Vous êtes sur la page 1sur 48

User manual.

ENG Automatic horizontal sliding car door.


Component: VF7+ CAN Electronic Module. V7.03.08-00

MAN-MU000007DENGTC-06.2019
2
230 V

Optional

0 ?

VF4+ OUTPUT 230 V. AC


SALIDA VF4+ SUPPLY
DO NOT OPEN
THE COVER
ALIMENTACIÓN
5 L1’
230 V
NO ABRIR LA TAPA
L2 1
6 GND
GND 2
7 L2’
L1 3

LANDING FLOOR
ALIMENTADOR DE RELLANO PISO

EMERGENCIA 66
CONTROL VF4+
EMERGENCY 67
26 FLOOR / PISO
SUPPLIER
23 12 V COM

BATTERY
ON 1 BAT BATERIA
OFF 2 ON

INPUTS STANDBY
29
ENTRADAS ESTADO
(yellow / amarillo)

28
FUSE 20A

1 2

ON OFF

VF7+ CAN
12 V 2 Ah
CONNECTION
INPUTS / OUTPUTS

5 - 7 Power Supply
The circuit has been designed to operate with a main supply of 230 V AC (+10%,-15%, 50
or 60 Hz).
The VF7+ CAN incorporates a soft-start system to control the bulk capacitors charge and
prevent short circuits.

Note: It is important that the Door Operator Module has a good earth connection.
PUERTO COM
COM PORT
13 Com Port
13
The serial port is used to connect with external devices, interfaces
and future expansion devices.
Operating speed 1.200 Baud per second, current loop.

21 - 26 Priority Inputs

21. Reopen
This signal may be used to connect the cabin “door open” button, an external barrier or
other devices. In order to activate this signal connect the re-open input (21) with the +12 V
(23). Use voltage free contacts. The reopening signal has priority over the closing signal.

22. Barrier failure


This input is used to detect a failure from the Photoelectric Barrier installed.

23. Out +12 V


Isolated 12 Volts output available to activate the priority inputs via a voltage free contact.
Features are:
a) This supply must only be used for this purpose.
b) This contact must be isolated from any other power supply.

24. Bypass contact


This signal is used to connect an external security switch to detect door closed position.

VF7+ CAN 3
INPUTS / OUTPUTS

25. Slow Close


This signal is used for ordering the door to close slowly. The slow close signal has priority
over the control signals and the barrier. It is designed to operate with fire fighting systems.

26. Floor Level


This input is used to connect the external emergency supplier to power an opening cycle in the
event a power failure when the lift is at a floor level. The Fermator emergency supplier uses a
12V battery, and it is able to provide power for 30 seconds to enable passenger evacuation.

Led indicators
A simple set of colours or modes in the LED indicators helps service personnel to identify
communication problems quickly without raving to check manuals for each status display.

OK status
LED for power indication and extra functionality during the learning
process is used. Blinking green led indicating proper working OK STATUS
conditions. If an alarm occurs the LED illuminates red.

There are two CAN LEDs: one red CAN ERR and one green CAN RUN.
• Indicator status and flash rates
The following Indicator states are displayed:
-- LED on: constantly on
-- LED off: constantly off
-- LED flickering: iso-phase on and off with a frequency of approximately 10 Hz: on
for approximately 50 ms and off for approximately 50 ms.
-- LED blinking: iso-phase on and off with a frequency of approximately 2,5 Hz: on
for approximately 200 ms followed by off for approximately 200 ms.
-- LED single flash: one short flash (approximately 200 ms) followed by a long off
phase (approximately 1.000 ms).
-- LED double flash: a sequence of two short flashes (approximately 200 ms),
separated by an off phase (approximately 200 ms). The sequence is finished by
a long off phase (approximately 1.000 ms).

4 VF7+ CAN
INPUTS / OUTPUTS

• CAN ERR
The CAN ERR LED indicates the status of the CAN physical layer and indicates errors
due to missing CAN messages (Red LED).
No ERROR LED State Description

1 Off No error The device is in working condition.

2 Single flash Warning limit reached At least one of the error counters of the CAN controller has
reached or exceeded the warning level (too many error
frames).
3 Flickering CAN Initialization Initialization of the CAN bus.

4 Double flash Error Control Event A guard event (NMT-Slave or NMT-master) or a heartbeat
event (Heartbeat consumer) has occurred.

5 On Bus Off The CAN controller is bus off.

Table 1: CAN ERR LED truth table

If at a given time several errors are present, the error with the highest number is indicated.
• CAN RUN
The CAN RUN LED indicates the status of the CAN network state machine (Green LED).
No ERROR LED State Description

1 Flickering CAN Initialization Initialization os the CAN bus.

2 Single flash STOPPED The Device is in STOPPED state.

3 Blinking PREOPERATIONAL The Device is in PREOPERATIONAL state.

4 On OPERATIONAL The Device is in OPERATIONAL state.

Table 2: CAN RUN LED truth table

Whilst the device is executing a reset the CAN RUN LED shall be off.

55 Encoder
ENCODER
An integral quadrature pulse encoder is connected to this input. The
purpose of the encoder, which is situated inside the motor, is to inform
the control of the exact position and speed of doors.
55

The software V7.03.08-00 is not compatible with the Fermator


asynchronous motor.

56 - 59 Motor
Output to the 3 phase motor varying the voltage and frequency to MOTOR
control speed and torque. U 56

VF7+ CAN power supply switch has to be turned off before V 57


disconnecting the motor power connector.
M W 58

PE 59
Note: Never change the motor with the circuit in power on.

On / Off Switch
Disconnects the unit from the 230 V AC mains supply.

VF7+ CAN 5
INPUTS / OUTPUTS

60 - 63 Can bus
This input is used to perform communication with CAN BUS. It is possible to make a serial
connection because the circuit has a double connector.

NC
60

CAN H
61
CAN-High (CAN+)

CAN L
62
CAN-Low (CAN-)

-
63
CAN GND (Ground)

Switch SW900
If VF7+ CAN is the last device of the physical CAN line, the Switch SW900 has to be
placed to set a resistance 120 ohms between CAN L and CAN H to close the line. This
resistance is used to avoid possible reflections.
GRAPHIC INTERFACE

Three main objectives can be achieved with the VF7+ CAN graphic interface:
1. To detect possible alarms or errors in the unit (Menu Alarms).
2. To see the parameters value and active signals (Menu Monitor).To modify the internal program
parameters and options (Menu Program).
3. To modify the internal program parameters and options ( Menu Program).
4. To modify the configuration of the VF7+ CAN ( Menu Configuration).
5. To modify the configuration of the parameters and options CAN ( Menu CAN).

Once the unit is connected it will show the software version Fermator V7.03.08-00

Push button to access the VF7+ CAN menus.

There are four main menus with different submenus: Menu Alarm, Menu Monitor, Menu Program,
Menu Configuration and CAN Menu.

Push the or button to select the menu.

Push the button to enter the VF7+ CAN menus.

Push the button to return to the software version screen.

6 VF7+ CAN
GRAPHIC INTERFACE

Menu Alarm
The Menu Alarm shows the alarms activated in the unit.

Push the or button to select the submenu.

Push the button to return to the VF7+ CAN menus.

VF7+ CAN 7
GRAPHIC INTERFACE

The Alarms Historic shows the last ten alarms activated in the unit.

Push the or button to see the different alarms.

The VF7+ CAN graphic interface shows the active alarm while the alarm is active.
When the alarm is disabled the VF7+ CAN returns to the last screen before the alarm appearance.

Alarm Counters

Parameter Description Units

Motor Overtemperature Number of times that the Motor overtemperature alarm has been activated. -

Motor Crit. Overtemp. Number of times that the Motor critical overtemperature alarm has been activated. -

VF7+ Overtemperature Number of times that the VF7+ CAN overtemperature alarm has been activated. -

VF7+ Crit. Overtemp. Number of times that the VF7+ CAN critical overtemperature alarm has been activated. -

Open Obstruction Number of obstructions in the opening movement. -

Controller Failures Number of times that the Controller Failures has been activated. -

Motor disconnections Number of times that the motor has been disconnected. -

Motor Number of times that the motor alarm has been activated. -

Wrong calibration Number of times that the Wrong calibration alarm has been activated. -

Calibration Number of times that the Calibration alarm has been activated. -

Referencing Number of times that the Referencing alarm has been activated. -

Belt Number of times that the Belt alarm has been activated. -

Learning Number of times that the Learning alarm has been activated. -

Encoder Number of times that the Encoder alarm has been activated. -

Friction Number of times that the Friction alarm has been activated. -

Bypass Number of times that the Bypass alarm has been activated. -

Shortcircuits Number of times that the short-Circuit alarm has been activated. -

UnderVoltages Number of times that the UnderVoltage alarm has been activated. -

Memory Number of times that the Memory alarm has been activated. -

Softstart Relay Number of times that the Softstart Relay alarm has been activated. -

Low capacitance Number of times that the Low capacitance alarm has been activated. -

Alarm CAN Counters

Parameter Description Units

Hardware Number of times that the Hardware alarm has been activated. -

Bus OFF Number of times that the Bus OFF alarm has been activated. -

HeartBeat Number of times that the HeartBeat alarm has been activated. -

Description Alarms

Alarm Description Possible problem Actions VF7+ CAN recovery

Motor The motor coil has The door could have high friction. Check the mechanical The alarm is disabled
Overtemp. reached 125ºC The door could be blocked during part. when the motor
The VF7+ CAN remains in the opening/closing movement. Check the motor. reaches 105ºC or after
normal operation. The motor could be damaged. 3 minutes without
measurements.

