Product: GENERATOR SET
Model: C18 GENERATOR SET C6C00300
Configuration: C18 Generator Set C6C00001-UP
Troubleshooting
C13, C15, and C18 Generator Set Engines
Media Number -SENR9706-18 Publication Date -01/04/2015 Date Updated -03/02/2020
i02056806
Use this procedure to troubleshoot any suspect problems with the CAN Data Link.
The test steps that are described in this test can help solve the following problems.
Faulty connectors
Terminating resistors
Short circuits
Open circuits
Faulty module
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch/mediaheaderinfoframeset.jsp&calledpa… 1/6
4/6/2020 C18 Generator Set C6C00001-UP(SEBP4495 - 40) - Documentation
Illustration 1 g01058327
Typical schematic
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch/mediaheaderinfoframeset.jsp&calledpa… 2/6
4/6/2020 C18 Generator Set C6C00001-UP(SEBP4495 - 40) - Documentation
Illustration 2 g01091318
P1 ECM connector
(P1-34) J1939 data link −
(P1-42) J1939 shield
(P1-50) J1939 data link +
B. Thoroughly inspect the J1/P1 ECM connector and the J2/P2 ECM connector. Inspect all of the
connectors that are associated with the circuit.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch/mediaheaderinfoframeset.jsp&calledpa… 3/6
4/6/2020 C18 Generator Set C6C00001-UP(SEBP4495 - 40) - Documentation
C. Perform a 45 N (10 lb) pull test on each of the wires in the ECM connectors that are associated with
the circuit.
D. Check the ECM connector (allen head screw) for the proper torque of 6.0 N·m (55 lb in).
E. Check the harness and wiring for abrasion and for pinch points.
Expected Result:
All connectors, pins and sockets are completely coupled and/or inserted. The harness and wiring are free of
corrosion, of abrasion or of pinch points.
Results:
Repair: Perform the following repair:Repair the connectors or wiring and/or replace the connectors or
wiring. Ensure that all of the seals are properly in place and ensure that the connectors are completely
coupled. Refer to Troubleshooting, "Electrical Connectors - Inspect".Verify that the repair eliminates
the problem.
STOP
Test Step 2. Verify the Proper Installation of the Data Link Circuit
B. Disconnect J1/P1 ECM connector and measure the resistance between P1-50 (CAN Data Link +) and
P1-34 (CAN Data Link -).
Expected Result:
Results:
Not OK - The range of the resistance is 114 Ohms to 126 Ohms. A terminating resistor is missing.
Repair: Verify that two terminating resistors exist on the data link. One resistor must be located on
each end of the data link. The engine is shipped with one terminating resistor that is installed between
the ECM and the customer connector.Refer to the Electrical Schematic in order to determine the
missing resistor.Verify that the repair eliminates the problem.
STOP
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch/mediaheaderinfoframeset.jsp&calledpa… 4/6
4/6/2020 C18 Generator Set C6C00001-UP(SEBP4495 - 40) - Documentation
D. Measure the resistance from the following pins to every pin on ECM connector P1 and to engine
ground.
Expected Result:
Results:
Repair: Make the necessary repairs.Verify that the repair eliminates the problem.
STOP
B. Fabricate a jumper wire. Use the jumper wire in order to short pin J to pin G on the service tool
connector.
C. Measure the resistance between P1-50 (CAN Data Link +) and P1-34 (CAN Data Link -) at the ECM
connector.
Expected Result:
Results:
Repair: Make the necessary repairs.Verify that the repair eliminates the problem.
STOP
B. If the module operates properly on a different engine, there may be a problem with the ECM.
C. If the module does not function properly on the different engine, replace the module.
Expected Result:
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisweb/mediasearch/mediaheaderinfoframeset.jsp&calledpa… 5/6
4/6/2020 C18 Generator Set C6C00001-UP(SEBP4495 - 40) - Documentation
Results:
Repair: The problem may be intermittent. If the problem is intermittent, refer to Troubleshooting,
"Electrical Connectors - Inspect".
STOP
Repair: Replace the module. Verify that the repair corrects the problem.
STOP
Copyright 1993 - 2020 Caterpillar Inc. Mon Apr 06 2020 22:14:00 GMT+0800 (Central Indonesia Time)