w SCHRACK-INFO
AC/DC voltage monitoring in 1-phase mains
Undervoltage monitoring
1 change over contact
Width 17.5 mm
Installation design
w TECHNICAL DATA
1. Functions 6. Output circuit
AC/DC undervoltage monitoring in 1-phase mains with adjustable 1 potential free change over contact
threshold and xed hysteresis. Rated voltage: 250V AC
Switching capacity: 1250VA (5A / 250V)
UNDER Undervoltage monitoring Fusing: 5A fast acting
Mechanical life: 20 x 106 operations
2. Time ranges Electrical life: 2 x 105 operations
Adjustment range at 1000VA resistive load
Tripping delay (Delay): - Switching frequency: max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
3. Indicators (according to IEC 947-5-1)
Green LED ON/OFF: indication of supply voltage Overvoltage category: III. (according to IEC 60664-1)
Yellow LED ON/OFF: indication of relay output Rated surge voltage: 4kV
10. Weight
Single packing: 74g
Package of 10pcs: 676g per Package
MONITORING RELAYS
w FUNCTIONS
Us
LED U
R
w CONNECTIONS
1~ L 1~ L +
24V
230V 24V
N N DC -
AC AC
E F1 E F1 E F1
F3 F2 F3 F2 F3 F2
11 11 11
R R R
12 14 12 14 12 14
11 11 11
12 14 12 14 12 14 Page
503
w DIMENSIONS
87mm
45mm
5mm 44mm
17,5mm
60mm
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w TECHNICAL DATA
w FUNCTIONS
Page
506
MONITORING RELAYS
w CONNECTIONS
Range 30V, supply voltage 24V AC/DC and fault latch Range 60V, supply voltage 230V AC and fault latch
24VAC/DC
L1
0V
N
max. max.
20A 20A
Reset
Reset
15 25
15 25
16 18 26 28
16 18 26 28
Umax=300V AC/DC
24VAC/DC
0V
max.
20A
Reset
15 25
16 18 26 28
Page
507
w DIMENSIONS
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w SCHRACK-INFO
• Undervoltage monitoring
• Supply voltage = measured voltage
• 1 change over contact
• Width 17.5 mm
• Installation design
w TECHNICAL DATA
w FUNCTIONS
Undervoltage monitoring for 3-phase AC mains with variable thres- Undervoltage monitoring
hold voltage US and fixed hysteresis. All measuring inputs (L1, L2 and The output relay R switches into on-position (yellow LED illuminated),
L3) must be connected to phase voltage. If single or 2-phase moni- when the measuring voltage of all connected phases exeeds the fixed
toring is required, unused input terminals (L) must be connected to threshold US by more than the fixed hysteresis H. When the voltage
mains voltage to have proper L-N voltage on the terminals L1, L2 and of one of the connected phases (L1, L2 or L3) falls below the fixed
L3. A phase failure can not be detected, if the reverse voltage coming threshold, the output relay R switches into off-position again (yellow
from the load exceeds the threshold US relay. LED not illuminated).
w CONNECTIONS w DIMENSIONS
Page
509
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w TECHNICAL DATA
For all the functions the LEDs MIN and MAX are flashing alternat- nated), the output relays switch into off-position (yellow LED not
ing, when the minimum value for the measured voltage was cho- illuminated). The output relays again switch into on-position (yel-
sen to be greater than the maximum value. If a failure already low LED illuminated) when the measured voltage falls below the
exists when the device is activated, the output relays remain in value adjusted at the MAX-regulator (red LED MAX not illuminat-
off-position and the LED for the corresponding threshold is illumi- ed). When the measured voltage falls below the value adjusted at
nated. the MIN-regulator, the set interval of the tripping delay (DELAY)
begins again (red LED MIN flashes). After the interval has expired
Under voltage monitoring (UNDER, UNDER+SEQ) (red LED MIN illuminated), the output relays switch into off-posi-
When the measured voltage (mean value of phase-to-phase volt- tion (yellow LED not illuminated).
ages) falls below the value adjusted at the MIN-regulator, the set
interval of the tripping delay (DELAY) begins (red LED MIN flash- Page
es). After the interval has expired (red LED MIN illuminated), the 511
output relays switch into off-position (yellow LED not illuminated).
The output relays again switch into on-position (yellow LED illu-
minated), when the measured voltage exceeds the value adjusted
at the MAX-regulator.
