CALCULO DE PARAMETROS ELECTRICOS DE CONDUCTORES

SISTEMA AUTOPORTANTE TEMP. DE OPERACION. : 40.00 C


O

TENSION (3Ø) 380 V COS Ø 0.900


TENSION (1Ø) 220 V SEN Ø 0.4359

Sección R R (40°C) R (40°C) DMG(3Ø) DMG(1Ø) re X (3Ø) X (1Ø) FCT (3Ø) FCT (1Ø)
(mm) (20°C) (Ohm/km (Ohm/k (mm) (mm) (mm) (Ohm/km (Ohm/km) Ohm/km.V Ohm/km.V
e (mm)
(Ohm/k ) m) )
16 1.91000
m) 2.04752 2.04752 8.23559 7.40000 1.63350 0.12267 0.11456 0.00554 ###
0.01912
25 1.20000 1.28640 1.28640 9.60833 7.40000 2.06910 0.11643 0.11456 0.00353 ###
0.01912
35 0.86800 0.93050 0.93050 10.84664 7.40000 2.46840 0.11225 0.11456 0.00259 ###
0.01912
50 0.64100 0.68715 0.68715 12.83793 7.95000 2.80962 0.11521 0.11999 0.00196 ###
0.01914
70 0.44300 0.47490 0.47490 15.32777 8.80000 3.57192 0.11045 0.12770 0.00139 ###
0.01918
95 0.32000 0.34304 0.34304 17.40611 9.85000 4.18902 0.10801 0.13624 0.00104 ###
0.01921
CÁLCULO ELÉCTRICO REDES DE DISTRIBUCIÓN SECUNDARIA

TIPO : AUTOPORTANTE TENSIÓN DE SERVICIO 380.0 V


SUBESTACIÓN : Nº 1 FACTOR DE POTENCIA 0.90
SERVICIO : PARTICULAR FACTOR DE SIMULTANEIDAD 0.60
CIRCUITO 1 CALIFICACIÓN ELÉCTRICA 0.6 kW

Punto Abonados Suma F.S. Suma de C.E. Suma Potencia I S FCT L CaidaV SumaDv DV
N N Pot. (kW) (kW) CE (kW) total (kW) (A) (mm2) (m) (V) (V) (%)

0 0 36 0.60 12.96 0 3 15.96 26.97 25 0.003530 2.00 0.113 0.113 0.03


1 8 36 0.60 12.96 0 3 15.96 26.97 25 0.003530 26.00 1.465 1.577 0.42
2 8 28 0.60 10.08 0 3 13.08 22.11 25 0.003530 30.00 1.385 2.963 0.78
3 3 20 0.60 7.20 0 3 10.20 17.24 25 0.003530 29.00 1.044 4.007 1.05
4 0 17 0.60 6.12 0 3 9.12 15.41 25 0.003530 17.00 0.547 4.554 1.20
5 4 17 0.60 6.12 0 3 9.12 15.41 25 0.003530 23.00 0.740 4.747 1.25
6 5 13 0.60 4.68 0 3 7.68 12.98 25 0.003530 23.00 0.624 5.371 1.41
7 4 8 0.60 2.88 0 3 5.88 9.94 25 0.003530 23.00 0.477 5.848 1.54
8 3 4 0.60 1.44 0 3 4.44 7.50 25 0.003530 23.00 0.360 6.209 1.63
9 1 1 0.60 0.36 3 3 3.36 5.68 25 0.003530 25.00 0.297 6.505 1.71
10 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 6.505 1.71

36 246.00
4.007
3.1 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 28.00 0.000 4.007 1.05
3.2 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 26.00 0.000 4.007 1.05

0 54.00
4.554
4.1 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 28.00 0.000 4.554 1.20
4.2 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 28.00 0.000 4.554 1.20
4.3 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 32.00 0.000 4.554 1.20

0 88.00

TOTAL 36
CÁLCULO ELÉCTRICO REDES DE DISTRIBUCIÓN SECUNDARIA

TIPO : AUTOPORTANTE TENSION DE SERVICIO 220.0 V


SUBESTACION : Nº 1 FACTOR DE POTENCIA 0.90
SERV ICIO : ALUMBRADO PÚBLICO FACTOR DE SIMULTANEIDAD 1.00
CIRCUITO :1 CALIFICACIÓN ELÉCTRICA 0.03 kW

