NGR NEED STUDY: ---

1. IN POWER PLANT SYSTEM FULL LOAD CURRENT IS = IFL= 225 AMPERE.

2. AS PER THUMB RULE SHORT CIRCUIT CURRENT OR FAULT CURRENT SHALL NOT MORE THAN 50% OF FULL LOAD CURRENT.

3. DIFFERENTIAL PROTECTION CAN WORK UP TO BELOW OR EQUAL OF 50 AMPERE FAULT CURRENT AND SAVE GENERATOR FROM FAULT
CURRENT.

4. IF VALUE OF FAULT CURRENT IS ABOVE 50 AMPERE THAN MANUFACTURE RECOMMENDED NGR REQUIREMENT TO MAINTAINED
GENERATOR UNAFFECTED.

5. HERE ISC OR FAULT CURRENT IS: ISC = 50% * IFL = 0.5 * 225 AMPERE = 112.5 AMPERE.

6. HERE FAULT CURRENT IS GREATER THAN 50 AMPERE, WHICH IS 112.5 AMPERE.

7. CONCLUSION: - MORE THAN 50 AMPERE FAULT CURRENT MANUFACTURE RECOMMENDED NGR REQUIREMENTS IN THIS PROJECT.

NOTE: - LOGIC MAINTAINED FAULT CURRENT MORE THAN CAPACITIVE CHARGING CURRENT IN GENERATOR SYSTEM.

KNOW THE THINGS:--

1. IFC = FAULT CURRENT =?

2. ICCC= CAPACITIVE CHARGING CURRENT =?

3. IFL = FULL LOAD CURRENT?

4. FAULT CURRENT LIMITATION BY STANDARDS?

5. DIFFERENTIAL PROTECTION WORK LIMITATION?

6. NGR CAPACITY REQUIREMENT WITH CALCULATION PROOF?

7. RELATION BETWEEN FAULT CURRENT AND CAPACITIVE CHARGING CURRENT?

PREPARED BY: ENG. NADEEMUDDIN / SENIOR ELECTRICAL ENGR. “(KHATIB & ALAMI) MODA