Académique Documents
Professionnel Documents
Culture Documents
resistance testing
Contents HOW IS LOW RESISTANCE
MEASURED?12
INTRODUCTION3
Two, three and four wire
Brief history of low resistance d.c. measurements 12
ohmmeters4 Two wire measurements 13
www.megger.com 1
FIGURES Fig 23: C1 clip being connected to end of
circuit being tested 22
Fig 1: Qualitative Resistance Temperature
Fig 24: Duplex hand spike being used to
Curve for Manganini 4
perform same test as shown in Fig 23 22
Fig 2: Bus bar connections 7
Fig 25: Correct and incorrect probe
Fig 3: Single strap with two contact surfaces 7 placements 24
Fig 4: Parallel straps on a large battery Fig 26: Basic styles of probes 24
complex 8
Fig 27: Temperature resistance curves for
Fig 5: Measuring carrier strip resistance 8 iron, copper and carbon 26
Fig 6: Test on graphite slugs for uniform Fig 28: Circuit breaker corrosion 27
density (ohms / inch) 9
Fig 29: Noise 27
Fig 7: Series of measurements across a
Fig 30: Hot spots 28
weld seam 9
Fig 31: Bar to bar test on d.c. motor rotor 29
Fig 8: Determining the remaining length
of cable on a reel 10 Fig 32: Lap winding test data 30
Fig 9: Conventional test, one kelvin at Fig 33: Commutator with 24 coils in series 30
either end of a multi-core cable 10 Fig 34: Wave winding test data 30
Fig 10: The C2 and P2 shown as separate Fig 35: Wave winding coil arrangement 31
cables from a meter to one of the cores 11
Fig 36: Single strap resistance target 31
Fig 11: C1 connected to an adjacent core
on the same end of the multi-core cable 11 Fig 37: Parallel strap resistance target 31
Fig 12: P1 connected to another core on the Fig 38: Wheatstone bridge circuit 32
same end of the multi-core cable 11 Fig 39: Kelvin bridge circuit 32
Fig 13: The other end of the cable Fig 40: DLRO100 Series 35
showing the unmarked core 11
Fig 41: DLRO10 / DLRO10X 35
Fig 14: Contact area reduced due to
Fig 42: DLRO10HD 36
overtightening 12
Fig 43: DLRO600 36
Fig 15: Typical joints that should be
tested 12 Fig 44: DLRO200 37
Fig 21: Probe / lead configurations 17 Fig 52: Duplex connect test leads 39
www.megger.com 3
The alloy is modified for strips of material used in measuring shunts, where a considerable number of improvements could be made to the
which operate at a higher ambient, up to 50 ºC. 1970s designs. Newly designed low resistance ohmmeters by Megger
include data storage and downloading capability, additional test modes,
The purpose of this booklet is to help the engineer, technician or user
reduced weight, extended battery life, etc.
to understand:
Through the acquisition of Programma Electric AB, Megger strengthened Periodic tests are made to evaluate an initial condition or to identify
the program of high current low resistance ohmmeters's (LRO's). unexpected changes in the measured values, and the trending of this
data helps to indicate, and may forecast, possible failure conditions.
Back in the late seventies the MOM (Micro Ohm Meter) was one of the
Excessive changes in measured values point to the need for corrective
first products developed by Programma Electric AB, and in the decades
action to prevent a major failure. When making field measurements,
that followed that series has been supplemented with MJÖLNER and
the user should have reference values that apply to the device being
MOM2. The MJÖLNER moved from transformer based technology
tested (the manufacturer should include this information in the
to switched technology, which has the benefit of a much lighter test
literature or name plate supplied with the device). If the tests are a
instrument. The latest innovation is the MOM2, which uses a patented
repeat of previous tests, then these records can also be used to observe
ultra capacitor technology to generate the high current, which makes
the range of the anticipated measurements.
it possible to get over 200 A in a hand held product that weight less
than 1 kg. If, when conducting tests, the user records the results and the
conditions under which the tests were done, the information becomes
This style of instrument served the industry well for a number of years,
the start of a database that can be used to identify any changes from
and the various versions continue to help end users solve problems.
fatigue, corrosion, vibration, temperature or other condition that can
However, electronics and battery technology advanced to the point
occur at the test site.
iv Basic Electrical Measurements; Melvin B. Stout; 1950; page 61.
www.megger.com 5
So obviously a joint or cable connection which becomes hot will only A general list of industries include:
ever become hotter until, if you are lucky, it is identified by thermal
■■ Power generation and distribution companies
imaging, and if you are not so lucky, when the lights go out as the
connection burns out and the protective device operates. ■■ Chemical plants
■■ Refineries
But what if you can’t use thermal imaging because there is no direct
line of site to the connections. These can cook away deep inside a panel ■■ Mines
Critical supplies fail regularly because of overheating connections due ■■ Telecommunications companies
to high resistance connections burning out. Because of their critical ■■ Automotive manufacturers
nature, this makes regular isolation and maintenance almost impossible.
■■ Aircraft manufacturers
Think about hospitals and data centers. Health and data are probably ■■ Anyone with UPS battery back-up systems
two of the most critical but vulnerable installations but get the least
downtime for maintenance of enclosed switchgear assemblies and What equipment needs low
panel busbar systems. resistance testing
As we have shown, low resistance ohmmeters have an application
Using the formula W=I2R we can estimate the power lost over a
in a wide range of industries, and can help identify a number
connection or connections.
of problems that could lead to apparatus failure. In general
For a 10kA joint/s with a 0.1mΩ resistance, the power is 10kW. manufacturing industries, motor windings, circuit breakers, bus bar
For a 10kA joint/s with a 1mΩ resistance, the power is 100kW. connections, coils, ground bonds, switches, weld joints, lightning
conductors, small transformers and resistive components all require
For a 6kA joint/s with a 0.1µΩ resistance, the power is 36W. to be tested for low resistance.
For a 6kA joint/s with a 100mΩ resistance, the power is 3600kW.
The following are some of the more typical applications.
Simply, the power manifests itself as heat.
