M Family Digital Feeder Relay

Three-phase and ground, single-phase or


ground feeder protection relay.

Features and Benefits ■ enerVista.com compatible (see page 275)


■ Advanced 16-bit microprocessor Protection and Control
■ Configurable logic, curves, digital I/Os ■ Phase, ground TOC and IOC
and LEDs
■ Thermal image protection
■ Flash memory for field upgrades
■ Circuit breaker control (open and close)
■ Two settings groups
■ Reclosure
■ Drawout case for easy maintenance
Monitoring and Metering
■ AC/DC power supply
■ Access via front panel keypad or ■ 32-event record, analog/digital
communication links oscillography
■ Compatible with M Family systems in User Interfaces
half or full 19" racks ■ M+PC software for setting, monitoring
Applications ■ Front RS232 and rear RS485 ports using
■ Primary circuit protection on distribution ModBus® RTU protocol up to 19,200 bps
networks at any voltage level
■ Backup/auxiliary protection for trans-
formers, generators and motors

1 GE Multilin
MIF M Family Digital Feeder Relay

Protection the three-phase CTs eliminating modified using M+PC software.


the need for an additional ground Two digital inputs and six relay
The MIF provides primary circuit sensor. For more sensitive detec- outputs are provided, four of them
protection for distribution tion, an additional core balance programmable. These config-
networks of any voltage, and (zero sequence) ground sensor urable outputs can be assigned
backup/auxiliary protection for encircling the three-phase either to a set of pre-configured
transformers, generators and conductors can be used. values, or to an OR/NOT combina-
motors. As part of the M Family, tion of the same values.
the MIF provides advanced digi- Instantaneous Overcurrent
tal protection which includes: Cold Load Pickup (Optional)
The MIF includes two separately
Phase TOC adjustable IOC units, each of This feature adapts the pickup of
which can be independently the overcurrent functions to over-
The TOC protection can be set enabled. MIF models provide two ride higher overload currents
from 0.1 to 2.4 times I n . MIF-P three-phase IOC units and two resulting from re-energization.
models incorporate three-phase ground IOC units, while MIFN
and ground TOC units, while MIF- models incorporate two single- Breaker Failure Protection
N models incorporate a single- phase or ground IOC units. The (Optional)
phase TOC unit. Four standard pickup setpoint can be set from 0.1 A simple “breaker has not
TOC curves can be selected in to 30 times I n and a time delay opened” feature is standard. A
addition to a user configurable from 0 to 100 seconds. more complex breaker failure
curve. Each curve can be set with
scheme can be easily implement- 6
customized time multipliers to Thermal Image Unit ed through a digital input and
coordinate with equipment.
A thermal image unit protects configurable output logic (logic
ANSI IEC/BS142 equipment against overheating gates and timers).
Normal inverse IEC A due to excessive load. Several
Very inverse IEC B operating curves can be set as a Breaker Health (Optional)
Extremely inv. IEC C function of heating time constant The breaker health threshold is
Definite time Definite time T1 (adjustable between three and set by the user to achieve “just in
600 minutes). Cool down time time” maintenance. When the
Ground TOC
constant T2 is adjustable from one cumulative I2 value exceeds the
This function has the same curve to six times the heating constant. threshold, an alarm occurs.
selection choices and settings as
the phase time overcurrent unit. Inputs and Outputs Circuit Breaker Control
The ground signal is normally The factory configuration of MIF The MIF permits operation of the
derived as the residual sum of inputs and outputs can be easily circuit breaker. Breaker opening
and closing operations can be
carried out by programming
specific outputs, and digital
Functional Block Diagram inputs can be used for verifying
the success of the operation.

