MiCOM P922

Voltage / Frequency relay

Voltage and frequency protection, combined with


measurements, communications, control and recording facilities
Applications
are included in the MiCOM P922. Moreover, logic equations • Protection of generators and
allow the user to customise the protection and control functions. motors against supply
abnormalities
• Earth/Ground fault protection
• Protection of plant or feeders
against unbalance
• Load shedding / load restoration

Protection
• Phase-to-phase or phase-to-neutral
protections
• [59] 3 independent overvoltage
thresholds (AND/OR logic)
• [27] 3 independent
Offering fast and reliable Fast fault diagnosis undervoltage thresholds
algorithms, MiCOM P922 can be (AND/OR logic)
• Event records (75)
applied to protect generators • [59N] 3 independent zero-
against overvoltages caused by • Fault records (5). sequence overvoltage thresholds
load rejection and motors against Disturbance records (32 samples
reverse phase sequence. per cycle) • [27D] 2 independent positive
The integral under/overfrequency sequence undervoltage
can be used for load shedding thresholds
User-friendly interfaces
applications. • [47] 2 independent negative
• Back-lit LCD
In addition, the relay offers the sequence overvoltage thresholds
following benefits: • Easy settings through the front
• [81U/81O] 6 independent
RS232 port
under/over frequency thresholds
Precise information • Simple system integration through
• 2 setting groups
a choice of protocols including
• True RMS measurements • Output contact latching
Courier, Modbus, IEC60870-5-103
• Peak and rolling demands • Blocking logic
High performance
Higher flexibility hardware
• Phase to phase or phase to • Reference voltage: 2 ranges from
neutral voltage protections 57V to 480V
• Programmable logic equations • Update of the firmware through
• Connection of 2, 3 or 4 VTs the front port
• Programmables opto-inputs,
output contacts and LEDs
Technical specifications
Busbar

3 Phase VTs 3 Phase VTs

Trip output Trip output

59N 27 59 27D 47 59N 27 59 27D 47


7 auxiliary 7 auxiliary
Loading outputs outputs
81U 81O 81U 81O
resistor
P922 5 opto-inputs
P922 5 opto-inputs

RS232 RS485
30 86 RS232 RS485
30 86
WD Watchdog WD Watchdog

Setting RS485 Setting RS485


software communication software communication

Configuration Negative Sequence Control and Supervision


• Schemes : 3VTs, 3VTs+residual, Overvoltage • Circuit breaker monitoring
2VTs+residual, 2VTs • Thresholds: 2
• Circuit breaker supervision
• Voltage protection: phase to • Settings: from 5V to 720V
• 2 logic equations (AND) with
phase or phase to neutral
associated timers (pickup /drop-off)
Positive Sequence
Voltage inputs Undervoltage
Measurements and records
• 4 VTs • Thresholds: 2
All records are time tagged to a
• 2 ranges: • Settings: from 5V to 480V resolution of 1ms.

Our policy is one of continuous development and the right is reserved to supply equipment which may or vary from that described.
Vn = 57 –130V
Measurement and display of all
Vn = 220 – 480V Under/overvoltage analogue and calculated quantities.
• Burden: <0.3VA per phase • Thresholds: 3 under / 3 over
• Thermal withstand: • Settings: Hardware description
2Vn permanent - under: from 5V to 480V • Watchdog: changeover contact
2.6Vn during 10s - over: from 5V to 960V
• 5 opto-inputs / 8 output contacts
• Logic of detection: selectable
Voltage protections • Back-lit LCD display
between "AND", "OR"
Each function generates one • Keypad: 7 tactile push-buttons
instantaneous (<30ms) and one Frequency protections • RS232 front port / RS485 rear
definite time-delayed information port
• Thresholds: 6
(from 0 to 599s) per threshold.
• Configuration: 81U or 81O • 8 LEDS, 4 freely programmable
The first threshold of each function
can also be inverse time-delayed, • fn = 50Hz or 60 Hz • Power supply: (±20%)
according to the formulas: 24 - 60Vdc , 48 - 150Vdc or
• Settings: from "fn –10Hz" to 130 - 250 Vdc /100 - 250 Vac
• Overvoltage: "fn + 10Hz"
t=TMS/(V/Vset –1) • Case: MiCOM 20TE, rack or
• Step of settings: 0.01 Hz flush mounting, MIDOS
• Undervoltage: connectors (2x28 points)
• Instantaneous information:
t=TMS/(1 –V/Vset)
2.5 cycles (50ms at 50 Hz)
• DT: from 0 to 599s Standards
Zero Sequence Overvoltage
• CE conformity to IEC 60947-1
• Thresholds: 3 • Accuracy: ±10mHz if V>0.2Vn
(EMC and LV directives)
• Settings: from 5V to 480V

T R A N S M I S S I O N & D I S T R I B U T I O N Protection & Control, HQ, 60 Route de Sartrouville, BP58, 78230 Le Pecq Cedex. France
Tél: +33 (0) 134 80 79 00 Fax: +33 (0) 134 80 79 13 Email: protection.control@tde.alstom.com Internet: www.tde.alstom.com

Publication: L1 1532 A © 2000 ALSTOM 090002 - ARCEAUX 49 Imp. - Printed in France

Vous aimerez peut-être aussi