Punto Luminarias Suma F.S. Suma de C.E. Suma Potencia I S FCT L CaidaV SumaDv DV
N N Pot. (kW) (kW) CE (kW) total (kW) (A) (mm2) (m) (V) (V) (%)

0 1 16 1.00 0.48 0 0 0.48 1.40 16 0.019120 2.00 0.018 0.018 0.00


1 1 15 1.00 0.45 0 0 0.45 1.31 16 0.019120 26.00 0.224 0.242 0.06
2 1 14 1.00 0.42 0 0 0.42 1.23 16 0.019120 30.00 0.241 0.483 0.13
3 1 13 1.00 0.39 0 0 0.39 1.14 16 0.019120 29.00 0.216 0.699 0.18
4 1 10 1.00 0.30 0 0 0.30 0.88 16 0.019120 17.00 0.098 0.797 0.21
5 1 6 1.00 0.18 0 0 0.18 0.53 16 0.019120 23.00 0.079 0.778 0.20
6 1 5 1.00 0.15 0 0 0.15 0.44 16 0.019120 23.00 0.066 0.844 0.22
7 1 4 1.00 0.12 0 0 0.12 0.35 16 0.019120 23.00 0.053 0.897 0.24
8 1 3 1.00 0.09 0 0 0.09 0.26 16 0.019120 23.00 0.040 0.937 0.25
9 1 2 1.00 0.06 0 0 0.06 0.18 16 0.019120 25.00 0.029 0.965 0.25
10 1 1 1.00 0.03 0 0 0.03 0.09 16 0.019120 25.00 0.014 0.980 0.26

11 246.00
0.699
3.1 1 2 1.00 0.06 0 0 0.06 0.18 16 0.019120 28.00 0.032 0.731 0.19
3.2 1 1 1.00 0.03 0 0 0.03 0.09 16 0.019120 26.00 0.015 0.746 0.20

2 54.00
0.797
4.1 1 3 1.00 0.09 0 0 0.09 0.26 16 0.019120 28.00 0.048 0.845 0.22
4.2 1 2 1.00 0.06 0 0 0.06 0.18 16 0.019120 28.00 0.032 0.877 0.23
4.3 1 1 1.00 0.03 0 0 0.03 0.09 16 0.019120 32.00 0.018 0.895 0.24

3 88.00

TOTAL 16
CÁLCULO ELÉCTRICO REDES DE DISTRIBUCIÓN SECUNDARIA

TIPO : AUTOPORTANTE TENSIÓN DE SERVICIO 380.0 V


SUBESTACIÓN : Nº 1 FACTOR DE POTENCIA 0.90
SERVICIO : PARTICULAR FACTOR DE SIMULTANEIDAD 0.60
CIRCUITO 2 CALIFICACIÓN ELÉCTRICA 0.6 kW

Punto Abonados Suma F.S. Suma de C.E. Suma Potencia I S FCT L CaidaV SumaDv DV
N N Pot. (kW) (kW) CE (kW) total (kW) (A) (mm2) (m) (V) (V) (%)

0 0 45 0.60 16.20 0 3 19.20 32.45 25 0.003530 2.00 0.136 0.136 0.04


1 8 45 0.60 16.20 0 3 19.20 32.45 25 0.003530 24.00 1.627 1.762 0.46
2 5 37 0.60 13.32 0 3 16.32 27.58 25 0.003530 24.00 1.383 3.145 0.83
3 7 32 0.60 11.52 0 3 14.52 24.54 25 0.003530 25.00 1.281 4.426 1.16
4 3 25 0.60 9.00 0 3 12.00 20.28 25 0.003530 25.00 1.059 5.485 1.44
5 8 22 0.60 7.92 0 3 10.92 18.46 25 0.003530 27.00 1.041 6.526 1.72
6 6 14 0.60 5.04 0 3 8.04 13.59 25 0.003530 27.00 0.766 7.292 1.92
7 5 8 0.60 2.88 0 3 5.88 9.94 25 0.003530 24.00 0.498 7.790 2.05
8 3 3 0.60 1.08 0 3 4.08 6.90 25 0.003530 24.00 0.346 8.136 2.14
9 0 0 0.60 0.00 3 3 3.00 5.07 25 0.003530 26.00 0.275 8.411 2.21
10 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 26.00 0.000 8.411 2.21