LED SEQ
Window function (WIN, WIN+SEQ)
The output relays switch into on-position (yellow LED illuminated)
when the measured voltage (mean value of phase-to-phase volt-
ages) exceeds the value adjusted at the MIN-regulator. When the
L1 L2 L3
measured voltage exceeds the value adjusted at the MAX-regula-
tor, the set interval of the tripping delay (DELAY) begins (red LED
MAX flashes). After the interval has expired (red LED MAX illumi-
MONITORING RELAYS
Phase failure monitoring (SEQ) Loss of neutral wire by means of evaluation of asymmetry
If one of the phase voltages fails, the set interval of the tripping A break of the neutral wire between power line and machinery is
delay (DELAY) begins (red LED SEQ flashes). After the interval has detected as soon as asymmetry between phase-to-phase voltage
expired (red LED SEQ illuminated), the output relays switch into and neutral wire occurs. If the asymmetry exceeds the value set at
off-position (yellow LED not illuminated). Reverse voltages of a the ASYM-regulator, the set interval of the tripping delay (DELAY)
consumer (e.g. a motor which continues to run on two phases begins (red LED ASYM flashes). After the interval has expired (red
only) do not effect the disconnection but can be monitored by LED ASYM illuminated), the output relays switch into off-position
using a proper value for the asymmetry. (yellow LED not illuminated). A break of the neutral wire between
our device and the machinery can not be detected.
LED SEQ
L1 L2 L3
Delay
Asymmetry monitoring
If the asymmetry of the phase-to-phase voltages exceeds the
value set at the ASYM-regulator, the set interval of the tripping
delay (DELAY) begins (red LED ASYM flashes). After the interval
has expired (red LED ASYM illuminated), the output relays switch
into off-position (yellow LED not illuminated). If the neutral wire is
connected to the device, the asymmetry of the phase voltages
referred to the neutral wire (Y-voltage) is monitored also. In that
case both values of the asymmetry are evaluated and if one of the
values exceeds the value set at the ASYM-regulator, the set inter-
val of the tripping delay (DELAY) begins (red LED ASYM flashes).
After the interval has expired (red LED ASYM illuminated), the
output relays switch into off-position (yellow LED not illuminated).
LED ASYM
Asym.
Page
L1 L2 L3
512
Delay
MONITORING RELAYS
w CONNECTIONS
F1-3
max. 20A
15 25
16 18 26 28
w DIMENSIONS
Page
513
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
• Undervoltage monitoring
• 1 change over contact
• Installation design
w TECHNICAL DATA
1. Functions 6. Output circuit
Undervoltage monitoring in 3-phase mains (each phase against 1 potential free change over contact
the neutral wire) with fixed threshold voltage US and fixed Rated voltage: 250V AC
hysteresis. Switching capacity: 1250VA (5A / 250V)
Fusing: 5A fast acting
2. Time range Mechanical life: 20 x 106 operations
Adjustment range Electrical life: 2 x 105 operations
Tripping delay: fixed, approx. 200ms at 1000VA resistive load
Switching frequency: max. 6/min at 100VA resistive
3. Indicators load (in acc. with IEC 60947-5-1)
Yellow LED ON/OFF: indication of relay output Overvoltage category: III (in acc. with IEC 60664-1)
Rated surge voltage: 4kV
4. Mechanical design
Self-extinguishing plastic housing, IP rating IP40 7. Measuring circuit
Mounted on DIN-rail TS 35 according to EN 60715 Measuring variable: AC sinus, 48 to 63Hz
Mounting position: any Measuring input: (= supply voltage)
Shockproof terminal connection according to VBG 4 Terminals: N-L1-L2-L3
(PZ1 required), IP rating IP20 Overload capacity: determined by tolerance
Tightening torque: max. 1Nm specified for supply voltage
Page Terminal capacity: Input resistance: –
514 1 x 0.5 to 2.5 mm² with/without multicore cable end Switching threshold US: fixed 195,5V (L-N)
1 x 4 mm² without multicore cable end Hysteresis H: approx. 5%
2 x 0.5 bis 1.5 mm² with/without multicore cable end Overvoltage category: III (in acc. with IEC 60664-1)
2 x 2.5 mm² flexible without multicore cable end Rated surge voltage: 4kV
10. Weight
Single packing: 72g
MONITORING RELAYS
w FUNCTIONS
Undervoltage monitoring for 3-phase AC mains with fixed thres-
hold voltage US and fixed hysteresis. All measuring inputs (L1, L2
and L3) must be connected to phase voltage. If single or 2-phase
monitoring is required, unused input terminals (L) must be connec-
ted to mains voltage to have proper L-N voltage on the terminals
L1, L2 and L3. A phase failure can not be detected, if the reverse
voltage coming from the load exceeds the threshold US.
