Académique Documents
Professionnel Documents
Culture Documents
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
MD
I n=
√ 3 *V* cosθ
Donde :
In: Corriente Nominal de Línea en A.
MD: Máxima Demanda en W
V : Tensión Nominal (V) :220
Cos: Factor de Potencia asumido :0.9
MD
I n=
V* cosθ
Donde:
Potenci MD
TABLERO CIRC Descripcion F.D. I (A) S (mm²)
a (W) (W)
1 Salida Taladro 1 (1x2500 W) STD 3.4.1 2500 0.75 1875 5.48 NH80 3x4
2 Salida Taladro 2 (1x2500 W) STD 3.4.1 2500 0.75 1875 5.48 NH80 3x4
3 Salida a Taladro3(1x2500 W) STD 3.4.2 2500 0.75 1875 5.48 NH80 3x4
4 Salida a Taladro4(1x2500 W) STD 3.4.3 2500 0.75 1875 5.48 NH80 3x4
5 Salida a esmeril 1 (1x3000 W) STD 3.4.3 3000 0.75 2250 6.58 NH80 3x4
STD-3.4
6 Salida a esmeril 2 (1x3000 W) STD 3.4.4 3000 0.75 2250 6.58 NH80 3x4
7 Salida a esmeril 3 (1x3000 W) STD 3.4.4 3000 0.75 2250 6.58 NH80 3x4
8 Alumbrado (12x2 u x 40 W) 960 1 960 4.85 NH80 2x2.5
9 Tomacorriente Normal (8 x 2u x 165 W) 2640 0.5 1320 6.67 NH80 2x4
NH80
5 Luz de Emergencia (1x1ux65W) 65 1 65 0.33
2x2.5
NH80
6 Alumbrado (6x2 u x 40 W) 480 1 480 2.42
2x2.5
7 Tomacorriente estabilizado (3 x 2u x 165 W) 990 0.75 742.5 3.75 NH80 2x4
N2XOH
SUBTOTAL STD 7.1 10175 7108 20.78
3x6
STD-7.2 TALLER 3
N2XOH
1 Salida a soldadora (1x15000) STD 7.2.1 0.5 7500 21.93
15000 3x6
2 Salida a Esmeril (2x1500 W) STD 7.2.2 3000 0.75 2250 6.58 NH80 3x4
N2XOH
3 0.5 7500 21.93
Salida a soldadora (1x15000) STD7.2.3 15000 3x6
STD 7.2.4
13
REMODELACION DEL SISTEMA ELECTRICO DE LOS TALLERES EXISTENTES
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
STD 7.2.5 Tomacorriente Normal (12x 2u x 165 W) 3960 0.5 1980 10.00 NH80 2x4
NH80
Luz de Emergencia (1x1ux65W) 65 1 65 0.33
2x2.5
NH80
Alumbrado (18x2 u x 40 W) 1440 1 1440 7.27
2x2.5
SUBTOTAL STD 7.2.5 6455 4228 21.35 NH80 2x6
6 SUB TABLERO 7.2.6 (Esmeril) 2 x 750 1500 0.75 1125 3.29 NH80 3x4
Tomacorriente estabilizado (10 x 300+165 W) 3165 0.75 2373.8 11.99 NH80 2x4
Tomacorriente Normal (3x 2u x 165 W) 990 0.5 495 2.50 NH80 2x4
STD 7.2.7
NH80
Luz de Emergencia (1x1ux65W) 65 1 65 0.33
2x2.5
NH80
Alumbrado Mezanine (6x2 u x 40 W) 480 1 480 2.42
2x2.5
SUBTOTAL STD 7.2.7 4700 3414 17.24 NH80 2x6
8 Salida a taladrol(1x2500) STD 7.2.8 2500 0.75 1875 5.48 NH80 3x4
9 Extractor de Humo (2 HP) STD 7.2.9 1500 0.75 1125 3.29 NH80 3x4
10 Extractor de Humo (2 HP) STD 7.2.10 1500 0.75 1125 3.29 NH80 3x4
N2XOH
SUBTOTAL SDT 7.2 60690 38109 111.43
3x25
1 Salida Mesas 1, 2 y 3 3000 0.75 2250 6.58 NH80 3x4
2 Salida Mesas 4, 5, 6 3000 0.75 2250 6.58 NH80 3x4
3 Salida Mesas 7, 8, 9 3000 0.75 2250 6.58 NH80 3x4
4 Tomacorriente Normal (6 x 2u x 165 W) 1980 0.5 990 5.00 NH80 3x4
STD 7.3
14
REMODELACION DEL SISTEMA ELECTRICO DE LOS TALLERES EXISTENTES
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
SDT 7.4.1
NH80
Luz de Emergencia (1x1ux65W) 65 1 65 0.33
2x2.5
NH80
Alumbrado (9x2 u x 40 W) 720 1 720 3.64
2x2.5
SUBTOTAL STD 7.4.1 3425 2353 11.88 NH80 2x6
Tomacorriente estabilizado (3 x 2u x 165 W) 990 0.75 742.5 3.75 NH80 2x4
Tomacorriente Normal (5x 2u x 165 W) 1650 0.5 825 4.17 NH80 2x4
SDT 7.4.2
NH80
Luz de Emergencia (1x1ux65W) 65 1 65 0.33
2x2.5
NH80
Alumbrado (9x2 u x 40 W) 720 1 720 3.64
2x2.5
SUBTOTAL SDT 7.4.2 3425 2353 11.88 NH80 2x6
N2XOH
SUBTOTAL STD 7.4. 36005 22500 65.79
3x10
1 Tomacorriente Normal (3 x 2u x 165 W) 990 0.5 495 2.50 NH80 2x4
