TRIBHUVAN UNIVERSITY

INSTITUTE OF ENGINEERING
DEPARTMENT OF ARCHITECTURE
PULCHOWK CAMPUS

BUILDING SERVICES-II

A
DESIGN REPORT ON

LIGHTING DESIGN IN
COMMERCIAL BUILDING

SUBMITTED BY:- SUBMITTED TO:-


Priyanka Shah Er. SANGEET LAL NAKARMI
(072/B.Arch/227) Department of Electrical Engineering
Rachana Shangroula
(072/B.Arch/228)
Sarika Regmi
(072/B.Arch/237)
ACKNOWLEDGEMENT

I would like to express heartfelt thanks to our course guide Er. Sangeet Lal Nakarmi for giving
us this project as well to the Dept. of Architecture for including this project in the course. I really enjoyed
doing this project. On the course of study, I had a chance to know about lighting in various types of
building areas and their importance.

Special gratitude goes to our seniors and colleagues who helped during this project. As well to our
teacher without whose guidance it was impossible to prepare this report.

Priyanka Shah (072/B.Arch/227)


Rachana Shangroula (072/B.Arch/228
Sarika Regmi (072/B.Arch/237)
CONTENTS
Page No.

1. Description of Building
2. Types of Luminaries Used
3. Lighting System Design
4. Calculation of Area of Conductor
5. Transformer Selection
6. Comments and Conclusion
7. Bibliography

1) DESCRIPTION OF BUILDING

The building is Complex kawpa which is a commercial complex having five floors with a basement area
for parking. The areas allocated are commercial spaces. The Ground floor consists departmental store, car
showroom, bike showroom, retail shops. The First floor consists of departmental store, boutique, furniture
showroom, liquor shop, jewelry shop, accessories shop, mobile shop, shoe shop, bag shop, beauty parlor.
The second floor consists of FM studio, staff rooms, kids corner, restaurants ,computer showroom, tailor
etc. The outdoor spaces consists of parking and planned landscaping.

Formula used during calculations:


1) CALCULATION OF LUMINARIES

Number of luminaries (N) = (E x A)/ (Ф x µu x µm)


Where,
N= no. of luminaries
E = required illumination level
A = area in which illumination is required
Ф = lumen output of luminaries
µu = utilization coefficient
µm = maintenance factor

2) SELECTING AREA OF CONDUCTOR

A= (1.5 x I x k x L)/ (permissible voltage drop)


Where,
A= area of conductor
I= current through the conductor
K=0.02 for copper
0.03 For aluminum
L= length of conductor
Permissible voltage drop allowed is 2%
7) TYPES OF LUMINARIES USED:

Description- Type of lamp Make/Model No. Output(LUMEN)


LED 6 fiamFDS001 SMD 6W 468
led -12 fiamFDS001 SMD 12W 936
led -18 fiamFDS001 SMD18W 1404
led-24 fiamFDS001 SMD24 W 1872
led-36 fiamFDS001 SMD 36W 2800
led-40 fiamFDS029 SMD 40W 3120
led - 50 fiamFDC201 COB 3900
led -20 1*20 W LED TL 2700

Legend:
LED 6
led -12
led -18
led-24
led-36
led-40
led - 50
led -20
1 ) power socket
2)SDB
3)MDB
4)Switch
8) LIGHTING SYSTEM DESIGN

CALCULATION
Calculation of Lighting Loads

A.BASEMENT FLOOR PLAN


 MCB-1
Room/Space No. of bulbs Wattage of each bulb Total Wattage
Store 10 12 120
parking 10 20 200

WATTAGE = 320W
CURRENT = 320/ (220*0.8) = 1.8A
THEREFORE, 1L= 2.5A
 MCB-2
Room/Space No. of bulbs Wattage of each bulb Total Wattage
Store 6 12 72
parking 6 20 120
maintenance room 15 12 180

WATTAGE = 372W
CURRENT = 372/ (220*0.8) = 2.1A
THEREFORE, 1L= 2.5A
 MCB-3
Room/Space No. of bulbs Wattage of each bulb Total Wattage
parking 20 20 400

WATTAGE = 400W
CURRENT = 400/ (220*0.8) = 2.27A
THEREFORE, 1L= 2.5A

TOTAL POWER SOCKETS IN SDB = 9

There are 3 lighting MCB


7 power MCB

B. GROUND FLOOR PLAN


I. FOR SDB 1
 MCB 1 ( 1L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


lobby 26 24 624
Toilet 17 6 102
stairs 2 12 24

WATTAGE = 750W
CURRENT = 750/ (220*0.8) = 4.2A
THEREFORE, 1L= 6A
 MCB 2 ( 2L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Retail shops 8nos 4x8=32 24 768
stairs 2 12 24

WATTAGE = 768W
CURRENT =768/ (220*0.8)= 4.3A
THEREFORE, 2L=6A

 MCB 3 (3L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Departmental store(up) 20 50 1000

WATTAGE = 1000W
CURRENT =1000/ (220*0.8) = 5.68A
THEREFORE, 2L=6A

 MCB 4 (4L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Departmental store(side) 14 50 700

WATTAGE = 700W
CURRENT =700/ (220*0.8) = 3.9A
THEREFORE, 2L=6A

 MCB 5(5L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Departmental store(side) 12 50 600
Retail shops 2nos 6x2 24 288

