes Yes Yes Yes Yes Yes
Notes:
― : “no” or “not available”.
① : AGR over-current release can not be used for DC. Please prepare DC over-current relay and connect with shunt trip device.
② : The time constant (L/R) of the circuit should be,
less than 2.0ms nearby rated current
less than 15ms for short circuit

(1)Shunt trip device is Instantaneously rated type. Continuously rated shunt trip device is not applicable.
(2)Undervoltage trip device is not applicable.
(3)Test jumper is not applicable.
For further details please contact TERASAKI.

2-2
Moulded Case Circuit Breakers for DC350V-600V
Frame size (A) 160 160 250 250 400 800 1000
Type S160-SD S160-GD S250-SD S250-GD S400-ND S800-ND S1000-ND
Number of poles 3 3 3 3 3 3 2* 3
■Ratings
Rated current, A 25 (16-25) 25 (16-25) 100 (63-100) 100 (63-100) 250 (160-250) 630 (400-630) 1000
Calibrated at 45°C 32 (20-32) 32 (20-32) 125 (80-125) 125 (80-125) 400 (250-400) 800 (500-800)
40 (25-40) 40 (25-40) 160 (100-160) 160 (100-160)
63 (40-63) 63 (40-63) 200 (125-200) 200 (125-200)
80 (50-80) 80 (50-80) 250 (160-250) 250 (160-250)
100 (63-100) 100 (63-100)
*2 poles breaker is same outline dimensions as 125 (80-125) 125 (80-125)
3 poles breaker. 160 (100-160) 160 (100-160)
Rated insulation voltage〔Ui〕 V 690 690 800 800 800 800 800
Rated impulse withstand voltage 〔U imp〕 kV
■Rated breaking capacity, kA
JIS C 8201-2-1 Ann.1 Ann.2
IEC 60947-2
DC 600V
500V
8

5/5
7.5/7.5
8

10/5
15/7.5
8

5/5
7.5/7.5
8

10/5
15/7.5
8

15/15
15/15
8

20/10
20/10
8



20/10
20/10
2
Icu/Ics ④⑤ 350V 10/10 ― 10/10 ― 20/20 30/15 ― 30/15
250V ― ― ― ― ― ― 50/20 ―
■External dimensions, mm

Ratings and Specifications


a d a 75 75 105 105 140 210 210
c
b 130+50 ⑰ 130+50 ⑰ 165+55 ⑰ 165+55 ⑰ 260 273 273
b c 68 68 68 68 103 103 103
d 95 95 95 95 145 145 145
Weight (' marked standard type) kg 0.8 0.8 1.5 1.5 4.2 8.5 9.8 10.8
■Connections and Mountings
Front-connected (FC) Terminal screws ' ' ' ' ' ― ―
With extension bars ○(BAR) ○(BAR) ○(BAR) ○(BAR) ○(BAR) ' '
Rear-connected (RC) Flat bar studs ○ ○ ○ ○ ○ ○ ○
Plug-in (PM) For switchboards ― ― ― ― ― ― ―
For distribution boards ― ― ― ― ― ― ―
Draw-out type (DR) ― ― ― ― ― ― ―
TemPlug70 (PG) ― ― ― ― ― ― ―
TemPlug45B (PG4) ― ― ― ― ― ― ―
DIN rail mount ○⑪ ○⑪ ― ― ― ― ―
Clip-in chassis mount ― ― ― ― ― ― ―
■Accessories (optional) Symbol
Auxiliary switch AX ● ● ● ● ● ● ●
Interior

Alarm switch AL ● ● ● ● ● ● ●
Shunt trips SH ● ● ● ● ● ● ●
Undervoltage trips UV ● ● ● ● ● ● ●
Motor operator MC ― ― ● ● ● ● ●
External operating Breaker-mounted HB ● ● ● ● ● ● ●
handle Door-mounted (variable depth) HP ● ● ● ● ● ● ●
Toggle extension HA ― ― ― ― ― ● ●
Mechanical interlock Slide type MS ― ― ― ― ― ― ―
Rear-connected type MB ― ― ― ― ― ― ―
Link type ML ― ― ― ― ― ― ―
Exterior

Wire type MW ― ― ― ― ― ― ―
Toggle holder HH ● ● ● ●
● ● ●
Toggle lock HL ● ● ● ●
Terminal cover For front-connected CF ●⑫ ●⑫ ●⑫ ●⑫ ● ● ●
For rear-connected and plug-in CR ●⑫ ●⑫ ●⑫ ●⑫ ● ● ●
Interpole barrier BA ●⑬ ●⑬ ●⑬ ●⑬ ●③ ●③ ●③
Terminal block for lead TF ● ● ● ● ● ● ●
Door flange DF ● ● ● ● ● ● ●
■Standard specifications
Overcurrent trip mechanism Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal, Fixed thermal,
fixed magnetic fixed magnetic fixed magnetic fixed magnetic fixed magnetic fixed magnetic fixed magnetic
Colour of cover Grey Grey Grey Grey Grey Grey Grey
Trip button (Colour) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red)
Handle position indication (ON: Red, OFF: Green) Yes Yes Yes Yes Yes Yes Yes
Suitability for isolation Yes Yes Yes Yes Yes Yes Yes
Reverse connection Yes Yes Yes Yes Yes Yes Yes
Notes:
' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”.
③ : Line side interpole barriers are supplied as standard. (Front connection only)
④ : Connect 3pole or 4pole in series when over DC250V.
⑤ : The time constant (L/R) of the circuit should be,
less than 2.0ms nearby rated current
less than 5ms for short circuit ≦ 10KA
less than 10ms for short circuit ≦ 20KA
less than 15ms for short circuit > 20KA
⑪ : Provided with DIN rail adaptor.
⑫ : Be sure to install the terminal covers on Line side (ON side) that is supplied as standard.
⑬ : Possible to fit on load side (option).
⑰ : + means the dimension of the terminal cover. See outline dimensions for details.

2-3
Moulded Case Circuit Breakers for DC350V-600V
Frame size (A) 1250 1600 2000 2500 3200
Type XS1250ND XS1600ND XS2000ND XS2500ND XS3200ND
Number of poles 2* 3 2* 3 2* 3 2* 3 2* 3
■Ratings
Rated current, A 1250 ① 1600 ① 2000 ① 2500 ① 3200 ①
Calibrated at 45°C

*2 poles breaker is same outline dimensions as


3 poles breaker.
Rated insulation voltage〔Ui〕 V AC 690 690 690 690 690
Rated impulse withstand voltage 〔U imp〕 kV 8 8 8 8 8
■Rated breaking capacity, kA
JIS C 8201-2-1 Ann.1 Ann.2 DC 600V ― 20/15 ― 20/15 ― 20/15 ― 20/15 ― 20/15
IEC 60947-2 500V ― 50/25 ― 50/25 ― 50/25 ― 50/25 ― 50/25
Icu/Ics ④⑤ 350V ― 50/25 ― 50/25 ― 50/25 ― 50/25 ― 50/25
250V 50/30 ― 50/30 ― 50/30 ― 50/30 ― 50/30 ―
■External dimensions, mm
a d a 210 210 320 320 320
c
b 370 370 450 450 450
b c 140 140 185 185 185
d 191 191 245 245 245
Weight (' marked standard type) kg 23.8 26.0 24.0 27.0 50.0 54.0 55.7 62.5 55.7 62.5
■Connections and Mountings
Front-connected (FC) Terminal screws ― ― ― ― ―
With extension bars ' ○ ○ ― ―
Rear-connected (RC) Flat bar studs ○ ' ' ' '
Plug-in (PM) For switchboards ― ― ― ― ―
For distribution boards ― ― ― ― ―
Draw-out type (DR) ― ○ ○ ― ―
TemPlug70 (PG) ― ― ― ― ―
TemPlug45B (PG4) ― ― ― ― ―
DIN rail mount ― ― ― ― ―
Clip-in chassis mount ― ― ― ― ―
■Accessories (optional) Symbol
Auxiliary switch AX ● ● ● ● ●
Interior

Alarm switch AL ● ● ● ● ●
Shunt trips SH ● ● ● ● ●
Undervoltage trips UV ― ― ― ― ―
Motor operator MC ● ● ● ● ●
External operating Breaker-mounted HB ● ● ― ― ―
handle Door-mounted (variable depth) HP ● ● ●⑦ ●⑦ ●⑦
Toggle extension HA ●⑥ ●⑥ ●② ●② ●②
Mechanical interlock Slide type MS ― ― ― ― ―
Rear-connected type MB ― ― ― ― ―
Link type ML ― ― ― ― ―
Exterior

Wire type MW ― ― ― ― ―
Toggle holder HH
● ● ● ● ●
Toggle lock HL
Terminal cover For front-connected CF ― ― ― ― ―
For rear-connected and plug-in CR ― ― ― ― ―
Interpole barrier BA ●③ ●③ ― ― ―
Terminal block for lead TF ● ● ● ● ●
Door flange DF ● ● ● ● ●
■Standard specifications
Overcurrent trip mechanism Magnetic(adjustable) ① Magnetic(adjustable) ① Magnetic(adjustable) ① Magnetic(adjustable) ① Magnetic(adjustable) ①
Colour of cover Grey Grey Grey Grey Grey
Trip button (Colour) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red)
Handle position indication (ON: Red, OFF: Green) Yes Yes Yes Yes Yes
Suitability for isolation Yes Yes Non Non Non
Reverse connection Non Non Non Non Non
Notes:
' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”.
① : Instantaneous trip oinly.
② : Supplied as standard.
③ : Line side interpole barriers are supplied as standard. (Front connection only)
④ : Connect 3pole in series when over DC250V.
⑤ : The time constant (L/R) of the circuit should be,
less than 2.0ms nearby rated current
less than 5ms for short circuit ≦ 10KA
less than 10ms for short circuit ≦ 20KA
less than 15ms for short circuit > 20KA
⑥ : One is supplied with every five breakers. Please specify if more are required.
⑦ : Fixed depth. (not adjustable)

2-4
Moulded Case Circuit Breakers for DC750V-1000V
Frame size (A) 160 160 160 250 250
Type PVE160-SDL PVS160-SDL PVS160-SDH PVS250-SDL PVS250-SDH
Number of poles 3 3 4 4 3 4 4
■Ratings
Rated current, A 25 (16-25) 50 (32-50) 50 (32-50) 50 (32-50) 100 (63-100) 100 (63-100) 100 (63-100)
Calibrated at 45°C 32 (20-32) 63 (40-63) 63 (40-63) 63 (40-63) 125 (80-125) 125 (80-125) 125 (80-125)
40 (25-40) 100 (63-100) 100 (63-100) 100 (63-100) 160 (100-160) 160 (100-160) 160 (100-160)
63 (40-63) 125 (80-125) 125 (80-125) 125 (80-125) 200 (125-200) 200 (125-200) 200 (125-200)
80 (50-80) 160 (100-160) 160 (100-160) 160 (100-160) 250 (160-250) 250 (160-250) 250 (160-250)
100 (63-100)
*2 poles breaker is same outline dimensions as 125 (80-125)
3 poles breaker. 160 (100-160)
Rated insulation voltage〔Ui〕 V AC 800 800 800 1000 800 800 1000
Rated impulse withstand voltage 〔U imp〕 kV
■Rated breaking capacity, kA
JIS C 8201-2-1 Ann.1 Ann.2
IEC 60947-2 Icu/Ics ①②
DC 1000V
750V
8


3/3
8


5/5
8


10/5
8

5/5

8


5/5
8


10/5
8

5/5

2
■External dimensions, mm
a d a 75 105 140 140 105 140 140
c
b 130+50×2 ⑰ 165+55×2 ⑰ 165+55×2 ⑰ 165+55×2 ⑰ 165+55×2 ⑰ 165+55×2 ⑰ 165+55×2 ⑰

Ratings and Specifications


b c 68 68 68 68 68 68 68
d 95 95 95 95 95 95 95
Weight (' marked standard type) kg 0.8 1.5 1.9 1.9 1.5 1.9 1.9
■Connections and Mountings
Front-connected (FC) Terminal screws ' ' ' ' ' ' '
With extension bars ○(BAR) ○(BAR) ○(BAR) ○(BAR) ○(BAR) ○(BAR) ○(BAR)
Rear-connected (RC) Flat bar studs ○ ○ ○ ○ ○ ○ ○
Plug-in (PM) For switchboards ― ― ― ― ― ― ―
For distribution boards ― ― ― ― ― ― ―
Draw-out type (DR) ― ― ― ― ― ― ―
TemPlug70 (PG) ― ― ― ― ― ― ―
TemPlug45B (PG4) ― ― ― ― ― ― ―
DIN rail mount ― ― ― ― ― ― ―
Clip-in chassis mount ― ― ― ― ― ― ―
■Accessories (optional) Symbol
Auxiliary switch AX ● ● ● ● ● ● ●
Interior

Alarm switch AL ● ● ● ● ● ● ●
Shunt trips SH ● ● ● ● ● ● ●
Undervoltage trips UV ● ● ● ● ● ● ●
Motor operator MC ― ● ● ● ● ● ●
External operating Breaker-mounted HB ● ● ● ● ● ● ●
handle Door-mounted (variable depth) HP ● ● ● ● ● ● ●
Toggle extension HA ― ― ― ― ― ― ―
Mechanical interlock Slide type MS ― ― ― ― ― ― ―
Rear-connected type MB ― ― ― ― ― ― ―
Link type ML ― ― ― ― ― ― ―
Exterior

Wire type MW ― ― ― ― ― ― ―
Toggle holder HH ● ● ● ● ● ● ●
Toggle lock HL ● ● ● ● ● ● ●
Terminal cover For front-connected CF ●⑧ ●⑧ ●⑧ ●⑧ ●⑧ ●⑧ ●⑧
For rear-connected and plug-in CR ●⑧ ●⑧ ●⑧ ●⑧ ●⑧ ●⑧ ●⑧
Interpole barrier BA ― ― ― ― ― ― ―
Terminal block for lead TF ● ● ● ● ● ● ●
Door flange DF ● ● ● ● ● ● ●
■Standard specifications
Overcurrent trip mechanism Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal,
fixed magnetic fixed magnetic fixed magnetic fixed magnetic fixed magnetic fixed magnetic fixed magnetic
Colour of cover Grey Grey Grey Grey Grey Grey Grey
Trip button (Colour) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red)
Handle position indication (ON: Red, OFF: Green) Yes Yes Yes Yes Yes Yes Yes
Suitability for isolation Yes Yes Yes Yes Yes Yes Yes
Reverse connection Yes Yes Yes Yes Yes Yes Yes
Notes:
' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”.
① : Connect 3poles or 4poles in series.
② : The time constant (L/R) of the circuit should be,
less than 2.0ms nearby rated current
less than 5ms for short circuit ≦ 10KA
less than 10ms for short circuit ≦ 20KA
less than 15ms for short circuit > 20KA
⑧ : Two terminal covers are supplied as standard. Be sure to install the terminal covers on Line side (ON side) and Load side (OFF side).
⑰ : + means the dimension of the terminal cover. See outline dimensions for details.