8 VF7+ CAN
GRAPHIC INTERFACE

Motor Critical The motor coil has The door could have high friction. Check the mechanical part. The alarm is disabled
Overtemp. reached 140ºC. The door could be blocked during Check the motor. after 5 minutes.
The VF7+ CAN stops the the opening/closing movement.
normal operation. The motor could be damaged.

VF7+ The VF7+ CAN has The door could have high friction. Check the mechanical part. The alarm is disabled
Overtemp. reached 90ºC. The VF7+ CAN metal cover may Tighten the screws of the when the VF7+ CAN
The VF7+ CAN remains in not be making good contact. metal cover. reach 70ºC.
normal operation. Check that the VF7+ CAN
is installed on a metal
surface.
VF7+ Critical The VF7+ CAN has The door could have high friction. Check the mechanical The alarm is disabled
Overtemp. reached 105ºC. The VF7+ CAN metal cover could part. when the VF7+ CAN
The VF7+ CAN stops the not be making good contact. Tighten the screws of reach 70ºC.
normal operation. the metal cover.
Check that the VF7+
CAN is installed on a
metal surface.
Open Obstruction A blockage has been The mechanical part may not Check the mechanical Push the OK button.
detected during the be correctly installed. part. The alarm is disabled
opening movement in The Bypass contact could be Check the Bypass after 10 seconds.
normal operation or in damaged. contact.
referencing mode and
bypass remain activated.

Controller An obstruction has been The lift controller could has Check the lift controller. Push the OK button.
Failures performed in salve mode some problems. Check the signal wires. The alarm is disabled
and the lift controller does after 15 seconds.
not reopened.

Motor The unit does not receive The motor is disconnected. The motor must be Push the OK button.
Disconnect a signal from the Motor. connected
If the Motor protection
disconnected has been
activated.

Motor The unit does not receive The Motor wire could be Check the motor wire. Push the OK button.
a correct signal from the damaged. Check the motor. The alarm is disabled
Motor. The Motor could be damaged. Check the mechanical after 20 seconds.
The mechanical part could not part.
be correctly installed.

Wrong When power on, the The motor or the circuit has Carry out a calibration. Push the OK button.
Calibration. encoder was not detected been changed, and a new
correctly by the circuit calibration has not been yet
completed.

Calibration. The VF7+ CAN can The motor encoder signals Check the encoder Push the OK button.
not complete the Motor are not arriving correctly to the wire.
Calibration process. VF7+ CAN. Carry out a calibration.

Referencing The VF7+ CAN can The learning process has not Carry out a learning Push the OK button.
not recognize the clear been carried out. process.
opening.
The VF7+ CAN remains in
normal operation.

Belt The belt is broken. The belt could be damaged. Check the mechanical Push the OK button.
The pulley could be damaged. part.

Learning The VF7+ CAN can not The mechanical part may not be Carry out a learning Push the OK button.
complete the learning correctly installed. process.
process.

Encoder The unit does not receive The encoder wire could be Check the encoder Push the OK button.
a signal from the encoder. damaged. wire.
The encoder could be damaged. Check the motor.

VF7+ CAN 9
GRAPHIC INTERFACE

Friction The door has high friction. The mechanical part may not be Check the mechanical Push the OK button.
The VF7+ CAN remains in correctly installed. part.
normal operation.

Bypass The bypass contact The bypass contact could have Check the bypass Complete cycle to close
remained closed but the short-circuit or be disconnected. contact. and open with contact
door is open or the bypass connect, carry out a
contact remained in open learning process, or
but the door is closed. change the parameter
The VF7+ CAN remains in of bypass contact
normal operation. connect to circuit.

Shortcircuit The power module has The motor could be short- Check the motor wire. Push the OK button.
been short-circuited. circuited. Check the motor. The alarm is disabled
If 3 short-circuits take VF7+ CAN malfunction. after 10 seconds.
place in one minute the
alarm will be permanent
activated.

UnderVoltage The internal voltage The VF7+ CAN could have Disconnect all inputs The internal voltage
decreases under 13V some internal problems. and outputs reached 15V.

Memory The memory is failing. The VF7+ CAN could have Return to Factory Return to factory
some internal problems. settings. settings.

Softstart Relay Failure to switch the soft- The VF7+ CAN could have some Contact Fermator Push the OK button.
start relay. internal problems. aftersales.
The VF7+ CAN remains in
normal operation.

Low The working conditions of the The additional force to open the Check the CDL spring and Push the OK button.
capacitance internal capacitor is not optimal. CDL may be reduced. contact Fermator aftersales.

Description Alarms CAN

Alarm Description Possible problem Actions VF7+ CAN recovery

Hardware The microprocessor CAN The VF7+ CAN could have Check the CAN bus Switch off and on the
failure peripheral could not be some internal problems. VF7+ CAN.
initialized. There is a short-circuit in the
It has been done a short- CAN bus
circuit during the VF7+
CAN start up.

Bus off A short-circuit has been There is a short-circuit in the Check the CAN bus Remove the CAN bus
done in the CAN bus CAN bus short-circuit.

HeartBeat The VF7+ CAN does not The lift controller could have Check the lift controller. Receive the HeartBeat
receive the HeartBeat some problems. Check the CAN bus wires. message
message

Remark: If the incidence is not solved with the previous tips please contact Fermator aftersales.

Monitor Menu

The Menu Monitor displays the VF7+ CAN parameters in real time.

Push the or button to select the submenu.

Push the button to return to the VF7+ CAN menus.

10 VF7+ CAN
GRAPHIC INTERFACE

* These parameters can be hidden depending on what options are disabled.

Push the or button to see the different parameters.

Monitor Parameters

Parameter Description Units

Supply Voltage Voltage supply in AC (V). V (RMS)

VF7+ Temperature Temperature in the power module area (ºC). ºC

Supply Type AC or DC supply. -

Monitor Door

Parameter Description Units

Position Position of the door in m, indicating the zero point with the door closed and the clear m
opening + Clutch length with the door open.

Status Status of the door (Door closed, Door open, Closing door, ...). -

CDL Door with Car Door Lock (automatic detection during learning). -

Friction Friction value detected during the learning process. Frictionless door when this Scaled from 0 to 150
parameter is 0.

Bypass Length * The distance from the closed door position to open bypass contact detected during m
the learning process.
* This parameter is hidden if the option “Bypass Connected to circuit” is disconnected.

VF7+ CAN 11
GRAPHIC INTERFACE

Monitor Motor

Parameter Description Units

Speed Motor speed. m/s

Voltage Voltage that the circuit applies to the motor (V). V (RMS)

RMS Current Output current (A). A

Motor Type Motor connected to the circuit. -

Temperature * Temperature in the PM motor (Temperature measurement option has to be enabled). ºC


* This parameter is hidden if the option “Temp. Measurement” is disable.

Speed limited by kinetic This is the maxim speed in closing limited by the kinetic energy. m/s
energy * * This parameter is hidden if the option “Energy limit” is disable.

Monitor Inputs

Parameter Description Units

Open Status of the open signal. -

Close Status of the close signal. -

Re-open Status of the re-open signal. -

Floor Status of the floor level signal. -

Slow Close Status of the slow close signal. -

Bypass Status of the Close Position signal. -

Barrier failure Status of the Barrier failure. -

Monitor Outputs

Parameter Description Units

Open Door Status of the door open signal. -

Closed Door Status of the door closed signal. -

Re-open Status of the Re-open signal. -

Obstruction Status of the obstruction signal. -

Barrier failure Status of the Barrier failure signal. -

Temperature Error Status of the temperature signal. -

Monitor Counters

Parameter Description Units

Hours Number of working hours. -

Total Cycles Number of cycles completed by the door. -

Powerups Number of connections to the mains supply or blackouts suffered. -

Learning Cycles Number of learning cycles made. -

Reopenings Number of re-open cycles. Only by external signal inputs of reopening. -

Op. Obstructions Number of obstructions in the opening movement. -

Cl. Obstructions Number of blockages in the closing movement. -

Security Device Faults Number of times the light curtain blocked more than 2 minutes or Barrier failure -
activates

12 VF7+ CAN
GRAPHIC INTERFACE

Monitor Information

Parameter Description Units

Software Version Circuit software version. -

Software subversion Circuit software subversion. -

Hardware Version Circuit hardware version. -

Hardware Subversion Circuit hardware subversion. -

Serial Number Identification serial number for each unit. -

Supplier Supplier identification code. -

Test Date Date of manufacture. -

Programming Menu

The Menu Program displays the VF7+ CAN internal parameters an options.