Undervoltage monitoring
The output relay R switches into on-position (yellow LED illumina-
ted), when the measuring voltage of all connected phases exeeds
the fixed threshold US by more than the fixed hysteresis H. When
the voltage of one of the connected phases (L1, L2 or L3) falls
below the fixed threshold, the output relay R switches into off-
position again (yellow LED not illuminated).
w CONNECTIONS w DIMENSIONS
Page
515
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w SCHRACK-INFO
• Voltage monitoring in 3-phase mains
• Undervoltage monitoring
• ON delay
• Supply voltage = measuring voltage
• 1 change over contact
• Width 17.5 mm
• Installation design
w TECHNICAL DATA
1. Functions 6. Output circuit
Undervoltage monitoring in 3-phase mains (each phase against 1 potential free change-over contact
the neutral wire) with adjustable ON delay, fixed threshold and Rated voltage: 250V AC
fixed hysteresis. Switching capacity: 1250VA (5A / 250V)
Fusing: 5A fast acting
2. Time ranges Mechanical life: 20 x 106 operations
Adjustment range Electrical life: 2 x 105 operations
Tripping delay: fixed, approx. 200ms at 1000VA resistive load
ON delay t: 5min to 15min Switching frequency: max. 60/min at 100VA resistive load
max. 6/min at 1000VA resistive load
3. Indicators (in accordance with IEC 60947-5-1)
Green LED U/t ON: all 3 tensions are allright Overvoltage category: III (in accordance with IEC 60664-1)
Green LED U/t flashes: indication of time period Rated surge voltage: 4kV
Yellow LED ON/OFF: indication of relay output
7. Measuring circuit
4. Mechanical design Measuring variable: AC sinus, 48 to 63 Hz
Self-extinguishing plastic housing, IP rating IP40 Measuring input: (=supply voltage)
Mounted on DIN-Rail TS 35 according to EN 50022 Terminals: N- L1- L2- L3
Mounting position: any Overload capacity: determined by tolerance
Page Shockproof terminal connection accordting to VBG 4 specified for supply voltage
(PZ1 required), IP rating IP20 Input resistance: -
516 Tightening torque: max. 1Nm Switching threshold US: fixed 165V (L-N)
Terminal capacity: Hysteresis H: approx. 5%
1 x 0.5 bis 2.5 mm² with/without multicore cable end Overvoltage category: III (in accordance with IEC 60664-1)
1 x 4 mm² without multicore cable end Rated surge voltage: 4kV
2 x 0.5 to 1.5 mm² with/without multicore cable end
2 x 2.5 mm² flexible without multicore cable end 8. Accuracy
Base accuracy: ±5% of rated value
5. Input circuit Adjustment accuracy: ≤5% of maximum scale value
Supply voltage: (= measured voltage) Repetition accuracy: ±2%
Terminals: N-L1-L2-L3 Voltage influence: -
Rated voltage UN: 3N~400/230V Temperature influence: ≤1%
Tolerance: -30% to +30% of UN
Rated consumption: 6 VA (0,8 W) 9. Ambient conditions
Rated frequency: 48 to 63 Hz Ambient temperature: -25 to +55°C
Duty cycle: 100% Storage temperature: -25 to +70°C
Reset time: 500 ms Transport temperature: -25 to +70°C
Hold-up time: - Relative humidity: 15% to 85% (in accordance with
Drop out voltage: determined by undervoltage IEC 60721-3-3 class 3K3)
detection (see measuring circuit) Pollution degree: 2, if built in 3
Overvoltage category: III (in acc. with IEC 60664-1) (in acc. with IEC 60664-1)
Rated surge voltage: 4 kV
10. Weight
Single packing: 72g
MONITORING RELAYS
w FUNCTIONS
Undervoltage monitoring for 3-phase mains with fi xed thres- Undervoltage monitoring with ON delay (Option E)
hold voltage and fi xed hysteresis. All measuring inputs (L1, L2 When the voltage of all connected phases exeeds the fixed
and L3) must be connected to phase voltage. If single or 2-phase threshold by more than the fixed hysteresis, the set interval t
monitoring is required, unused input terminals (L) must be begins (green LED U/t flashes). After the set interval t has
connected to mains voltage to have proper L-N voltage on the expired, the output relay R switches into on-position (yellow LED
terminals L1, L2 and L3. If there is a reverse voltage on account R illuminated, green LED U/t illuminated). When the voltage of
of a consumer, which exeeds the fi xed threshold, detection of one of the connected phases falls below the fixed threshold, the
phase failure isn't possible. output relay R switches into off-position (yellow LED R not
illuminated, green LED U/t not illuminated).