2-5
Moulded Case Circuit Breakers for DC750V-1000V
Frame size (A) 400 400 800 800
Type PVS400-NDL PVS400-NDH PVS800-NDL PVS800-NDH
Number of poles 3 4 4 3 4 4
■Ratings
Rated current, A 250 (160-250) 250 (160-250) 250 (160-250) 630 (400-630) 630 (400-630) 630 (400-630)
Calibrated at 45°C 400 (250-400) 400 (250-400) 400 (250-400) 800 (500-800) 800 (500-800) 800 (500-800)

*2 poles breaker is same outline dimensions as


3 poles breaker.
Rated insulation voltage〔Ui〕 V AC 800 1150 1150 800 1150 1150
Rated impulse withstand voltage 〔U imp〕 kV 8 8 8 8 8 8
■Rated breaking capacity, kA
JIS C 8201-2-1 Ann.1 Ann.2 DC 1000V ― ― 5/5 ― ― 5/5
IEC 60947-2 Icu/Ics ①② 750V 10/5 10/10 ― 10/10 10/10 ―
■External dimensions, mm
a d a 140 185 185 210 280 280
c
b 260 260 260 273 273 273
b c 103 103 103 103 103 103
d 145 145 145 145 145 145
Weight (' marked standard type) kg 4.2 5.6 5.6 8.5 11.5 11.5
■Connections and Mountings
Front-connected (FC) Terminal screws ' ' ' ― ― ―
With extension bars ○(BAR) ○(BAR) ○(BAR) ' ' '
Rear-connected (RC) Flat bar studs ○ ○ ○ ○ ○ ○
Plug-in (PM) For switchboards ― ― ― ― ― ―
For distribution boards ― ― ― ― ― ―
Draw-out type (DR) ― ― ― ― ― ―
TemPlug70 (PG) ― ― ― ― ― ―
TemPlug45B (PG4) ― ― ― ― ― ―
DIN rail mount ― ― ― ― ― ―
Clip-in chassis mount ― ― ― ― ― ―
■Accessories (optional) Symbol
Auxiliary switch AX ● ● ● ● ● ●
Interior

Alarm switch AL ● ● ● ● ● ●
Shunt trips SH ● ● ● ● ● ●
Undervoltage trips UV ● ● ● ● ● ●
Motor operator MC ● ● ● ● ● ●
External operating Breaker-mounted HB ● ● ● ● ● ●
handle Door-mounted (variable depth) HP ● ● ● ● ● ●
Toggle extension HA ― ― ― ● ● ●
Mechanical interlock Slide type MS ― ― ― ― ― ―
Rear-connected type MB ― ― ― ― ― ―
Link type ML ― ― ― ― ― ―
Exterior

Wire type MW ― ― ― ― ― ―
Toggle holder HH
● ● ● ● ● ●
Toggle lock HL
Terminal cover For front-connected CF ● ● ● ● ● ●
For rear-connected and plug-in CR ● ● ● ● ● ●
Interpole barrier BA ●⑯ ●⑨ ●⑨ ●⑯ ●⑩ ●⑩
Terminal block for lead TF ● ● ● ● ● ●
Door flange DF ― ― ― ― ― ―
■Standard specifications
Overcurrent trip mechanism Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal, Adj. thermal,
fixed magnetic fixed magnetic fixed magnetic fixed magnetic fixed magnetic fixed magnetic
Colour of cover Grey Grey Grey Grey Grey Grey
Trip button (Colour) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red)
Handle position indication (ON: Red, OFF: Green) Yes Yes Yes Yes Yes Yes
Suitability for isolation Yes Yes Yes Yes Yes Yes
Reverse connection Yes Yes Yes Yes Yes Yes
Notes:
' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”.
① : Connect 3poles or 4poles in series.
② : The time constant (L/R) of the circuit should be,
less than 2.0ms nearby rated current
less than 5ms for short circuit ≦ 10KA
less than 10ms for short circuit ≦ 20KA
less than 15ms for short circuit > 20KA
⑨ : For front connection, both line and load side interpole barriers are supplied as standard.
For rear connection, line side interpole barriers are supplied as standard.
⑩ : For front connection, 5pcs line side interpole barriers and 3pcs load side interpole barriers are supplied as standard.
For rear connection, 5pcs line side interpole barriers are supplied as standard.
⑯ : For front connection and rear connection, 2pcs line side interpole barriers are supplied as standard.

2-6
Switch-disconnectors for DC600V-1000V
Frame size (A) 160 160 160 250 250 250
Type S160-SDN PVS160-SNL PVS160-SNH S250-SDN PVS250-SNL PVS250-SNH
Number of poles 3 4 4 3 4 4
■Ratings
Rated current, A 160 160 160 250 250 250

Rated insulation voltage〔Ui〕 V 690 800 1000 800 800 1000


Rated operational voltage V DC 600 800 1000 600 800 1000
Rated short time withstand current, kA 2(0.3sec.) 3(0.3sec.) 3(0.3sec.) 3(0.3sec.) 3(0.3sec.) 3(0.3sec.)
Rated impulse withstand voltage 〔U imp〕 kV 8 8 8 8 8 8
■Performance
Utilization category ①⑲
JIS C 8201-3 IEC 60947-3
■External dimensions, mm
a d
DC

a
DC-22A

75
DC-22A

140
DC-22A

140
DC-22A

105
DC-22A

140
DC-22A

140
2
c
b 130+50 ⑰ 165+55×2 ⑰ 165+55×2 ⑰ 165+55 ⑰ 165+55×2 ⑰ 165+55×2 ⑰
b c 68 68 68 68 68 68
d 95 95 95 95 95 95

Ratings and Specifications


Weight (' marked standard type) kg 0.8 1.9 1.9 1.5 1.9 1.9
■Connections and Mountings
Front-connected (FC) Terminal screws ' ' ' ' ' '
With extension bars ○(BAR) ○(BAR) ○(BAR) ○(BAR) ○(BAR) ○(BAR)
Rear-connected (RC) Flat bar studs ○ ○ ○ ○ ○ ○
Plug-in (PM) For switchboards ― ― ― ― ― ―
For distribution boards ― ― ― ― ― ―
Draw-out type (DR) ― ― ― ― ― ―
TemPlug70 (PG) ― ― ― ― ― ―
TemPlug45B (PG4) ― ― ― ― ― ―
DIN rail mount ○⑪ ― ― ― ― ―
Clip-in chassis mount ― ― ― ― ― ―
■Accessories (optional) Symbol
Auxiliary switch AX ● ● ● ● ● ●
Interior

Alarm switch AL ● ● ● ● ● ●
Shunt trips SH ● ● ● ● ● ●
Undervoltage trips UV ● ● ● ● ● ●
Motor operator MC ― ● ● ● ● ●
External operating Breaker-mounted HB ● ● ● ● ● ●
handle Door-mounted (variable depth) HP ● ● ● ● ● ●
Toggle extension HA ― ― ― ― ― ―
Mechanical interlock Slide type MS ― ― ― ― ― ―
Rear-connected type MB ― ― ― ― ― ―
Link type ML ― ― ― ― ― ―
Exterior

Wire type MW ― ― ― ― ― ―
Toggle holder HH ● ● ● ● ● ●
Toggle lock HL ● ● ● ● ● ●
Terminal cover For front-connected CF ●⑫ ● ●⑧ ●⑫ ●⑧ ●⑧
For rear-connected and plug-in CR ●⑫ ● ●⑧ ●⑫ ●⑧ ●⑧
Interpole barrier BA ●⑬ ● ― ●⑬ ― ―
Terminal block for lead TF ● ● ● ● ● ●
Door flange DF ● ● ● ● ● ●
■Standard specifications
Colour of cover Grey Grey Grey Grey Grey Grey
Trip button (Colour) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red) Yes (Red)
Handle position indication (ON: Red, OFF: Green) Yes Yes Yes Yes Yes Yes
Suitability for isolation Yes Yes Yes Yes Yes Yes
Reverse connection Yes Yes Yes Yes Yes Yes
Notes:
' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”.
① : Connect 3poles or 4poles in series.
⑧ : Two terminal covers are supplied as standard. Be sure to install the terminal covers on Line side (ON side) and Load side (OFF side).
⑪ : Provided with DIN rail adaptor.
⑫ : Be sure to install the terminal covers on Line side (ON side) that is supplied as standard.
⑬ : Possible to fit on load side (option).
⑰ : + means the dimension of the terminal cover. See outline dimensions for details.
⑲ : The time constant (L/R) of the circuit should be less than 2.0ms nearby rated current.

2-7
Switch-disconnectors for DC600V-1000V
Frame size (A) 400 400 800 800
Type PVS400-NNL PVS400-NNH PVS800-NNL PVS800-NNH
Number of poles 4 4 4 4
■Ratings
Rated current, A 400 400 630 630
800 800

Rated insulation voltage〔Ui〕 V 1150 1150 1150 1150


Rated operational voltage V DC 800 1000 800 1000
Rated short time withstand current, kA 5(0.3sec.) 5(0.3sec.) 10(0.3sec.) 10(0.3sec.)
Rated impulse withstand voltage 〔U imp〕 kV 8 8 8 8
■Performance
Utilization category ①⑲ DC DC-22A DC-22A DC-22A DC-22A
JIS C 8201-3 IEC 60947-3
■External dimensions, mm
a d a 185 185 280 280
c
b 260 260 273 273
b c 103 103 103 103
d 145 145 145 145
Weight (' marked standard type) kg 5.6 5.6 11.5 11.5
■Connections and Mountings
Front-connected (FC) Terminal screws ' ' ― ―
With extension bars ○(BAR) ○(BAR) ' '
Rear-connected (RC) Flat bar studs ○ ○ ○ ○
Plug-in (PM) For switchboards ― ― ― ―
For distribution boards ― ― ― ―
Draw-out type (DR) ― ― ― ―
TemPlug70 (PG) ― ― ― ―
TemPlug45B (PG4) ― ― ― ―
DIN rail mount ― ― ― ―
Clip-in chassis mount ― ― ― ―
■Accessories (optional) Symbol
Auxiliary switch AX ● ● ● ●
Interior

Alarm switch AL ● ● ● ●
Shunt trips SH ● ● ● ●
Undervoltage trips UV ● ● ● ●
Motor operator MC ● ● ● ●
External operating Breaker-mounted HB ● ● ● ●
handle Door-mounted (variable depth) HP ● ● ● ●
Toggle extension HA ― ― ● ●
Mechanical interlock Slide type MS ― ― ― ―
Rear-connected type MB ― ― ― ―
Link type ML ― ― ― ―
Exterior

Wire type MW ― ― ― ―
Toggle holder HH
● ● ● ●
Toggle lock HL
Terminal cover For front-connected CF ● ● ● ●
For rear-connected and plug-in CR ● ● ● ●
Interpole barrier BA ●⑨ ●⑨ ●⑩ ●⑩
Terminal block for lead TF ● ● ● ●
Door flange DF ― ― ― ―
■Standard specifications
Colour of cover Grey Grey Grey Grey
Trip button (Colour) Yes (Red) Yes (Red) Yes (Red) Yes (Red)
Handle position indication (ON: Red, OFF: Green) Yes Yes Yes Yes
Suitability for isolation Yes Yes Yes Yes
Reverse connection Yes Yes Yes Yes
Notes:
' : Standard. This configuration used unless otherwise specified. ○ : Optional standard. Specify when ordering. ● : “yes” or “available”. ― : “no” or “not available”.
① : Connect 4poles in series.
⑨ : For front connection, both line and load side interpole barriers are supplied as standard. For rear connection, line side interpole barriers are supplied as standard.
⑩ : For front connection, 5pcs line side interpole barriers and 3pcs load side interpole barriers are supplied as standard. For rear connection, 5pcs line side interpole barriers are
supplied as standard.
⑲ : The time constant (L/R) of the circuit should be less than 2.0ms nearby rated current.