NH80
2 Luz de Emergencia (1x1ux65W) 65 1 65 0.33
2x2.5
STD 7.5 TALLER 2 PASADIZO
NH80
3 Alumbrado (13x2 u x 40 W) 1040 1 1040 5.25
2x2.5
4 Tomacorriente estabilizado (3 x 2u x 165 W) 990 0.75 742.5 3.75 NH80 2x4
Tomacorriente estabilizado (4 x 2u x 165 W) 1320 0.75 2250 11.36 NH80 2x4
Tomacorriente Normal (3 x 2u x 165 W) 990 0.5 495 2.50 NH80 2x4
SDT 7.5.1
NH80
Luz de Emergencia (1x1ux65W) 65 1 65 0.33
2x2.5
NH80
Alumbrado (5x2 u x 40 W) 400 1 400 2.02
2x2.5
SUBTOTAL SDT 7.5.1 TALLER 2 MEZANINE 2775 3210 9.39 NH80 3x6
SUBTOTAL STD 7.5. 5860 5553 16.24 NH80 3x6
N2XOH
STD 7.6 Salida a soldadora (1x15000) 15000 0.5 7500 21.93
3x6
1 Tomacorriente Normal (8x 2u x 165 W) 2640 0.5 1320 6.67 NH80 2x4
2 Salida Mesas 1 y 2 2000 0.75 1500 7.58 NH80 2x4
3 Salida Mesas 3 y 4 2000 0.75 1500 7.58 NH80 2x4
STD 7.7
15
REMODELACION DEL SISTEMA ELECTRICO DE LOS TALLERES EXISTENTES
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
N2XOH
SUBTOTAL TDP 7(F.S.=0.5) 165.51
173450 56606 3x70
3562.
6 Salida a amoladora 2 (1x4750 W) 4750 0.75 10.42 NH80 3x4
5
7 Salida Fragua(1x2500 W) 2500 0.75 1875 5.48 NH80 3x4
8 Salida Taladro (1x1000 W) 1000 0.75 750 3.79 NH80 2x4
9 Salida compresor (1x2500 W) 2500 0.75 1875 5.48 NH80 3x4
10 Salida esmeril (750 W) 750 0.75 562.5 2.84 NH80 2x4
SUBTOTAL STD 8.4 48250 28688 83.88 N2XOH 3x25
1 Tomacorriente Normal (7 x 2u x 165 W) 2310 0.5 1155 5.83 NH80 2x4
2 Luz de Emergencia (1x1ux65W) 65 1 65 0.33 NH80 2x2.5
STD 8.5 TALLER 4
16
REMODELACION DEL SISTEMA ELECTRICO DE LOS TALLERES EXISTENTES
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Donde:
V: Caída de Tensión en Voltios
I: Corriente de línea en circuito trifásico
L: Longitud del tramo considerando en met.
R: Resistencia unitaria del conductor(Ohms/m)
Cos: Factor de Potencia de la Carga = 0.9
Sen: Seno del ángulo del F. de P.
Remplazando:
V = KIL
CALCULO DE X
Se ha utilizado la sgte fórmula:
DMG
X L = 2* * f(2* 10 - 4* ln )
RMG
Donde:
Remplazando:
V = KIL
S R20°C R40°C XL K 3F K 1F
mm² Ohmio/Km Ohmio/Km Ohmio/Km Ohmio/Km Ohmio/Km
2.5 7.4100 7.9791 0.1170 12.5265 14.4644
4 4.6100 4.9640 0.1090 7.8205 9.0303
6 3.0800 3.3165 0.1030 5.2478 6.0596
10 1.8300 1.9705 0.0973 3.1453
16 1.1500 1.2383 0.0915 1.9994
25 0.7270 0.7828 0.0915 1.2894
35 0.5240 0.5642 0.0889 0.9467
50 0.3870 0.4167 0.0882 0.7162
70 0.2680 0.2886 0.0868 0.5154
95 0.1930 0.2078 0.0847 0.3879
120 0.1530 0.1648 0.0846 0.3207
150 0.1240 0.1335 0.0845 0.2720
185 0.0991 0.1067 0.0845 0.2302
18
REMODELACION DEL SISTEMA ELECTRICO DE LOS TALLERES EXISTENTES
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
O (kW) (V)
PABELLON, COMPUTO TDP-1 29.08 85.03 N2XOH 3x1-35 35.00 0.9467 2.82 1.28
GARITA TDP-2 15.00 43.86 N2XOH 3x1-16 47.08 1.9994 4.13 1.88
N2XOH 3x1-
MAQUINAS Y HERRAMIENTAS TDP-3 53.00 154.97 91.14 0.3207 4.53 2.06
120
N2XOH 3x1-
CONSTRUCCIONES METALICAS TDP-4 70.00 204.68 95.98 0.2302 4.52 2.06
185
BOMBAS TDP-5 23.14 67.66 N2XOH 3x1-95 135.14 0.3879 3.55 1.61
N2XOH 3x1-
HIDROBIOLOGICO TDP-6 77.48 226.55 74.47 0.2720 4.59 2.09
150
ELECTRICIDAD, DIESEL,
TDP-7 56.61 165.53 N2XOH 3x1-70 57.55 0.5154 4.91 2.23
REFRIGERACION, AUTOMOTRIZ
N2XOH 3x1-
CONSTRUCCIONES METALICAS TDP-8 90.78 265.44 75.50 0.2302 4.61 2.10
185
MAQUINAS Y HERRAMIENTAS STD 3.4 11.62 33.98 N2XOH 3x1-6 4.00 5.2478 0.71 0.32
19