45 254.00
5.485
4.1 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 29.00 0.000 5.485 1.44
4.2 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 5.485 1.44
4.3 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 5.485 1.44
4.4 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 5.485 1.44
4.5 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 5.485 1.44

0 129.00
8.136
8.1 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 8.136 2.14
8.2 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 23.00 0.000 8.136 2.14
8.3 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 8.136 2.14
8.4 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 8.136 2.14

0 98.00
TOTAL 45
CÁLCULO ELÉCTRICO REDES DE DISTRIBUCIÓN SECUNDARIA

TIPO : AUTOPORTANTE TENSION DE SERVICIO 220.0 V


SUBESTACION : Nº 1 FACTOR DE POTENCIA 0.90
SERV ICIO : ALUMBRADO PÚBLICO FACTOR DE SIMULTANEIDAD 1.00
CIRCUITO :2 CALIFICACIÓN ELÉCTRICA 0.03 kW

Punto Luminarias Suma F.S. Suma de C.E. Suma Potencia I S FCT L CaidaV SumaDv DV
N N Pot. (kW) (kW) CE (kW) total (kW) (A) (mm2) (m) (V) (V) (%)

0 0 22 1.00 0.66 0 0 0.66 1.93 16 0.019120 2.00 0.025 0.025 0.01


1 1 22 1.00 0.66 0 0 0.66 1.93 16 0.019120 24.00 0.303 0.328 0.09
2 1 21 1.00 0.63 0 0 0.63 1.84 16 0.019120 24.00 0.289 0.617 0.16
3 1 20 1.00 0.60 0 0 0.60 1.75 16 0.019120 25.00 0.287 0.904 0.24
4 1 19 1.00 0.57 0 0 0.57 1.66 16 0.019120 25.00 0.272 1.176 0.31
5 1 13 1.00 0.39 0 0 0.39 1.14 16 0.019120 27.00 0.201 1.378 0.36
6 1 12 1.00 0.36 0 0 0.36 1.05 16 0.019120 27.00 0.186 1.564 0.41
7 1 11 1.00 0.33 0 0 0.33 0.96 16 0.019120 24.00 0.151 1.715 0.45
8 1 10 1.00 0.30 0 0 0.30 0.88 16 0.019120 24.00 0.138 1.853 0.49
9 1 2 1.00 0.06 0 0 0.06 0.18 16 0.019120 26.00 0.030 1.883 0.50
10 1 1 1.00 0.03 0 0 0.03 0.09 16 0.019120 26.00 0.015 1.897 0.50

10 254.00
1.176
4.1 1 5 1.00 0.15 0 0 0.15 0.44 16 0.019120 29.00 0.083 1.260 0.33
4.2 1 4 1.00 0.12 0 0 0.12 0.35 16 0.019120 25.00 0.057 1.317 0.35
4.3 1 3 1.00 0.09 0 0 0.09 0.26 16 0.019120 25.00 0.043 1.360 0.36
4.4 1 2 1.00 0.06 0 0 0.06 0.18 16 0.019120 25.00 0.029 1.389 0.37
4.5 1 1 1.00 0.03 0 0 0.03 0.09 16 0.019120 25.00 0.014 1.403 0.37

5 129.00
1.853
8.1 1 7 1.00 0.21 0 0 0.21 0.61 16 0.019120 25.00 0.100 1.953 0.51
8.2 2 6 1.00 0.18 0 0 0.18 0.53 16 0.019120 23.00 0.079 2.032 0.53
8.3 2 4 1.00 0.12 0 0 0.12 0.35 16 0.019120 25.00 0.057 2.090 0.55
8.4 2 2 1.00 0.06 0 0 0.06 0.18 16 0.019120 25.00 0.029 2.118 0.56

7 98.00
TOTAL 22
CÁLCULO ELÉCTRICO REDES DE DISTRIBUCIÓN SECUNDARIA

TIPO : AUTOPORTANTE TENSIÓN DE SERVICIO 380.0 V


SUBESTACIÓN : Nº 1 FACTOR DE POTENCIA 0.90
SERVICIO : PARTICULAR FACTOR DE SIMULTANEIDAD 0.60
CIRCUITO 3 CALIFICACIÓN ELÉCTRICA 0.6 kW