2-8
3 Characteristics
Time/Current characteristic curves, Ambient Compensating Curves
3
S160-SD, S160-GD, PVE160-SDL, S250-SD, S250-GD 3P……………3-2

Characteristics
S400-ND, S800-ND 3P ……………………………………………………3-3
S1000-ND 2P, 3P ……………………………………………………………3-3
XS1250ND, XS1600ND, XS2000ND 2P, 3P ……………………………3-4
XS2500ND, XS3200ND 2P, 3P ……………………………………………3-5
PVS160-SDL, PVS250-SDL 3P, 4P ………………………………………3-6
PVS160-SDH, PVS250-SDH 4P …………………………………………3-6
PVS400-NDL 3P ……………………………………………………………3-6
PVS400-NDL, PVS400-NDH, PVS800-NDH 4P …………………………3-7
PVS800-NDL 3P, 4P ………………………………………………………3-7

3-1
Time/Current characteristic curves, Ambient Compensating Curves

Type Time/Current characteristic curves, Ambient Compensating Curves

S160-SD 3P
S160-GD 3P
3
PVE160-SDL 3P

hour
2
140
1
40 125A
30
20 Calibrated
130

Percent current rating


100A 25A temperature
minute
10
6 40A
4 120
80A
2
1 Max. 110
40 63A
Tripping Time

30
20 160A 32A
100
10
6
4 90
2 Min.
1 25A
calibrated at 45°C 5 15 25 35 45 55 60
160A
second

0.6 Ambient temperature (°C)


0.4
0.2
0.1
0.06 Rated current (A) Magnetic trip current (A)
0.04 25 750
0.02 32 750
40 750
0.01
63 1220
0.005 80 1220
100
125

200

300
400
500
700
1000
1500
2000

3000
4000
5000

8000

100 1940
Percent Rated Current 125 1940
160 2070
Notes : Setting current ±20%

S250-SD 3P
S250-GD 3P
3 3
2 2
hour

hour

1 1
40 40
30 30
20 20
minute

minute

10 10
6 6
4 4
2 2
100-200A(Max) 250A(Max)
1 1
40 40
Tripping Time

Tripping Time

30 30
20 20
10 10
6 6
4 4
250A(Min)
2 100-200A(Min) 2
1 1
second

second

0.6 0.6
0.4 0.4
0.2 0.2
0.1 0.1
0.06 0.06
0.04 0.04
0.02 0.02
0.01 0.01
0.005 0.005
100
125

200

300
400
500
700
1000

1500
2000

3000
4000
5000

8000

100
125

200

300
400
500
700
1000

1500
2000

3000
4000
5000

8000

Percent Rated Current Percent Rated Current

140

Calibrated
130
Percent current rating

temperature
200A,250A
120 125A,160A
Rated current (A) Magnetic trip current (A)
100 1300
125 1625 110
160 2080
200 2600 100A
250 2750 100
Notes : Setting tolerance ±20%
90

calibrated at 45°C 5 15 25 35 45 55 60
Ambient temperature (°C)

3-2
Time/Current characteristic curves, Ambient Compensating Curves

Type Time/Current characteristic curves, Ambient Compensating Curves

S400-ND 3P 3

hour
2
140
1
40
30
20 Calibrated
130

Percent current rating


temperature

minute
10
6 400A
4 120
2
1 110
40 250A
30
Tripping Time

20
100
10
6
4 90
2
calibrated at 45°C 5 15 25 35 45 55 60
1
second

0.6 Ambient temperature (°C)


0.4
0.2
0.1
0.06
0.04
0.02
0.01
0.005
Rated current (A)
250
400
Magnetic trip current (A)
3000
4800 3
100
125

200

300
400
500
700
1000
1500
2000

3000
4000
5000

8000
Notes : Setting tolerance ±20%
Percent Rated Current

Characteristics
S800-ND 3P 3
hour

2
1
140
40
30
20 Calibrated
130

Percent current rating


temperature
minute

10
6
4 120 630A,800A
2
1 110
40
Tripping Time

30
20
100
10
6
4
90
2
1 calibrated at 45°C 5 15 25 35 45 55 60
second

0.6 Ambient temperature (°C)


0.4
0.2
0.1
0.06
0.04
0.02
0.01
Rated current (A) Magnetic trip current (A)
0.005 630 6300
100
125

200

300
400
500
700
1000

1500
2000

3000
4000
5000

8000

800 8000
Percent Rated Current Notes : Setting tolerance ±20%

S1000-ND 2P, 3P 3
2
hour

140
1 Calibrated
40
30 temperature
20 130
Percent current rating
minute

10
6
Max.
120
4
2
1 110
40
30
Tripping Time

20 100
10 Min.
6
4 90
2
calibrated at 45°C 5 15 25 35 45 55
1
second

0.6 Ambient temperature (°C)


0.4
0.2
0.1
0.06
0.04
0.02
0.01
Rated current (A) Magnetic trip current (A)
0.005
1000 8000
100
125

200
300
400
500
700
1000

1500
2000

3000
4000
5000

8000

Notes : Setting tolerance ±20%


Percent Rated Current

3-3
Time/Current characteristic curves, Ambient Compensating Curves

Type Time/Current characteristic curves, Ambient Compensating Curves

XS1250ND 2P, 3P 3
2

hour
1
40

20

minute
10
6
4

1
40
Tripping Time

20

10
Setting tolerance Setting tolerance
6 (Scale4) (Scale8)
4

2
second

1
Adjustable setting
0.6 range of magnetic trip.
Five stages
0.4
within this range.
0.2

0.1 Rated current Magnetic trip current (A)


0.06 (A) Scale 8 7.1 6.3 5 4
0.04 1250 8000 7100 6300 5000 4000
0.02 Notes : Setting tolerance ±10% at 8000A and ±25% for other settings.
0.01
0.006
1000
1250

2000

3000

5000
6000
8000
10000

20000

30000

Rated Current (A) Note: Magnetic trip only. Use the external over-current relay.

XS1600ND 2P, 3P 3
2
hour

1
40

20
minute

10
6
4

1
40
Tripping Time

20

10
Setting tolerance Setting tolerance
6 (Scale4) (Scale8)
4

2
second

1
Adjustable setting
0.6 range of magnetic trip.
Five stages
0.4
within this range.
0.2

0.1 Rated current Magnetic trip current (A)


0.06 (A) Scale 8 7.1 6.3 5 4
0.04 1600 8000 7100 6300 5000 4000
0.02 Notes : Setting tolerance ±10% at 8000A and ±25% for other settings.
0.01
0.006
1000
1250

2000

3000

5000
6000
8000
10000

20000

30000

Rated Current (A) Note: Magnetic trip only. Use the external over-current relay.

XS2000ND 2P, 3P 3
2
hour

1
40

20
minute

10
6
4

1
40
Tripping Time

20

10
Setting tolerance Setting tolerance
6 (Scale4) (Scale8)
4

2
second

1
Adjustable setting
0.6 range of magnetic trip.
Five stages
0.4
within this range.
0.2

0.1 Rated current Magnetic trip current (A)


0.06 (A) Scale 8 7.1 6.3 5 4
0.04 2000 8000 7100 6300 5000 4000
0.02 Notes : Setting tolerance ±10% at 8000A and ±25% for other settings.
0.01
0.006
1000
1250

2000

3000

5000
6000
8000
10000

20000

30000

Rated Current (A) Note: Magnetic trip only. Use the external over-current relay.

3-4
Time/Current characteristic curves, Ambient Compensating Curves

Type Time/Current characteristic curves, Ambient Compensating Curves

XS2500ND 2P, 3P 3
2

hour
1
40

20

minute
10
6
4

1
40
Tripping Time

20

10
Setting tolerance Setting tolerance
6 (Scale4) (Scale8)
4

2
second

1
Adjustable setting
0.6 range of magnetic trip.
Five stages
0.4
within this range.
0.2

0.1 Rated current Magnetic trip current (A)


0.06 (A) Scale 8 7.1 6.3 5 4
2500 8000 7100 6300 5000 4000

3
0.04

0.02 Notes : Setting tolerance ±10% at 8000A and ±25% for other settings.
0.01
0.006
1000
1250

2000

3000

5000
6000
8000
10000

20000

30000

Rated Current (A) Note: Magnetic trip only. Use the external over-current relay.

Characteristics
XS3200ND 2P, 3P 3
2
hour

1
40

20
minute

10
6
4

1
40
Tripping Time

20

10
Setting tolerance Setting tolerance
6 (Scale6) (Scale12)
4

2
second

1
Adjustable setting
0.6 range of magnetic trip.
Five stages
0.4
within this range.
0.2

0.1 Rated current Magnetic trip current (A)


0.06 (A) Scale 12 11 10 8 6
0.04 3200 12000 11000 10000 8000 6000
0.02 Notes : Setting tolerance ±10% at 12000A and ±25% for other settings.
0.01
0.006
1000
1250

2000

3000

5000
6000
8000
10000

20000

30000

Rated Current (A) Note: Magnetic trip only. Use the external over-current relay.

3-5
Time/Current characteristic curves, Ambient Compensating Curves

Type Time/Current characteristic curves, Ambient Compensating Curves

PVS160-SDL 3P, 4P
PVS160-SDH 4P
PVS250-SDL 3P, 4P
PVS250-SDH 4P 3 3
2 2

hour

hour
1 1
40 40
30 30
20 20
minute

minute
10 10
6 6
4 4
2 2
50-200A(Max) 250A(Max)
1 1
40 40
Tripping Time

Tripping Time
30 30
20 20
10 10
6 6
4 4
250A(Min)
2 50-200A(Min) 2
1 1
second

second
0.6 0.6
0.4 0.4
0.2 0.2
0.1 0.1
0.06 0.06
0.04 0.04
0.02 0.02
0.01 0.01
0.005 0.005
100
125

200

300
400
500
700
1000

1500
2000

3000
4000
5000

8000

100
125

200

300
400
500
700
1000

1500
2000

3000
4000
5000

8000
Percent Rated Current Percent Rated Current

PVS160-SDL, PVS160-SDH
Rated current (A) Magnetic trip current (A) 140
50 650
63 819 Calibrated
100 1300 130 50A
Percent current rating

temperature
125 1625 200A,250A
160 2080 120 125A,160A
Notes : Setting tolerance ±20%

110
PVS250-SDL, PVS250-SDH 100A
Rated current (A) Magnetic trip current (A) 63A
100 1300 100
125 1625
160 2080
90
200 2600
250 2750 calibrated at 45°C 5 15 25 35 45 55 60
Notes : Setting tolerance ±20%
Ambient temperature (°C)

PVS400-NDL 3P 3
hour

2
140
1
40
30
20 Calibrated
130
Percent current rating

temperature
minute

10
6 400A
4 120
2
1 110
40 250A
30
Tripping Time

20
100
10
6
4 90
2
calibrated at 45°C 5 15 25 35 45 55 60
1
second

0.6 Ambient temperature (°C)


0.4
0.2
0.1
0.06
0.04
0.02
0.01
Rated current (A) Magnetic trip current (A)
0.005 250 2000
100
125

200

300
400
500
700
1000
1500
2000

3000
4000
5000

8000

400 3200
Percent Rated Current Notes : Setting tolerance ±20%

3-6
Time/Current characteristic curves, Ambient Compensating Curves

Type Time/Current characteristic curves, Ambient Compensating Curves

PVS400-NDL 4P 3

hour
2
140
1
40
30
20 Calibrated
130

Percent current rating


temperature

minute
10
6 400A
4 120
2
1 110
40 250A
30
Tripping Time

20
100
10
6
4 90
2
calibrated at 45°C 5 15 25 35 45 55 60
1
second

0.6 Ambient temperature (°C)


0.4
0.2
0.1
0.06
0.04
0.02
0.01
0.005
Rated current (A)
250
Magnetic trip current (A)
3000
3
100
125

200

300
400
500
700
1000
1500
2000

3000
4000
5000

8000
400 4800
Percent Rated Current Notes : Setting tolerance ±20%

Characteristics
PVS400-NDH 4P 3
hour

2
140
1
40
30
20 Calibrated
130

Percent current rating


temperature
minute

10
6 400A
4 120
2
1 110
40 250A
30
Tripping Time

20
100
10
6
4 90
2
calibrated at 45°C 5 15 25 35 45 55 60
1
second

0.6 Ambient temperature (°C)


0.4
0.2
0.1
0.06
0.04
0.02
0.01
Rated current (A) Magnetic trip current (A)
0.005 250 2000
100
125