Using a DLRO to check the contact resistance of switchgear, lapped Motor armature
joints on busbars and cable lug connections before the power is
switched on is the only sure way to prevent poor connections becoming Armature windings can be tested to identify shorting between
potentially catastrophic failures. adjacent coils or conductors. Squirrel cage bars in the rotor can
separate from the end plates, resulting in loss of performance. If a
Industries with significant motor seems to be losing power, a low resistance test should be
resistance problems done. Alternatively, tests can be made when bearings are being
Industries that consume vast amounts of electrical power must replaced at a periodic or annual shutdown.
include low resistance ohmmeter measurements in their maintenance ■■ Motor bar to bar tests
operations. Not only does abnormally high resistance cause unwanted
Motor bar to bar tests on d.c. motor rotors are done to
heating, possibly leading to danger, but it also causes energy losses,
identify open or shorted coils. These tests are done with spring
which increase operating costs; in effect you are paying for energy
loaded hand probes. This is a dynamic method to determine
which you can not use.
the conditions of the windings and the soldered connections
In addition, there are industries that have critical specifications on to the riser on the commutator segments. When test data is
bond connections to ensure solid connections to 'ground beds.' Poor reviewed periodically, the effects of overheating due to excessive
connections reduce the effectiveness of the ground bed and can cause temperature rise can be identified.
significant power quality related problems and / or catastrophic failure
For more detailed information, see 'motor bar to bar tests'
in the event of major electrical surge. A number of sub-assembly
section' in Appendices.
operations supply components to aircraft manufacturers that specify
low resistance connections to the airframe. Strap connections between
cells on a power back-up battery system also require very low resistance.
Bus bars in a power system consisting of lap joints and other connections, This is the only field application in which the user makes measurements
are used to deliver current to the elements in the system. These bolted on an energized system. More for detailed information, see 'battery
connections can be degraded by vibration and corrosion (see Fig 2). The strap test' section in Appendices.
bolts are stressed to a specific tightness (torque), and the quickest and
Please note that there are various levels of 'float current' in a battery
most economical way to determine the quality of the connection is to
system and the test procedure must account for this current flow. A test
measure the resistance across the joint. The user should have historical
is done with the test current added to the float current and a second
data to make a determination on the suitability of the connection. If left
test is made with the test current opposed to the float current. These
uncorrected, loss of power and / or excessive heating could lead to a
two measurements are averaged to determine the 'ohmic' value of the
meltdown at the connection.
connection.
Transformer winding tests are done in the factory and then periodically
in the field. The factory test is done at ambient temperature. A second
factory test is a heat run to check that, at rated power, the resistance of
the windings stays within its designed temperature rise characteristics.
www.megger.com 7
Carrier strips 'carry' the plates in a cell. The plates are suspended
Circuit breakers
from the carrier strips into the liquid in the cell. If the resistance of
the terminal to carrier strip welds is too high, the battery’s ability to Due to arcing at the pads of a circuit breaker, carbonized layers can
carry current is limited. In addition to measuring strap resistance, a build up and the live contact area will reduce or become pitted,
low resistance ohmmeter can also be used to measure the quality of leading to increased resistance and heating. This situation reduces
these welds (see Fig 5). the efficiency of the circuit breaker and can lead to failure on an
active transmission system resulting in the loss of a substation. When
planning a test, the user must be aware of IEC62271-100 (minimum
50 A) ANSI and ANSI C37.09 (minimum 100 A) for test current
requirements. When tests are done on large oil circuit breakers, the
best instrument is one that ramps up current, holds it for a period
of time and then ramps down (see "Ramp testing" on page 31).
Aircraft assembly
Cement plants and other raw Over time, the bonding of static wicks, antenna, control linkage
material processing applications and battery terminals must be inspected. The integrity of a welded
exhaust system should also be checked and documented.
The electrical system at a cement plant or other raw materials
In normal operations, excessive static electricity will not effect the
processing facility includes motors, relays, disconnect switches,
operation of most navigation and communications systems. The
etc. Tests of these power carrying elements, as part of a regular
best (lowest) resistance connections will improve the performance
program or when major retrofits take place, is critical to the ongoing
of such systems.
operation of the plant. The quality of the current connections can
identify weak elements or connections in the system.
source of power for the engine, and power lost across a high resistance
bond (such as a poor Cadweld joint) reduces the efficiency of the transit Welding spot or seam
system. The user can select a five foot section of track without a bond,
make a measurement and then measure a five foot section with a bond The quality of a spot weld can be determined by measuring the
to determine the quality of the connection. As a rule of thumb, these resistance across the joined materials. The quality of a seam weld can
measurements should be within a few microhms (or ±5%). be determined by a series of tests along the weld seam. Readings
should stay within a narrow band of values. An increase and then
Graphite electrodes a drop in readings shows that the uniformity of the weld is out of
specification. To make the measurement correctly, the user should
Graphite electrodes have a negative temperature characteristic (as the fabricate a fixture to keep the probes in a fixed relationship. Readings
temperature of the element increases the resistance measurement will are then taken at a number of points across the weld seam and
decrease). Graphite slugs are extruded as large diameter cylinders and plotted (see Fig 7). These measurements are normally in the microhm
can be up to six feet in length. One of the applications for these large region and special care is required in the design of the test fixture.
Low resistance tests are done as a quality control step to check the
density of the graphite extrusion. Due to the size of the electrodes, this
test requires a special test fixture to introduce the test current across
the surface of the ends, ensuring a uniform current density through the
volume of the sample. The potential probes are then connected across
a known length of the sample to determine the 'ohms per unit length'
(see Fig 6).
Fig 6: Test on graphite slugs for uniform density (ohms / inch)
www.megger.com 9
Measuring cable resistance of
multicore cables of at least 3 cores
When measuring cable resistance, the standard method is to connect
the current and potential lead at each end of the cable core to be tested
(see Fig 9).
A reel of insulated copper wire may have a tag, which shows the wire When the cable is too long to use extension test leads or passes through
gauge along with the ohms per unit length. When wire remains on the the floors of a building, the above method cannot be used. However,
reel after partial utilization, the remaining length can be calculated by there is a way to configure the test leads to accurately measure the
measuring the resistance of the wire and making a calculation using the resistance of each core of the cable with the DLRO positioned at one
ohms per length specification (see Fig 8). end of the cable to be tested. The current and potential test leads must
be connected individually and not as a single kelvin type connection.
Alternatively, if the tag has been destroyed, the user can cut off a
Step 1: Connect the current and potental leads C2 and P2 to the core
known length of wire, measure that sample and determine the ohms
under test. In Fig 10 it is the core with the blue marker.
per length. This value can then be used with the reading taken when
measuring the balance of wire on the reel to calculate the remaining Step 2: Connect the current lead C to an adjacent core. In Fig 11 it is
length. The temperature of the reel of cable will be approximately the unmarked core.
the same as the temperature of the sample. Though the internal
Step 3: Connect the potential lead P1 to the other core. In Fig 12 it is
temperature of the reel can be slightly different, a reasonable estimate
the core with the red marker.
of the remaining length of cable can be calculated. If the user reviews
the temperature charts in "Effects of temperature" on page 26, an
estimate of the inaccuracy can be determined. This method also applies
to aluminum and steel wires as long as the wire has an insulating
coating to prevent shorting between adjacent loops of wire.
