10. RKC REX-CB100 Series Temperature Controller

10.1 How to set new temperature (Set-Value)

1. Press SET key.


2. Use LEFT key to move the cursor to the left and right.
3. Use DOWN, UP key to change the value.
4. Press SET key to store the new Set-Value.

10.2 How to set parameters

1. Press SET key for 5 second.


2. Use LEFT key to move the cursor to the left and right.
3. Used DOWN, UP key to change the value.
4. Press SET key to move to next parameter.
5. Press SET key for 5 second to store the new parameters.

Symbol Name Description Setting Updated


AL1 First alarm Set alarm set-value of first alarm 0003 ***

AΓU Auto tune Turn the auto-tune ON/OFF 0000


SΓU Self-tuning Turns the self-tune ON/OFF 0000
P (Heating side) Set heating-side proportional band. 30
Proportional ON/OFF action with P set to “0” or “0.0”
band
I Integral time Eliminates offset occurring control is 240
performed. I action turns OFF with I set to
“0”
D Derivative time Prevents ripples by predicting output change 60
thereby improving control stability.
D action turns OFF with D set to “0”
Ar Anti-reset Prevents overshoot and /or undershoot 100
windup caused by integral action.
I action turns OFF with this action set to “0”
Γ (Heating side) Set control output cycle 2 ***
Proportional
cycle
Pb PV bias setting Sensor correction is made by adding bias 0000
value to measured value
LCK Set data lock Perform set data change enable/disable 0000 - enable
1000 - disable

___________________________________________________________________________________
SRM XD248 Instruction Manual (Rev.6) --------------------------------------------------------------------Page: 75
_____________________________________________________

10.3 How to change the initial set mode


Note: In order to enter the initial set mode, always set the set data locking (LCK) to “1000”.
Any setting other than “0000” cannot enter the initial set mode.
Refer to section “11.2 To set parameters” to set (LCK) to “0000”.

1. Press SET + LEFT key for 5 second.


2. Use LEFT key to move the cursor to the left and right.
3. Used DOWN, UP key to change the value.
4. Press SET key to move to next parameter.
5. Press SET +LEFT key for 5 second to store the new system parameters.

Symbol Name Description Setting Updated


Cod Initialize code selection 0000
SL1 Input type selection 0000
SL2 Engineering unit selection (degree C or F) 0000
SL3 Heater break alarm (HBA) selection 0000
Control loop break alarm (LBA) selection
Special specification (Z-132) selection
Selection of control loop break alarm output
terminals
SL4 First alarm (ALM1) type selection 0110 ***
First alarm (ALM1) hold action selection
0110 =Band alarm
SL5 Second alarm (ALM2) type selection 0000
Second alarm (ALM2) hold action selection
SL6 Direct/reserve action selection 0001
Control action type selection
Control output type selection
(Heating/Cooling side)
SL7 Energize /de-energize alarm selection 0000
Special specification (Z-124) selection
SL8 SL8 can not be set 0000
SL9 SL9 can not be set 0000
SL10 Option selction 0000
SL11 SV alarm selection 0000

___________________________________________________________________________________
SRM XD248 Instruction Manual (Rev.6) --------------------------------------------------------------------Page: 76