200

300
400
500
700
1000
1500
2000

3000
4000
5000

8000

400 3200
Percent Rated Current Notes : Setting tolerance ±20%

PVS800-NDL 3P, 4P 3
hour

2
PVS800-NDH 4P 1
140
40
30
20 Calibrated
130
Percent current rating

temperature
minute

10
6
4 120 630A,800A
2
1 110
40
30
Tripping Time

20
100
10
630A
6
4 90
800A
2
1 calibrated at 45°C 5 15 25 35 45 55 60
second

0.6 Ambient temperature (°C)


0.4
0.2
0.1
0.06
0.04
0.02
0.01 Rated current (A) Magnetic trip current (A)
0.005 630 3500
100
125

200

300
400
500
700
1000
1500
2000

3000
4000
5000

8000

800 3500
Percent Rated Current Notes : Setting tolerance ±20%

3-7
4 Mounting and
Connection
Connection of conductors to DC circuit breakers…………………………4-2
Insulation distance DC600V or less …………………………………………4-7
Insulation distance DC750V-1000V
PVE160-SDL 3P ………………………………………………………………4-8
PVS160-SDL 3P, PVS250-SDL 3P …………………………………………4-9
4
PVS160-SDL 4P, PVS250-SDL 4P,

Mounting and Connection


PVS160-SNL 4P, PVS250-SNL 4P ………………………………4-10
PVS160-SDH 4P, PVS250-SDH 4P ………………………………………4-11
PVS160-SNH 4P, PVS250-SNH 4P ………………………………………4-12
PVS400-NDL 3P………………………………………………………………4-13
PVS400-NDL 4P, PVS400-NDH 4P ………………………………………4-14
PVS400-NNL 4P, PVS400-NNH 4P ………………………………………4-15
PVS800-NDL 3P………………………………………………………………4-16
PVS800-NDL 4P, PVS800-NDH 4P ………………………………………4-17
PVS800-NNL 4P, PVS800-NNH 4P ………………………………………4-18

4-1
Connection of conductors to DC circuit breakers
It is more difficult to interrupt DC current than AC current because DC current does not have a zero point. Therefore for high
DC voltages, 3-pole or 4-pole circuit breaker main contacts are connected in series to ensure breaking performance. As
illustrated below, the main power conductors for DC-use air circuit breakers, moulded case circuit breakers, and switch
disconnectors shall be connected generally as shown below but also depending on the type of breaker, the number of poles,
and the DC operating voltage.

Non-grounded system Grounded system Grounded system


(Protection + Isolation function) (Protection) (Protection + Isolation function)

Source Source Source

Ordinally
connection

Load Load Load

Load Load Load

Reverse
connection

Source Source
Source

Applicable Rated breaking Applicable Rated breaking Applicable Rated breaking


No.s of
Type of breakers voltage capacity voltage capacity voltage capacity
poles
(V) Icu/Ics (V) Icu/Ics (V) Icu/Ics

S1000-ND 2P ≦250 50kA/20kA ≦250 50kA/20kA ≦150 50kA/20kA

✽:2 poles breaker is a 3 pole breaker with the center pole omitted.

Non-grounded system Grounded system Grounded system


(Protection + Isolation function) (Protection) (Protection + Isolation function)

Source Source Source

Ordinally
connection

Load Load Load

Applicable Rated breaking Applicable Rated breaking Applicable Rated breaking


No.s of
Type of breakers voltage capacity voltage capacity voltage capacity
poles
(V) Icu/Ics (V) Icu/Ics (V) Icu/Ics

XS1250ND 2P ≦250 50kA/30kA ≦250 50kA/30kA ≦150 50kA/30kA


XS1600ND 2P ≦250 50kA/30kA ≦250 50kA/30kA ≦150 50kA/30kA
XS2000ND 2P ≦250 50kA/30kA ≦250 50kA/30kA ≦150 50kA/30kA
XS2500ND 2P ≦250 50kA/30kA ≦250 50kA/30kA ≦150 50kA/30kA
XS3200ND 2P ≦250 50kA/30kA ≦250 50kA/30kA ≦150 50kA/30kA

✽:2 poles breaker is a 3 pole breaker with the center pole omitted.

4-2
Non-grounded system Grounded system Grounded system
(Protection + Isolation function) (Protection) (Protection + Isolation function)

Source Source Source

Ordinally
connection

Load Load Load

Load Load Load

Reverse
connection

Source
Source
Source
4
Applicable Rated breaking Applicable Rated breaking Applicable Rated breaking
No.s of

Mounting and Connection


Type of breakers voltage capacity voltage capacity voltage capacity
poles
(V) Icu/Ics (V) Icu/Ics (V) Icu/Ics

S160-SD 3P ≦600 5kA/5kA ≦600 5kA/5kA ≦400 5kA/5kA


S160-SD 3P ≦500 7.5kA/7.5kA ≦500 7.5kA/7.5kA ≦350 7.5kA/7.5kA
S160-SD 3P ≦350 10kA/10kA ≦350 10kA/10kA ≦250 10kA/10kA
S160-GD 3P ≦600 10kA/5kA ≦600 10kA/5kA ≦400 10kA/5kA
S160-GD 3P ≦500 15kA/7.5kA ≦500 15kA/7.5kA ≦350 15kA/7.5kA
S250-SD 3P ≦600 5kA/5kA ≦600 5kA/5kA ≦400 5kA/5kA
S250-SD 3P ≦500 7.5kA/7.5kA ≦500 7.5kA/7.5kA ≦350 7.5kA/7.5kA
S250-SD 3P ≦350 10kA/10kA ≦350 10kA/10kA ≦250 10kA/10kA
S250-GD 3P ≦600 10kA/5kA ≦600 10kA/5kA ≦400 10kA/5kA
S250-GD 3P ≦500 15kA/7.5kA ≦500 15kA/7.5kA ≦350 15kA/7.5kA
S400-ND 3P ≦600 15kA/15kA ≦600 15kA/15kA ≦400 15kA/15kA
S400-ND 3P ≦350 20kA/20kA ≦350 20kA/20kA ≦250 20kA/20kA
S800-ND 3P ≦600 20kA/10kA ≦600 20kA/10kA ≦400 20kA/10kA
S800-ND 3P ≦350 30kA/15kA ≦350 30kA/15kA ≦250 30kA/15kA
S1000-ND 3P ≦600 20kA/10kA ≦600 20kA/10kA ≦400 20kA/10kA
S1000-ND 3P ≦350 30kA/15kA ≦350 30kA/15kA ≦250 30kA/15kA
PVE160-SDL 3P ≦750 3kA/3kA ≦750 3kA/3kA ≦500 3kA/3kA
PVS160-SDL 3P ≦750 5kA/5kA ≦750 5kA/5kA ≦500 5kA/5kA
PVS250-SDL 3P ≦750 5kA/5kA ≦750 5kA/5kA ≦500 5kA/5kA
PVS400-NDL 3P ≦750 10kA/5kA ≦750 10kA/5kA ≦500 10kA/5kA
PVS800-NDL 3P ≦750 10kA/10kA ≦750 10kA/10kA ≦500 10kA/10kA
S160-SDN 3P ≦600 ― ≦600 ― ≦400 ―
S250-SDN 3P ≦600 ― ≦600 ― ≦400 ―

4-3
Connection of conductors to DC circuit breakers

Non-grounded system Grounded system Grounded system


(Protection + Isolation function) (Protection) (Protection + Isolation function)

Source Source Source

Ordinally
connection

Load Load Load

Applicable Rated breaking Applicable Rated breaking Applicable Rated breaking


No.s of
Type of breakers voltage capacity voltage capacity voltage capacity
poles
(V) Icu/Ics (V) Icu/Ics (V) Icu/Ics

XS1250ND 3P ≦600 20kA/15kA ≦600 20kA/15kA ≦400 20kA/15kA


XS1250ND 3P ≦500 50kA/25kA ≦500 50kA/25kA ≦350 50kA/25kA
XS1600ND 3P ≦600 20kA/15kA ≦600 20kA/15kA ≦400 20kA/15kA
XS1600ND 3P ≦500 50kA/25kA ≦500 50kA/25kA ≦350 50kA/25kA
XS2000ND 3P ≦600 20kA/15kA ≦600 20kA/15kA ≦400 20kA/15kA
XS2000ND 3P ≦500 50kA/25kA ≦500 50kA/25kA ≦350 50kA/25kA
XS2500ND 3P ≦600 20kA/15kA ≦600 20kA/15kA ≦400 20kA/15kA
XS2500ND 3P ≦500 50kA/25kA ≦500 50kA/25kA ≦350 50kA/25kA
XS3200ND 3P ≦600 20kA/15kA ≦600 20kA/15kA ≦400 20kA/15kA
XS3200ND 3P ≦500 50kA/25kA ≦500 50kA/25kA ≦350 50kA/25kA

4-4
Non-grounded system Grounded system Grounded system
(Protection + Isolation function) (Protection) (Protection + Isolation function)

Source Source Source

Ordinally
connection

Load Load Load

Load Load Load

Reverse
connection

Source
Source
Source
4
Applicable Rated breaking Applicable Rated breaking Applicable Rated breaking
No.s of

Mounting and Connection


Type of breakers voltage capacity voltage capacity voltage capacity
poles
(V) Icu/Ics (V) Icu/Ics (V) Icu/Ics

PVS160-SDL 4P ≦750 10kA/5kA ≦750 10kA/5kA ≦550 10kA/5kA


PVS250-SDL 4P ≦750 10kA/5kA ≦750 10kA/5kA ≦550 10kA/5kA
PVS160-SDH 4P ≦1000 5kA/5kA ≦1000 5kA/5kA ≦750 5kA/5kA
PVS250-SDH 4P ≦1000 5kA/5kA ≦1000 5kA/5kA ≦750 5kA/5kA
PVS400-NDL 4P ≦750 10kA/10kA ≦750 10kA/10kA ≦750 10kA/10kA ②
PVS400-NDH 4P ≦1000 5kA/5kA ≦1000 5kA/5kA
PVS800-NDL 4P ≦750 10kA/10kA ≦750 10kA/10kA ≦750 10kA/10kA
PVS800-NDH 4P ≦1000 5kA/5kA ≦1000 5kA/5kA ≦750 5kA/5kA
PVS160-SNL 4P ≦800 ― ≦800 ― ≦600 ―
PVS250-SNL 4P ≦800 ― ≦800 ― ≦600 ―
PVS160-SNH 4P ≦1000 ― ≦1000 ― ≦750 ―
PVS250-SNH 4P ≦1000 ― ≦1000 ― ≦750 ―
PVS400-NNL 4P ≦800 ― ≦800 ― ≦750 ―
PVS400-NNH 4P ≦1000 ― ≦1000 ―
PVS800-NNL 4P ≦800 ― ≦800 ― ≦750 ―
PVS800-NNH 4P ≦1000 ― ≦1000 ―
Note ②:The breaking capacity goes down to Icu10kA / Ics5kA for ground fault protection.

4-5
Connection of conductors to DC circuit breakers

Non-grounded system Grounded system Grounded system


(Protection + Isolation function) (Protection) (Protection + Isolation function)

Source Source Source

Ordinally
connection

Load Load Load

Load Load Load

Reverse
connection

Source Source
Source

Applicable Rated breaking Applicable Rated breaking Applicable Rated breaking


No.s of
Type of breakers voltage capacity voltage capacity voltage capacity
poles
(V) Icu/Ics (V) Icu/Ics (V) Icu/Ics

AR216S ③ 3P ≦600 40kA/40kA ≦600 40kA/40kA ≦400 40kA/40kA


AR220S ③ 3P ≦600 40kA/40kA ≦600 40kA/40kA ≦400 40kA/40kA
AR325S ③ 3P ≦600 40kA/40kA ≦600 40kA/40kA ≦400 40kA/40kA
AR332S ③ 3P ≦600 40kA/40kA ≦600 40kA/40kA ≦400 40kA/40kA
AR440S ③ 3P ≦600 40kA/40kA ≦600 40kA/40kA ≦400 40kA/40kA

Note ③:AGR over-current release can not be used for DC. Please prepare DC over-current relay and connect with shunt trip device.

Non-grounded system Grounded system Grounded system


(Protection + Isolation function) (Protection) (Protection + Isolation function)

Source Source Source

Ordinally
connection

Load Load Load

Load Load Load

Reverse
connection

Source
Source
Source

Applicable Rated breaking Applicable Rated breaking Applicable Rated breaking


No.s of
Type of breakers voltage capacity voltage capacity voltage capacity
poles
(V) Icu/Ics (V) Icu/Ics (V) Icu/Ics

AR325-NDH ③ 4P ≦800 30kA/30kA ≦800 30kA/30kA ≦600 30kA/30kA

Note ③:AGR over-current release can not be used for DC. Please prepare DC over-current relay and connect with shunt trip device.

4-6
Insulation distance DC600V or less
The insulation distances between the breaker and earthed metal parts and insulators shown in the table below must be
maintained to prevent arcing faults occurring due to conductive ionised gas. In addition, any exposed line-side conductors
must be completely covered, right up the breaker casing or to below the height protected by any interpole barriers. This can
done by using an insulation tube or tape, in order to provide positive protection against short circuit or ground fault due to
metal chipping, surge voltage, dust particles or salt. If terminal covers are not being used, the interpole barriers supplied with
the breaker as standard must be used.

