Académique Documents
Professionnel Documents
Culture Documents
Abstract: In order to parallel several single phase inverters to increase power capacity and system reliability, several control
schemes are proposed: a parallel control scheme, a voltage control scheme and a load sharing control scheme. The parallel
control technique is based on preemptive priority, which makes no absolute master or slave inverter into reality. In order to
ensure N+1 redundant structure, synchronization signal generating mechanism, a parallel digital bus and a no-conflicted
protocol on the bus also are introduced. In order to control voltage, the voltage control scheme employs a local feedback
controller. To implement load sharing, the load sharing control scheme introduces an improved droop method to droop
voltage and frequency. The analysis of the proposed method and design procedure are provided. Based on the simulation and
experiment results, it shows that the proposed scheme can implement load sharing effectively. The experimental results with
different type loads show that the output current error is less than 1% rating current for each inverter.
Key Words: Parallel control, synchronization, load sharing, inverter
2.1 Proposed Control Scheme N+1 redundant structure [7] system is a very stable and
economical redundant way. N+1 redundancy in an
In the conventional control approach to paralleling inverter system requires two key conditions: The first is
inverters, usually there is a common circuit block which, each inverter has independent detecting circuit, and can
if it fails, renders the entire system inoperable, monitor and modify itself input and output voltages and
especially in master-slave system, if the master is currents. The second is that each inverter can share load
damaged and there is no master and no synchronization current perfectly. There is no master/slave concept, and
signal, such case is deadly to the system. To overcome each inverter can work independently.
this problem, each inverter could not depend on center
control unit or some master inverter. When the master
inverter faults, the system can generate a new master in
some rules in time and implement the
synchronization signal jointing seamless. In actual
system, there is alternating current (AC) supply, so it
is clear that the AC supply parameters (frequency,
phase and amplitude) must be the synchronization
signal and the static switch become the master
accordingly. The priory of AC supply signal is higher
than that of inverter because the system must switch
in the light of AC supply parameters immediately at
the moment AC supply power off. There are also
master and slave in the system, but not absolutely, so
the combination method of priority and preemptive is
a good choice: Fig.1 Synchronization signal generating mechanism
If there is AC supply signal anytime in the system,
static switch is the temporary master, which means AC It is clear that the first condition is very easy to fulfill.
supply signal’s priory is higher. Each inverter in the The preemptive priority satisfies the no master/slave
system tracks and captures AC supply signal and tries concept. To share load current perfectly, the
to synchronize itself output signal with AC supply communication protocol on the parallel bus is very
signal. important to the parallel system to change information.
If there is no AC supply, the temporary master is The no-conflicted protocolütoken bus protocol can be
generated by the way of preemptive, other inverters used on the bus, for the stations connected on the bus
become temporary slaves. When this temporary master make up of a logical ring, and each station has a logical
fails, it is also can generate the temporary master by number in order. It is easy to distinguish each member
preemptive. for each member station knows it’s pre-station and
In this model, for each inverter sends out successive station. Further more, it is not complex to
synchronization signal all the time though the signal is implement the protocol in actual system.
not work at most time, the time of generating the master Fig.2 shows the paralleling N+1 redundant structure
by preemptive is almost negligible, which ensures the system, where several inverters parallel each other by
master switching seamlessly. the parallel bus, when the “AC input” is switched off by
2.3 Synchronization Scheme and Redundant static switch unit, the inverters will converter the DC
Structure input to AC to supply AC output for other systems.
When the static switch unit switches on, it will send
It is clear synchronization signal is sent by the temporary commands to each inverter by the parallel bus, and then
master, so the synchronization signal generating all inverters will stop work, the AC input will output
mechanism is the same mechanism of generating directly.
temporary master.
In Fig.1, Ai is the synchronization signal output point
generated by each inverter. Di is the detected point of
synchronization signal in each inverter. E is the
sending point of static switch unit’s synchronization
signal, if there are AC supply and static switch in the
parallel inverters system. As long as we chose
resistances R1, R2, R3 and R4 appropriately in the circuit,
it can ensure the preemptive priority logic. To some
extend, synchronization signal generating logic can
describe as the following equation: Fig.2 Paralleling redundant system
205
1
3 VOLTAGE CONTROL SCHEME H v ( s) = (7)
τ 1s + 1
The inverter can be presented as shown in Fig.3. The H i ( s ) = k1 (8)
PWM just as a switch and switch rate is controlled. If H r ( s ) = k2 (9)
PWM unit has a duty ratio λ , ideally the output
voltage is λ E . It is clearly that by varying λ as 4 LOAD SHARING CONTROL SCHEME
λ = λ sin ω t , we can get the desired output voltage
A simple schematic of two parallel inverters can be got
V1 = λ0 E sin ω t .