Fig 13: The other end of the cable shows the unmarked core
carrying C1 connected to core with the blue marker (the core
to be tested) and the core with the red marker carrying P1
connected to core with the blue marker (the core to be tested)
the connections with short jumper cables
Using the simple configuration (see Fig 13) shows that the resistance
of long multi-core cables can be measured by using 2 cores of the cable
as part of the measuring circuit.
When bus bar lapped joints or terminal lugs are overtightened, the
material of the joint becomes dished and instead of becoming a better
connection the resistance starts to increase as the surface area contact
becomes distorted. This is why each joint and connection in a system
normally has a manufacturer’s torque setting.
But that’s not the whole story. If the joint has some contamination
when it is tightened to its torque setting, the higher resistance may go
undiscovered and the connection begins a journey on the downward
spiral to overheating, arcing and eventual failure.
Fig 12: P1 connected to another core on the same end of the resistance of the joint is at its optimal value before being made live and
multi-core cable put to work.
www.megger.com 11
Single bolted connections have always had issues with the relationship
between tightness and optimal surface area contact.
The measured value will include the test lead wire resistance and contact
probe resistance values, which will affect the measurement by adding
some tens of milliohms to the actual resistance. In most instances this
will make little practical difference to the measured value, but when the
measurement is below 1 ohm the two wire method can easily introduce
an error, which could be several percent, into the measured resistance
Fig 18: Simplified example of a 4 wire measurement
value.
The specifications on some hand held meters show a 200 milliohm D.C. vs. A.C.
range with one milliohm sensitivity. The lead resistance can be zeroed The issue here is the selection of the correct type of test current. A d.c.
out, but that leaves the uncertainty of the contact resistances, which instrument should be used when trying to measure the pure resistance
can change with each measurement. Contact resistance values can of a circuit or device. An a.c. instrument is used for applications such as
be in the 35 milliohm range at each probe and can vary with the ground bed tests or impedance tests.
temperature of the material under investigation.
A special impedance meter is used to do tests on industrial batteries.
The two wire test method is best used for readings above 10.00 ohm The word impedance is used to show that a measurement comprised
up to 1.0 to 10.0 megohm. of a resistance and reactance, which can be either an inductive or
capacitive component. These measurements are conducted as
part of a battery maintenance program; typically a low resistance
Three wire measurements
ohmmeter is used to do strap connection verification tests.
Three wire d.c. tests are reserved for very high resistance and is typically
Three or four wire a.c. measuring systems are used to do
used for measurements above 10 megohms. We normally associate
tests on 'ground beds' with special frequencies that exclude
these types of tests with diagnostic insulation resistance. The test
measurement errors from 50 / 60 Hz ground currents. The use
method uses a third test lead as a guard, and allows for resistances, in
of a.c. prevents the test current polarizing ions in the soil,
parallel with the test circuit, to be eliminated from the measurement.
thereby changing the conditions and thus the measured
This parallel resistance is usually considerably lower than the insulation
values. This is an area of interest to the electrical power
resistance being measured. In fact it can, in severe cases, effectively
distribution and telecommunication fields. The low
short out the insulation resistance such that a meaningful measurement
ground resistance path is required for maintaining the
cannot be carried out without the use of a guarding circuit.
potential of the ground wire to the 'earth' potential.
Electrical performance of the power system
This test method is described and illustrated in the Megger booklets
minimizes shock hazards as a path to ground is
'A Stitch in Time' and 'A Guide To Diagnostic Insulation Testing Above
made available for the energy from lightning and
1 kV'.
other static voltages that can affect the power
control system. The same conditions pertain
Four wire measurements to the telephone systems, as high resistance
grounds can cause excessive noise on the
Four wire tests are the most accurate method when measuring
voice and data links (see the Megger
circuits below 10 ohms as this method eliminates errors due to lead
booklet 'Getting Down to Earth' for more
and contact resistances. This is the test method associated with low
information on ground resistance tests).
www.megger.com 13
Both of these industries require not only low ground bed resistance but
10 amp models
also low resistance 'a.c. / d.c. bonds' between the ground bed and the
active circuits.
Normal Mode: The user connects all four test leads and presses the
test button on the instrument to start a test. The instrument checks the
The difference between continuity continuity of the test connections and then applies forward and reverse
and low resistance current. The reading is shown for a short period (10 seconds).
In basic terms, continuity shows us that we are connected to both ends
of the same cable. This is normally done as a 2-wire test with a resistance Auto Mode: Allows forward and reverse current measurements to
measurement of 10 mΩ or above. In many cases, this is acceptable for be made (the average value is shown) by making contact with all four
a value to be recorded on certification. But it is worth bearing in mind probes. Each time the probes are removed and reconnected to the load,
that continuity can also be proved with an indication such as a buzzer another test is done. This mode, which is similar to the Continuous
or test lamp. Mode found on older instruments, is an excellent time saving method
to use when battery straps are tested with hand-spikes. It has the added
Low resistance measurements can start at 0.1µΩ, often revealing advantage, when hand-spikes are used, that the contact detection
connection issues with joints and contacts which can prove to be points sensing ensures good contact before heavy currents are applied. This
of failure in waiting. This test uses the 4-wire test method which is avoids arcing when contact is made, which erodes the probe tips as well
not susceptible to test lead or probe / clip connection resistance to the as potentially damaging the surface of the item under test.
device under test as it can be on the continuity 2-wire method.
Continuous Mode: Allows repeated measurements to be made on
Test modes the same test sample. Once the test leads are connected and the test
button pressed, a measurement is made every set number of seconds
Digital low resistance ohmmeters designed in the 1970s and 1980s
until the circuit is broken.
tended to offer two modes of operation, each designed for specific
applications. Recent microprocessor technology has allowed newer Unidirectional Mode: Applies a current in one direction only. While
instruments to include additional modes, further extending the this type of measurement does not negate standing emfs, it does speed
capabilities of these models. The following is a brief review of the types up the measuring process. In many test conditions, such as battery
of test modes available on different vintage instruments: straps tests, it is not necessary to do a reversed current test on the
sample. This mode is also used when objects with inductive properties,
Models designed in the 1970s and such as motors and transformers, are tested.
