Professionnel Documents
Culture Documents
2. AS PER THUMB RULE SHORT CIRCUIT CURRENT OR FAULT CURRENT SHALL NOT MORE THAN 50% OF FULL LOAD CURRENT.
3. DIFFERENTIAL PROTECTION CAN WORK UP TO BELOW OR EQUAL OF 50 AMPERE FAULT CURRENT AND SAVE GENERATOR FROM FAULT
CURRENT.
4. IF VALUE OF FAULT CURRENT IS ABOVE 50 AMPERE THAN MANUFACTURE RECOMMENDED NGR REQUIREMENT TO MAINTAINED
GENERATOR UNAFFECTED.
5. HERE ISC OR FAULT CURRENT IS: ISC = 50% * IFL = 0.5 * 225 AMPERE = 112.5 AMPERE.
7. CONCLUSION: - MORE THAN 50 AMPERE FAULT CURRENT MANUFACTURE RECOMMENDED NGR REQUIREMENTS IN THIS PROJECT.
NOTE: - LOGIC MAINTAINED FAULT CURRENT MORE THAN CAPACITIVE CHARGING CURRENT IN GENERATOR SYSTEM.
PREPARED BY: ENG. NADEEMUDDIN / SENIOR ELECTRICAL ENGR. “(KHATIB & ALAMI) MODA