Académique Documents
Professionnel Documents
Culture Documents
Krishnan Gowri
Pacific Northwest National Lab.
Richland, WA
AIA Quality Assurance
Learning Objectives
90.1-1999
major rewrite 90.1-2001
90.1-1980 minor
updated revisions
90.1-1989
updated
90.1-2007
90.1-1975 updates
first issued 90.1-2004
updates,
reorganization
Prescriptive
Envelope
Option
Mandatory
HVAC
Provisions Trade Off
Energy Code
(required for most Option Compliance
SWH compliance options)
Other Simplified
Prescriptive Building Envelope Option
Compliance
¾ Meet or exceed minimum R-values in table
Only R-value of insulation, not to include air films, etc
OR
¾ Meet maximum U-factor, C-factor, or F-factor for the
entire assembly
OR
¾ Perform area-weighted average U-factor, C-factor, or
F-factor calculations
Only if there are multiple assemblies within a single class of
construction for a single space-conditioning category
Fenestration
prescriptive
requirements
(§6.5)
mandatory
provisions
(§6.4)
Energy
Simplified
Cost
Budget
Approach
Method
Option
(ECB, §11)
(§6.3)
Simplified
proposed 90.1-compliant
Approach
HVAC design Option (§6.3) HVAC system
Limited to…
¾ Buildings with 1 or 2 stories
¾ Buildings < 25,000 ft2
¾ Single-zone systems (unitary or split)
¾ Air-cooled or evaporatively cooled
Load calculations
Controls
• Zone Thermostatic and Dead Band, Off-hour, Setback, Optimum Start
• Zone Isolation and Ventilation Fan Controls
• Humidification and Dehumidification Controls
• Freeze protection controls
Economizers
Simultaneous heating and cooling limitation
Air system design and control
Hydronic system design and control
Heat rejection equipment
Energy recovery
Exhaust hoods
Radiant heating systems
Hot gas bypass limitation
Lighting Compliance Requirements
Controls
Connected
Power
< Lighting
Power Exemptions
Allowance
Non-
Switching Tradable
Additional Allowances
Interior Lighting Power - Building Area Method
• 11 addenda to Envelope
• 32 addenda to Mechanical
• 11 addenda to Lighting
• 17 addenda to “Other” (ECB, Appendix G, etc.)
Large Office (500,000 sf) Medium Office (54,000 sf) Hospital (200,000 sf)
National Weighted‐Average National Weighted‐Average
Prototype Energy Savings Energy Cost Savings
24
Pending Addenda
(includes approved unpublished addenda and addenda in public review)
Envelope
¾ Prescriptive requirements revised for all climate zones (Addenda-bb)
¾ Continuous air barrier requirements
¾ Skylight requirement
Mechanical
¾ VAV fan requirements for large single zone units
¾ Heat pump requirements to include IEER
¾ Centrifugal fan cooling tower limitation
¾ Pump head calculation requirement
¾ Pipe sizing and insulation requirements
Lighting
¾ Interior lighting power density
¾ Day lighting requirements
¾ Electric motor efficiency requirements
Envelope Addenda-bb
(example comparison of requierments with 90.1-2004 for Insulation Above deck Roof)
Climate Zone R-value U-factor R-value U-factor R-value U-factor R-value U-factor
Climate Zone R-value U-factor R-value U-factor R-value U-factor R-value U-factor
20%
Percentage Savings
15%
10%
5%
0%
i
r
e
a
n
n
m
h
ks
ue
h
so
ise
x
m
ve
i
en
or
ag
sto
to
ad
ut
isc
ni
ph
le
an
pa
rq
ia
Bo
ou
m
ng
ul
oe
el
ic
y
Sa
em
ou
nc
M
ue
_
irb
Ri
lti
D
Ch
nc
rli
Ph
El
ra
5B
H
uq
4C
M
1A
Ba
Fa
6B
7
Bu
Va
1B
_F
3B
5A
2A
2B
lb
3A
4A
8
n
6A
5C
Sa
4B
3C
Climate Location
Commissioning Requirements in ASHRAE 90.1
HVAC System Compliance Requirement
Section 6.7 Submittals
Completion requirements
¾ Drawings - including location and performance data on all equipment,
distribution system sizes, and terminal air or water design flow rates
¾ Manuals – including operation and maintenance requirements,
calibration information, control sequences, set points, etc.
System balancing
¾ Air system balancing – minimize throttling losses, adjust fan speeds of
fans > 1hp to meet design flow conditions
¾ Hydronic system balancing – minimize throttling losses, adjust pump
speed to meet design flow conditions
System commissioning
¾ Control systems tested, calibrated and adjusted
¾ For projects >50,000 sf, commissioning instructions provided as per
ASHRAE Guideline 1-1996: The commissioning process
Commissioning Requirements in ASHRAE 90.1
Lighting controls (addenda–az, public review draft)
9.4.6 Functional Testing. Lighting controls shall be tested prior to occupancy to
ensure that control elements are calibrated, adjusted, and in proper working
condition in accordance with the construction documents and manufacturer’s
installation instructions. When occupant sensors, time switches, or photosensors are
used, the following functionality testing shall be performed:
a. Confirm that the sensitivity and time-out adjustments for occupant sensors yield
acceptable performance (i.e. lights turn off only after space is vacated).
b. Confirm that the time switches are programmed to turn the lights off.
c. Confirm that photosensor controls reduce electric light levels based on the amount of
usable daylight in the space as specified.
The construction documents shall state the party who will conduct and certify the
functional testing. The party responsible for the functional testing shall not be directly
involved in either the design or construction of the project and shall provide
documentation certifying that the installed lighting controls meet or exceed all
documented performance criteria. Certification shall be specific enough to verify
conformance.
Future Cx Requirements in Codes and Standards