Push the or button to select the sub-menu.

Push the or button to see the different parameters of each submenu.

To modify a parameter or an option carry out the following steps:

1. Select the parameter / option to be modified and push the button to enter in modify mode.

2. The parameter value or option status will appear blinking; push the or button to
increase / decrease the parameter value or enable / disable the option.

3. Push the button to save the modification.

VF7+ CAN 13
GRAPHIC INTERFACE

* These options can be hidden depending on what options are disabled.


Program Options

Options basic

Door Model T1 Automatic horizontal sliding door 1 panel side opening.

T2 Automatic horizontal sliding door 2 panel side opening.

T3 Automatic horizontal sliding door 3 panel side opening.

T4 Automatic horizontal sliding door 4 panel side opening.

C2 Automatic horizontal sliding door 2 panel centre opening.

C4 Automatic horizontal sliding door 4 panel centre opening.

C6 Automatic horizontal sliding door 6 panel centre opening.

C8 Automatic horizontal sliding door 8 panel centre opening.

Control Master The unit will execute the instructions directly. Example: Curtain activation will cause the doors to
re-open immediately without any signal from the lift controller.

Slave There is no automatic reopen movements. The doors will only react to an instruction given by
the main lift controller. Example: When the light curtain detects an obstacle instead of reopen
automatically the VF7+ CAN module will send a signal to the lift controller with the Light Curtain
output (42, 43, 44). The main lift controller must remove the close signal and active the open
signal.

Rotation Clockwise (CW) During the opening movement the motor will rotate clockwise.
Sense
Counterclockwise During the opening movement the motor will rotate counterclockwise.
(CCW)

14 VF7+ CAN
GRAPHIC INTERFACE

Program Options

Inputs 1 Input
Number
The unit will be controlled by a single CAN Control Operation frame (see section 6.2):
0xB5 0xFB 0x88 0x20 will cause a door closing.
0xB5 0xFB 0x88 0x00 will cause a door opening.

2 Inputs

The unit will be controlled by two CAN Control Operation frames (see section 6.2).
0xB5 0xFB 0x88 0x20 will cause a door closing.
0xB5 0xFB 0x88 0x40 will cause a door opening.
0xB5 0xFB 0x88 0x00 will cause the door to remain static.
If both frames are applied : 0xB5 0xFB 0x88 0x60; then the priority is defined by Priority Input option. This option is to
inform the circuit that the closed door contact is connected to the circuit. In the event that it is connected to the circuit it
enables the options referring to the Bypass, otherwise these options are hidden.

Door with This option allow select if the operator has reduction or not. If “No” reduction is selected, the Gear Ratio and Pinion
reduction Perimeter parameters in Program Parameters menu will be hidden. These parameters will automatically be set to 80mm
for the Pinion Perimeter and 1.00 for the Gear Ratio.

Bypass This option is to inform the circuit that the closed door contact is connected to the circuit. In the event that it is connected
Connected to to the circuit, it enables the options referring to the Bypass, otherwise these options are hidden.
circuit

Program Options

Options interact

Inputs Priority Open In the event that the open signal and close signals are activated at the same time the door
must open.

Close In the event that the open signal and close signals are activated at the same time the door
must close.

Stop In the event that the open signal and close signals are activated at the same time the door
must stop.

Slow Close In the event that the open signal and close signals are activated at the same time the door
must close in slow speed.

No Test priority If enabled, the Test cycle does not have priority over the input signals.

Keyboard shortcuts If enabled, keyboard shortcuts are allowed in:


-- The home screen:
• Learning: Push the button during 3 seconds.

• Test: Push the button during 3 seconds.

• Rotates the screen display: Push the and button during 1 seconds.

• Move the door to open: Push button during 1 seconds.

• Move the door to close: Push button during 1 seconds.

-- The Menu Alarms:


• Reset Historic Alarms: Push the button during 3 seconds.

HK Firefight If enabled, the first opening operation after a power up it is totally “slave”.

Slow close signal Action Slow close is performed when the Slow close input is activated.

Command Slow close/ open is performed when the Slow close input and Close/Open input are activated.

VF7+ CAN 15
GRAPHIC INTERFACE

Program Options

Unlock on standby If enabled, with the clutch/CDL fully closed the VF7+ CAN opens the clutch/CDL only if the closing signal is
removed or after a delay time (Eco Delay). Once the clutch is open the VF7+ CAN remains in standby. (This
option is not compatible with Eco Mode No).

Signal Clo. by Bypass * When it is active the closed signal output takes the value of the bypass input.
IMPORTANT: With this option enabled it is possible to have a output signal open and close active at the same
time.
* This option is hidden if the option “Bypass Connected to circuit” is disconnected.

Bypass Function * When it is active after a power blackout the VF7+ CAN will only need to reach the closed door position once
(detection of Bypass contact transition closed to open) to apply the normal speed profile.
IMPORTANT: The bypass contact must be installed before carrying out the door learning process. If the bypass
contact is removed or changes its position a door learning process has to be repeated.
* This option is hidden if the option “Bypass Connected to circuit” is disconnected.

Change rotation by When it is active the option "Rotation Sense" is auto detected during the learning process.
Bypass * * This option is hidden if the option “Bypass Connected to circuit” is disconnected.

Close Anticipated The Closed output is activated when the door is closed but doesn't need the Clutch to close. This signal is
activated when the door arrives to the distance of the “Clutch Length”.

Opening Closing
* This option is hidden if the option “Bypass Connected to circuit” is connected and “Signal Close by Bypass”
is activated .

Open Anticipated The Open output is activated when the door is within 50 mm of fully open.

Barrier fail. Only Close When it is active the Barrier failure output will only be activated when the door is closing.

Program Options

Options inputs logics

NC Slow Close If enabled, Slow close signal is activated without voltage (Normally closed contact).

NC Floor level If enabled, Floor level is activated without voltage (Normally closed contact).

NC Reopen If enabled, Reopen signal is activated without voltage (Normally closed contact).

NC Barrier failure If enabled, Barrier failure is activated without voltage (Normally closed contact).

NC Bypass If enabled, Close position is activated without voltage (Normally closed contact).

Program Options

Options functions

Eco Mode No The VF7+ CAN always applies the Close Maintenance Torque.

Control * The VF7+ CAN stops applying the Close Maintenance Torque if the closing signal is removed.
* Only selectable with option basic “Inputs Number” in two inputs.

Control delay * The VF7+ CAN stops applying the Close Maintenance Torque if the closing signal is
removed and the programmable time delay has finished (Eco delay).
* Only selectable with option basic “Inputs Number” in two inputs.

Close delay * The VF7+ CAN stops applying the Close Maintenance Torque after a programmable
time delay (Eco delay) since the door is closed.
* Only selectable with option basic “Inputs Number” in one inputs and Unlock on
standby activated.

CDL Electronic If enabled, after a power failure the VF7+ CAN opens the Car Door Lock if the cabin is at floor level.

16 VF7+ CAN
GRAPHIC INTERFACE

Program Options

Barrier timer * If enabled, an intelligent timer is used in case of a barrier permanent obstruction. The protection is disabled
after 2 minutes permanently blocked. If a physical obstruction occurs during the next closing movement, the
VF7+ CAN reopens and wait 2 minutes before closing again. If another physical obstruction occurs during the
next closing cycle the VF7+ CAN reopens and wait 4 minutes before closing again. Finally, if another physical
obstruction occurs during the next closing cycle the VF7+ CAN reopens and remains open. The photocell or
curtain is enabled again when there is not any physical obstruction during the closing movement.

Temperature measurement If enabled, the VF7+ CAN measures the motor temperature.

Temperature Protection Drive When the overheating alarm is active the circuit does not allow the door closing cycle.

Lift When the overheating alarm is active the lift does not allow the door closing cycle.

Energy limit The circuit limits the maximum velocity in order not to exceed a kinetic energy of 10 joules.

Obstruction Backstep If enabled and an obstruction occurs in the opening or closing movement the VF7+ CAN makes a backward
movement and waits a delay time (Backstep delay).

E.P.S. Slave If enabled, the Emergency Power Supplier will not open the door if the closing signal is activated.

E.P.S. Open Clutch If enabled, the Emergency Power Supplier will only open the car door clutch.

Op. Static Torque If enabled, a constant torque will be applied when the door is completely open.

Clo. Static Torque If enabled, a constant torque will be applied when the door is completely closed. Closing constant torque will
be applied according to the Eco Mode selected option.

Standby Hold If enabled, The circuit maintains the door stopped in any position of the clear opening. In this case the
parameters “Hold torque” and “Standby Hold Time” are enabled otherwise these parameters are hidden.