1980s
100 amp and above models
Continuous Mode: Allows the test current to flow and a measurement
taken when the current and potential probes contact the test specimen. Normal Mode: The user connects all four test leads and presses the
This mode of operation is usually implemented when the helical spring test button on the instrument to start a test. The instrument checks
point lead sets are used and is the normal method when conducting the continuity of the test connections and then applies the test current.
field tests. Battery life is extended, as the test current flows only when
Continuous Mode: Used to monitor test conditions for a period of
the tests are in progress.
time. After the test leads are connected and the test button is pressed,
Momentary Mode: Requires both sets of test leads to be connected to tests will be recorded every set number of seconds until the test button
the specimen. The measurement is done when the switch is toggled to is pressed again or contact is broken with any of the test probes.
the Momentary position. This mode of operation is used when separate
Auto Mode: Because of the heavy test currents used, the user connects
current and potential leads are connected to the specimen.
the current leads, selects the desired test current and presses the test
button. As soon as the potential leads are connected, a test will start.
To make another test, the user breaks contact with the voltage probes
and then remakes contact. This is an excellent mode for measuring
individual joints in a bus bar.
www.megger.com 15
Use and misuse of low resistance To be compliant with circuit breaker standards, a minimum 50 A
ohmmeters (IEC) and 100 A (ANSI) is required when performing low resistance
The effective operation of a low resistance ohmmeter relies on the user measurements.
using the correct test leads. Battery operated instruments are designed
In circuit breakers, contaminations have been seen that influences the
for a specific lead resistance, based on the operational life of the test
results to a higher value than what can be expected. By using a high
sequence. The specified leads allow for a reasonable current drain from
current, it breaks through the contamination and by that the user gets
the power supply for the test cycle. If leads with a higher resistance
the correct value.
are used, the current used for the test can be lower than the meter
requires, potentially causing a signal-to-noise problem that can reduce Instruments designed specifically to test transformers have a special
the accuracy and / or repeatability of the measurement. high voltage power level at the start of a test, to saturate the winding.
These instruments then switch to a lower constant current mode to
If leads with lower than the specified resistance values are used, the test
measure the winding on the transformer.
cycle for the instrument will be shorter than anticipated. This situation
may be suitable if the meter is to be used in a test program with high It is also important that the instrument discharges the transformer
background electrical noise. The use of special leads with shielding can when the measurement is completed. If not, lethal voltages can be
also be a solution for these high noise situations. present at disconnection. Dedicated test instruments with these
features integrated are available.
A common error in the field is to use a low resistance ohmmeter to
sample the resistance of a ground bed. This application is incorrect, as Warning: Never use a non-dedicated LRO to measure the winding
the ground bed test method requires an instrument that toggles the resistance on a power transformer, since lethal voltages can be present if
test signal at a known frequency and current level. A low resistance a winding is not discharged correctly before the leads are disconnected.
ohmmeter used in this application will provide an erroneous reading as
the ground current will have an undue influence on the measurement. Probe and lead selection
The potential and current leads are either connected separately or to
A genuine ground tester works in essentially the same way as a low
a probe. When probes are used the potential connection is identified
resistance ohmmeter, that is, by injecting a current into the test sample
with a P. The connections are placed in contact with the sample so
and measuring the voltage drop across it. However, the earth typically
that the P-identified contacts or leads are positioned towards each
carries numerous currents originating from other sources, such as the
other. The current contacts are then positioned outside or away from
utility. These will interfere with the d.c. measurement being taken by a
the potential connections. This causes the current to flow with a more
low resistance ohmmeter. The genuine ground tester, however, operates
uniform current density across the sample being measured.
with a definitive alternating square wave of a frequency distinct from
utility harmonics. In this manner, it is able to do a discrete measurement, For the more rigorous tests, separate test leads are used and the current
free of noise influence. connections are positioned away from the potential connections by
a distance that is 1.5 times the circumference of the sample being
Current selection measured. ASTM Standard B193-65 provides guidelines for making a
Depending on the selected instrument, the current selection can be measurement that will establish uniform current density. This standard
either manual or automatic. The user should select the highest current suggests separating the current probes from the potential probes by
suitable for the test to provide the best signal to noise ratio for the 1.5 times the cross sectional perimeter of the test specimen. Fig 20
measurement. On instruments that offer current levels in excess of 10 A, on the following page shows a test being made to the standard on a
care is required to minimize any heating of the sample that would itself cylindrical test item.
cause the resistance of the sample to change.
The use of probes, Kelvin Clips, or C-clamps will meet most field
Instruments designed to test circuit breakers have much higher current requirements as the user should be making repetitive measurements
characteristics. For high current paths, like overhead line joints, bus bars under the same conditions. The sharp points on the probes should
and circuit breakers, it is important to make the measurement with the leave a mark on the specimen for future tests. In some situations a
highest current possible, to be able to detect degraded current paths. marker pen can show the test area and the probe positions will be
Phenomena called 'hot spots' heat up the current path at high currents identified by the probe indents.
and the heat increases resistance even more, which makes the situation
Leads are available in a number of lengths to meet different field
worse. This problem needs to be detected before it happens within
application requirements. The probe selection is made from separate
nominal currents and creates a problem.
10 Amp micro-ohmmeter
The field portable micro-ohmmeter with a 10 A
maximum test current is the 'work horse' instrument
Fig 21: Probe / lead configurations
for most users because it covers the majority of field
applications. The 10 A output not only provides
Low range tests
a comfortable and suitable test current through
When measuring on the extreme edge of precision and sensitivity,
the test sample to make the measurement, but
factors that would be too small to be of consequence in conventional
also allows for reduced weight and improved
tests, become significant.
battery operation.
In low resistance tests, thermal emfs (electromotive forces), also
known as Seebeck voltage, can produce voltage gradients across the
test sample. Although only on the millivolt level, and of little or no
influence on common multimeter tests, these can cause fluctuations
www.megger.com 17
The best 10 A micro-ohmmeters offer measurements from 0.1 microhm In addition to circuit breakers, electrical utilities and test companies
to 2000 ohms with a best resolution of 0.1 microhm at the low end of use higher current micro-ohmmeters on other high voltage apparatus,
the range and accuracy of ±0.2%, ±0.2 microhm. On some instruments, including:
different measurement modes can be selected which address different
■■ Cables
types of test conditions. Measurement modes could include manual,
automatic or a continuous test, or a high power test on windings. ■■ Cable joints
■■ Lightning protections
■■ Switch and contact breaker resistance
■■ Welds
■■ Bus bar and cable joints
■■ Bus bars
■■ Aircraft frame bonds and static control circuits
■■ Switchgear in general
■■ Welded joint integrity
When a 100 A (or above) micro-ohmmeter is used, users should be
■■ Intercell strap connections on battery systems
aware of certain technical issues related to tests at high currents. Some
■■ Resistive components (quality control)
users have shown that they do a 10 A test and then see improved
■■ Small transformer and motor winding resistance resistance readings with 100 A (or more) test currents. This difference
■■ Rail and pipe bonds in the measurements raises the question of whether there is a need for
additional maintenance. A strict reading of Ohm’s Law does not indicate
■■ Metal alloy welds and fuse resistance
the need for the higher current to do the measurement. In the equation
■■ Graphite electrodes and other composites R = V/I, the magnitude of the current is not defined. Is this a situation
■■ Wire and cable resistance where the high current is blasting contaminants away from the contacts,
and at the same time welding the contacts together? The user should
■■ Transmitter aerial and lightning conductor bonding
be aware that they could be masking a potential problem in a power
100 Amp and above micro- distribution system and avoiding necessary maintenance.
ohmmeter Users should also be aware that high current meters are intended to be
According to IEC62271-100, a test of the contact resistance of high used at high currents. Their accuracy may reduce considerably at low
voltage a.c. circuit breakers calls for a test current with any convenient currents, particularly when measuring small resistances.