easily by Fig. 3. For the nature of the line impedance
has a profound effect on the load sharing control, the
line impedance is represented by a pure inductance X ,
V0 is output voltage on the load. The complex power at
the load due to the inverter1 is given by:
S1 = P1 + jQ1 = V0 I1* (10)
Fig.3 Inverter model
where I1* is the conjugate of inverter1’s and is given
From the model we can get: by:
v1 = ( s 2 LC + sRL C + 1)vo + ( sL + RL )io (2) V (cos θ1 + jsin θ1 ) − V0
where iL is inverter filter inductor current, io is load I1* = 1 (11)
jX
current, ic is capacitance current, vo is output where θ1 is the phase angle of V1 .
voltage and v1 is PWM output voltage. Then, we can get:
Usually, the output voltage Vo is used as a feedback V V (cos θ 1 + sinθ 1) − V0 2
S1 = 1 0 (12)
signal to correct the PWM unit’s duty radio. However, jX
this method, used in almost all switched mode DC/DC
The real power P1 and reactive power Q1 is:
power supplies, can not be used in an inverter
developed to operate in parallel since its setting time is V1 V0 sin θ1
P1 = (13)
much too slow. X
V V cos θ 1-V02
Q1 = 1 0 (14)
X
For the error between V1 and V0 is very tiny, then
sin θ1 = θ1 , assume that V1 = k1V0 , we can get:
k1 V 02θ1
P1 = (15)
X
Fig.4 Proposed voltage controller (k cos θ1 − 1)V02
Q1 = 1 (16)
X
In order to increase the loop gain we have taken the LC Similarly for inverter2, if V2 = k2V0 :
filter out of the feedback loop [8]. A block diagram of
the voltage controller is shown in Fig.4, where Vref is k2 V 02θ 2
P2 = (17)
the sine wave reference. Then we can get the equation: X
(1+ H v kv ki A ) v1 = kv ki Avref − H i ki Aic − H r Aio (3) (k cos θ 2 − 1)V02
Q2 = 2 (18)
Using (2), and (3) we can get: X
where θ 2 is the phase angle of V2 .
vo + Gi ( s )io = Gv ( s ) vref (4)
Equations (15), (16), (17) and (18) show that the real
where: power flow predominantly depends on the power angles
§ Hr A · θ1 and θ 2 , and the reactive power flow is mostly
sL + ¨ RL + ¸
© 1 + H v k v ki A ¹ influenced by the amplitude of voltages V1 and V2 .
Gi ( s ) = (5)
§ H i ki A · To avoid overloading one inverter, it is efficient to
s 2 LC + sC ¨ RL + ¸ +1 control real power by modifying phase error ( θ1 , θ 2 )
© 1 + H v k v ki A ¹
and control reactive power by voltage amplitude ( V1 ,
k v ki A
V2 ).
1 + H v k v ki A
Gv ( s ) = (6) Further, we can get:
§ H i ki A ·
s 2 LC + sC ¨ RL + ¸ +1 kV 2
© 1 + H v k v ki A ¹ ΔPi = i o Δθ i (19)
X
Here, we select the signal filters as follows: The varying of output voltage phase is implemented by
varying the output voltage frequency:
206
d(Δθ i ) 6 show the frequency and circular current between two
Δf i = (20) inverters respectively.
dt
So we can get the equation: From Fig.5 and 6, we can see that the frequencies are
X d(ΔPi ) adjusted quickly and there is little error between two
Δf i = (21) inverters’ frequencies after 0.5 s, the inverters are
kiV02 dt
almost synchronized after 1 s and the average frequency
Vo cos θ i errors of two inverters are 0.00003. From Fig 6, we can
ΔQi = ΔVi (22)
X see that the circular current is decreased distinctly after
Though voltage and frequency drooping is a effective 0.5 s to 0.7 A, which also implies the phase error is a
method, there are also defects [9]. For the frequency key factor to the system. The adjusting process is
character is not only affected by real power P , also almost 0.5 s and the system comes into steady. The
affected by ΔP . At the same time, from the parallel results prove that the load sharing scheme is very
bus each inverter can get others real power and reactive effective.
power, which means that each inverter knows other’s 7DE6LPXODWLRQ3DUDPHWHUV
statement and that information is very useful to
implement load sharing control, therefore the drooping Parameter Value
method can take other’s statement into consideration. Output Power 3 kVA
f n +1 = f n + k1 Δ P − k 2 Pn +1 (23) Voltage, Frequency 220 V, 50 Hz
where: Capacitance 20 ȝF
1 N
ΔP = ε ( Pn +1 − Pn ) + (1 − ε )( ¦ Pin − Pn ), 0˘ ε İ1 (24) Inductance 1 mH
N i =1 RL, τ 1 0.02 Ω , 0.5 ȝs
Similar to equation (23), we can get: kv , A 0.74, 0.95
Vn +1 = Vn + k3ΔQ − k4 (Vn +1 − Vn ) (25)
H i ( s ) , H r (t ) 0.93, 0.015+0.1( cos 2ω t + 1 )
where:
1 N ki , k1 , k2 1.87, 8e -9, 3e -9
ΔQ = ¦ Qi − Qn (26) k3 , k 4 , ε
N i =1 0.08, 0.5, 0.5
207
though we choose the low power factor cos φ with 0.6,
in Fig. 7 and 8, the output voltages and currents of two
6 CONCLUSION
inverters still have little errors about 0.34 A and 3.1 V, In this paper, an efficient control scheme is proposed
which ensure the little circular currents error and load for parallel operating single phase inverters, which
sharing. To some extend, output voltages and currents ensures that each inverter is equal and system
are misshapen, but in such lower factor condition, the redundant structure. A feedback controller increases the
results are reasonable. The results imply the parallel loop gain and ensures stability for smaller load currents
system has power capability to bear non-linear loads. and rectifier loads. An improved droop method is also
proposed for the inverter parallel operation, which
adaptively controls the reference voltage of each
inverter. This improves the output voltage regulation
and the current sharing. For engineering practical
project application and detailed requirements for power
supply, negligible influence by factors such as
nonlinear and instability of system are taken to careful
consideration. Two 3 kVA forward converters are built
and parallel connected for the experimental set up.
Simulation and experimental results verify the excellent
performance of the proposed method. The experimental
Fig.7 Output current of each inverter with results with those loads shows that each inverter’s
non-liner load output current error is less than 1% rating current.
REFERENCES
[1] Garabandic D S, Petrovic T B. Modeling Parallel
Operating PWM DC/DC Power Supplies. IEEE Trans. on
Industrial Electronics, October 1995,42 (5): 545-551.
[2] Rajagopalan J, Xing K, Guo Y, Lee F C, Manners B.
Modeling and Dynamic Analysis of Paralleled DC/DC
Converters with Master-Slave Current Sharing Control //
Proc. of the 1996 Power Electronics Specialists Conference,
1996:678-684.
[3] Jou Hurng-liahng, Wu Jinn-chang. A New Parallel
Processing UPS with the Performance of Harmonic
Suppression and Reactive Power Compensation//EEE
Fig.8 Output voltage of each inverter with PESC’94, 1994:1443-1450.
non-liner load [4] Joachim Holtz, Wolfgang Lotzkat, Karl-Heinz Werner.A
High-power Multitransistor-Inverter Uninterruptible Power
From Fig.9, it is clear that two inverters can bear the Supply System. IEEE Trans. Power eletronics, 1988, 3 (1):
rectified loads well and the output current waveforms 278-285.
are better than that in Fig.9 also demonstrates the [5] Joachim Holtz, Karl-Heinz Werner. Multi-Inverter UPS
System with Redundant Load Sharing Control. IEEE Trans.
validity of virtual impendence. Industrial Electronics, 1990,37 (6): 506-513.
[6] Kawabata T, Miyashita T, Saahida N, Yamamoto Y. Three
Pahse Parallel Processing UPS Using Multi-functional
Inverter//IEEE IAS’89, 1989: 982-987.
[7] Lars Thorsell, Lindman Per. Reliability Analysis of a
Direct Parallel Connected n+1 Redundant Power System
Basedon Highly Reliable DC/DC Modules. INTELEC-88,
1988, 24(2): 551-556.
[8] P De Visschere, Kuyken H, Baert D. A new way for
controlling a stand-alone DC/AC converter. International
Journal of Electronice, 1985, 58 (6): 957-980.
[9] Choi H S, Cho B H, A novel droop method for converter
parallel operation. IEEE Trans. on Power Electronics,
January 2002,17: 25-32.
Fig.9 Output voltage and current of one inverter
with rectified load
208