Insulating Sheathed wire


tube or tape

Interpole barrier Interpole barrier


Exposed Compression
conductor terminal
Line side
(ON side)

Load side
(OFF side)

Insulation plate Top plate (earthed metal) Interpole barrier


(Insulation tube or tape
is also acceptable)
Side plate
B1
B2
B1
B2
B1
B2
E 4

Mounting and Connection


A
D
A
A Insulation tube
or tape

Front connection, Front connection, Rear connection, C


terminal screw extension bar Plug-in
A . Distance from lower breaker to exposed live part of upper breaker terminal (front connection) or distance from
lower breaker to end face of upper breaker (rear connection).
B1. Distance from end face of breaker to top plate.
B2. Distance from end face of breaker to insulation plate.
C . Gap between breakers.
D . Distance from side of breaker to side plate (earthed metal).
E . Dimension of insulation over exposed conductors.

Insulation distance, mm (DC 600 V or less) Note ①


A
Moulded Case Circuit Breakers B1 B2 C D E
Note ②

Possible to set close Not less than the length of


S160-SD S160-GD S160-SDN ⑤ 50 50 50 ✽ 25
Note ③ the bare live part Note ④
S250-SD S250-GD S250-SDN ⑤ 65 65 65 ✽ 〃 50 〃
S400-ND S800-ND S1000-ND 150 120 80 〃 80 〃
XS1250ND XS1600ND XS2000ND XS2500ND XS3200ND 150 150 100 〃 100 〃
Notes:
①. Required to allow free and uninterrupted flow of arc gases. Ensure additional clearance or insulation distance if required to perform wiring, barrier installation or electrical work or to meet
the need for more insulation distance between bare live parts and grounded metal members in a switchboard or the like.
②. The figures are for lower breakers.
③. When the accessories are fitted it is not possible to set close.
④. For front connected breakers, insulate all exposed conductors of the line side until the breaker end. If interpole barriers are packed, be sure to use the barriers; more over, insulate all
exposed conductors by insulating tape or the like so that the tape overlaps with the barriers.
⑤. Be sure to install the terminal covers (supplied as standard) on the line side of the breakers.
✽. If using extension bars (optional), ensure the insulation distance specified for the application.

4-7
Insulation distance DC750V-1000V
The insulation distances between the breaker and earthed metal parts and insulators shown in the table below must be
maintained to prevent arcing faults occurring due to conductive ionised gas. In addition, any exposed line-side conductors
must be completely covered, right up the breaker casing or to below the height protected by any terminal covers or interpole
barriers. This can done by using an insulation tube or tape, in order to provide positive protection against short circuit or
ground fault due to metal chipping, surge voltage, dust particles or salt. The terminal covers or the interpole barriers supplied
with the breaker as standard must be used. For DC750V-1000V breakers, the front and the rear insulating plates must also
be installed.

PVE160-SDL 3P

Front-connected

Terminal cover
B

Insulating plate
(supplied as standard)
130

Mounting plate

Mounting plate
B

Terminal cover
A 75 A 70

Rear-connected

Terminal cover
Insulating plate
(supplied as standard)
B

Mounting plate
130

Mounting plate
Terminal cover
B

Insulating plate
(supplied as standard)
A 75 A 70

Minimum insulation distance (mm) Insulating plate


Type Connection
A B Terminal cover Insulating plate

1pc of 130mm×75mm for F.C.


Front-connected 2pcs are supplied for line
PVE160-SDL 3P 25 50 or 140mm×75mm for R.C. is
Rear-connected and load side as standard.
supplied as standard.

4-8
PVS160-SDL 3P, PVS250-SDL 3P

Front-connected

5 5
Terminal cover
Insulating plate
(supplied as standard)
B

Insulating plate
(supplied as standard)
165

Mounting plate

Mounting plate
4
B

Terminal cover

Mounting and Connection


A 105 A 70

Rear-connected

5 5
Terminal cover
Insulating plate
(supplied as standard)
B

Insulating plate
(supplied as standard)
165

Mounting plate

Mounting plate
B

Terminal cover
A 105 A 70

Minimum insulation distance (mm) Insulating plate


Type Connection
A B Terminal cover Insulating plate

PVS160-SDL 3P Front-connected 2pcs are supplied for line 2pcs of 115mm×137.5mm


50 65
PVS250-SDL 3P Rear-connected and load side as standard. are supplied as standard.

4-9
Insulation distance DC750V-1000V

PVS160-SDL 4P, PVS250-SDL 4P, PVS160-SNL 4P, PVS250-SNL 4P

Front-connected

Terminal cover
B
165

Mounting plate

Mounting plate
B

Terminal cover
A 140 A 68

Rear-connected

Terminal cover
B
165

Mounting plate

Mounting plate
B

Terminal cover
A 140 A 68

Minimum insulation distance (mm)


Type Connection Terminal cover
A B
PVS160-SDL 4P
PVS250-SDL 4P Front-connected
50 65 2pcs are supplied for line and load side as standard.
PVS160-SNL 4P Rear-connected
PVS250-SNL 4P

4-10
PVS160-SDH 4P, PVS250-SDH 4P

Front-connected

20 20

Terminal cover
Insulating plate
(supplied as standard)
B

Insulating plate
(supplied as standard)
165

Mounting plate

Mounting plate
4
B

Terminal cover

Mounting and Connection


A 140 A 70

Rear-connected

20 20

Terminal cover
Insulating plate
(supplied as standard)
B

Insulating plate
(supplied as standard)
165

Mounting plate

Mounting plate
B

Terminal cover
A 140 A 70

Minimum insulation distance (mm) Insulating plate


Type Connection
A B Terminal cover Insulating plate

PVS160-SDH 4P Front-connected 2pcs are supplied for line 2pcs of 180mm×147.5mm


50 65
PVS250-SDH 4P Rear-connected and load side as standard. are supplied as standard.

4-11
Insulation distance DC750V-1000V

PVS160-SNH 4P, PVS250-SNH 4P

Front-connected

13 13

Terminal cover
Insulating plate
(supplied as standard)
B

Insulating plate
(supplied as standard)
165

Mounting plate

Mounting plate
B

Terminal cover
A 140 A 70

Rear-connected

13 13

Terminal cover
Insulating plate
(supplied as standard)
B

Insulating plate
(supplied as standard)
165

Mounting plate

Mounting plate
B

Terminal cover
A 140 A 70

Minimum insulation distance (mm) Insulating plate


Type Connection
A B Terminal cover Insulating plate

PVS160-SNH 4P Front-connected 2pcs are supplied for line 2pcs of 166mm×137.5mm


30 65
PVS250-SNH 4P Rear-connected and load side as standard. are supplied as standard.

4-12
PVS400-NDL 3P

Front-connected
Ionised gas area
G G Interpole barrier

Insulating plate

F
A

Insulating plate (supplied as standard)

E
D
260

420

Mounting plate

4
B

Mounting and Connection


260
105
C 140 C

Rear-connected
Ionised gas area
G G Interpole barrier

Insulating plate
A

(supplied as standard)
F

Insulating plate
E
D
420
260

Mounting plate
B

260
105
C 140 C

Minimum insulation distance (mm) Insulating plate


Type Connection
A B C D E F G Front panel side Mounting plate side

Front-connected
PVS400-NDL 3P 160 80 80 30 140 160 60 Not supplied Supplied as standard
Rear-connected

4-13
Insulation distance DC750V-1000V

PVS400-NDL 4P, PVS400-NDH 4P

Front-connected
Front panel
G G Ionised gas area
Interpole barrier

Insulating plate

F
A

(supplied as standard)

E
D
Insulating plate
260

420

Mounting plate
B

305 Interpole barrier 105


C 185 C

Rear-connected
Front panel
G G Ionised gas area
Interpole barrier

Insulating plate
A

(supplied as standard)
F

E
D

Insulating plate
420
260

Mounting plate
B

305
105
C 185 C

Minimum insulation distance (mm) Insulating plate


Type Connection
A B C D E F G Front panel side Mounting plate side

PVS400-NDL 4P Front-connected
160 80 80 30 140 160 60 Not supplied Supplied as standard
PVS400-NDH 4P Rear-connected

4-14
PVS400-NNL 4P, PVS400-NNH 4P

Front-connected
Front panel Ionised gas area
G G Interpole barrier
A

F
Insulating plate

E
D
Insulating plate
260

Mounting plate

4
B

Mounting and Connection


C 185 C Interpole barrier 103

Rear-connected
Front panel
G G Ionised gas area
Interpole barrier
A

Insulating plate
F

E
D

Insulating plate
260

Mounting plate
B

C 185 C 103

Minimum insulation distance (mm) Insulating plate


Type Connection
A B C D E F G Front panel side Mounting plate side

PVS400-NNL 4P Front-connected
120 80 80 30 80 80 40 Not supplied Not supplied
PVS400-NNH 4P Rear-connected

4-15
Insulation distance DC750V-1000V

PVS800-NDL 3P

Front-connected
330
Ionised gas area
Interpole barrier

Insulating plate
A

F
Insulating plate (supplied as standard)

E
D
273

513

Mounting plate
B

G G 105
C 210 C

Rear-connected
330 Ionised gas area
Interpole barrier

Insulating plate
A

Insulating plate (supplied as standard)


F

E
D
273

513

Mounting plate
B

G G 105

C 210 C

Minimum insulation distance (mm) Insulating plate


Type Connection
A B C D E F G Front panel side Mounting plate side

Front-connected
PVS800-NDL 3P 160 80 80 80 140 160 60 Not supplied Supplied as standard
Rear-connected

4-16
PVS800-NDL 4P, PVS800-NDH 4P

Front-connected
400
Front panel
Ionised gas area
Interpole barrier

Insulating plate

F
A

(supplied as standard)

E
D
Insulating plate
273

513

Mounting plate

4
B

Mounting and Connection


G G 105
C 280 C

Rear-connected 400
Front panel
Ionised gas area
Interpole barrier

Insulating plate
A

(supplied as standard)
F

E
D

Insulating plate
273

513

Mounting plate
B

105
G G

C 280 C

Minimum insulation distance (mm) Insulating plate


Type Connection
A B C D E F G Front panel side Mounting plate side

PVS800-NDL 4P Front-connected
160 80 80 80 140 160 60 Not supplied Supplied as standard
PVS800-NDH 4P Rear-connected

4-17
Insulation distance DC750V-1000V

PVS800-NNL 4P, PVS800-NNH 4P

Front-connected
400
Front panel
Ionised gas area
G G Interpole barrier

F
A

Insulating plate

E
D
Insulating plate
273

Mounting plate
B

103
C 280 C

Rear-connected
400
Front panel
Ionised gas area
Interpole barrier
G G

Insulating plate
A

(supplied as standard)
F

E
D

Insulating plate
273

Mounting plate
B

103

C 280 C

Minimum insulation distance (mm) Insulating plate


Type Connection
A B C D E F G Front panel side Mounting plate side

PVS800-NNL 4P Front-connected
120 80 80 80 80 80 60 Not supplied Not supplied
PVS800-NNH 4P Rear-connected

4-18
5 Outline
Dimensions
DC Air Circuit Breakers Outline Dimensions
AR216S, AR220S 3P …………………………………………………………5-2
AR325S, AR332S 3P …………………………………………………………5-4
AR325-NDH 4P…………………………………………………………………5-6
AR440S 3P ……………………………………………………………………5-8
DC Moulded Case Circuit Breakers Outline Dimensions
S160-SD, S160-GD, S160-SDN, S250-SD, S250-GD, S250-SDN 3P …5-10
S400-ND 3P …………………………………………………………………5-11
S800-ND 3P …………………………………………………………………5-11
5
S1000-ND 2P, 3P ……………………………………………………………5-12

Outline Dimensions
XS1250ND 2P, 3P ……………………………………………………………5-13
XS1600ND 2P, 3P ……………………………………………………………5-14
XS2000ND 2P, 3P ……………………………………………………………5-15
XS2500ND, XS3200ND 2P, 3P ……………………………………………5-16
PVE160-SDL 3P………………………………………………………………5-17
PVS160-SDL, PVS250-SDL 3P ……………………………………………5-18
PVS160-SDL, PVS250-SDL, PVS160-SNL, PVS250-SNL 4P …………5-18
PVS160-SDH, PVS250-SDH, PVS160-SNH, PVS250-SNH 4P ………5-19
PVS400-NDL 3P………………………………………………………………5-20
PVS400-NDL, PVS400-NDH 4P ……………………………………………5-21
PVS400-NNL, PVS400-NNH 4P ……………………………………………5-21
PVS800-NDL 3P………………………………………………………………5-22
PVS800-NDL, PVS800-NDH 4P ……………………………………………5-23
PVS800-NNL, PVS800-NNH 4P ……………………………………………5-23

5-1
DC Air Circuit Breakers
Outline dimensions (mm)

¡Type AR216S 3P, AR220S 3P Draw-out type

Terminal size
Type ○1
t ○2
t ○3
t W
AR216S 20 15 25 22.5
AR220S 20 15 25 ―

CP

Maintenance
rear panel cut 158.5 158.5 space

front panel cut


CP
405

335※2

329

460

490

500
R
11
6
50

42.5
33
20

30

250

164 164 238

177 177 draw-out handle


For fitted with breaker fixing bolts
204 204
panel cut-out Maintenance Maintenance
space 240 240 space
94
141

4-ø14
120 120

Mounting holes
※ 1 : ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Conductors including connecting bolts should be separated min-7mm from Draw-out arm.
※ 2 : Panel cut should be 339 mm not 335 mm when the door flange is used.