Motor protection If enabled, The circuit checks if the motor is connected. In the event the motor is disconnected the circuit has
disconnec. an alarm.

Low capacitance If enabled, The circuit checks the capacitors health.


protec.

Program Parameters

* These parameters can be hidden depending on what options are disabled.

VF7+ CAN 17
GRAPHIC INTERFACE

Programming Parameters (Speed Profiles)

Open profile

Close profile

Program Parameters

Parameters generals

Parameter Description Units Min Max

Moving mass Moving mass of the door. (kg) 1 500

Gear ratio Gear ratio when a reduction pulley is used. - 1.00 10.00

Program Parameters

Parameters speeds

Parameter Description Units Min Max

Open Initial Speed The initial speed at opening. (m/s) 0.025 0.100

Close Initial Speed The initial speed at closing. (m/s) 0.025 0.100

Open Proximity Speed The approximation speed at opening. (m/s) 0.025 0.100

Close Proximity Speed The approximation speed at closing. (m/s) 0.025 0.100

Open Clutch Speed Clutch speed at opening. (m/s) 0.025 0.100

Close Clutch Speed Clutch speed at closing. (m/s) 0.025 0.100

Open Limit Speed Speed limit at opening. (m/s) 0.100 1.000

Close Limit Speed Speed limit at closing. (m/s) 0.100 0.600

Open Acceleration The opening acceleration. (m/s2) 0.050 0.700

Close Acceleration The closing acceleration. (m/s2) 0.050 0.700

Open Deceleration The opening deceleration. (m/s2) 0.050 0.700

Close Deceleration The closing deceleration. (m/s2) 0.050 0.500

18 VF7+ CAN
GRAPHIC INTERFACE

Program Parameters

Parameters lengths

Parameter Description Units Min Max

Open Length Door clear opening + Clutch length. (m) 0.100 5.000

Open Initial Length The space at the initial opening movement. (m) 0 0.100

Close Initial Length The space at the initial closing movement. (m) 0.001 0.100

Open Proximity Length The space at the final opening movement. (m) 0.001 0.050

Close Proximity Length The space at the final closing movement. (m) 0.001 0.040

Clutch Length The required space to open/close the Clutch. (m) 0.000 0.100
In the event that the operator has not a Clutch (semi-automatic) put this value
to 0.

Additional Clutch Additional clutch movement to personalize the opening distance in (m) 0.000 0.200
Movement emergency mode.

Pinion Perimeter Perimeter of the motor pinion. (mm) 10.00 300.00


* This parameter is hidden if the option “Door with reduction” is NO.

Backstep length * Length of the backwards movement (Obstruction Backstep option). (m) 0.010 0.150
* This parameter is hidden if the option “Obstruction Backstep” is disabled.

Program Parameters

Parameters torques

Parameter Description Units Min Max

Max open torque Maximum torque in the opening movement. (Value 0 is disabled the limit torque). (N·m) 1.0 4.0

Max close torque Maximum torque in the closing movement. (Value 0 is disabled the limit torque). (N·m) 0.5 3.0

Hold torque Torque applied to maintain the door stopped in any position of the clear opening. (N·m) 0.5 1.5
* This parameter is hidden if the option “Standby Hold” is disabled.

Op. Final Constant Torque * Static torque applied to maintain the door stopped in open positions. (N·m) 0.1 1.1
* This parameter is hidden if the option “Op. Static Torque” is disabled.

Clo. Final Constant Torque * Static torque applied to maintain the door stopped in closed positions. (N·m) 0.1 1.1
* This parameter is hidden if the option “Clo. Static Torque” is disabled.

Program Parameters

Parameters times *
* This menu is hidden if the option “ECO mode” is “No” or “Control” and the options “Obstruction Backstep” and “Standby Hold ” are disabled.

Parameter Description Units Min Max

Eco Delay * Programmable time delay (Eco mode option). (s) 1 300
* This parameter is hidden if the option “ECO mode” is “No” or “Control”.

Backstep delay * Programmable time delay (Obstruction Backstep option). (s) 0 5


* This parameter is hidden the option “Obstruction Backstep” is disabled.

Standby Hold Time * Programmable time during the hold voltage is applied. (s) 0 1.800
* This parameter is hidden if the option “Standby Hold ” is disabled.

VF7+ CAN 19
GRAPHIC INTERFACE

Program Actions

Program Actions

Test Carries out a door open or close cycle to verify proper operation.

Door Learning Carries out a Door Learning process to set up the door.
If the Motor calibration has not been completed before, it will be carried out during this process.
This process must be carries out without the landing door coupled.
The door will carry out a close movement and then will carry out two complete movements to detect the clear
opening. From the information obtained the microprocessor will calculate the acceleration and deceleration ramps
to give the optimum control of the doors. Once the learning process has been completed the parameters are stored
in non-volatile EEPROM.
Learning process:

1. The door will close completely in slow speed until the end to detect the 0 position. If the first movement is
not “close” and the “Bypass Connected to circuit” is connected and “Change rotation by Bypass” activated
the VF7+ CAN will arrive at open position, and will automatically change the rotation sense. Then it will
start to close.
2. The door will open slowly counting the pulses from the encoder until it reaches the open mechanical stop.
”When it starts to open, it is necessary to open the CDL with by hand”
3. The door will close after a short delay. It will calculate the acceleration and deceleration ramps to give the
optimum control of the doors.

Note: If the last movement is not “close” without “Bypass Connected to circuit” it is necessary to change the
rotation sense and restart the Door Learning process.

Program Calibration

Program Calibration

Calibration The motor calibration process has to be carried out to detect the electrical characteristics of the motor
installed.

The calibration has to be carried out only once when the motor or the VF7+ CAN module are replaced.

Remove the motor belt before carrying out a calibration.

To perform an optimal calibration of the motor installed the process has to be carried out without load.
Never perform calibration with the car door and landing door coupled.

20 VF7+ CAN
GRAPHIC INTERFACE

Menu Configuration
The Menu Configuration is used to change the VF7+ CAN configuration.

Push the or button to see the different options.

To modify an option carry out the following steps:

1. Select the option to be modify and push the button to enter in modify mode.

2. The option status will appear blinking, push the or button to enable/disable it.

3. Push the button to save the modification.

Menu Configuration

Language The unit can be programmed in the following languages:


• English.
• Spanish.
• German.
• French.
• Italian.

Display Rotates the screen display (Straight / Invert).

Dynamic menus If disabled, the VF7+ CAN show all menus.

VF7+ CAN 21
GRAPHIC INTERFACE

Guide Starting guide to configure main parameters and options in VF7+ CAN. The following steps have to be followed
in order to configure VF7+ CAN according to the Guide:

When making the first start-up in a VF7+ CAN replacement the menu will be automatically opened so as to
configure the parameters related to the door where the VF7+ CAN will be replaced.

Factory Settings Sets all parameters to the factory value.

Reset Historic Alarms Clear the Historic Alarms.

Password Entering the correct password the advanced menu will be unlocked.

Menu CAN

The Menu CAN is used to adjust the VF7+ CAN communication settings.

Push the or button to see the different options.

To modify an option carry out the following steps:

1. Select the option to be modified and push the button to enter in modify mode.

2. The option status will appear blinking, push the or button to change the option.

3. Push the button to save the modification.

22 VF7+ CAN
GRAPHIC INTERFACE

CAN Configuration Menu

Door It can be up to 8 VF7+ CAN working on the same CAN bus. Each VF7+ CAN has to be configured as one different door (1 to 8)

Baudrate Next CAN baudrates can be selected: 1000 kB, 800 kB, 500 kB, 250 kB, 125 kB, 50 kB, 20 kB, 10 kB.

Heartbeat If enabled, the VF7+ CAN has to receive a CAN frame continuously from the lift controller. See section 6.4 for more details.

Traffic mode If enabled, the answer of the Frame Rx is not used in a writing operation.

Limit ECO Tx This option defines the VF7+ CAN operation when the manoeuvre tries to write a parameter out of the allowed values.
If enabled, the answer of the frame will be the limited value.
If disabled, the answer of the write frame will be always the sent value (the circuit will save the maximum or minimum
allowed value).
See section 7.3 for more information about allowed values.

Status time It is the time between two status frames.


This value is not saved in the eeprom.

Standard Reduced Menu

The Standard reduced menu is shown below.

Push the or button to see the different options.

To modify an option carry out the following steps:

1. Select the option to be modified and push the button to enter in modify mode.

2. The option status will appear blinking, push the or button to change the option.

3. Push the button to save the modification.

By default, the devices will be programmed with the reduced menu. To visualize the standard menu, the
technical staff must be introduce in the Password option the code ↓↓↓↓↑↑↑↑ .

The standard menu can be visualized until the screen shutdown.

VF7+ CAN 23
CAN COMMUNICATION PROTOCOL

The CAN communication is done with short messages using a frame. The messages are sent in
hexadecimal code.

First, it is sent the reception or transmission Node. This parameter specifies the reception node or the
transmission node from the frame. This parameter takes 2 bytes.

