Vous êtes sur la page 1sur 2

MANUAL LOADER/AUTO-MANUAL STATION MC96

· Manual Loader : type A, B or D


· Auto/Manual station : type C
· Input : 4~20 mA, 0~1 K ohms
· Isolated 4~20 mA output
· 85~265 V AC SMPS
· Accuracy : ± 1% typical
· Input fail indication

BEE

TABLE 1 : FUNCTION TYPE


Type Input Output Mode
A None 4~20 mA Manual
B 0~1 K feedback Relays Manual
C 4~20 mA 4~20 mA Auto / Manual
D 4~20 mA feedback 4~20 mA Manual

SPECIFICATIONS All specifications at ambient of 25 °C, unless specified otherwise

FUNCTION TYPE Factory set INDICATION


See Table 1 Display Upper : 4 digit, 7 segment 0.56”
(14.2 mm) red LED display
INPUT Lower : 4 digit, 7 segment 0.56”
Resistance 0~1 K ohms (14.2 mm) green LED display
Linear input 4~20 mA Status indication 2 LEDs for relay status
Load resistance for 250 W, internally provided
4~20 mA input OTHER
Transmitter supply 22 V DC, nominal, 30 mA max Keyboard Tactile, 3 keys
Range limits See Table 2 Enclosure construction Plug-in (circuit removable
Accuracy See Table 2 without affecting terminal wiring)
Temperature coefficient 0.5% of span / 25 °C Dimensions (in mm) 96(H) x 96(W) x 100(D)
of accuracy Mounting Panel mount
Panel cutout 92 x 92 mm
OUTPUTS Supply voltage a) 85~265 V AC, 50/60 Hz
Type B b) 20~35 V DC (factory option)
No. of relays 2 electromagnetic relays Power consumption 3 watts maximum
Relay contact type NO-C-NC Operating ambient 0 ~ 50 °C
Relay contact rating 5A / 230V AC, resistive temperature
SSR drive 12 V DC drive signal for external Relative humidity Below 90%, non
SSR condensing

Types A, C, D
Current output 4~20 mA isolated from input
Maximum load for 600 ohms
current output
Mutual isolation between 1 KV AC / 1 minute
input/output/supply
MANUAL LOADER/AUTO-MANUAL STATION MC96

TABLE 2
RANGE LIMITS RANGE IN WHICH TYPICAL ACCURACY WORST CASE
INPUT (%) ACCURACY IS SPECIFIED AT 30 °C ACCURACY
LOW SCALE HIGH SCALE LOW SCALE HIGH SCALE (%) (%)

0~1 K ohms, 3-wire 0 100 0 100 ±1 ±2


4~20 mA 0 100 0 100 ±1 ±2

CONNECTION DIAGRAMS

2-WIRE RESISTANCE :
SHORT 13 & 15
SHORT
1 11 FOR RESISTANCE
85~265V AC/DC VS
0%
2 12

+ 3 13
* NO1
EXT SSR1
RELAY1 4 14
C1 100 %

5 15
NC1
+ 6 16
*EXT SSR2 NO2
RELAY2 7 17
C2

8 18
NC2
9 19

10 20
* - FACTORY OPTION

TYPE B

1 11
85~265V AC/DC VS
2 12

3 13

4 14
4~20 mA in #
5 15

6 16
+
# FOR 2-WIRE
7 17 TRANSMITTER
WITH EXTERNAL
SUPPLY, USE mA INPUT
8 18
+
VTX +
9 19 2-WIRE
TRX
V/Iout 16 9
10 20 FOR 2-WIRE
TRANSMITTER
USING
INTERNAL
SUPPLY

TYPE C, D

www.beeinstruments.com
1st Floor, Krishna Bldg., Shamrao Vithal Lane,
off. Lamington Rd., Mumbai - 400007, India

BEE INSTRUMENTS Mobile : + 91 98217 27104


Tel : +91 22 23800783 / 23864484 / 23876707
Fax : +91 22 2387 6729
(Madhu Group) email : sales@beeinstruments.com
website : www.beeinstruments.com