5-2
P:ACB Front cover center line

AR216S 3P, AR220S 3P

Inter-pole barrier

107
67
299.5

85
P
C

85
125
CONNECTED position
TEST position Control circuit terminal cover (optional)
ISOLATED position Lifting hole 2-ø20 Inter-pole barrier 1.6t
14 21 AR216S AR220S
199 35 35 conductor overlap. max 85 85
18

ON-OFF button cover 15 15


15.5

2-ø11
W

25 25

12
25

20 42.5
W

14.5 14.5
345.5

345.5
149

Inter-pole barrier 2t
17
M8 screw
W

earth terminal

5
25

25 25

204.5
150.5

48.5
W

¶1
15.5

40

3-ø11 9 25
59.5

Outline Dimensions
59.5

33 t2
94 141 110 40
345 100 100 140
265 445

Draw-out arm
(comes out when breaker is drawn out)

5-3
DC Air Circuit Breakers
Outline dimensions (mm)

¡Type AR325S 3P, AR332S 3P Draw-out type

CP

Maintenance
rear panel cut 211.5 211.5 space

front panel cut


CP
335※2
405

329

460

490

500
R
11
6
50

33

60
20

30

250

216 216 238

230 230
draw-out handle
For fitted with 257 257
breaker fixing bolts
panel cut-out
293 293

Maintenance Maintenance
space space
94
141

4-ø14

172.5 172.5
※ 1 : ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Conductors including connecting bolts should be separated min-7mm from Draw-out arm.
※ 2 : Panel cut should be 339 mm not 335 mm when the door flange is used.

Mounting holes

5-4
P:ACB Front cover center line

AR325S 3P, AR332S 3P

Inter-pole barrier

109
142
406

120
P
C

120
161
CONNECTED position
TEST position Control circuit terminal cover (optional) P
C
ISOLATED position Lifting hole 2-ø20
5
14 21
130 130
199 35 conductor overlap. max
Inter-pole barrier 1.6t
18

ON-OFF button cover 15


12.5
25 25 25

100

12
20 65
12.5

345.5

Inter-pole barrier 2t
5
120

17 4-ø11
M8 screw
12.5

earth terminal
25 25 25
100

204.5

48.5
165

Outline Dimensions
¶1
12.5

40

9
25
59.5

33
94 141 110 40 20
345 100 197.5
265 445

Draw-out arm
(comes out when breaker is drawn out)

5-5
DC Air Circuit Breakers
Outline dimensions (mm)

¡Type AR325-NDH 4P Draw-out type

CP

Maintenance
rear panel cut 211.5 331.5 space

front panel cut


CP
335※2
405

329

460

490

500
R
11
6
50

33

60
20

30

250

216 336 238

230 350
draw-out handle
For fitted with 257 377
breaker fixing bolts
panel cut-out
293 413

Maintenance Maintenance
space space
94
141

4-ø14

※ 1 : ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Conductors including connecting bolts should be separated min-7mm from Draw-out arm. 172.5 292.5
※ 2 : Panel cut should be 339 mm not 335 mm when the door flange is used.

Mounting holes

5-6
P:ACB Front cover center line

AR325-NDH 4P

Inter-pole barrier

32
110
70
120
P
C

526

120
129
32
CONNECTED position
TEST position Control circuit terminal cover (optional) P
C
ISOLATED position Lifting hole 2-ø20
5
14 21
130 130 130
199 35 conductor overlap. max
Inter-pole barrier 1.6t
18

ON-OFF button cover 15


12.5
25 25 25

100

12
20 65

5
12.5

345.5

Inter-pole barrier 2t
120

17 4-ø11
12.5
25 25 25
100

204.5

48.5

Outline Dimensions
165

¶1
12.5

40

9
25
59.5

33
94 141 110 40 20
345 100 M8 screw 317.5
265 445 earth terminal

Draw-out arm
(comes out when breaker is drawn out)

5-7
DC Air Circuit Breakers
Outline dimensions (mm)

¡Type AR440S 3P Draw-out type

P
rear panel cut C
Maintenance
158.5 435.5 space
front panel cut
P
C

500
490
335 ※2

460
405

329
16

50
R1
20
30

33

42.5

250 238
164 441
For fitted with 177 454 draw-out handle
breaker fixing bolts
Maintenance space 204 481
Maintenance
space
240 517
panel cut-out

※ 1 : ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
Conductors including connecting bolts should be separated min-7mm from Draw-out arm.
※ 2 : Panel cut should be 339 mm not 335 mm when the door flange is used.

5-8
P:ACB Front cover center line

AR440S 3P

Inter-pole barrier

42.5

157.5
192
P
C

181
576.5

192
181
15

175.5
210
50
15

Control circuit terminal cover

CONNECTED position

TEST position
ISOLATED position

14 21 Lifting hole 2-ø20

40 conductor overlap. max P


199 C
ON-OFF button cover 20 417
4-ø11
18

Inter-pole barrier 1.6t


12.5

42.5
25

12
5
12.5 25

100

20
25

345.5

Inter-pole barrier 2t
120

17
12.5
25 25 25

204.5

Outline Dimensions
100

48.5
40
165

¶1
12.5

25
59.5

M8 screw
Front panel 375 earth terminal
9
35
375 33
Rear panel
100
295 428
Draw-out arm
94 141 193 (comes out when breaker is drawn out)

4-ø14
397

P
C
120

5-9
ASL : Arrangement Standard Line
DC Moulded Case Circuit Breakers H
L : Handle Frame Centre Line C L : Handle Centre Line

Outline dimensions (mm) S160-SD 3P, S160-GD 3P, S160-SDN 3P


ø5 ø5
Front-connected ø9 .5(2
(63 5-4 ø9 .5(2
(63 5-4
Preparation of -16 0A -16 0A
conductor
0A )
) 0A )
) With extension bars ✽ Drilling plan
(optional) (front view)
3P Terminal cover 66 16.5(max.) 14(max.) 3P

6.5(max.)

9(max.)
61 max.t5 max.t5 HL
HL 60.3 25 25 28
4
M5✕0.8 screw (25-40A) 3P
50

Mounting hole
M8 screw (63-160A) HL

24
102

111
130

45
114

C
L C
L C
L C
L C
L

22 M4✕0.7
Mounting screw

36.5
50 52 7.7 M4✕0.7
25 Tapped hole
75 68

8.5
10.5 95 ø8.3 ✽ Straight bars only.
17 For line side, use with the terminal cover.

A A
Rear-connected Detail of Drilling plan (front view) Panel cutout (front view)
B

connecting part
E

3P C DC D 3P 3P
Terminal cover 66 3P
Mounting hole HL 57 HL HL HL
5.3

Terminal cover 56 Mounting plate 37.5


(max. t3.2)
F
130

111
102

114

114
7.7
45

48
C
L C
L C
L

M4✕0.7
52

22
Mounting screw
102

ø20 38.5
75
68 52 25 77
Studs are horizontal M4✕0.7
95 102 direction only 50 Tapped hole
25 25
Rated current (A) A B C D E F
25-40 10.5 6.5 4 13 16 4 Panel cutout dimensions shown give an allowance
63-160 12.5 8.5 4 13 16 5 of 1.0mm or more around the handle escutcheon.

Outline dimensions (mm) S250-SD 3P, S250-GD 3P, S250-SDN 3P

Front-connected Preparation of With extension bars ✽ Drilling plan


conductor (optional) (front view)
3P ø9 3P
11(max.)

Conductor
HL Terminal cover 65.5 HL overlap, max
28 3P
Terminal cover 25(max.) 35 35
11.5

Mounting hole 4
Mounting hole max.t7 23
55

HL
30.5

M8 screw
19

24
144

165
102

126
165

45

C C C C C
45

L L L L L

22 M4✕0.7 22
Mounting screw

70 46 7 M4✕0.7
35
105 60 Tapped hole
68 ø11
10.5 95 ✽ Straight bars only.
For line side, use with the terminal cover.

Rear-connected
Detail of Drilling plan (front view) Panel cutout (front view)
connecting part

3P Terminal cover 3P 3P 3P
Mounting hole Mounting plate ø24 H
52.5 L
5.3

HL Terminal cover 65.5 (max. t3.2) HL HL


6
102

144

126

48
165

144
45

C
L C
L Conductor C
L C
L
overlap, max
7

24 21 ø9
22
20
9

105 M4✕0.7 M4✕0.7


6 13 16 35 53.5
Stud can be turned Mounting screw Tapped hole
60 72 35 35 35 35 107
45° or 90°
68 107
Panel cutout dimensions shown give an
allowance of 1.0mm around the handle
escutcheon.

5-10
ASL : Arrangement Standard Line
H
L : Handle Frame Centre Line CL : Handle Centre Line

Outline dimensions (mm) S400-ND 3P

Front-connected Preparation of With extension bars Drilling plan (front view)


conductor 148 (optional)

ø1
HL 120

4
On side 36 ø11
Interpole barrier

30 14.5

30 14.5
Off side 35 28
(removable) HL 8 36
110 3P
M10 screw

(max.)
30

44.5

44.5
HL

12
(max.)
Interpole barrier
max. t10
Mounting hole 116 (removable)

349
260
102

214
228
260

90
CL CL CL CL CL
M6
51 Mounting screw Trip button
(red)

44.5
85.3 14.7 45 M6
97 Tapped hole
90 103 8 35
140 4 107
127.5
145
(With handle cap)

Rear-connected
Drilling plan (front view) Panel cutout (front view)

Stud can be turned 45° or 90°


Mounting plate HL 3P
HL 3P
CL
8

103
102

R6
90

214
228
CL

92
CL CL
228
260

70
39

110

45
3 15

39
30

overlap max.
Conductor

15
ø1

30 45 45 118
overlap max.
ø1

97
Conductor

M6
3

ø3

103 90
6

4 107 Tapped hole


Panel cutout dimensions shown
127.5
145 give an allowance of 1.0mm
around the handle escutcheon.
Note: Studs are factory installed in horizontal direction both on the line and load sides.

Outline dimensions (mm) S800-ND 3P 5


Front-connected
Interpole barrier
Drilling plan (front view)
3P

Outline Dimensions
(removable) HL 3 t1 L1
ø1 Toggle extension
Mounting hole 13 (removable) 3P
80

HL

170
141

126
46.5 55.5

273
90

ASL ASL ASL


117

28 13
132

Trip button 51
(red)
15 32 25

M8 M8
8

80

70
Mounting screw Tapped hole
40 t2 L2
140 Conductor
overlap, max 103
210 4 107 Rated Current (A) L1 L2 t1 t2
127.5 630 32 34 8 8
80.5 145 800 32 35 10 10

Rear-connected Drilling plan (front view) Panel cutout (front view)

Toggle extension Stud can 3P


(removable) be turned 90° HL ø15 for accessory wiring 3P
8

3P
ø4

when necessary HL HL
10

103

13
30.5
126
126

R6
92

ASL ASL ASL


32 25

122

M8
8
117

117

28 13 Tapped hole
20

70 70
42

ø13

Conductor 172
103 M8 overlap, max 70
4 107 Mounting screw 43 70 70 43
127.5
80.5 145 Panel cutout dimensions shown give an allowance
Note: Studs are factory installed in horizontal direction both on the line and load sides. of 1.0mm around the handle escutcheon.

5-11
ASL : Arrangement Standard Line
DC Moulded Case Circuit Breakers H
L : Handle Frame Centre Line C L : Handle Centre Line

Outline dimensions (mm) S1000-ND 2P, 3P

Front-connected Interpole barrier Preparation of conductor Drilling plan (front view)


Mounting hole
(removable)
3P
HL 3 14 32
ø1 Toggle extension
110

13 (removable) 3P
HL

80
170

141

126
46.5 55.5

273
90
ASL ASL ASL

117
132
28 13
51
Trip button
(red)
15 32 25

M8 M8
80

70
8

Mounting screw Tapped hole


45 14 35
140 Conductor 103
overlap, max
210 4 107
127.5
80.5 145

Rear-connected Drilling plan (front view) Panel cutout (front view)


Secured in vertical
Toggle extension position only
(removable) ø15 for accessory wiring 3P 3P

1
ø5
3 when necessary HL HL
ø1 3P
HL
13

30.5
126
126

25 32 20
R6
Conductor overlap, max

92
103

ASL M8 ASL ASL


117

28 13 Tapped hole 117


122
45

70 172
103
M8 12
4 107 43 70 70 43
Tapped hole 70 70
127.5 Panel cutout dimensions shown give an allowance
80.5 145 of 1.0mm around the handle escutcheon.

Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

5-12
ASL : Arrangement Standard Line
H
L : Handle Frame Centre Line CL : Handle Centre Line

Outline dimensions (mm) XS1250ND 2P, 3P

Front-connected

Mounting hole Drilling plan (front view)

Toggle extension
(removable) Conductor
overlap, max

M8
Mounting screw

Rear-connected
Drilling plan (front view) Panel cutout (front view)

Mounting plate

M8 Mounting screw

Conductor
overlap, max

Mounting plate
Insulating plate
Soft plastic tubing ø50 to be
provided on center pole and
neutral pole of vertical
terminal type for insulation.
5
Note: Studs are factory installed in horizontal direction both on the line and load sides. ø15 for accessory wiring when necessary
Please specify when ordering if vertical direction is reqired.