w CONNECTIONS w DIMENSIONS
87mm
45mm
Page
5mm 44mm 517
17,5mm
60mm
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w SCHRACK-INFO
• AC current monitoring in 1-phase mains
• 1 change over contact
• Width 17.5 mm
• Installation design
w TECHNICAL DATA
1. Functions Mechanical life: 20 x 106 operations
AC current monitoring in 1-phase mains with adjustable Electrical life: 2 x 105 operations
threshold and fixed hysteresis. at 1000 VA resistive load
Switching frequency: max. 60/min at 100 VA
2. Time ranges resistive load
Adjustment range max. 6/min at 1000 VA
Tripping delay (Delay): - resistive load
(according to IEC 947-5-1)
3. Indicators Overvoltage category: III. (according to IEC 60664-1)
Green LED ON: indication of supply voltage Rated surge voltage: 4 kV
Yellow LED ON/OFF: indication of relay output
7. Measuring circuit
4. Mechanical design Measuring variable: AC sinus, 48 to 63 Hz
Self-extinguishing plastic housing, IP rating IP40 Measuring input: 5A AC
Mounted on DIN-rail TS 35 according to EN 50022 Terminals: Li, Lk
Mounting position: any Overload capacity: 7A (ex 5A - distance > 5mm)
Shockproof terminal connection according to VBG 4 Starting current:
(PZ1 required), 1s 40A
IP rating IP20 3s 20A
Page Tightening torque: max. 1 Nm Input resistance: 10 mΩ
Terminal capacity: Switching threshold Is: 10% to 100% of In
518 1 x 0.5 to 2.5 mm2 with/without multicore cable end Hysteresis H: fixed 10%
1 x 4 mm2 without multicore cable end Overvoltage category: III (according to IEC 60664-1)
2 x 0.5 to 1.5 mm2 with/without multicore cable end Rated surge voltage: 4 kV
2 x 2.5 mm2 flexible without multicore cable end
8. Accuracy
5. Input circuit
Base accuracy: ±5% of maximum scale value
Supply voltage: 230 V AC
Adjustment accuracy: ⱕ5% of maximum scale value
Terminals: Li-N
Repetition accuracy: ±2%
Tolerance: -15% to +15% of Un
Voltage influence: -
Rated consumption: 5 VA (0,8 W)
Temperature influence: ⱕ0.05% / °C
Rated frequency: AC 48 to 63 Hz
Duty cycle: 100%
Reset time: 500 ms 9. Ambient conditions
Wave form: Sinus Ambient temperature: -25 to +55 °C
Hold-up time: - (according to IEC 68-1)
Drop out voltage: >20% of rated voltage Storage temperature: -25 to +70 °C
Overvoltage category: III (according to IEC 60664-1) Transport temperature: -25 to +70 °C
Rated surge voltage: 4 kV Relative humidity: 15% to 85%
(according to IEC 721-3-3 class 3K3)
6. Output circuit Pollution degree: 2, if built in 3
1 potential free change over contact (according to IEC 664-1)
Rated voltage: 250 V AC Vibration resistance: 10 to 55 Hz 0.35 mm
Switching capacity: 1250 VA (5 A / 250 V AC) (according to IEC 68-2-6)
Fusing: 5A fast acting Shock resistance: 15 g 11 ms
(according to IEC 68-2-27)
MONITORING RELAYS
w FUNCTIONS
The supply voltage U must be constantly applied to the
device (green LED illuminated). The output relay R switches
into on-position (yellow LED illuminated) when the measured
current exceeds the value adjusted at the Is regulator. The
output relay R switches into off-position (yellow LED not
illuminated) when the measured value for the current falls
below the set value by more than the fixed hysteresis.