value between 50 A and the rated normal current. ANSI C37.09 specifies
that the test current should be a minimum of 100 A. Most electrical
Nominal vs. absolute test current
utilities prefer to test at higher currents, as they believe this is more
levels
representative of working conditions.
Battery operated digital low resistance ohmmeters have different test
Field portable micro-ohmmeters are available that can deliver anywhere currents, which are a function of the selected range. The lowest range
from 100 A up to 600 A (subject to the load resistance and supply has the highest current level and as the range increases the current
voltage). The best instruments have measurement resolution to 0.1 decreases. As the range increases by a factor of 10, the test current will
microhm and offer variable test current to address a wider range of decrease by a factor of 10. This action allows for a balance of weight
applications. If a test is done at 10 A and then at a higher current, the and function; if the current were to increase as the range increases, this
user can get a better understanding of the maintenance requirements field instrument would lose much of its portability, and its usefulness for
for the circuit breaker. field tests would decrease significantly. In power plants, substation and
distribution sites, the test equipment is exposed to interference from
As previously stated, in circuit breakers, contaminations have been seen high currents generated in the area. The user will have to determine
that influence the results to a higher value than what can be expected. the test current level to provide the most accurate and repeatable
By using a high current, it breaks through the contamination and by that measurements.
the user gets the correct value.
www.megger.com 19
Suppose the instrument is rated at IP42. A moisture rating of 2 means
'dripping water'. Therefore, it would not be resistant to flying spray. An
Evaluation / interpretation
instrument which is used in an environment that exceeds its IP rating of results
likely means that the user will need a new instrument very soon. What
about a rating of IP40? A moisture rating of 0 means that the instrument Repeatability
is not protected against any liquid ingress. A good quality low resistance ohmmeter will provide repeatable readings
within the accuracy specifications for the instrument. A typical accuracy
The following tables provide a guide to various IP ratings and what they
specification is ±0.2% of reading, ±2 LSD (least significant digit). For a
mean to the user:
reading of 1500.0, this accuracy specification allows a variance of ±3.2
Table 2: Ingress and access protection (0.2% x 1500 = 3; 2 LSD = 0.2).
First No. Description
Additionally, the temperature coefficient must be factored into the
0 Non-protected
reading if the ambient temperature deviates from the standard
1 Objects equal to or greater than 50 mm
Protected against access with back of hand calibration temperature.
2 Objects equal to or greater than 12.5 mm
Protected against access with jointed finger
3 Objects equal to or greater than 2.5 mm
Spot readings / base expectations
Protected against access with a tool for readings
4 Objects equal to or greater than 1 mm Spot readings can be very important in understanding the condition
Protected against access with a wire
of an electrical system. The user should have some idea of the level of
5 Dust protected
the expected measurement based on the system’s data sheet or the
6 Dust tight
supplier’s nameplate. Using this information as a baseline, variances can
Table 3: Ingress of liquids protection be identified and analyzed. A comparison can also be made with data
Second Description collected on similar equipment.
No.
0 Non-protected As noted, the data sheet or nameplate on a device should include
1 Water dripping vertically electrical data relevant to its operation. The voltage, current and power
2 Water dripping, enclosure tilted up to 15° requirements can be used to estimate the resistance of a circuit, and the
3 Spraying water, up to 60° angle from vertical operating specification can be used to determine the allowed change
4 Splashing water, any direction
in a device (for example, with battery straps, connection resistances
5 Jetting water, any direction
will change with time). Various national standards provide guidance for
6 Powerful jetting water, any direction
periodic test cycles.
7 Temporary immersion in water
8 Continuous immersion in water The temperature of the device will have a strong influence on the
expected reading. As an example, the data collected on a hot motor
will be different from a cold reading at the time of the installation. As
the motor warms up, the resistance readings will go up. The resistance
of copper windings responds to changes in temperature based on
the basic nature of copper as a material. A more detailed review of
temperature effects is covered in the appendix. Using the nameplate
data for a motor, the expected percentage change in resistance due to
temperature can be estimated using Table 4 for copper windings or the
equation on which it is based.
R(end of test)/R(start of test) the user will get an idea of when the circuit breaker should be pulled for
The following are several examples of where trending can help the user In these and many other systems, time lost to repair defective equipment
make better informed maintenance decisions: may be small compared to the cost of having equipment out of service
for weeks. Periodic tests can avert many problems. Analyzing data
against past results and reasonable standards allows the user to select
the time when corrective work should be done.
www.megger.com 21
The value of a system is in its ability to work on demand. Operations
are predicated on many systems being available at an instant’s notice.
When elements break, production is lost and time is wasted making
emergency repairs. Taking and analyzing periodic low resistance
measurements saves companies money by helping identify problems
before they result in catastrophic failure.
Fig 24: Duplex hand spike being used to perform same test as
shown in Fig 23
When using the current and potential as split test leads there is the ■■ Higher test currents give a better chance of good reliable test
ability to locate faulty components and connections by probing at each results
connection or joint and looking at the increase in resistance. ■■ Bad low current results do not always indicate that a contact
is in a bad state (contamination) or that a good result
An example is measuring the resistance of a cable to lug joint or lug to indicates a good contact condition (hot spots)
bolted connection while still connected to a system.
The International Standards for high voltage Circuit Breaker tests can be
found in IEC 622 7 1 and IEEE C32.09.
In Figs 23 and 24, a kelvin clip is shown connected to a bus bar for the
C2 and P2 connections, although these connections could easily be
Test Current (d.c.)
done using separate clips.
■■ Minimum 50 A (IEC): 100 A (ANSI)
Fig 23 shows a large C1 clip being connected to the end of the circuit
being tested, which in this case is the end of a cable. A single probe Potential sources of error / ensure
tip is being used for the P1 connection to easily probe to the point the
quality results
measurement is required.