Outline Dimensions
Panel cutout dimensions shown give an
allowance of 1.5mm around the handle
escutcheon.

Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

5-13
ASL : Arrangement Standard Line
DC Moulded Case Circuit Breakers H
L : Handle Frame Centre Line C L : Handle Centre Line

Outline dimensions (mm) XS1600ND 2P, 3P

Front-connected
Drilling plan (front view)
Insulating plate
Toggle extension
(removable)

Mounting angle

M8
Mounting screw

Conductor
overlap, max

Rear-connected Drilling plan (front view) Panel cutout (front view)


Mounting angle

M8
Mounting screw
overlap, max

Insulation tube
Conductor

(ON
OFF side All poles )
side Center pole

Panel cutout dimensions shown give an


allowance of 1.5mm around the handle
escutcheon.

Draw-out Breaker fixing screw


395 (draw-out) Drilling plan (front view)
Auxiliary 3P Mounting hole 325 (disconnected)
circuit terminals
(Automatic connection) Draw-out handle 295 (test)
220 (removable) 265 (connected) 225
ø12
105

Toggle extension ø12 ø12


(removable) Mounting hole
200

20
170
50
75
100 60
420
220

190
20

°
90
70
20 25

25
120

※ 300 (max.) 282


316 200 Mounting angle 215
20

15
396 (connected) 70 70
※Contact TERASAKI if manual connection is required.
526 (draw-out) Conductor overlap, max Conductor overlap, max

Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

5-14
ASL : Arrangement Standard Line
H
L : Handle Frame Centre Line CL : Handle Centre Line

Outline dimensions (mm) XS2000ND 2P, 3P

Front-connected
Drilling plan (front view)
3P 65
Mounting hole 30 ø11
130 28.8 HL
Mounting angle
20
90

30
Toggle extension
(removable)
105
257

232
450

ASL ASL ASL

30
58 98.5

79
193

M10
Mounting screw
250 302 ø12
20

1
90
15 30

10 20 18
105 105 Conductor
overlap, max 60 225
320
380

Rear-connected Drilling plan (front view) Panel cutout (front view)


M10 HL
Mounting screw HL HL

30
Toggle extension
(removable) Mounting angle
105

232
95

ASL ASL ASL

144
30
79
160

0
30

R1
65

302 ø12
1 ø11 20
10 185 20 30 Conductor overlap, max 105 105
119
245 130 15 Panel cutout dimensions shown
340 give an allowance of 2mm around
the handle escutcheon.

Draw-out
Auxiliary
circuit terminals
(Automatic connection)
3P
HL
Manual operating toggle
(removable)
561(draw-out)
371(disconnected)
341(test)
Drilling plan (front view)
5
311(connected) Mounting hole ø14
Mounting hole 334 340(3P) ø14
34

HL
Draw-out toggle HL
(removable)

Outline Dimensions
ø11
314

20
232
65
160 95

15 30 20

ASL
624

ASL ASL
112
310

280
20 °
20

90
30

105105
※ Conductor overlap, max
405(max.) 308 25 290(3P) 268
13 371
466
※Contact TERASAKI if manual connection is required. Mounting angle

Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

5-15
ASL : Arrangement Standard Line
DC Moulded Case Circuit Breakers H
L : Handle Frame Centre Line C L : Handle Centre Line

Outline dimensions (mm) XS2500ND 2P, 3P, XS3200ND 2P, 3P

裏 面形
Rear-connected

Toggle extension M10


3P (removable) Mounting screw
Mounting hole
90 28.8 Mounting angle
HL
257

113
450

ASL ASL
58 98.5

178
193

40
90
1 20
30

250 ø14 105 105


320 10 185 20 40 Conductor overlap, max
20
245 150
340

HL
HL Mounting angle

30
105

ASL 232
144

ASL
30
79
10
R

302 ø12
119

Panel cutout dimensions shown


give an allowance of 2mm around
the handle escutcheon.
Note: 2 poles breaker is same outline dimensions as 3 poles breaker.

5-16
ASL : Arrangement Standard Line
H
L : Handle Frame Centre Line CL : Handle Centre Line

Outline dimensions (mm) PVE160-SDL 3P

Front-connected Preparation of ø5 ø5 With extension bars ✽ Drilling plan


ø9 .5(2 ø9 .5(2 (optional)
conductor (63 5-4
-16 0A
(63 5-4
-16 0A
(front view)
Terminal cover 0A ) 0A ) 3P
3P ) )
HL
HL 67.6 25 25 29.6
16.5(max.) 14(max.) 4

6.5(max.)

9(max.)
max.t5 max.t5 3P
50

Mounting hole
HL
M5✕0.8 screw (25-40A)
M8 screw (63-160A)
25.6
Insulating plate
102

111
130

45
114

C
L C
L C
L C
L C
L

22 M4✕0.7
Mounting screw

36.5
M4✕0.7
50

25 Tapped hole
Insulating plate

8.5
1.6t ø8.3
50 17
53.6 6.1 ✽ Straight bars only.
75 69.6 For line and load side, use with the terminal covers.
10.5 96.6

A A
Rear-connected Detail of Drilling plan (front view)
B

Panel cutout (front view)


connecting part
E

3P C DC D 3P 3P
Terminal cover Mounting plate (max. t3.2) 3P
Mounting hole HL 67.6 HL HL
Terminal cover HL
5.3

Insulating plate 37.5


F

Insulating plate
130

111
102

114

114
45

48
6.1

C
L C
L C
L
50.4

22 M4✕0.7
Mounting screw
100.4

50 ø20
5.3

1.6t 38.5
75 25 77
69.6 50.4 Studs are horizontal M4✕0.7
96.6 100.4 direction only 50 Tapped hole
25 25
Rated current (A) A B C D E F
25-40 10.5 6.5 4 13 16 4 Panel cutout dimensions shown give an allowance
63-160 12.5 8.5 4 13 16 5 of 1.0mm or more around the handle escutcheon.

Outline Dimensions

5-17
ASL : Arrangement Standard Line
DC Moulded Case Circuit Breakers H
L : Handle Frame Centre Line C L : Handle Centre Line

Outline dimensions (mm) PVS160-SDL 3P, PVS250-SDL 3P

Front-connected Preparation of With extension bars ✽ (optional) Drilling plan (front view)
3P
conductor 3P
67.1 HL
60.6 ø9 Conductor

11(max.)
HL Terminal cover 57.5 35 35 overlap, max
23 29.6
Terminal cover 3P

11.5
Mounting hole 4
25(max.) Mounting hole
55

HL

30.5
max.t7

19
M8 screw

25.6
144

165
102

126
165

C C C C C
45

L L L L L

22 M4✕0.7 22
Mounting screw

35 M4✕0.7
55

Tapped hole
ø11 Insulating plate
Insulating plate
70 Insulating plate 1.6t 115 Insulating plate
105 47.6 5.4
61.6
115
10.5 69.6 ✽ Straight bars only.
96.6 For line and load side, use with the terminal covers.

Rear-connected
Drilling plan (front view) Panel cutout (front view)
3P
HL Terminal cover 67.1 Mounting plate
60.2 (max. t3.2) 3P 3P 3P
Mounting hole 57.1 Insulating plate ø24 H
55

52.5 L
5.3

Terminal cover HL HL
6

Insulating plate
102

144

126

48
165

144
C C Conductor C C
45

L L L L
overlap, max
5.4

24 21 ø9
22
20
9

Stud can be turned M4✕0.7 M4✕0.7


5.3

6 13 16 35 53.5
55

45° or 90° Mounting screw Tapped hole


1.6t 35 35 35 35 107
61.6
105 Panel cutout dimensions shown give an
Insulating plate 10.5 69.6 70.4
allowance of 1.0mm around the handle
115 96.6 105.4
escutcheon.

Outline dimensions (mm) PVS160-SDL 4P, PVS250-SDL 4P, PVS160-SNL 4P, PVS250-SNL 4P

Front-connected Preparation of With extension bars ✽ (optional) Drilling plan (front view)
4P conductor 4P
65.5 HL
59 ø9 Conductor
11(max.)

HL Terminal cover 57.5 35 35 35 overlap, max


23 28
Terminal cover 4P
11.5

Mounting hole 4
25(max.)
55

Mounting hole HL
30.5

max.t7
19

M8 screw

24
144

102

165

126
165

45

C
L C
L C
L C
L C
L

22 M4✕0.7 22
Mounting screw

35 M4✕0.7
55

Tapped hole
ø11
46 140
35 7
105 60
10.5 68 ✽ Straight bars only.
140 For line and load side, use with the terminal covers.
95

Rear-connected Drilling plan (front view) Panel cutout (front view)


Terminal cover 65.5 Mounting plate
4P
58.6 (max. t3.2) 4P 4P 4P
HL
57.1 ø24 HL
2.3
5.3

Mounting hole Terminal cover HL HL 52.5


6
102

144

126
165

48
144

Conductor
45

C
L C
L C
L C
L
overlap, max
24 21
7

22 ø9
20
9

M4✕0.7 53.5
5.3

6 13 16 35 142
60 Tapped hole
35 35 35 35 35
35 10.5 68 72 Panel cutout dimensions shown give an
105 95 107 Stud can be turned M4✕0.7
Mounting screw allowance of 1.0mm around the handle
140 45° or 90°
escutcheon.

5-18
ASL : Arrangement Standard Line
H
L : Handle Frame Centre Line CL : Handle Centre Line

Outline dimensions (mm) PVS160-SDH 4P, PVS250-SDH 4P

Front-connected Preparation of With extension bars ✽ (optional) Drilling plan (front view)
conductor 4P
4P
Terminal cover 67.1 HL
60.6 ø9 Conductor

11(max.)
35 35 35

10
HL 57.5 23 overlap, max 29.6
Terminal cover 4P

11.5
Mounting hole 4
55 25(max.) Mounting hole HL

30.5
max.t7

19
M8 screw

25.6
144

165
102

126
165

C C C C
45
L L L L

22 M4✕0.7 22
Mounting screw

35 M4✕0.7
55

Tapped hole
ø11
Insulating plate
1.6t Insulating plate Insulating plate
35 180
10

47.6 5.4
105
61.6
140 Insulating plate ✽ Straight bars only.
10.5 69.6
180 96.6 For line and load side, use with the terminal covers.

Rear-connected Drilling plan (front view) Panel cutout (front view)


Mounting hole 4P Terminal cover 67.1
HL Mounting plate
60.2 (max. t3.2) 4P 4P 4P
57.1
Insulating plate ø24
65

HL
2.3
5.3

Terminal cover HL Insulating plate HL 52.5


6
102

144

126
165

48
144
45

C
L C
L Conductor C
L C
L
overlap, max
5.4

24 21 ø9
22
20
9

M4✕0.7 53.5
5.3

6 13 16 Stud can be turned 35 142


65

1.6t Tapped hole


45° or 90° 35 35 35 35 35
61.6 Panel cutout dimensions shown give an
M4✕0.7
140 Insulating plate 10.5 69.6 70.4 Mounting screw allowance of 1.0mm around the handle
180 96.6 105.4 escutcheon.

Outline dimensions (mm) PVS160-SNH 4P, PVS250-SNH 4P


5
Front-connected Preparation of With extension bars ✽ (optional) Drilling plan (front view)

Outline Dimensions
4P conductor 4P
67.1 HL
60.6 ø9 Conductor
11(max.)

HL Terminal cover 57.5 35 35 35 overlap, max


23 29.6
Terminal cover 4P
11.5

Mounting hole 4
25(max.) Mounting hole
55

HL
30.5

max.t7
19

M8 screw

25.6
144

165
102

126
165

C C C C
45

L L L L

22 M4✕0.7 22
Mounting screw

35 M4✕0.7
55

Tapped hole
ø11
Insulating plate
35 Insulating plate 1.6t 166 Insulating plate Insulating plate
105 47.6 5.4
140 61.6
166 10.5 69.6 ✽ Straight bars only.
96.6 For line and load side, use with the terminal covers.

Rear-connected Drilling plan (front view) Panel cutout (front view)


4P
Mounting hole HL Terminal cover 67.1 Mounting plate
60.2 (max. t3.2) 4P 4P 4P
57.1 Insulating plate ø24 HL
55
2.3
5.3

Terminal cover HL Insulating plate HL 52.5


6
102

144

126
165

48
144
45

C
L C
L Conductor C
L C
L
overlap, max
5.4

24 21 ø9
22
20
9

M4✕0.7 53.5
5.3

6 13 16 35
55

Stud can be turned Tapped hole 142


1.6t 45° or 90° 35 35 35 35 35
61.6 Panel cutout dimensions shown give an
140 10.5 70.4 M4✕0.7
Insulating plate 69.6 allowance of 1.0mm around the handle
166 105.4 Mounting screw
96.6 escutcheon.