w DIMENSIONS w CONNECTIONS
Page
519
w WEIGHT
Single packing: 70g
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w TECHNICAL DATA
w FUNCTIONS
Page
522
MONITORING RELAYS
w CONNECTIONS
Range 20mA, supply voltage 24V AC/DC and fault latch Range 1A, supply voltage 230V AC and fault latch
24VAC/DC
15 25
15 25
16 18 26 28
16 18 26 28
24VAC/DC
15 25
16 18 26 28
Page
523
w DIMENSIONS
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w SCHRACK-INFO
• Output relay
• 1 potential free change over contact
w TECHNICAL DATA
1. Functions 6. Output circuit
Monitoring of phase sequence, phase failure and asymmetry 1 potential free change-over contact
with adjustable asymmetry, connection of neutral wire optional. Rated voltage: 250V AC
Switching capacity: 1250VA (5A / 250V)
2. Time ranges Fusing: 5A fast acting
Tripping delay: fixed, approx. 100 ms Mechanical life: 20 x 106 operations
Electrical life: 2 x 105 operations
3. Indicators at 1000VA resistive load
Green LED ON: indication of supply voltage Switching frequency: max. 60/min at 100VA resistive load
Yellow LED ON/OFF: indication of relay output max. 6/min at 1000VA resistive load
(according to IEC 60947-5-1)
4. Mechanical design Overvoltage category: III (according to IEC 60664-1)
Self-extinguishing plastic housing, IP rating IP40 Rated surge voltage: 4kV
Mounted on DIN-Rail TS 35 according to EN 50022
Mounting position: any 7. Measuring circuit
Tightening torque: max. 1Nm Measuring variable: 3(N)~, sinus, 48 to 63 Hz
Terminal capacity: Measuring input: (=supply voltage)
1 x 0.5 bis 2.5 mm² with/without multicore cable end Terminals: (N)- L1- L2- L3
1 x 4 mm² without multicore cable end Overload capacity: determined by tolerance
Page 2 x 0.5 to 1.5 mm² with/without multicore cable end specified for supply voltage
524 2 x 2.5 mm² flexible without multicore cable end Input resistance: -
Asymmetry: 5% to 25% adjustable,
5. Input circuit or disengageable
Supply voltage: (= measured voltage) Overvoltage category: III (according to IEC 60664-1)
Terminals: (N)-L1-L2-L3 Rated surge voltage: 4 kV
Rated voltage Un: 3(N)~400/230V AC
Tolerance: -30% to +30% of Un 8. Accuracy
Rated consumption: 8 VA (0,8 W) Base accuracy: ±5% of maximum scale value
Rated frequency: AC 48 to 63 Hz Adjustment accuracy: ≤5% of maximum scale value
Duty cycle: 100% Repetition accuracy: ±2%
Reset time: 500 ms Voltage influence: -
Hold-up time: - Temperature influence: ≤0.05% / ° C
Drop out voltage: >20% of the supply voltage
Overvoltage category: III (according to IEC 60664-1) 9. Ambient conditions
Rated surge voltage: 4 kV Ambient temperature: -25 to +55°C (acc. to IEC 60068-1)
Storage temperature: -25 to +70°C
Transport temperature: -25 to +70°C
Relative humidity: 15% to 85%
(acc. to IEC 60721-3-3 class 3K3)
Pollution degree: 2, if built in 3 (acc. to IEC 60664-1)
Vibration resistance: 10 to 55Hz 0.35 mm
(according to IEC 60068-2-6)
Shock resistance: 15g 11ms (acc. to IEC 60068-2-27)
MONITORING RELAYS
w FUNCTIONS w CONNECTIONS
A1 11
R
A2 12 14
11
12 14
Asymmetry monitoring
The output relay R switches into off-position (yellow LED not
illuminated) when the asymmetry exceeds the value set at the w DIMENSIONS
ASYM-regulator. Reverse voltages of a consumer (e.g. a motor
which continues to run on two phases only) do not effect the
disconnection.
87mm
45mm
Phase failure monitoring 5mm 44mm
The output relay switches into off-position (yellow LED not 17,5mm
60mm
illuminated), when one of the three phases fails.
