Transformer data
Make : ABB
Rated Power Sn : 50MVA
Rated Voltage (primary) : 220 KV
Rated Voltage(secondary1) : 11 KV
DIFFERENTIAL PROTECTION
Alarm
Trip
OVER EXITATION:
Set voltage=110%,k=2
Sl.no Set voltage (%) Injected voltage (%) Calculated time Operated time
1 110 120 43.55 42.76
2 110 125 19.36 19.14
3 110 130 10.89 10.8
4 110 135 6.96 6.93
Sign Sign