Then, it is sent the Data Frame, which contains the message. The Data Frame takes 8 bytes.

All Data Frames begin with the same structure:

• Read/Write&Byte/Word: The first parameter indicates the action to be performed, Read or Write,
and the size of the parameter to read or write. This parameter takes 1 byte.

Action Size Code

Byte 0x5B
Read
Word 0x39

Byte 0xB5
Write
Word 0x93

To perform the communication, three types of Data Frame are used:


– Frame Rx (call back).
– Frame Tx.
– Frame Rx.

Frame Rx (call Back)

This frame indicates the operator state, it is a reception frame. It is updated and sent automatically every
100 milliseconds.
Structure:

-- State Frame structure:

The code that indicates that the State Frame starts is 0xFE1E.

24 VF7+ CAN
CAN COMMUNICATION PROTOCOL

• Active Alarm 00- : Alarm code appears if an error is detected. The alarm code references are :

Code Alarm

0x00 No alarm

0x12 Motor temperature

0x02 Motor temperature Critical

0x18 VF7+ temperature

0x17 VF7+ temperature Critical

0x10 Open Obstruction

0x0f Controller Failures

0x1b Motor disconnect

0x0a Motor

0x1d Wrong Calibration

0x11 Calibration

0x19 Referencing

0x0b Belt

0x1a Learning

0x0d Encoder

0x09 Friction

0x1c Bypass

0x01 Shortcircuit

0x1e UnderVoltages

0x07 Memory

0x1f Softstart Relay

0x14 CAN HW failure

0x16 CAN Bus Off

0x15 CAN heartbeat

Note: see section 5.1 for more details.

• Phase: It indicates the movement of the door:

Code Phase

0x00 Closed

0x01 Opening

0x02 Open

0x03 Closing

0x04 Re-opening

0x05 Middle open

0x06 Learning in process

0x07 Alarm

VF7+ CAN 25
CAN COMMUNICATION PROTOCOL

• Status: It indicates the status of the operator. More than one status can be activated at the same
time:
Code Status

0x01 Obstruction

0x02 Re-Opening

0x04 Over-temperature

0x08 Barrier failure

0x10 Learning in process

0x20 Door fully open

0x40 Door fully closed

0x80 Test in process

-- Example: (XXXX) 39 FE 1E 00 02 20 00 00
0xXXXX → Reception Node
0x39 → Read Word
0xFE1E → Start of Frame
0x00 → No alarm
0x02 → Open
0x20 → Open relay activated

Frame Tx

This frame is used to communicate to the operator for read or write a parameter or to do an action.
Because of that there are two different structures.

Structure 1 (Read/Write a parameter):

-- Parameter Address:
See the section 7.
-- Value:
Value to write.
This parameter is not used in read actions.
-- Example: (XXXX) 39 FB BA 00 00 00 00 00
0xXXXX → Transmission Node
0x39 → Read Word
0xFBBA → Soft Release
0x0000 → Value

Structure 2 (Action):

26 VF7+ CAN
CAN COMMUNICATION PROTOCOL

-- Control Operation:
Specifies which action has to be performed.
Code Action

0x40 Open

0x88 0x20 Close

0x80 Slow close

0x10 Re-open

0x80 Learning
0xFB 0x84
0x40 Test

0x01 1 Input / 2 Inputs

0x87 0x02 Auto / Manual

0x04 Rotation sense

0x08 Master / Slave

IMPORTANT: The lift controller must keep the close signal enabled all the time when the lift is in motion.
When the lift controller does not keep the close signal enabled the clutch will open and the door will be able
to be opened with a force not greater than 300N (point 5.3.15.1 of EN 81-20).

Re-open (0x10) only will be executed if the door is closing (0x20), then the final code will be 0x30 (0x10 +
0x20). But if a slow closing is performing then the final code will be 0x90.

-- Example: (XXXX) B5 FB 88 40 00 00 00 00
0xXXXX → Transmission Node
0xB5 → Write Byte
0xFB8840 → Open the door

Frame Rx

This frame is the answer of the Frame Tx. It is a reception frame.


Structure:

-- Parameter Address:
See the section 7.
-- Value:
Indicates the parameter value.
-- Example: (XXXX) 39 FB BA 17 77 00 00 00
0xXXXX → Reception Node
0x39 → Read Word
0xFBBA → Soft Release
0x1777 → 6007

VF7+ CAN 27
CAN COMMUNICATION PROTOCOL

Heartbeat

If Heartbeat option is activated on the VF7+ CAN module a Heartbeat frame has to be sent to the VF7+
CAN continuously. If this frame is not received, the Heartbeat alarm will be activated.

The frame has to be sent to Reception Node 0x0704 and the other information (read/write, byte/word,
parameter address, value) is not taken into account.

-- Example: (0x0704) XX XX XX XX XX XX XX XX
0x0704 → Reception Node
0xXXXX → Rest of the frame. It is not taken into account.

CAN ADRESSES

Menu Alarm

Parameter Adress Size Units / CAN Interpretation

Current Alarm 0xfba6 Byte 0x12: Motor over temperature


0x02: Motor over temperature Critical
Last Alarm 01 0xfd2a Byte 0x18: VF7+ over temperature
0x17: VF7+ over temperature Critical
0x10: Open Obstruction
Last Alarm 02 0x0100 Byte 0x0f: Lift controller Failures
0x1b: Motor disconnect
Last Alarm 03 0x0101 Byte 0x0a: Motor
0x1d: Wrong calibration
0x11: Calibration
Alarm Historic

Last Alarm 04 0x0102 Byte


0x19: Referencing
0x0b: Belt
Last Alarm 05 0x0103 Byte 0x1a: Learning
0x0d: Encoder
Last Alarm 06 0x0200 Byte 0x09: Friction
0x1c: Bypass contact error
0x01: Short-C.
Last Alarm 07 0x0201 Byte
0x1e: UnderVoltages
0x07: Memory
Last Alarm 08 0x0202 Byte 0x1f: Softstart Relay
0x20: Low capacitance
Last Alarm 09 0x0203 Byte 0x14: CAN HW failure
0x16: CAN Bus Off
0x15: CAN heartbeat
Last Alarm 10 0x0204 Byte

28 VF7+ CAN
CAN ADRESSES

Parameter Adress Size Units / CAN Interpretation

Motor Overtemp. 0x0003 Word Number of times that the Motor overtemperature alarm has been activated.

Motor Crit. Overtemp. 0x0062 Word Number of times that the Motor critical overtemperature alarm has been activated.

VF7+ Overtemp. 0xfbd5 Word Number of times that the VF7+ CAN over temperature alarm has been activated.

VF7+ Crit. Overtemp. 0x0061 Word Number of times that the VF7+ CAN critical over temperature alarm has been activated.

Open Obstruction 0x0206 Word Number of obstructions in the opening movement.

Controller Failures 0x0107 Word Number of times that the Lift controller Failures has been activated.

Motor disconnections 0x010f Word Number of times that the motor has been disconnected.

Motor 0x0207 Word Number of times that the motor alarm has been activated.

Wrong calibration 0x0208 Word Number of times that the Wrong calibration alarm has been activated.
Alarm Counters

Calibration 0x0209 Word Number of times that the Calibration alarm has been activated.

Referencing 0x020a Word Number of times that the Referencing alarm has been activated.

Belt 0x020b Word Number of times that the Belt alarm has been activated.

Learning 0x020c Word Number of times that the Learning alarm has been activated.

Encoder 0x020d Word Number of times that the Encoder alarm has been activated.

Friction 0x020e Word Number of times that the Friction alarm has been activated.

Bypass 0x020f Word Number of times that the Bypass alarm has been activated.

Shortcircuits 0xfbc6 Word Number of times that the short-Circuits alarm has been activated.

UnderVoltages 0x0210 Word Number of times that the UnderVoltages alarm has been activated.

Memory 0x0211 Word Number of times that the Memory alarm has been activated.

Softstart Relay 0x0212 Word Number of times that the Softstart Relay alarm has been activated.

Low capacitance 0x0213 Word Number of times that the Low capacitance alarm has been activated.

Parameter Adress Size Units / CAN Interpretation

Hardware 0x0216 Word Number of times that the Hardware alarm has
been activated.

Bus OFF 0x0217 Word Number of times that the Bus OFF alarm has
CAN

been activated.

HeartBeat 0x0218 Word Number of times that the HeartBeat alarm has
been activated.

Menu Monitor

Parameter Adress Size Units / CAN Interpretation

Supply Voltage 0xfcbd Byte V rms


Parameters

VF7+ CAN Temp. 0xfc6e Byte Degrees Celsius

Supply Type 0x0104 Byte 0x00: DC


0x01: AC

VF7+ CAN 29
CAN ADRESSES

Parameter Adress Size Units / CAN Interpretation

Position 0xfc76 Word mm

Status 0xfc78 Byte 0x00: Closed.