Punto Abonados Suma F.S. Suma de C.E. Suma Potencia I S FCT L CaidaV SumaDv DV
N N Pot. (kW) (kW) CE (kW) total (kW) (A) (mm2) (m) (V) (V) (%)

0 0 14 0.60 5.04 0 3 8.04 13.59 25 0.003530 2.00 0.057 0.057 0.01


1 1 14 0.60 5.04 0 3 8.04 13.59 25 0.003530 28.00 0.795 0.851 0.22
2 0 13 0.60 4.68 0 3 7.68 12.98 25 0.003530 28.00 0.759 1.611 0.42
3 4 13 0.60 4.68 3 3 7.68 12.98 25 0.003530 26.00 0.705 2.315 0.61
4 5 9 0.60 3.24 0 0 3.24 5.48 25 0.003530 25.00 0.286 2.601 0.68
5 4 4 0.60 1.44 0 0 1.44 2.43 25 0.003530 25.00 0.127 2.728 0.72

14 134.00
1.611
2.1 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 1.611 0.42
2.2 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 1.611 0.42
2.3 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 1.611 0.42
2.4 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 1.611 0.42

0 100.00
1.611
2a 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 1.611 0.42
2b 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 1.611 0.42
2c 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 1.611 0.42
2d 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 25.00 0.000 1.611 0.42

0 100.00
1.611
2.11 0 0 0.60 0.00 0 0 0.00 0.00 25 0.003530 8.00 0.000 1.611 0.42

0 8.00

TOTAL 14
CÁLCULO ELÉCTRICO REDES DE DISTRIBUCIÓN SECUNDARIA

TIPO : AUTOPORTANTE TENSION DE SERVICIO 220.0 V


SUBESTACION : Nº 1 FACTOR DE POTENCIA 0.90
SERV ICIO : ALUMBRADO PÚBLICO FACTOR DE SIMULTANEIDAD 1.00
CIRCUITO :3 CALIFICACIÓN ELÉCTRICA 0.04 kW

Punto Luminarias Suma F.S. Suma de C.E. Suma Potencia I S FCT L CaidaV SumaDv DV
N N Pot. (kW) (kW) CE (kW) total (kW) (A) (mm2) (m) (V) (V) (%)

0 0 15 1.00 0.60 0 0 0.60 1.75 16 0.019120 2.00 0.023 0.023 0.01


1 1 15 1.00 0.60 0 0 0.60 1.75 16 0.019120 28.00 0.321 0.344 0.09
2 1 14 1.00 0.56 0 0 0.56 1.63 16 0.019120 28.00 0.300 0.644 0.17
3 1 13 1.00 0.52 0 0 0.52 1.52 16 0.019120 26.00 0.259 0.902 0.24
4 1 2 1.00 0.08 0 0 0.08 0.23 16 0.019120 25.00 0.038 0.941 0.25
5 1 1 1.00 0.04 0 0 0.04 0.12 16 0.019120 25.00 0.019 0.960 0.25

5 134.00
0.644
2.1 1 6 1.00 0.24 0 0 0.24 0.70 16 0.019120 25.00 0.115 0.759 0.20
2.2 1 3 1.00 0.12 0 0 0.12 0.35 16 0.019120 25.00 0.057 0.816 0.21
2.3 1 2 1.00 0.08 0 0 0.08 0.23 16 0.019120 25.00 0.038 0.854 0.22
2.4 1 1 1.00 0.04 0 0 0.04 0.12 16 0.019120 25.00 0.019 0.873 0.23

4 100.00
0.644
2a 1 4 1.00 0.16 0 0 0.16 0.47 16 0.019120 25.00 0.076 0.720 0.19
2b 1 3 1.00 0.12 0 0 0.12 0.35 16 0.019120 25.00 0.057 0.778 0.20
2c 1 2 1.00 0.08 0 0 0.08 0.23 16 0.019120 25.00 0.038 0.816 0.21
2d 1 1 1.00 0.04 0 0 0.04 0.12 16 0.019120 25.00 0.019 0.835 0.22

4 100.00
0.759
2.11 2 2 1.00 0.08 0 0 0.08 0.23 16 0.019120 8.00 0.012 0.771 0.20

2 8.00

TOTAL 15