Page
525
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w TECHNICAL DATA
9. Ambient conditions
Ambient temperature: -25 to +55°C Pollution degree: 3 (in accordance with IEC 60664-1)
(in accordance with IEC 60068-1) Vibration resistance: 10 to 55Hz 0.35 mm
-25 to +40°C (in accordance with
(in accordance with UL 508) IEC 60068-2-6)
Storage temperature: -25 to +70°C Shock resistance: 15g 11ms
Transport temperature: -25 to +70°C (in accordance with
Relative humidity: 15% to 85% IEC 60068-2-27)
(in accordance with
IEC 60721-3-3 class 3K3)
w FUNCTIONS w CONNECTIONS
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
6. Output circuit
1 potential free change over contact
Terminals: 11-12-14
Rated voltage: 250V AC
Switching capacity: 1250VA AC1 B300/P300
(in accordance with IEC 60947-5-1);
therm. constant current 5A
Fusing: 5A fast acting
Mechanical life: 20 x 106 operations
Electrical life: 2 x 105 operations
at 1000VA resistive load
Switching frequency: max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
Overvoltage category III. (in accordance with IEC 60664-1)
Rated surge voltage: 6kV
MONITORING RELAYS
w FUNCTIONS
Temperature monitoring of the motor winding with fault latch Application of an external Reset
If the supply voltage U is applied (green LED illuminated) and the cumu-
lative resistance of the PTC-circuit is less than 3.6k: (standard tempera-
ture of the motor), the output relay switches into on-position.
Pressing the test/reset key under this conditions forces the output relay
to switch into off-position. It remains in state as long as the test/reset key
is pressed and thus the switching function can be checked in case of
fault. The test function is not effective by using an external reset key.
When the comulative resistance of the PTC-circuit exceeds 3.6k: (at
least one of the PTCs has reached the cut-off temperature), the output
relay switches into off-position (red LED illuminated).
The output relay switches into on-position again (red LED not illumina-
ted), if the cumulative resistance drops below 1.65k: by cooling down of Application of internal Test/Reset - key
the PTC and either a reset key (internal or external) was pressed or the
supply voltage was disconnected and re-applied.
w CONNECTIONS w DIMENSIONS
Monitoring Monitoring
Temperature sensor Thermal contact
U U
87mm
45mm
T3 A1 A2 T3 A1 A2
T1 T2 T1 T2
A1 11 A1 11
R R 5mm 44mm
35mm
60mm
A2 12 14 A2 12 14
Page
R1 R2 R1 R2 529
11 12 14 11 12 14
Reset Reset
Note:
Only one of this circuit versions (either monitoring of the temperature sensor or monitoring of the thermal contact) can be executed!!
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w TECHNICAL DATA
w FUNCTIONS
Page
w CONNECTIONS w DIMENSIONS 531
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w SCHRACK-INFO
Level monitoring of conductive liquids
Multifunction
Secure isolation of the measuring circuit
1 change over contact
Width 35mm
Installation design
w TECHNICAL DATA
1. Functions 7. Measuring circuit
Level monitoring of conductive liquid, timing for tripping delay and turn-off Measuring input: conductive probes
delay seperatly adjustable and the following functions (selectable by (Type SK1, SK2, SK3)
means of rotary switch): Terminals: E1-E2-E3
Pump up pump up or minimum monitoring Sensitivity: 0,25 to 100k: (4mS to 10PS)
Pump down pump down or maximum monitoring Sensor voltage: 12V AC
Sensor current: max. 7mA
2. Time ranges Wiring distance (capacity of cable 100nF/km):
Adjustment range max. 1000m (set value <50%)
Tripping delay (Delay ON): 0.5s to 10s max. 100m (set value 100%)
Turn-off delay (Delay OFF): 0.5s to 10s Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 6kV
3. Indicators
Green LED ON: indication of supply voltage 8. Accuracy
Yellow LED ON/OFF: indication of output relay Base accuracy: -
Adjusting accuracy: -
Repetition accuracy: -
4. Mechanical design
Voltage influence: -
Self-extinguishing plastic housing, IP rating IP40
Temperature influence: -
Mounted on DIN-rail TS 35 according to EN 50022
Mounting position: any
Shockproof terminal connection according to VBG 4 (PZ1 required), 9. Ambient conditions
IP rating IP20 Ambient temperature: -25 to +55°C
Tightening torque: max. 1Nm Storage temperature: -25 to +70°C
Terminal capacity: Transport temperature: -25 to +70°C
Page 1 x 0.5 to 2.5mm² with/without multicore cable end Relative humidity: 15% to 85%
1 x 4mm² without multicore cable end (in accordance with IEC 60721-3-3
532 2 x 0.5 to 1.5mm² with/without multicore cable end class 3K3)
2 x 2.5mm² flexible without multicore cable end Pollution degree: 2, if built in 3
(in accordance with IEC 60664-1)
5. Input circuit
Terminals: A1-A2 10. Weight
Rated voltage Un: see table ordering information or Single packing: 140g
printing on the unit
Tolerance: -15% of +10% of Un
Rated consumption: 2VA (1.0W)
Rated frequency: AC 48 to 63Hz
Duty cycle: 100%
Reset time: 500ms
Hold-up time: -
Drop-out voltage: >30% of supply voltage
Overvoltage category: III (in accordance with IEC 60664-1)
Rated surge voltage: 6kV
6. Output circuit
1 potential free change over contact
Rated voltage: 250V AC
Switching capacity: 1250VA AC1 B300/P300
(in accordance with IEC 60947-5-1)
therm. constant current 5A
Fusing: 5A fast acting
Mechanical life: 20 x 106 operations
Electrical life: 2 x 105 operations
at 1000VA resistive load
Switching frequency: max. 6/min at 1000VA resistive load
(in accordance with IEC 60947-5-1)
Overvoltage category: III. (in accordance with IEC 60664-1)
Rated surge voltage: 6kV
MONITORING RELAYS
w FUNCTIONS
Pump up Pump down
Connection of the probe rods E1, E2 and E3. Alternatively the electri- Connection of the probe rods E1, E2 and E3. Alternatively the electrically
cally conducting container can be connected in lieu of the test probe E3. conducting container can be connected in lieu of the test probe E3.