0x01: Opening.
0x02: Open.
0x03: Closing.
0x04: Re-opening.
0x05: Middle open.
Door

0x06: Learning in process


0x07: Alarm.

Car Door Lock 0x0002 Byte 0x00: It doesn't have.


0x01: Mechanical.
0x02: Electronic.

Friction 0xfbd6 Byte Scaled from 0 to 150.

Bypass Position 0x0006 Byte mm

Parameter Adress Size Units / CAN Interpretation

Speed 0xfd53 Word mm / s

Voltage 0xfc54 Byte V rms

RMS Current 0xfba9 Word The value received has to be divided by 100 to obtain Amperes RMS.
Motor

Installed Motor 0xfe6c Byte 0x03: PM vC motor.

Temperature 0x0001 Byte Degrees Celsius.

Speed limited by kinetic 0xfe91 Word mm/s

Parameter Adress Size Units / CAN Interpretation

Working Hours 0xfbd0 Word Number of working hours.

Total Cycles 0xfbbc & 0xfbbe Double Number of cycles of the door.

PowerUps 0xfbd2 Word Number of connections to the mains supply or blackouts suffered.

Learning Cycles 0xfbca Word Number of learning cycles made.


Counters

Reopen Cycles 0xfbcc & 0xfbce Double Number of re-open cycles. Only by external signal inputs of
reopening.

Op. Obstructions 0xfbc2 Word Number of blockages in the opening movement.

Cl. Obstructions 0x0106 Word Number of blockages in the closing movement.

Security Dev. Faults 0xfbc0 Word Number of times the light curtain has fault or blocked more than 2
minutes.

Parameter Adress Size Units / CAN Interpretation

Software Version 0xfbba Word Circuit software version.

Software subversion 0xfbaa Byte Circuit software subversion.


Information

Hardware Version 0xf915 & 0xf917 Double Circuit hardware version.

Hardware Subver. 0xfbaf Word Circuit hardware subversion.

Serial Number 0xfcf4 & 0xfcf6 Double Identification serial number for each unit.

Supplier 0xfba8 Byte Supplier identification code.

Test Date 0xfbc4 Word Date of manufacture. Number of days passed since 01/01/15.

30 VF7+ CAN
CAN ADRESSES

Menu Program

Note: If an attempt is made to write a parameter with a non-allowed value, the VF7+ CAN will save the
maximum or minimum allowed value. The frame Rx sent by the circuit can be chosen depending on Limit
ECO Tx option on CAN Configuration Menu.

Parameter Adress Size Units / CAN Interpretation

Door Model 0xfe93 Byte 0x00: 1 panel side opening. 0x04: 2 panel centre opening.
0x01: 2 panel side opening. 0x05: 4 panel centre opening.
0x02: 3 panel side opening. 0x06: 6 panel centre opening.
0x03: 4 panel side opening. 0x07: 8 panel centre opening.

Control 0x0023 Byte 0x00: Slave


0x01: Master
Options Basic

Rotation Sense 0x0022 Byte 0x00: Clockwise


0x01: Counterclockwise

Inputs 0x0020 Byte 0x00: Two Inputs


0x01: One Input

Door with reduction 0x0301 Byte 0x00: No


0x01: Yes

Bypass Connected to 0x0220 Byte 0x00: Not connected:


circuit 0x01: Connected

Parameter Adress Size Units / CAN Interpretation

Priority Input 0x0026 0x00: Open


Byte 0x01: Close
0x02: Stop
0x03: Slow close

Test don't priority 0x0029 Byte 0x00: Off


0x01: On

HK Firefight 0x0025 Byte 0x00: Off


0x01: On

Slow close signal 0x0034 Byte 0x00: Action


0x01: Command
Options Interat

Unlock on standby 0x0035 Byte 0x00: Off


0x01: On

Signal Close by Bypass 0x0039 Byte 0x00: Off


0x01: On

Function Bypass 0x003b Byte 0x00: Off


0x01: On

Change rotation by 0x0221 Byte 0x00: Off


Bypass 0x01: On

Close Anticipated 0x0033 Byte 0x00: Off


0x01: On

Open Anticipated 0x0222 Byte 0x00: Off


0x01: On

Barrier failure Only Close 0x003a Byte 0x00: Off


0x01: On

VF7+ CAN 31
CAN ADRESSES

Parameter Adress Size Units / CAN Interpretation

NC Slow Close 0x002e Byte 0x00: Off


0x01: On
Options Inputs logic

NC Floor level 0x0031 Byte 0x00: Off


0x01: On

NC Reopen 0x002f Byte 0x00: Off


0x01: On

NC Barrier failure 0x0030 Byte 0x00: Off


0x01: On

NC Bypass 0x0032 Byte 0x00: Off


0x01: On

Parameter Adress Size Units / CAN Interpretation

Eco Mode 0x002c Byte 0x00: Not


0x01: Control
0x02: Close Delay
0x03: Control Delay

Electronic CDL 0x002b Byte 0x00: Off


0x01: On

Barrier timer 0x0024 Byte 0x00: Off


0x01: On

Temperature 0x0037 Byte 0x00: Off


measurement 0x01: On

Temperature Protection 0x0038 Byte 0x00: Elevator


0x01:Drive

Energy limit 0xfe2d Byte 0x00: Off


Options Functions

0x01: On

Obsctruction Backstep 0x0036 Byte 0x00: Off


0x01: On

E.P.S. Slave 0x0027 Byte 0x00: Off


0x01: On

E.P.S. Open Clutch 0x0028 Byte 0x00: Off


0x01: On

Open Static Torque 0x0108 Byte 0x00: Off


0x01: On

Close Static Torque 0x010c Byte 0x00: Off


0x01: On

Standby Hold 0x0024 Byte 0x00: Off


0x01: On

Motor protection 0x0302 Byte 0x00: Off


disconnec. 0x01: On

Low capacitance protec. 0x0303 Byte 0x00: Off


0x01: On

Parameter Adress Size Units / CAN Interpretation Min Max

Door mass 0xfe8f Word Kg 1 500


Parameters
General

Gear ratio 0xfcf9 Word * The value received has to be divided by 100. 100** 1000*
If it is received a 250, it means a reduction factor of 1 : 2,50

32 VF7+ CAN
CAN ADRESSES

Parameter Adress Size Units / CAN Interpretation Min Max

Open Initial Speed 0x0009 Byte mm/s 25 100

Close Initial Speed 0x000a Byte mm/s 25 100

Open Proximity Speed 0xfccc Byte mm/s 25 100

Close Proximity Speed 0x0004 Byte mm/s 25 100


Parameters Speeds

Open Clutch Speed 0xfca3 Byte mm/s 25 100

Close Clutch Speed 0x0005 Word mm/s 25 100

Open Limit Speed 0xfd14 Word mm/s 100 1000

Close Limit Speed 0xfd16 Word mm/s 100 600

Open Acceleration 0xfc44 Word mm/s2 50 700

Close Acceleration 0xfc47 Word mm/s2 50 700

Open Deceleration 0xfc45 Word mm/s 2


50 700

Close Deceleration 0xfc48 Word mm/s2 50 700

Parameter Adress Size Units / CAN Interpretation Min Max

Open Length 0xfbb2 Word mm 100 5000

Open Initial Length 0x0007 Byte mm 0 100

Close Initial Length 0x0008 Byte mm 1 100


Parameters Lengths

Open Proximity Length 0xfca9 Byte mm 1 50

Close Proximity Length 0xfcaa Byte mm 1 40

Clutch Length 0xfca5 Byte mm 0 100

Additional clutch Movement 0x0109 Byte mm 0 200

Pinion Perimeter 0x000b Word mm 10 300

Backstep length 0x000d Byte mm 10 150

Parameter Adress Size Units / CAN Interpretation Min Max

Max open torque 0x000f Byte The value received has to be divided by 10 to obtain Nm. 10 40
Parameters

Max close torque 0x0010 Byte The value received has to be divided by 10 to obtain Nm 5 30
Torques

Hold torque 0x0012 Byte The value received has to be divided by 10 to obtain Nm 5 15

Final Constant Torque 0x010a Byte The value received has to be divided by 10 to obtain Nm 1 11

Final Constant Torque 0x0225 Byte The value received has to be divided by 10 to obtain Nm 1 11

Parameter Adress Size Units / CAN Interpretation Min Max

Eco Delay 0xfec7 Word s 1 300


Parameters
Times

Backstep delay 0x000e Word ms 0 5000

Time Standby Hold 0x0011 Word s 0 1800

VF7+ CAN 33
CAN ADRESSES

Parameter Adress Size Units / CAN Interpretation

Test 0xfe1c Byte 0x00: Test done


0x01: Start Test
Actions

0x02: Test in process

Door learning 0xfe1d Byte 0x00: Door leaning done


0x01: Start Door leaning
0x02: Door learning in process

7.4 Menu Configuration


Parameter Adress Size Units / CAN Interpretation

Save the parameters 0xfcca Byte 0x01: Save

7.5 Menu CAN


Parameter Adress Size Units / CAN Interpretation

Heartbeat 0x005a Byte 0x00: Off


0x01: On

Traffic mode 0x005b Byte 0x00: Off


0x01: On

Limit ECO Tx 0x005c Byte 0x00: Off


0x01: On

Status time 0xfe22 Byte ms * 10 Min Max

1 255

INSTALLATION PROCESS

The whole installation process has to be carried out when a new circuit board is installed on a door.