Primary or Secondary Metering


52 The MIF can monitor both the
primary and secondary current
3 50PH 50PL 51P 50NH 50NL 51N
* metering values, by previously
49 setting the corresponding CT
ratio.
METERING

BREAKER HEALTH
OSCILLOGRAPHY
50GH 50GL 51G
* EVENT RECORDING
COLD LOAD PICKUP
CONFIGURABLE I/O AND LEDS
CONFIGURABLE LOGIC

MIF 50BF
Digital Feeder Relay
(*) Alternative Connections Optional Features 732754A3.ai

www.GEindustrial.com/Multilin 2
MIF M Family Digital Feeder Relay

Typical Wiring
NOTE: For reference only. For connections for a specific MIF model, please refer to its external connections drawing.
ZERO SEQUENCE ALTERNATIVE CT WIRING FOR
GROUND SENSING CONNECTION RESIDUAL GROUND SENSING
PHASE A ZERO SEQUENCE NOTE: 14 AWG wiring PHASE A
CT GROUND CT recommended(2.5mm2) CT
A << >> PHASE B
A AC PHASE B
A
CT or CT
LINE B << >> PHASE C
B DC B
CT PHASE C
CT
C << >> C C

C1 C2 C3 C4 C5 C6 C7 C8 A1 A2
C1 C2 C3 C4 C5 C6 C7 C8
IA N IB N IC N IG N +/L -/N
CIRCUIT IA N IB N IC N IG N
BREAKER POWER
Internally fused
CURRENT INPUTS 1A/250V fast blow
CURRENT INPUTS

GE Multilin SDA B12(*) A


52a 52a

RS485
MIF SDB A12(*)
TRIP COIL -
TRIP B
<< COIL
>> A5 Digital Feeder Protection
TRIP

CONTROL GND B11(*)


GROUND
POWER + A6

6 CAUTION: Fork or ring terminals must be used on the


READY

termainal block. B5
NOTE: Suitable disconnect devices (switch or circuit
breaker) recommended located near the relay. B6

OUT1/2 OUT1
OVERVOLTAGE CATEGORY: II B7 INPUT

(*) Terminals B12, A12 and B11 must be connected to SELV


INTPUTS(**)

(safety extra-low voltage) parts (on the PLC). They are A8 CC1
DIGITAL

DIGITAL OUTPUTS(**)

PROGRAMMABLE
not to be tested for hipot test under any circumstance. B8
A9 CC2 CONTROLLER
(**) In basic model, inputs and outputs are configured as JX
A10 COM
OUT3

follows:
INPUTS OUTPUTS B9
CC1: Disable 50P Function OUT1: Phase Trip
CC2: Disable 50N Function OUT2: Ground Trip
OUT4

OUT3: 50 Trip B10


OUT4: 49 Alarm RS232
COM

SAFETY A7 INPUT
GND
GROUND GROUND
BUS 732753A8.ai

MIF Guideform
Specifications Ordering
For an electronic version of the MIF MIF * * * * E * 00 * 00 *
guideform specifications, please MIF Digital feeder relay
visit: www.GEindustrial.com/ P Three-phase + ground relay
N Single-phase or ground relay
Multilin/specs, fax your request
A ANSI curves
to 905-201-2098 or email to I IEC curves
literature.multilin@indsys.ge.com. 0 MIF-N models
1 MIF-P: In = 1 A (pickup range: 0.1 – 2.4 A)
5 MIF-P: In = 5 A (pickup range: 0.5 – 12 A)
1 Ground CT In = 1 A (pickup range: 0.1 – 2.4 A)
5 Ground CT In = 5 A (pickup range: 0.5 – 12 A)
N Sensitive ground In = 1 A (pickup range: 0.005 – 0.12 A)
0 No options, basic unit
1 Option 1*
2 Option 2 **
F 24 – 48 VDC/AC power supply (range: 19 – 58 VDC)
H 110 – 250 VDC (range: 88 – 300 VDC)
110 – 230 VAC p.s. (range: 88 – 264 VAC)
C Individual relay
S Mounted in an M+ system†

* configurable I/O, event recording, oscillography


** I/O, cold load pickup, breaker failure protection, breaker health, configurable logic plus Option 1 features
† If relays are to be mounted in an M+ system, then either an M050 half 19" rack or M100 full 19" rack case must be
ordered. The M050 and M100 racks are provided at no additional cost based on the number of relays ordered.

enerVista enabled See page 275. Accessories


www.enerVista.com
B1315P1 Depth reducing collar, reduces the mounting depth by 63mm

3 www.GEindustrial.com/Multilin