When the air-fluid level falls below the minimum probe E2 the set interval When the maximum probe E1 gets moistened the set interval of tripping
of tripping delay (Delay ON) begins. After the expiration of the interval, delay (Delay ON) begins. After the expiration of the interval the output
the output relays R switches into on-position (yellow LED illuminated). relays R switches into on-position (yellow LED illuminated). When the
When the air-fluid level again rises above the maximum probe E1, the air-fluid level falls below the minimum probe E2, the set interval of
set interval of turn-off delay (Delay OFF) begins. After the expiration of turn-off delay (Delay OFF) begins. After the expiration of the interval, the
the interval the output relays R switches into off-position (yellow LED output relays R switches into off-position (yellow LED not illuminated).
not illuminated).
UU U
ProbeE1
Probe E1 Probe E1
Level
Level
Level
Level
ProbeE2
Probe E2 Probe E2
ProbeE3
Probe E3 Probe E3
U U
Probe E2
Probe E2
Level
Level
Probe E3
Probe E3
Page
Note
Use cables with low capacity for wiring the probes especially with extended wiring length.
533
Following processes are suggested for the adjustment:
- The existent time delay should be to minimum (0,5s).
- The function selector switch must be in position pump down.
- Turn the sensitivity controller slowly clockwise from min to max until the relais switches into on-position. (probes must be in dipped state)
- The moistened probes should be taken out of the liquid to control if the relais switches into off-position.
If the relais doesn't switch into off-position, turn the sensitivity controller slightly back to min. (counter clockwise)
- Set the existent time delay to desired value to fade out a short term moisten the probes by waves in the liquid.
- Set the function selector switch to desired position. (either pump up or pump down)
w CONNECTIONS w DIMENSIONS
L
N
87mm
45mm
A1 A2
E1 E2 E3
Probe
max.
A1 15
R
Probe
A2 16 18 min.
5mm 44mm
Mass probe
35mm
16 18 15 60mm
Order no. blue: on stock, usually ready for delivery on the day of order!
MONITORING RELAYS
w TECHNICAL DATA
1. Functions 6. Output circuit
Level monitoring of conductive liquid, timing for tripping delay and turn- 2 potential free change-over contacts
off delay separately adjustable and the following functions (selectable by Rated voltage: 250V AC
means of rotary switch) Switching capacity (distance <5 mm):
Pump up pump up or minimum monitoring 750VA (3A / 250V)
Pump down pump down or maximum monitoring Switching capacity (distance >5 mm):
1250VA (5A / 250V)
2. Time ranges Fusing: 5A fast acting
Adjustment range Mechanical life: 20 x 106 Operations
Tripping delay (Delay ON): 0.5s 10s Elektrische Lebensdauer: 2 x 105 Operations
Turn-off delay (Delay OFF): 0.5s 10s at 1000VA resistive load
Switching frequency: max. 60/min at 100VA
3. Indicators resistive load
Green LED ON: indication of supply voltage max. 6/min at 1000VA
Yellow LED ON/OFF: indication of relay output resistive load
(in accordance with IEC 60947-5-1)
4. Mechanical design Overvoltage category: III (in accordance with IEC 60664-1)
Self-extinguishing plastic housing, IP rating IP40Mounted on DIN-Rail TS Rated surge voltage: 4kV
35 according to EN 60715
Mounting position: any 7. Measuring circuit
Shockproof terminal connection according to VBG 4 Input: conductive probes
Page (PZ1 required),IP rating IP20 (type SK1, SK2, SK3)
Tightening torque: max. 1Nm terminals E1-E2-E3
534 Terminal capacity: Sensitivity: 0.25 to 100k1 (4mS to 1μS)
1 x 0.5 to 2.5 mm² with/without multicore cable end Sensor voltage: 12V AC
1 x 4 mm² without multicore cable end Sensor current: max. 7mA
2 x 0.5 to 1.5 mm² with/without multicore cable end Wiring distance (capacity of cable 100nF/km)
2 x 2.5 mm² flexible without multicorecable end max. 1000m (set value <50%) max.