1. Connections
• Connect the motor wire and encoder wire (#55, #56, #57, #58, #59).
• Disconnect all other inputs and CAN.
• If it has been installed the Bypass to the VF7+ CAN, Connect the bypass wire (#23, #24).
• Connect the 230 V AC mains supply to the controller (#5, #6, #7).

2. Switch on the VF7+ CAN door controller button I/O in the front of the box.

3. Select the CAN Door. Go to Menu CAN and select the Door.

4. Follow the Guide for configuration of VF7+ CAN main parameters if the circuit board is a replacement.
Starting guide to configure main parameters and options in VF7+ CAN. The following steps have to be
followed in order to configure VF7+ CAN according to the Guide:

34 VF7+ CAN
INSTALLATION PROCESS

5. Door Test

• Activate the Test option to open the door and verify the proper operation. Activate again the test
option to close the door.

6. Connect the wires coming from the lift controller


• Connect the CAN communication cables (# 60 to #63).
• Connect the priority inputs cables (#21 to #26).

If the circuit board is already installed only do this steps

1. Connections
• Connect the motor wire and encoder wire (#55, #56, #57, #58, #59).
• Disconnect all other inputs and CAN.
• If it has been installed the Bypass to the VF7+ CAN, Connect the bypass wire (#23, #24).
• Connect the 230 V AC mains supply to the controller (#5, #6, #7).

2. Switch on the VF7+ CAN door controller button I/O in the front of the box.

VF7+ CAN 35
INSTALLATION PROCESS

3. Select the CAN Door. Go to Menu CAN and select the Door.

4. Place the door in the middle position in order to see the starting movement.

5. Activate the Door Learning option to start the learning cycle. Go to Menu Program → Program
Actions in the VF7+ CAN Graphic Interface.
This process must be done without the landing door coupled.

The correct steps that the door has to make are:


The door will close completely in slow speed until the end to detect the 0 position.
If the first movement is not “close” and the “Bypass Connected to circuit” is connected and “Change
rotation by Bypass” activated the VF7+ CAN will arrive at the open position and it will automatically
change the rotation sense. Then it will start to close.
The door will open slowly counting the pulses from the encoder until it reaches the open mechanical
stop. ”When it starts to open, it is necessary to open the CDL with by hand”
The door will close after a short delay. It will calculate the acceleration and deceleration ramps to
give the optimum control of the doors.

Note: If the last movement is not “close” without Bypass Connected to circuit, it is necessary to
change the rotation sense and restart the Door Learning process .

6. Door Test
• Activate the Test option to open the door and verify the proper operation. Activate again the
test option to close the door.

7. Connect the wires coming from the lift controller


• Connect the CAN communication cables (# 60 to #63).
• Connect the priority inputs cables (#21 to #26).

POWER FAILURES

The VF7+ CAN incorporates two new security systems related to power failures:

• Anti-banging system: When a power failure occurs while the door is opening, closing or fully open,
the new anti-banging system brakes the PM motor to perform a slow closing and avoid the door
slamming on closing.

• CDL electronic: When a power failure occurs while the door is fully closed, the VF7+ CAN detects
the voltage drop and opens the CDL if the car is at the floor level. This new security system could be
used with a CDL. The CDL electronic system could be enabled or disabled by software.

Note: After the power supply has been restored and the open signal is activated the doors will open slowly
for the first operation in order to recognize the clear opening.

36 VF7+ CAN
LIFT STANDARD EN 81-20/50

In this section the modifications are listed for customer awareness in order to comply with the new lift
standard EN 81-20/50.

Kinetic energy

• The average closing speed has to be limited to 10 J. To create this limit it is necessary to know
the moving mass, the door opening and the number of door panels. These parameters are
programmed by default except when the unit is a spare part. In this case the parameters have
to be introduced by the VF7+ CAN menu program .

In order to comply with the standard it is necessary to configure some options and parameters:

Menu Option Configuration to comply EN 81-20/50

Door model. Select door model.

Photoc. / Curtain timer. Enable.

Eco Mode. Select modes Control, Close delay or Control delay.

Security Device. Curtain.


Programming options
Close Anticipated (recommended). Enable.

Unlock on standby. Enable.

Temperature measurement. Enable.

Energy limit. Enable.

Menu Option Configuration to comply EN 81-20/50

Max. open torque. Limit only in case of a glass door. If glass door the value must to be up to 1,2.

Programming parameters Max. close torque. Up to 1,2.

Door mass. Masses of the door and landing door. To know check Annex 1 and Annex 2.

Light curtain
• The light curtain is mandatory and it can be
connected to the lift controller or to the VF7+
CAN in the pin 21.
• In case of failure or deactivation of the light
curtain the kinetic energy of the doors must be
BARRIER
limited to 4J. To limit it the lift controller has to FAILURE
activate the slow close input, pin 25, of VF7+
CAN.

Overheating protection
• The internal temperature of the PM motor is measured by the VF7+ CAN when the option of
“Temperature measurement” inside the “Programming options” menu is enabled.

Door contact
• A separate monitoring signal is necessary to check that the car door(s) is / are in the closed
position. To comply this point an additional door contact is added, and the signal should be
connected to the lift controller.
The maximum contact rating is 2 A 230 Vac.

VF7+ CAN 37
REFERENCE DATA

Electrical characteristics

Minimum Nominal Maximum Units

Voltage: 200 230 253 * V AC

Current: - - 1,3 * A
Input ratings:
Frequency: 50 * - 60 Hz

Power: - - 299 * W [1 Φ]

Voltage: - - 106 * V

Current: - - 1,15 * A
Output ratings:
Frequency: 1 - 100 * Hz

Power: - - 121,9 * W [3 Φ]

Note *: Testing carried out according to nominal charge of the PM motor. Power 94 W S3 30% 5 min.

Protection requirements

Protective class: Protective Class I (1)

Residual-current device [RCD] RCD Type A [Recommended]

Over-voltage category Over-voltage category III

Electrical supply system: Supply earthing systems TT, NT, IT, not corner-earthed.

Short-circuit current rating [SCCR]: - - 1,5 kA

IP rating: - - 20

1. The accessible connections and parts listed below are of protective class 0. It means that the protection of these circuits relies only
upon basic insulation and becomes hazardous in the event of a failure of the basic insulation. Therefore, devices connected to these
circuits must provide electrical-shock protection as if the device was connected to supply mains voltage. In addition, during installation
these parts must be considered, in relation with electrical shock, as supply mains voltage circuits.
Class 0 circuits:
CAN BUS 60, 61, 62, 63.
SERIAL COMMUNICATION 13.
PRIORITY INPUTS 21, 22, 23, 24, 25, 26.
MOTOR ENCODER 55.

Protection requirements: CDM intended for installation in closed electrical operating area. During installation or maintenance, it is not
required to open the enclosure while CDM is energised.

Environmental characteristics

Minimum Nominal Maximum Units

Humidity - - 95 %

Altitude - - 2.000 m

Pollution degree - - 2

Enclosure details UL 94-5VA

38 VF7+ CAN
REFERENCE DATA

Mechanical characteristics

277 34
110

BARRIER
FAILURE

262

Dimensions L: 278 mm W: 123 mm D:34 mm

Mass 1,59 kg

Motor PM requirements

Type Synchronous permanent magnet

Number of poles 10

Electrical characteristics

Minimum Nominal Maximum Units

Voltage Supply 50 106 144 V

Current 0,18 1,15 2,13 A

Power 15 162 405 W

Torque 0 1,5 2,5 N·m

Speed 600 r.p.m.

Thermal class

Encoder Magnetic Incremental ABI (channel A, channel and index).

Resolution - 180 - pulses / rev.

Wiring requirements for the female connectors

Minimum Nominal Maximum Units

Power supply 0,2 / 25 - 2,5 / 14 mm2 / AWG

CAN Bus 0,25 / 24 - 1,5 / 16 mm2 / AWG

Priority inputs 0,25 / 24 - 1,5 / 16 mm2 / AWG

Motor power - 0,75 / 18 - mm2 / AWG

Motor Encoder - 0,14 / 26 - mm2 / AWG

Performance

Minimum Nominal Maximum Units

Opening Speed 0,01 - 1,00 m/s

Closing Speed 0,01 - 0,60 m/s

Safety Force 60 - 150 N

VF7+ CAN 39
ANNEX 1

Procedure calculation of moving mass

See annex 1 for calculation of


additional moving mass

Car door additional

+ moving mass depending on:


model, opening, PL, = Car door system
moving mass
HL, panel type and

For landing door calculation


consider same model, ope-
Moving mass of basis door
T2, PL: 800, HL: 2.000 mm, ning, PL, HL and panel type.
Consider worst scenario of fire
+ Complete system
moving mass
Sheet metal panel, NOF
homologation certification.