5-19
ASL : Arrangement Standard Line
DC Moulded Case Circuit Breakers H
L : Handle Frame Centre Line C L : Handle Centre Line

Outline dimensions (mm) PVS400-NDL 3P

Front-connected
Preparation of conductor With extension bars (optional) Drilling plan (front view)
3P

ø1
Interpole barrier

4
HL ON side : 37.6 8 37.6
(removable) ø11
OFF side : 36.6

30 14.5

30 14.5
HL 1.6t
110
Mounting hole 1.6t
M10 screw

(max.)
30

44.5

44.5
HL

12
(max.)

116 100 Insulating plate


416

102

349
260

214
228
260

90
CL CL CL CL
M6
51 Mounting screw

Insulating plate
86.9 13.1 45 M6
98.6 Tapped hole
8 104.6 120 Trip button 8 36.6
129.1 148 (red)
90 146.6
60 140 60

Note: See section 4 for the installation of the insulating plate.

Rear-connected
Insulating plate
Drilling plan (front view) Panel cutout (front view)
Mounting plate
Interpole barrier 3P
Stud can be turned
45° or 90° HL
HL
CL
104.6
8

Insulating plate

R6
214
228
102
90

92
68.4

CL CL
228
260

108.4
39
15

45
39
30

overlap, max
3

15
ø1
Conductor

30 45 45
118
overlap, max

M6
ø1

Conductor

98.6
Tapped hole
3

ø3

8 104.6
45 45
6

129.1
146.6

Note: Studs are factory installed in horizontal direction both on the line and load sides. Panel cutout dimensions shown give an allowance
See section 4 for the installation of the insulating plate. of 1.0mm around the handle escutcheon.

5-20
ASL : Arrangement Standard Line
H
L : Handle Frame Centre Line CL : Handle Centre Line

Outline dimensions (mm) PVS400-NDL 4P, PVS400-NDH 4P

Front-connected Preparation of conductor With extension bars (optional) Drilling plan (front view)
4P

ø1
Interpole barrier

4
HL ON side : 37.6 8 37.6
(removable) ø11
OFF side : 36.6

30 14.5

30 14.5
HL 1.6t

110
Mounting hole 1.6t
M10 screw

(max.)
30

44.5

44.5
HL

12
(max.)

116 100 Insulating plate


420

102

349
260

214
228
260

90
CL CL CL CL
M6
51 Mounting screw

Insulating plate
86.9 13.1 45 M6
98.6 Trip button Tapped hole
8 104.6 (red) 8 36.6
129.1
45 45 45 146.6 52.5
70 115 60 60 60
60 185 60 81.5 126.5

Note: See section 4 for the installation of the insulating plate.

Rear-connected Insulating plate


Mounting plate Drilling plan (front view) Panel cutout (front view)
Interpole barrier Stud can be turned 4P
45° or 90° HL
HL
CL
8

104.6

Insulating plate
102
90

R6
CL
228
260

214
228

92
68.4

CL
108.4
39
15

45
39
30

overlap, max
3

15
ø1
Conductor

30 45 45 45
overlap, max

36.5
ø1

98.6 M6
Conductor

118
3

8 104.6 Tapped hole


ø3

129.1 45 45 45
6

146.6

Note: Studs are factory installed in horizontal direction both on the line and load sides. Panel cutout dimensions shown give an allowance
See section 4 for the installation of the insulating plate. of 1.0mm around the handle escutcheon.

Outline dimensions (mm) PVS400-NNL 4P, PVS400-NNH 4P


5
Front-connected Preparation of conductor With extension bars (optional) Drilling plan (front view)

Outline Dimensions
4P
ø1

Interpole barrier
4

HL ON side : 36
(removable) ø11
OFF side : 35
30 14.5

30 14.5

HL 8 36
110

Mounting hole
M10 screw
(max.)

30
44.5

44.5

HL
12

(max.)

116
102

349
260

214
228
260

90

CL CL CL CL
M6
51 Mounting screw

85.3 14.7 45 M6
97 Trip button Tapped hole
8 103 (red) 8 35
127.5
45 45 45 145 52.5
70 115 60 60 60
185 81.5 126.5

Note: See section 4 for the installation of the insulating plate.

Rear-connected
Mounting plate Drilling plan (front view) Panel cutout (front view)
Interpole barrier Stud can be turned 4P
45° or 90° HL
HL
CL
8

103
102
90

R6

CL
228
260

214
228

92

CL
70
39

110
15

45
39
30

overlap, max
3

15
ø1
Conductor

30 45 45 45
overlap, max

36.5
ø1

97 M6
Conductor

118
3

8 103 Tapped hole


ø3

127.5 45 45 45
6

145

Note: Studs are factory installed in horizontal direction both on the line and load sides. Panel cutout dimensions shown give an allowance
See section 4 for the installation of the insulating plate. of 1.0mm around the handle escutcheon.

5-21
ASL : Arrangement Standard Line
DC Moulded Case Circuit Breakers H
L : Handle Frame Centre Line C L : Handle Centre Line

Outline dimensions (mm) PVS800-NDL 3P

Front-connected
Interpole barrier Drilling plan (front view)
(removable) 3P Mounting hole t1 L1
3
HL ø1 1.6t
Toggle extension
160

13 (removable) Insulating plate


110

80
HL

Mounting hole
170

141

126
513

46.5 55.5

273
90

ASL ASL ASL

117
132

Trip button 51 29.6 11.4


40
(red)
32 25

M8 70 M8
80

80
8

Mounting screw Tapped hole


15

Insulating plate Conductor t2 L2


140
overlap, max 8 104.6
129.1 Rated Current (A) L1 L2 t1 t2
60 210 60 80.5 146.6 630 (400-630) 33.6 35.6 8 8
800 (500-800) 33.6 36.6 10 10
Note: See section 4 for the installation of the insulating plate.

Rear-connected
Drilling plan (front view) Panel cutout (front view)
Interpole barrier 1.6t
Insulating plate
Toggle extension Stud can be 3P ø15 for accessory
(removable) turned 90° HL wiring when

8
necessary
ø4
HL HL
10

Insulating plate
104.6

13 30.5
126
126

R6

92
ASL ASL ASL
120.4
20 32 25

M8
8

117
117

29.6 11.4 Tapped hole


70 70
42

ø13

Conductor
overlap, max 70 172
8 104.6 M8
129.1 Mounting screw 43 70 70 43
80.5 146.6 Mounting plate

Note: Studs are factory installed in horizontal direction both on the line and load sides. Panel cutout dimensions shown give an allowance
See section 4 for the installation of the insulating plate. of 1.0mm around the handle escutcheon.

5-22
ASL : Arrangement Standard Line
H
L : Handle Frame Centre Line CL : Handle Centre Line

Outline dimensions (mm) PVS800-NDL 4P, PVS800-NDH 4P

Front-connected
Interpole barrier 4P Mounting hole t1 L1
(removable) HL 3 Drilling plan (front view)
ø1 1.6t
Toggle extension
13 (removable) Insulating plate
110

80
HL

Mounting hole
170

141

126
46.5 55.5
513

273
90
ASL ASL ASL

117
132
Trip button 51 29.6 11.4
40
(red)
32 25 M8
70

80
8 Tapped hole
Insulating plate M8
15

Conductor t2 L2 Mounting screw


70 70 70 overlap, max 8 104.6
129.1 Rated Current (A) L1 L2 t1 t2
105 175 80.5 146.6 630 (400-630) 33.6 35.6 8 8
60 280 60 800 (500-800) 33.6 36.6 10 10

Note: See section 4 for the installation of the insulating plate.

Rear-connected Drilling plan (front view) Panel cutout (front view)


1.6t
Interpole barrier Insulating plate
Toggle extension Stud can be 4P ø15 for accessory
(removable) turned 90° HL wiring when

8
necessary

ø4
H L HL
10

104.6

Insulating plate 13

30.5
126
126

R6

92
ASL ASL ASL
120.4
20 32 25

M8
8

117
117

29.6 11.4 Tapped hole


70 70 70
42

ø13

Conductor
overlap, max 70 172
8 104.6 M8
129.1 Mounting screw 43 70 70 70 43
80.5 146.6 Mounting plate

Note: Studs are factory installed in horizontal direction both on the line and load sides. Panel cutout dimensions shown give an allowance
See section 4 for the installation of the insulating plate. of 1.0mm around the handle escutcheon.

Outline dimensions (mm) PVS800-NNL 4P, PVS800-NNH 4P


5
Front-connected

Outline Dimensions
Interpole barrier Mounting hole
(removable) 4P Drilling plan (front view)
3
HL ø1 t1 L1
Toggle extension
13 (removable)
110

80

HL

170
141

126
46.5 55.5

273
90

ASL ASL ASL


Trip button
117
132

(red) 51 28 13
40
32 25

70 M8
80
8

Tapped hole
M8
15

Conductor t2 L2 Mounting screw


70 70 70 overlap, max 8 103
127.5 Rated Current (A) L1 L2 t1 t2
105 175 80.5 145 630 (400-630) 32 34 8 8
280 800 (500-800) 32 35 10 10

Note: See section 4 for the installation of the insulating plate.

Rear-connected Drilling plan (front view) Panel cutout (front view)


Interpole barrier
Toggle extension Stud can be 4P ø15 for accessory
(removable) turned 90° HL wiring when
8

necessary
ø4

H L HL
10

103

13
30.5
126
126

R6
92

ASL ASL ASL


20 32 25

122

M8
8

117
117

28 13 Tapped hole
70 70 70
42

ø13

Conductor
overlap, max 70 172
8 103 M8
127.5 Mounting screw 43 70 70 70 43
80.5 145

Note: Studs are factory installed in horizontal direction both on the line and load sides. Panel cutout dimensions shown give an allowance
See section 4 for the installation of the insulating plate. of 1.0mm around the handle escutcheon.

5-23
TERASAKI ELECTRIC CO., LTD.
Head Office: 7-2-10 Hannancho, Abenoku
Osaka, Japan
Circuit Breaker Division: 7-2-10 Kamihigashi, Hiranoku Osaka, Japan
Telephone: 81-6-6791-9323
Fax: 81-6-6791-9274
Email: int-sales@terasaki.co.jp
http://www.terasaki.co.jp/

TERASAKI ELECTRIC (M) SDN, BHD. TERASAKI ELECTRIC (EUROPE) LTD.


Lot 3, Jalan 16/13D, 40000 Shah Alam, Selangor Darul 80 Beardmore Way, Clydebank Industrial Estate
Ehsan, Malaysia Clydebank, Glasgow, G81 4HT, Scotland (UK)
Telephone: 60-3-5549-3820 Telephone: 44-141-941-1940
Fax: 60-3-5549-3960 Fax: 44-141-952-9246
Email: terasaki@terasaki.com.my Email: marketing@terasaki.co.uk
http://www.terasaki.com/

TERASAKI ELECTRIC TRADING & SERVICES (M) TERASAKI ELECTRIC (EUROPE) LTD.
SDN. BHD. FILIALE ITALIA
No. 20 & 22, Jalan Rajawali 2, Bandar Puchong Jaya, Via Ambrosoli, 4A-20090 Rodano, Milano, Italy
Jalan Puchong, 47100 Selangor Darul Ehsan, Malaysia Telephone: 39-02-92278300
Telephone: 60-3-8070-2486, 60-3-8075-1542 Fax: 39-02-92278320
Fax: 60-3-8070-2481 Email: terasaki@terasaki.it
Email: sales@terasaki.com.my http://www.terasaki.it/

TERASAKI DO BRASIL LTDA. TERASAKI ELECTRIC (EUROPE) LTD.


Rua Cordovil, 259-Parada De Lucas, 21250-450 SUCURSAL EN ESPAÑA
Rio De Janeiro-R.J., Brazil Pol. Ind. Coll de la Manya, C/Cal Ros dels Ocells 5-7,
Telephone: 55-21-3301-9898 08403 Granollers, Barcelona, Spain
Fax: 55-21-3301-9861 Telephone: 34-93-879-60-50
Email: terasaki@terasaki.com.br Fax: 34-93-870-39-05
http://www.terasaki.com.br Email: terasaki@terasaki.es
http://www.terasaki.es/

TERASAKI ELECTRIC (CHINA) LTD. TERASAKI ELECTRIC (EUROPE) LTD. FILIAL SVERIGE
72 Pacific Industrial Park, Xin Tang Zengcheng, Box 2082 SE-128 22 Skarpnäck Sweden
Guangzhou 511340, China Telephone: 46-8-556-282-30
Telephone: 86-20-8270-8556 Fax: 46-8-556-282-39
Fax: 86-20-8270-8586 Email: info@terasaki.se
Email: terasaki@public.guangzhou.gd.cn http://www.terasaki.se/

TERASAKI ELECTRIC GROUP SHANGHAI TERASAKI CIRCUIT BREAKERS (S) PTE. LTD.
REPRESENTATIVE OFFICE 17 Tuas Street Singapore 638454
Room No. 1405-6, Tomson Commercial Building Telephone: 65-6744-9752
710 Dong Fang Road, Pudong, Shanghai, 200122, China Fax: 65-6748-7592
Telephone: 86-21-58201611 Email: tecs@pacific.net.sg
Fax: 86-21-58201621
Email: terasaki@vip.163.com

Ratings and specifications are subject to change without notice.