100m (set value 100%)
5. Input circuit Overvoltage category: III (in accordance with IEC 60664-1)
Supply voltage: Rated surge voltage: 6kV
230V AC terminals A1-A2
Tolerance: 8. Accuracy
230V AC -15% to +15% Adjustment accuracy: -
Rated frequency: 48 to 63Hz Repetition accuracy: -
Rated consumption: Voltage influence: -
230V AC 2VA (1.5W) Temperature influence: -
Duration of operation: 100%
Reset time: 500ms 9. Ambient conditions
Residual ripple for DC: - Ambient temperature: -25 to +55°C (in acc. with IEC 60068-1)
Drop-out voltage: >30% of the supply voltage -25 to +40°C (in acc. with UL 508)
Overvoltage category: III (in acc. with IEC 60664-1) Storage temperature: -25 to +70°C
Rated surge voltage: 4kV Transport temperature: -25 to +70°C
Relative humidity: 15% to 85% (in accordance with
IEC 60721-3-3 class 3K3)
Pollution degree: 3 (in acc. with IEC 60664-1)
Vibration resistance: 10 to 55Hz 0.35 mm
(in acc. with IEC 60068-2-6)
Shock resistance: 15g 11ms (in acc. with IEC 60068-2-27)
MONITORING RELAYS
w FUNCTIONS
Pump up Pump down
Connection of the probe rods E1, E2 and E3. Alternatively the electrically Connection of the probe rods E1, E2 and E3. Alternatively the electrically
conducting container can be connected in lieu of the test probe E3.When conducting container can be connected in lieu of the test probe E3.When
the air-fluid level falls below the minimum probe E2 the set interval of the the maximum probe E1 gets moistened the set interval of the trip-ping
tripping delay (DELAY ON) begins. After the expiration of the interval the delay (DELAY ON) begins. After the expiration of the interval the output
output relays switch into on-position (yellow LED illuminated). When the relays switch into on-position (yellow LED illuminated). When the air-fluid
air-fluid level again rises above the maximum probe E1, the set interval of level falls below the minimum probe E2, the set interval of the turn-off
the turn-off delay (DELAY OFF) begins. After the expira-tion of the inter- delay (DELAY OFF) begins. After the expiration of the interval the output
val the output relays switch into off-position (yellow LED not illuminated). relays switch into off-position (yellow LED not illuminated).
U U
Probe E1 Probe E1
Level
Level
Probe E2 Probe E2
Probe E3 Probe E3
U U
Probe E2 Probe E2
Level
Level
Probe E3 Probe E3
Page
w NOTE 535
Use cables with low capacity for wiring the probes especially with extended wiring length.
Following processes are suggested for the adjustment:
- The existent time delay should be to minimum (0,5s).
- The function selector switch must be in position pump down.
- Turn the sensitivity controller slowly clockwise from min to max until the relais switch into on-position. (probes must be in dipped state)
- The moistened probes should be taken out of the liquid to control if the relais switch into off-position. If the relais doesn't switch into off-position,
turn the sensitivity controller slightly back to min. (counter clockwise)
- Set the existent time delay to desired value to fade out a short term moisten the probes by waves in the liquid.
- Set the function selector switch to desired position (either pump up or pump down)
w CONNECTIONS w DIMENSIONS
L1
N
A1 15 25
E1 E2 E3
Sonde max.
15 25
Sonde min.
16 18 26 28
26 28
Massesonde
16 18 A2
Order no. blue: on stock, usually ready for delivery on the day of order!