The user can compromise low resistance measurements if the wrong test
In Fig 24, a duplex hand spike is being used to perform the same equipment is used or the temperature at the test site is not determined
tests. Roughly the same resistance values will be measured, although and noted on the test data sheet. Before a test, surface preparation can
in practice they will have slight differences due to the current density be critical. Heavy scale or oxide coatings should be removed to expose
difference produced by the different C1 connection point. a clean surface and ensure good current connections.
High currents in low resistance Do not use thermocouple extension wire in place of copper leads as the
measurement material mismatch will produce erratic data that will change as the site
Low resistance measurements are good for identifying resistive temperature varies with the seasons.
www.megger.com 23
measurement and produce an error in the reading. The ideal current
connection injects current above the potential measurement position.
When these points are close to each other the Kelvin clip or C-clamp
connectors are used, injecting current 180º from the potential
connection (see Fig 25).
The test leads are matched to battery operated meters to ensure that
the nominal level of test current will be delivered to the test specimen.
Finally, probes are designed to make electrical connection with the test
sample. They are not intended to be used to clean surfaces, open tins,
etc.
Accuracy statements
Linear Spring Points: These probes are designed with spring points, accuracy of the field measurements. An instrument that includes an accuracy
which recess into the handle to allow for unevenness of the surface. notation of +0.2% / ºC should not be used in the field, as its best utilization
They are designed for clean surfaces as they have no 'cutting' action to would be in a laboratory with a constant ambient environment.
Helical Spring Points: The tips rotate and compress into the body of instrument.
the probe, allowing the probes to break through any grease or surface
film, ensuring an accurate measurement. Additionally, these probes will Interference
leave a mark on the test surface to identify the points where the test
was done. Care should be taken when using these probes if the surface A strong electrical field, flux linkage from a high current circuit or voltage
being contacted is sensitive to pressure points. induced from a high voltage conductor can cause interference at the test site.
In addition ground currents can induce noise on a conductor. Interference
C-Clamps: A current passes through the C-clamp and screw thread
can reduce sensitivity and produce unstable readings. An instrument with low
while the potential passes through a four point anvil insulated from the
noise rejection, or hum attenuation may be stable when tested on the bench,
clamp metal.
but be erratic in selective field conditions.
The output current delivered by the instrument is not critical, as the In most field applications the user determines the suitability of a field
instrument will be measuring the actual test current at the time of measurement against a pre-selected specification. In most cases,
the test. However, the instrument must be able to deliver sufficient these specifications have been generated from the following formula
current to produce a clear signal in the presence of typical noise. A (at 20 ºC (68 ºF)):
A de-energized test specimen provides a stable platform on which Copper (annealed) 1.72 0.68 10.4
to make the measurement. Live circuits can produce an unstable test Iron (99.98% pure) 10 3.94 60.2
platform. An example of the latter is the test of battery straps on a UPS Lead 22 8.66 132
Manganin (Cu 84%, Ni 4%, 44 17.3 264
system. The charging and / or discharging currents may induce noise
Mn 12%)
across the battery straps being measured, and at the same time cause Mercury 95.78 37.7 576
the resistance values to increase (due to heating of the strap and its Platinum 9.9 3.9 59.5
connections). Silver 1.65 0.65 9.9
Tungsten 5.5 2.17 33.1
When collecting data, the user must define the test conditions. As
Zinc 6.1 2.4 36.7
noted previously, temperature can have a significant influence on
any measurements made. The user should note the temperature and
document any electrical equipment that is in operation in the test area.
v Electrical Metermen’s Handbook; Third Edition; 1965; page 479
www.megger.com 25
Effects of temperature When making a measurement on a specific material, the user can
calculate the change in resistance due to a change in temperature
Resistance measurements are dependent on temperature. If the original by multiplying the resistance at the reference temperature by the
data was read at one temperature but later tests are conducted at temperature coefficient of resistance and by the change in temperature:
other temperatures, this temperature data is required to determine the
suitability of the measurements. All materials do not react to temperature R2-R1 = (R1)(a)(T2 – T1)
to the same degree. Aluminum, steel, copper and graphite have specific
R1 = resistance of the conductor at the reference temperature
temperature coefficients that will affect the degree of changes that can
take place with temperature at the site of the measurement. R2 = resistance of the conductor when the measurement is made
Low resistance measurements rely on the user conducting the tests T1 = reference temperature
within the operating temperature range of the instrument (the user
T2 = temperature at which the measurement is made
must be aware of field conditions). When the user sees out-of-tolerance
measurements, one of the first steps is to check the instrument’s reading a = temperature coefficient of resistance for the material being tested
with a suitable calibration shunt.
The user should also be aware of operating and storage temperature
As mentioned previously, resistance measurements are dependent on specifications of the instrument they are using to ensure that it is suitable
temperature. The resistance of all pure metals increases with rising for the environment in which it will be used.
temperature. The proportional change in resistance for a specific
material with a unit change in temperature is called the temperature
coefficient of resistance for that material. Temperature coefficients are
expressed as the relative increase in resistance for a one degree increase
in temperature. While most materials have positive temperature
coefficients (resistance increases as temperature rises), carbon graphite
materials have negative temperature coefficients (resistance decreases
as temperature rises).
Copper - Brass 3
Copper - Nickel 10
Copper - Lead - Tin Solder 1-3
Cooper - Aluminum 5
Copper - Kovar 40
Copper - Copper Oxide >500
www.megger.com 27
Hot spots Calibration in the field
Calibration of low resistance ohmmeters can be checked in the field
Hot spots from degrading contact inhibits the contacts ability to carry by the use of a shunt. Calibration is done using individual current and
nominal or overload currents and, dependant on the severity of the potential 12-gauge copper leads, to ensure correct current distribution
contact state, this can result in temperature rises. through the shunt and an accurate potential measurement. Be aware
that 'test probes' do not provide accurate positioning of the leads to
check instrument calibration. They can, however, be used to determine
the relative calibration of the instrument.
The typical test will show excessive overheating in the coils due to fatigue Large test currents produce large forces on the core and can cause
or corrosion of the internal coil and / or the internal connections. Low damage and generate heat, which will affect the resistance value.
resistance tests on transformers addresses small, medium, large single,
large poly-phase and auto-transformer windings. Tests are done on: It is also important that the instrument discharges the transformer when
the measurement is completed. If not, lethal voltages can be present
■■ Dual windings with the test current connected through the at disconnection. Dedicated test instruments with these features
windings in opposed polarities
integrated are available.
