Document Name: POWER LOAD & BATTERY CALCULATIONS

Project:

Equipment: Fire Alarm Control Panel-


Battery Size in Ampere-Hours = [Battery Derating Factor] x [{Standby Current x 24} + {Alarm
Current x 30/60}]

Equipment Tag No. = MFACP-MAIN PANEL CPU#1 ###


Minimum battery size, Amp.-hrs 11.8974 ###
Total standby current, amperes 0.401 ###
Total alarm current, amperes 0.581 ###
Power Supply/Riser P1/R1 P1/R2
Quantity Main Power Supply
No. of hours standby, hours 24 Hours
Alarm condition, minutes 30 Minutes
Battery Derating Factor 1.2
Standby Alarm Module P1/R1 P1/R2
(mA) (mA) Model No. Qty Qty
115 115 SFSI-CPU 1 ###
70 70 3X-FIB8 ###
98 98 3-RS485, not required on 3X ###
60 60 MN-COM1S ###
98 98 3X-NET8/3X-NET 1 ###
15.5 16.6 3X-PMI Paging Microphone ###
144 204 3-SDC1 1 ###
38 50 4X-LCD 1 ###
144 204 3-SSDC1 ###
264 336 3-SDDC1 ###
62 1120 3-ZA20A ###
62 62 3-ZA20A (Standby Unit) ###
62 2480 3-ZA40A ###
62 62 3-ZA40A (Standby Unit) ###
44 44 3X-ETH1 ###
112 112 3-ASUFT ###
80 80 3-ASU/CHAS4 ###
60 95 3-MODCOM/P ###
64 5540 3-ZA95 ###
64 64 3-ZA95 (Standby Unit) ###
500 500 FSB-PC Gateway ###
200 200 X-20 Gateway ###
105 105 3-FIBMB2 ###
79 79 SMXLO2/SMXHI2 ###
20 20 MMXVR ###
0 0 CLA-PS10 ###
144 144 3-ANNCPU3 ###
10 10 3-ANNSM ###
5 5 3-LDSM ###
2 38 LED/Switch Strip 3 ###

Total Battery Requirements = 11.8974 AH


Battery Size Provided for = AH

Prepared by: