Académique Documents
Professionnel Documents
Culture Documents
Training Manual
[Revision (0), July 1998]
Prepared by :
J.K.Goyal S.P. Joshi
Sr. Trg. Officer SO/E
Checked by :
P.K. Dutta T.S. Marwaha
SME(E) Head (F&IS)
Reviewed by :
O.P. Goyal J.P. Moolani
Maint. Supdt. Trg. Supdt.
Contents
Chapter-8 : Glossary
Glossary .................................................................................... 59
???
Electrical Safety Electrical Authorisation 1
ELECTRICAL SAFETY
1.1 INTRODUCTION
Safety is the most important aspect of any electrical job. Every one who
works on or around electrical equipment must know what the dangers
are and what steps can be taken to make sure that all personnel are
protected from these dangers.
The current level is greatest when voltage is high and resistance is low.
The max. current value is limited by the third factor. The current capacity
of the source. Touching an energized spark wire having voltage of
30000 V will result in a shock but not a dangerous one because the
current capacity is not there. Whereas touching a 30V battery with a
high current capacity can result in death if body resistance is low
enough. In general any current source at 30V or more must be
considered dangerous.
From the above it is clear that 1 mA or less is not even noticeable to most
people. This very low level does not even cause a shock. Shock can
generally be felt from current in the range of 1 to 20 mA. There may be
some loss of muscular control, so that the victim may not be able to let
go off the source. A current of 20-50 mA will cause a painful shock, with
muscle contractions and breathing difficulties. As current continues to
increase, so do the pain and contractions. At approximately 100 mA, the
heart goes into ventricular fibrillation can uncoordinated libration of the
heart muscle and death will occur unless prompt medical treatment is
given. Above 200 mA, flesh begins to burn, and muscles contractions
are severe that the chest muscles squeeze the heart, stopping it for the
duration of the shock. These faults are more frightening when note is
taken that the highest current value given is only one fifth of an amp.
Sometimes people survive a shock by sheer luck and sometimes they
don’t.
1.4 GROUNDING
Grounding practices have one paramount aim. It is to prevent any
potential difference from being applied across any part of a human body.
The ground connections constitute a system from the stand point of
safety of personnel and satisfactory operation of the internal and
external power system.
Electrical Authorisation 4Electrical Safety
1.4.2 Caution
When applying portable grounds to isolated apparatus the connection
to the ground tap must be made first and broken last. The grounds must
remain applied throughout the duration of the work.
Some switching locations are remote from the station. At such locations
a permanently installed ground gradient control mat may not be found.
A portable grounding mat may be used to serve the same purpose.
Ground rods are used at remote switching locations so that in case of
current flow in the operating rod of the switch, the potential differences
at the earth’s surface tend to be larger than at the station where a
grounding system exists.
???
Electrical Output System Electrical Authorisation 7
2.0 INTRODUCTION
Input/Output System :
In RAPS power is generated at 21 KV and delivered at 220 KV to grid via 21/
220 KV step up transformer (Main Transformer or Generator Transformer).
For station requirement power is taken from Two sources viz one from grid
via 220 KV/3.3 KV Transformer SSST (SUT) and other from our own
Generator i.e. via 21 KV/3.3 KV Transformer (USST OR UT).
The power received at 3.3. KV is used at various potential levels i.e. 3.3. KV
itself, 415V, 250V DC etc.
Thus, complete electrical system (input & output) of the station can be
categorised as (broadly) :
i. 220 KV system
ii. 3.3 KV system
iii. 415V system
iv. 250V DC system
2.1 2 2 0 K V S YS T E M
In 220 KV system following are the major equipments:
i. Circuit Breakers (CBs)
ii. Disconnect Switches (DS)
iii. Current Transformers (CTs)
iv. Potential Transformers (PTs)
v. Lightning Arresters (LA)
Electrical Authorisation 8Electrical Output System
2.4 A B C B O P E R ATION :
Three methods of ABCB operation are there
(i) Remote electrical,
(ii) Local electrical &
(iii) Local pneumatic.
Electrical Output System Electrical Authorisation 11
automatically in breaker.
(i) All protections which trip the breaker.
(ii) Close & Trip circuit supervision coils
(iii) Control circuit failure alarm
(iv) Low air pressure alarm
Now the OTO for 513-CB-8 to “test close” will be similar to that for 513-CB-
Electrical Authorisation 18Electrical Output System
The main transformer protections are 87, 64, 63 and for USST, the protection
is 87.
Protections for SSST are Differential, phase back up, ground back up and
gas relay. Protections (63).
For Bus A1/B1 & A2/B2 the protections are differential and impedance relay.
Protections for transmission lines are mainly Zone protections (distance
relays).
2.11 ISLANDING
All the transmission line breakers automatically trips at under frequency.
(47.1 Hz) An under frequency. alarming occurs at 47.5 Hz. Now any one or
all of lines breakers can be selected for not to trip at under frequency. with
the help of a blocking switch in CER. With under frequency. Blocking a
particular line (say Udaipur line) can be blocked from tripping. All other lines
will trip at under frequency. where as Udaipur line will not. In that case
Udaipur load will be supplied by station only.
Electrical Output System Electrical Authorisation 19
clockwise direction.
???
3.3 KV/415V & LV System (Part-A) Electrical Authorisation 21
3.1 INTRODUCTION
Circuit breakers are devices that open and close a set of electrical
contacts to interrupt or complete an electrical circuit. Switchgear is a
self-contained, enclosed assembly of circuit breakers and related
components. Both circuit breakers and switchgear serve to protect plant
circuits from various electrical problems. They can be used to switch
power on and off, and they can isolate circuits on which work is being
performed.
All circuit breakers have two main function : (1) switch functions, which
control the opening and closing of electrical circuits and (2) protective
functions, which sense electrical circuit problem and open electrical
circuits automatically. Breakers that are close to the main power source
for a circuit are larger than breakers near the loads, because they carry
more power. For instance, a distribution breaker is responsible for
carrying power to a larger part of the circuit than a load center breaker;
therefore, the distribution center breaker is larger and able to handle a
larger amount of current than a load center breaker.
draws the plunger up and extends the rod that moves the latch
mechanism, tripping the breaker.
or decrease the area through which fluid flows in the dashpot; this
increases or decreases the breaker’s trip time.
movable arc contact and the stationary arc contact. The arc contacts are
more rugged and are made to withstand the heat of the arc. As the
movable arc contact pulls away from the stationary contact, the arc
forms. At this point, the arc can be extinguished.
Most larger breakers carry three-phase AC current. These breakers are
also referred to as three-pole breakers, because they have three sets of
movable and stationary contacts, separated by insulated barriers. The
barriers insure that arcing occurring in one phase does not spread to
other phases or to other breaker components.
3.12 SWITCHGEAR
The term “switchgear” can be used to refer to more than one thing.
Normally switchgear is defined as an assembly of devices that control
electric power and protect machines and circuits.
Switchgear is typically large, free-standing, fully enclosed, and self-
contained. In a switchgear assembly, when circuit problems occur in one
circuit, that circuit can be interrupted and isolated while other
unaffected circuits continue to function normally.
The switchgear assembly resembles a file cabinet; its “drawers” are
called cubicles.
The enclosure protects personnel from contact with the energized parts
inside by isolating the components of the switchgear in separate
sections. Most switchgear assemblies can be divided into three
sections: a front section, which contains circuit breakers and related
instrumentation; a bus section, which contains bus work that distributes
power throughout the assembly; and a cable section, which contains
cables that supply power to the assembly and distribute power to load.
One important feature of the switchgear sections is that the sections are
physically separated from one another by partitions within the metal
enclosure. This separation confines any damage to one section and
prevents it from spreading to other parts of the switchgear.
???
3.3 V, 415 V & LV System (Part-B) Electrical Authorisation 35
(f) Just shift breaker from “In” position towards test position with the
help of Hand lever. Safety latch will remain in “pushed position”.
(g) By “Hand efforts” bring the breaker truck to test position.
(h) Achievement of “test” position will be indicated by release of
“safety latch”.
(i) Again put 4 PST & 250 V DC fuses.
For “vice versa” OTO a similar & reverse order of operations will be
done.
category of breakers are there which can be operated from field only &
that too manually. “Closing spring” charging is through a manual lever.
Example of 3rd category is LP compressor supply breaker.
In all the 415 V breaker, closing is through a stored energy spring.
Now spring is either charged through 250V DC motor or manually
through hand lever. In case of breakers having spring charging motor, a
toggle switch is provided on brk. front in field to switch off the motor
supply. (Unit #2 L&T make brk. this facility is not there).
In the field, each breaker front has got following (i) Test close/Test open
push button. Breaker can be closed or opened in test position. (ii)
Emergency Trip push button - Brk. can be tripped in any case with this
push button. (iii) A toggle switch for charging spring motor ON/OFF. (iv)
“Over load” Reset push button. (iv) Spool mechanism to engage Hand
lever with it so as breaker can be taken from one position to other. (In
case of Unit #1 I.T.E. breaker, a shutter closes this spool as long as
breaker is in closed condition. This prevents breaker position to change
from Rack in / Test / Rack out to each other when it is in closed condition.
4 PST and 250 V DC close and trip fuses are mounted on the back of brk.
cabinet.
4.6 PROTECTIONS
All the 415 V breakers are provided with dual type over current relay.
Apart from this breakers of some imp loads like mod. pump etc. are also
provided with ground fault relay.
Overload Reset is by a push button provided on breaker front.
MCC : Full form of MCC is motor control centre. As stated above 415 V
buses supply comparatively bigger loads directly through breaker.
Motor of 60HP to 300 HP are directly supplied by 415 V buses. Where as
smaller loads (up to 60 HP) are supplied through MCC. MCC in turn is
supplied by 415 V buses through 415 V breaker.
Small loads on all cl-IV, III & II are supplied by MCC. One MCC has got
input supply from any one of class of power. Obviously all loads supplied
by one MCC are on same class of power.
MCC is nominated by English letters A,B,C,D,........... One MCC consists
of many small cells arranged in vertical columns & horizontal rows. Each
cell supplies a unique load. Columns are nominated by english letters
A,B,C, ......, where as rows are by numbers 1,2,3,......... Thus one MCC
Electrical Authorisation 463.3 V, 415 V & LV System (Part-B)
cell address consist of 2 english letters & one number. For example
MCC-CD-5 means MCC is ‘C’ in which ‘D’ column, 5 row cell, is there.
Each MCC cell has got a metallic tag on it, addressing on it to which load
it is supplying to.
(a) Isolator :
This is just mechanical “make & break” of contacts. It has no automation
nor any protection contained in it’s own.
Purpose of isolator is to cut off the supply to MCC cell when
maintenance. is to be done. Isolator has mechanical interlock with MCC
cell door. When isolator is open then only MCC cell door can be closed
or opened.
3.3 V, 415 V & LV System (Part-B) Electrical Authorisation 47
(c) Contractor :
These are contacts which makes & breaks actual supply to load.
Contacts are operated by a 115 V solenoid. It is termed as M contact
also. Types of contactor depends on current rating of load.
(f) Overload :
This is a bimetallic element. Due to over current or overload, it makes/
breaks contact in contactor solenoid circuit.
???
Preventive Maintenance of Breakers Electrical Authorisation 49
Preventive Maintenance of
Breakers
???
Overhauling of Breakers Electrical Authorisation 53
OVERHAULING OF
BREAKERS
after the solvent cleaning. After the breaker is cleaned with solvent, it is
dried off with compressed air.
6.4 CONTACTS
In a three phases breaker, each of the movable arc contacts should
touch its stationary arc contact at the same time when the breaker is
closing. Likewise, the three contacts should separate simultaneously
when the breaker opens. If all three phases do not make or break at the
same time, equipment damage could result. Another important
sequence is that of the arc contacts and the main contacts. Arc contacts
should be the last to open and the first to close.
Three common inspections can be made on the contacts when using a
slow close handle: gap, wipe, and pressure.
Contact gap may refer to two different measurements : (1) any gap that
remains between arc contacts if the three phases are not closing
simultaneously, and (2) the gap that occurs between the movable main
contacts and the stationary main contacts when the arc contacts first
touch or first break. If the gap in any phase is found to vary from the
specified distance, it can usually be corrected by adjusting part of the
movable contact linkage.
Contact pressure is the spring force of the contacts pushing against one
another. If the contacts do not press firmly against each other, the
resulting loose connection could cause arcing or overheating. The
springs holding the contacts together should be checked, adjusted, and
replaced, if necessary, according to the breaker manufacturer’s
instructions.
After overhauling of the breaker megaohmmeter tests are usually
performed on the wiring and conductors inside the breaker to insure that
insulation is per-forming properly. On a three phase breaker, tests
should be made line to load within each phase with the breaker contacts
open; from phase to phase; and from phase to ground. The readings
should be recorded and compared with other maintenance records for
trends of deteriorating insulation.
Electrical Authorisation 56 Overhauling of Breakers
???
Indian Electricity Rules Electrical Authorisation 57
INDIAN ELECTRICITY
RULES
Rule-3 : Authorisation :
1. A supplier or consumer, or the owner, agent a manager of
a mine, or the agent of any company operating in oil field or
the owner of drilled well in an oil field or a contractor for the
time being under contract with a supplier or a consumer to
carry out duties incidental to the generation,
transformation, transmission, conversion, distribution or
use of energy may authorise any person for the purpose of
any or all of the following , namely, sub-rule (2) of rule-36,
cl.(a) of sub-rule (1) of rule-51, cl.(a) of sub-rule (1) and
(Cls. (e) and (f) of sub-rule(2) of rule-64), sub-rule (2) of
rule-110, sub-rules (1) and (4) of rule-121, sub-rule (4) of
rule-123, rule-124 & sub-rule (8) of rule-125.
while it is in operation and shall, before leaving the area in which such
machine is operating, ensure that the supply is disconnected from the
flexible cable which supplies the machine. When any such machine is in
operation, steps shall be taken to ensure that the flexible cable is not
dragged along by the machine.
???
Indian Electricity Rules Electrical Authorisation 61
GLOSSARY
???