■■ Wye to wye windings with and without a neutral connection;
the leg of the other winding is connected to the potential Warning: Never use a non-dedicated LRO to measure the winding
lead to measure the voltage at the internal connection
resistance on a power transformer. Lethal voltages can be present
■■ Wye to delta windings; a jumper is used to connect the if a winding is not discharged correctly before the test leads are
current from the wye winding to the delta winding (this test
mode reduces the test time) disconnected.
www.megger.com 29
The expected resistance can be calculated by the equation:
In this example:
Expected Rm = 0.958 A
In Fig 33 (lap winding, 24 coils), all the coils are connected in series. the measurement from bar #1 to bar #2 will be the series value of the
two coils. If the test probes are across the open coil, the total resistance
The resistance of each coil will be measured with the resistance of all of of the other nineteen coils will be shown.
the other coils connected in parallel. The primary question for the user is
what constitutes an acceptable reading for a specific coil (Rm) since the
remaining 23 coils in parallel will lower the resistance of the coil being
tested. For this example, we will assume that the resistance of the coil
before insertion into the motor (Rc) was 1 A.
The following are examples of how these target levels are determined:
Example 1: In Fig 36, the user is measuring the resistance (R0) across
a single battery strap (both sides of the terminal). The straps on
each side of the terminal have a resistance of 20 microhm and the
connections to the terminals each have a resistance of 5 microhm.
Under these conditions, the target resistance that the user wants to see
is 15 microhm. A significant variance from this resistance in the actual
reading would show a loose connection.
Fig 37: Parallel strap resistance target
www.megger.com 31
Protection relays are also sensitive to the a.c. ripple, which can exist knowledge of the values of the ratio resistors and the adjusted value of
within the output current of the test equipment. These small ripples the rheostat arm. The basic formula is:
can look like a potential fault, for example, a.c. signal and also trip the
X = B/A x R
Circuit Breaker under test.
Where:
Is this a reason to keep these relays in place?
Wheatstone and Kelvin bridges The Wheatstone Bridge can be constructed to a variety of ranges and
A Wheatstone bridge can be used to measure resistance by comparing is generally used for all but the highest and lowest measurements. It's
an unknown resistor against precision resistors of known value. A Kelvin suited to a range of about 1 to 100,000 A.
double bridge is a variant of the Wheatstone bridge and can be used for
measuring very low resistances. Kelvin bridge
The Kelvin Bridge (also known as the Thomson Bridge) is used for
Wheatstone bridge
precision measurements below the typical range of the Wheatstone
A pioneering method for measuring resistance was devised in 1833 by Bridge. Sir William Thomson (Lord Kelvin) devised the concept circa
S. H. Christie and made public by Sir Charles Wheatstone. The simplest 1854. The classic arrangement has six resistors in a rectangle, bisected
arrangement is a square pattern of four resistors with a galvanometer by a galvanometer (see Fig 39). A comparatively large current is passed
connected across one diagonal and a battery across the other (see Fig through the unknown resistance and a known resistance of a low
38). Two of the resistors are of known appropriate values and comprise value. The galvanometer compares the voltage drops across these two
the ratio arm (A + B). A third has a known value which can be varied in resistances with the double ratio circuit comprised of the other four
small increments over a wide range, and is thus designated the rheostat resistors.
arm (R). The fourth is the resistance being measured, the unknown arm
(X).
For very low measurements, the Kelvin Bridge has the advantage of
nullifying extraneous resistances from leads and contacts by employing
the system of double ratio arms. The resistances of the connecting
Fig 38: Wheatstone bridge circuitvii
leads are in series with the high resistance ratio arms and not with
The bridge is considered balanced when the rheostat arm has been the reference or tested resistors. The two pairs of ratio resistors (A/B,
adjusted (tweaked) so that current is divided in such a way that there a/b) are paralleled with each other and connected across with the
is no voltage drop across the galvanometer and it ceases to deflect (is galvanometer. One pair (a/b) is in series with the unknown (X) and the
nulled). The resistance being measured can then be calculated from a reference standard (R). The latter is an adjustable low resistance, usually
vii Electrical Meterman’s Handbook; Third Edition; 1965; page 479 viii Electrical Meterman’s Handbook; Third Edition; 1965; page 480
■■ Compressed
Rail, including tram and underground
■■ Crimped
■■ Rolling stock and infrastructure
■■ Soldered
■■ Track high current joints
■■ Conductive adhesive
■■ Signalling systems
■■ Joints subject to
■■ Stress
Marine
■■ Vibration
■■ Power wiring systems
■■ Heat
■■ Protection systems
■■ Cold
■■ Ship-to-shore bonding
■■ Corrosion
■■ Cable
■■ Fatigue
■■ Connection points
www.megger.com 33
Space exploration and engineering Electrical infrastructure
■■ Structural metal to metal ■■ Transformer windings
■■ UPS supplies
■■ Checking assembled connections
■■ Generator supplies
■■ During maintenance
Medical
■■ Grounding and bonding systems for protection against
■■ Microshock
■■ Macroshock
Robotics
■■ Wiring systems and connections which are subjec to stress/
movement/vibration
■■ Grounding of machine
For more information on these and many other Megger products, The DLRO10 displays the average of measurements achieved using
please contact us at 866-254-0962 or. Or visit our web site us.megger. forward and reverse current, while the DLRO10X displays both individual
com for the most up-to-date news, product and service information measurements and the average. The DLRO10X uses a menu system
24 hours a day. controlled by a two axis paddle to allow the user to manually select the
test current. The unit also adds real time download of results and on-
DLRO100 series board storage for later download to a PC.
The DLRO100 offers a unique range of 100 A digital low resistance
testers. Never before has CAT IV 600 V safety, operational IP54
ingress protection for dust and water, and lightweight, fast charge,
Li Ion battery technology been available on a continuous 100 A low
resistance tester.
There are three models in the series, all of which have CAT IV 600 V
and can test currents from 10 A to 110 A. The mid-range model adds
data storage and DualGroundTM tests. The top of the range model
adds to this, the capability of asset tags to enter unique asset ID’s
with the DLRO100 Asset Tag Windows app, Bluetooth® download
and USB remote operation.
www.megger.com 35
DLRO10HD / DLRO10HDX DLRO600
Common with the DLRO10 series, the DLRO10HD and DLROHDX All the features of the DLRO10 and 10X, plus additional current up to
feature output power limiting to 0.25 W so as not to heat the test piece. 600 A to accommodate the preferred standards to test circuit breaker
However, the DLRO10HD and DLROHDX have the additional benefit of contacts. Yet ease of portability has been retained, with the instrument
combining this with two high power, high compliance ranges. Benefits weighing in at only 33 pounds!
include the ability to use much longer test leads, the ability to heat and,
Measurement range from 0.1 millohm to 1 ohm facilitates all standard
therefore, identify circuit weakness and the ability to maintain 10 A for
high current requirements. Memory stores up to 300 results while an
at least a minute, which allows for improved tests on inductive loads. In
RS232 connection enables downloading to printer or laptop. The added
addition the DLRO10HDX comes with on-board memory for up to 200
data manipulation capabilities enable current limitation at standard
test records and the ability to download saved test results to external
values up to 600 A, thereby eliminating the need for multiple testers to
software.
conform to a variety of standards.