See annex 1 for basis door


moving mass information Landing door additional
moving mass depending on:
+ model, opening, PL,
HL, panel type and Fire
= Landing door system
moving mass
homologation
See annex 1 for calculation of
additional moving mass

Compact product line

# Model Opening Number of panels PL [mm] HL [mm] Panel type Fire homologation Moving mass [Kg]

0 Compact Side 2 800 2.000 Sheet metal F.R. E120 29,46

# Concept Multiplier factor

1 Difference from T2 to C2 0,02

2 Difference of 100 mm in PL 0,03

3 Difference of 100 mm in HL 0,01

4 Difference from F.R. E120 to F.R. EI60 0,16

5 Difference from F.R. E120 to F.R. EI120 0,20

6 Difference from F.R. E120 to F.R. EW60 0,12

7 Difference from F.R. E120 to F.R. E30 Russia 0,00

8 Difference from F.R. E120 to F.R. EI60 Russia 0,16

9 Difference from F.R. E120 to F.R. EI60 Ukraine 0,16

10 Difference from Sheet metal panels to Wien type vision panels 0,28

11 Difference from Sheet metal panels to Flush big vision panels 0,23

12 Difference from Sheet metal metal to Full glass in skirting panels 0,07

13 Difference from Compact to Compact PM model 0,01

14 Difference from Compact to Compact+ PM 150 model 0,05

40 VF7+ CAN
ANNEX 1

40/10 product line


# Model Opening Number of panels PL [mm] HL [mm] Panel type Fire homologation Moving mass [Kg]

0 40/10 PM Side 2 800 2.000 Sheet metal F.R. E120 31,93

# Concept Multiplier factor

1 Difference from T2 to T3 0,08

2 Difference from T2 to C2 0,00

3 Difference from T2 to C4 0,26

4 Difference of 100 mm in PL 0,07

5 Difference of 100 mm in HL 0,03

6 Difference from F.R. E120 to F.R. EI30 0,19

7 Difference from F.R. E120 to F.R. EI60 0,19

8 Difference from F.R. E120 to F.R. EI120 0,25

9 Difference from Sheet metal panels to Double skin panels 0,32

10 Difference from Sheet metal panels to Flush big vision panels 1,02

11 Difference from Sheet metal panels to Full glass in skirting panels 0,95

12 Difference from Sheet metal panels to Wien type vision panels 0,32

13 Difference from Sheet metal panels to Vision panels 0,61

Premium product line


# Model Opening Number of panels PL [mm] HL [mm] Panel type Fire homologation Moving mass [Kg]

0 Premium PM Side 2 800 2.000 Sheet metal F.R. E120 36,61

# Concept Multiplier factor

1 Difference from T2 to T3 0,07

2 Difference from T2 to T1 -0,17

3 Difference from T2 to C2 -0,03

4 Difference from T2 to C4 0,30

5 Difference from T2 to C6 1,15

6 Difference of 100 mm in PL 0,07

7 Difference of 100 mm in HL 0,11

8 Difference from F.R. E120 to F.R. EI30 0,18

9 Difference from F.R. E120 to F.R. EI60 0,18

10 Difference from F.R. E120 to F.R. EI120 0,24

11 Difference from Sheet metal panels to Double skin panels 0,12

12 Difference from Sheet metal panels to Flush big vision panels 0,60

13 Difference from Sheet metal panels to Full glass in skirting panels 0,60

14 Difference from Sheet metal panels to Foam filled panels -0,17

VF7+ CAN 41
ANNEX 1

Platinum product line


# Model Opening Number of panels PL [mm] HL [mm] Panel type Fire homologation Moving mass [Kg]

0 Platinum Side 2 800 2.000 Double skin F.R. E120 56,85


PM

# Concept Multiplier factor

1 Difference from T2 to C2. 0,06

2 Difference of 100 mm in PL. 0,08

3 Difference of 100 mm in HL. 0,07

50/11 product line


# Model Opening Number of panels PL [mm] HL [mm] Panel type Fire homologation Moving mass [Kg]

0 50/11 Side 2 800 2.000 Sheet metal F.R. E120 31,93

# Concept Multiplier factor

1 Difference from T2 to T3 0,08

2 Difference from T2 to T4 0,25

3 Difference from T2 to C2 0,00

4 Difference from T2 to C4 0,26

5 Difference from T2 to C6 0,30

6 Difference from T2 to C8 0,35

7 Difference of 100 mm in PL 0,07

8 Difference of 100 mm in HL 0,03

9 Difference from F.R. E 120 to F.R. EI 30 0,19

10 Difference from F.R. E 120 to F.R. EI 60 0,19

11 Difference from F.R. E 120 to F.R. EI 120 0,25

12 Difference from Sheet metal panels to Double skin panels 0,32

13 Difference from Sheet metal panels to Flush big vision panels 1,02

14 Difference from Sheet metal panels to Full glass in skirting panels 0,95

15 Difference from Sheet metal panels to Wien type vision panels 0,32

16 Difference from Sheet metal panels to Vision panels 0,61

42 VF7+ CAN
ANNEX 2

Example 1: Increment of PL and HL

Door to be calculated:

Model Opening Number of panels PL [mm] HL [mm] Panel type Fire protection

40/10 PM Side 2 900 2.100 Metal Sheet F.R. E120

Taking as basis(1):

Model Opening Number of panels PL [mm] HL [mm] Panel type Fire Moving mass [Kg]
homologation

40/10 PM Side 2 800 2.000 Metal Sheet F.R. E120 31,93

Calculations:

Difference Difference Difference Difference per Difference Difference per SUM Moving mass
per per number of per PL HL per panel fire homologation
opening panels (each 100 mm) (each 100 mm) type

There are There are 31,93 x 0,07(2) 31,93 x 0,03(3) = There are There are 2,23 + 0,95 31,93 + 3,18 =
equals equals = 2,23 Kg 0,95 Kg equals equals = 3,18 35,11 Kg

1. These specifications are in the Annex 1.


2. This factor is the increment of 100 mm in PL. There is the number 4 of the second table of 40/10 PM
in the Annex 1.
3. This factor is the increment of 100 mm in HL. There is the number 5 of the second table of 40/10
PM in the Annex 1.

Example 2: Difference of opening and number of panels + increment of PL and HL


Door to be calculated:

Model Opening Number of panels PL [mm] HL [mm] Panel type Fire protection

Premium PM Side 1 800 2.000 Double skin F.R. E120

Taking as basis(1):

Model Opening Number of panels PL [mm] HL [mm] Panel type Fire homologation Moving mass [Kg]

Premium PM Side 2 800 2.000 Metal Sheet F.R. E120 36,61

Calculations:

Difference Difference Difference per PL Difference Difference Difference SUM Moving


per opening per number (each 100 mm) per HL per panel per fire mass
of panels (each 100 mm) type homologation

36,61 x (-0,17) = -6,13 Kg There are There are 36,61 x 0,12 There are 4,39 – 6,13 36,61 – 1,74
equals equals = 4,39 Kg equals = -1,74 Kg = 34,87 Kg

1. These specifications are in the Annex 1.


2. This factor is the difference between T2 (side 2 panels) to T1 (side 1 panel). There is the number 2
of the second table of Premium PM in the Annex 1.
3. This factor is the difference between sheet metal panel and double skin panel. There is the number
11 of the second table of Premium PM in the Annex 1.

VF7+ CAN 43
ANNEX 3

Reduction, Clutch length and Pinion Perimeter

44 VF7+ CAN
ANNEX 3

VF7+ CAN 45
ANNEX 4

Graphic interface map

* These options and parameters can be hidden depending on what options are disabled.

46 VF7+ CAN
ATTENTION: Any proposed modification not shown in this manual, should be clarified with our
Technical Department before actioning.
TECNOLAMA accepts no responsability for any damage produced in the equipment described in
this manual and associated installation if the instructions given have not been followed.
TECNOLAMA reserves the right to modify the product or specifications in this technical brochure
without prior notification.

DECLARATION CE OF CONFORMITY

Tecnolama, S.A.
Ctra. Constantí Km 3
43204 REUS (Spain)

We hereby declare that the products described in this document conform


with the following E.U. council directive:

Norm EN 81-1/2. DIRECTIVE 2006/42/EC (Machinery directive),


DIRECTIVE 2014/30/EU (Electromagnetic compatibility),
of the European Parliament and of the Council.
VF7+ CAN Electronic Module
(19/31701583)
Reus, 03-06-19

David Román
General Manager

Tecnolama, S.A. ● Ctra. Constantí, Km 3 ● 43204 REUS (Spain) ● Tel.: +34 977 774 065
Fax: +34 977 771 615 ● www.fermator.com ● e-mail: info.es@fermator.com