The unique design allows the weight and size of the DLRO200 to be
kept to a minimum; the instrument weighs less than 14.5 kg (32 lbs).
This small size plus a water / dust ingress rating of IP54 makes the test
set equally at home in the workshop, on the production floor or in the
field.
MOM2 avoids problems with incorrect test results due to low test current when
The MOM2 micro-ohmmeter is designed to measure the resistance of high current devices such as circuit breakers are tested. It can also do
circuit breaker contacts, bus bar joints and other high current links. true d.c. ripple free current tests of bus bars, circuit breakers, fuses, etc.
MOM2 uses an ultra capacitor to generate the high output current. Use the MJÖLNER600, with excessive power resources for demanding
The ultra capacitor is able to store a huge amount of energy compared applications, for superior measurement accuracy and when 300 A
to conventional capacitors and can deliver very high current during the continuous is required.
www.megger.com 37
With its lightweight and rugged suitcase design, it makes the
MOM200A / MOM600A
MJÖLNER200 and MJÖLNER600 an excellent choice when a portable
The MOM200A™ is designed to check and measure contact resistances
solution is needed. When the case is closed, the product can withstand
in high voltage circuit breakers, disconnecting switches (isolators) and
the impact of water, dust or sand – it even floats.
bus bar joints. It is an excellent choice when 200 A or less are needed
for measurement.
Optional accessories are a remote control and PC software.
The MOM200A is ideal for finding poor connections, since it can put
MOM690A out 100 A for extended periods. Its range, extending up to 20 millohm,
The MOM690A supplements Meggers family of micro-ohmmeters. In makes it ideal for measuring many different types of connections, and,
addition to high current capacity, the MOM690A features microprocessor with its weight at 14 kg (31 lb), it's convenient to take along with you.
based measurement, storage and reporting. The built-in software enables
individual tests or a whole series of tests and store the results. The MOM600A, with output current between 100 and 660 A, comes
in two versions, a 115 V and a 230 V.
With the optional MOMWin™ software test results can also be exported
to a PC for further analysis and reporting. Ranges are set automatically, A complete MOM200A and MOM600A includes a cable set (including
resistances are measured continually and test results an be automatically separate sensing cables) and a transport case.
BT51
Where economy and simplicity of operation are paramount, the
Megger DUCTER BT51 requires only the setting two position range
switch. Ranges of 2 A and 20 mA are selectable, with 1 millohm and
0.01 millohm resolution, respectively.
Fig 48: MOM690A The instrument operates with a 2 A test current, provides warning
indicators, and is supplied with duplex hand spike leads.
Cat. No. 247000 features the tried and popular dual-pak design, where
the charger is a separate item that can be left behind while the measuring
module affords the maximum in portability. Where self containment is a
premium.
www.megger.com 39
Product comparison chart
Measurement range 2000 mΩ and 1.9999 mΩ - 1999.9Ω 1.9999 mΩ - 1999.9Ω 0 Ω - 250 mΩ 0 Ω - 250 mΩ
20.00 mΩ
Best resolution 1 mΩ 0.1 μΩ 0.1 μΩ 0.1 μΩ 0.1 μΩ
0.01 mΩ
Inaccuracy ± 1% ± 2 digit ± 0.2% ± 0.2 μΩ ± 0.2% ± 0.2 μΩ ± 0.2% ± 0.2%
Ripple free DC n n n n n
Additional smoothing
on DC
DualGround
Ramp up/down
(Automatic)
AC Demagnetization
Remote control
Built in printer
User settable High and n
low test limits
Data storage n n
100 A (10min ) 200 A (15 min) 200 A (15 min) Long test times can help locate weaknesses by
heating
100 mΩ 19 mΩ 11 mΩ 11 mΩ Subtract expected test resistance and you can
calculate max. test lead length
***Power limited to 0.25W for sensitive
applications
0.1 μΩ - 1.999 Ω 0.1 μΩ - 999.9 mΩ 0.1 μΩ - 999.9 mΩ
n
Depending on model
7.9 kg (18 lbs) 14.5 kg (33 lbs) 14.5 kg (33 lbs) 14.5 kg (33 lbs) Weight excluding leads
400 x 300 x 200 mm 410 x 250 x 270 mm 410 x 250 x 270 mm (16 x 410 x 250 x 270 mm Dimensions
(16 x 12 x 7.9 in) (16 x 10 x 11 in) 10 x 11 in) (16 x 10 x 11 in)
www.megger.com 41
Technical Data Mjolner200 Mjolner600 MOM2 MOM200 MOM600A
Test currents 5 - 200 A 5 - 600 A 220 A 0 - 200 A 0 - 600 A
Current steps 1A 1A
Max test time at max 2 min 15 sec 3 sec - discharging 20 sec 15 sec
current
Max continuous 200 A 300 A N/A 100 A (15 min) 100 A
current
Max. resistance for 19mΩ, with cables 2mΩ, with cables 2 mΩ, with cables 17mΩ, with cables 9mΩ, with cables
max. current
Ripple free DC n n n
Additional smoothing
on DC
DualGround n n n
Ramp up/down n n
(Automatic)
AC Demagnetization
Remote control n n n
Built in printer n n
Battery operated n
CAT rating *
External voltage
protection
Noise immunity spec
Dimensions 486 x 392 x 192 mm 486 x 392 x 192 mm 217 x 92 x 72 mm 280 x 178 x 246 mm 356 x 203 x 241 mm
(19 x 15 x 7.6 in) (19 x 15 x 7.6 in) (8.5 x 3.6 x 2.8 in) (11 x 7 x 9.7 in) (14 x 8 x 9.5 in)
100 A (10 min) Long test times can help locate weaknesses by
heating
With cables, 600A 0,5mΩ Subtract expected test resistance and you can
calculate max. test lead length
***Power limited to 0.25W for sensitive
applications
0 μΩ - 200 mΩ
1.0 μΩ
± 1% + 1 μΩ
www.megger.com 43
NOTES
www.megger.com 45
Guide to low resistance testing_en_V01
Copyright © 2017
866-254-0962 • www.megger.com