WATTAGE = 888W
CURRENT =888/ (220*0.8) = 5.04A
THEREFORE, 2L=6A

 MCB 6 (6L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Retail shops 7 nos 4x4+6x3=34 24 816

WATTAGE = 816W
CURRENT =816/ (220*0.8) = 4.6A
THEREFORE, 2L=6A
TOTAL POWER SOCKETS IN DB 1 = 9

There are 6 lighting MCB


9 power MCB

II. FOR SDB 2

 MCB 1 (1L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Retail shops 24 24 576
lobby 5 24 120
stairs 2 12 24
store 6 12 72
office bike showroom 2 24 48

Wattage = 840
Current = 840/ (220*0.8) = 4.7A
THEREFORE, 1L = 6A

 MCB 2 (2L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


lobby 40 24 960

Wattage = 960W
Current =960/ (220*0.8) = 5.4
THEREFORE, 2L=6A

 MCB 3

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Bike showroom 16 50 800
ATM 2 12 24

Wattage = 960W
Current =960/ (220*0.8) = 5.4
THEREFORE, 3L=6A

 MCB 4 (4L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Car showroom 21 50 1050

Wattage = 1050
Current = 1050/ (220*0.8) = 5.9A
THEREFORE, 4L = 6A

 MCB 5 (5L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Car showroom 12 50 600
Car showroom 4 50 200
Retail shop 6 24 144
office 2 24 48

Wattage = 992
Current = 992/ (220*0.8) = 5.6A
THEREFORE, 5L = 6A

 MCB 6 (6L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Car showroom 21 50 1050

Wattage = 1050
Current = 1050/ (220*0.8) = 5.9A
THEREFORE, 2L = 6A

TOTAL POWER SOCKETS IN DB 2 = 9


There are 6 lighting MCB

A. FIRST FLOOR PLAN

I. FOR SDB 1

 MCB 1 (1L)
Room/Space No. of bulbs Wattage of each bulb Total Wattage
lobby 12 24 288
Toilet 18 6 108
stairs 1 36 36

Wattage = 432
Current = 432/ (220*0.8) = 1.57A
THEREFORE, 1L = 2.5 A
 MCB 2 (2L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Ladies accessories 18 36 648
Gents Accessories 7 36 252

Wattage = 900
Current = 900/ (220*0.8) = 5.11A
THEREFORE, 2L = 6 A

 MCB 3 (3L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Mobile shop 9 36 324
Gents Accessories 13 36 468

Wattage = 792
Current = 792/ (220*0.8) = 4.5A
THEREFORE, 3L = 6 A

 MCB 4 (4L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Mobile shop 9 36 324

Wattage = 324
Current = 324/ (220*0.8) = 1.84A
THEREFORE, 4L =2.5 A

 MCB 5 (5L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Jewellery shop 27 36 972

Wattage = 972
Current = 972/ (220*0.8) = 5.52A
THEREFORE, 5L =6 A

 MCB 6 (6L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Department store 13 50 650

Wattage = 650
Current =650/ (220*0.8) = 3.69A
THEREFORE, 6L =6 A

 MCB 7 (7L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Department store 8 50 400

Wattage = 400
Current =400/ (220*0.8) = 2.27A
THEREFORE, 7L =2.5 A

 MCB 8 (7L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Department store 20 50 1000

Wattage = 1000
Current =1000/ (220*0.8) = 5.68A
THEREFORE, 8L =6 A

 MCB 9 (9L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Department store 9 50 450

Wattage = 450
Current =450/ (220*0.8) = 2.55A
THEREFORE, 9L =6 A

 MCB 10 (10L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Shoe shop 21 36 756

Wattage = 756
Current =756/ (220*0.8) = 4.3A
THEREFORE,10L =6 A

TOTAL POWER SOCKETS IN DB 1 = 6


There are 10 lighting MCB
6 power MCB

II. FOR SDB 2


 MCB 1 (1L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Bag shop 21 36 756

Wattage = 756
Current =756/ (220*0.8) = 4.3A
THEREFORE,1L =6 A

 MCB 2 (2L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Liquor shop 9 36 324
Staircase 1 36 36

Wattage = 360
Current =360/ (220*0.8) =2.04A
THEREFORE,2L =2.5 A

 MCB 3 (3L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Boutique 23 36 828
Changing room 2 12 24

Wattage = 852
Current =852/ (220*0.8) =4.84A
THEREFORE,4L =6 A

 MCB 4 (4L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Lobby 18 24 432
Wattage = 432
Current =432/ (220*0.8) =2.45A
THEREFORE,4L =6 A

 MCB 5 (5L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Beauty parlour 13 36 468
Facial room 6 12 72
Hairwash 6 12 72
Washroom 2 12 24
Store 2 12 24
Wattage = 660
Current =660/ (220*0.8) =3.75A
THEREFORE,5L =6 A

 MCB 6 (6L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Furniture showroom 20 50 1000

Wattage = 1000
Current =1000/ (220*0.8) =5.68A
THEREFORE,6L =6 A

 MCB 7 (7L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Furniture showroom 13 50 650

Wattage = 650
Current =650/ (220*0.8) =3.7A
THEREFORE,7L =6 A

 MCB 8 (8L)
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Ladies Accessories 4 36 144
Furniture showroom 12 50 600

Wattage = 744
Current =744/ (220*0.8) =4.22A
THEREFORE,8L =6 A

TOTAL POWER SOCKETS IN DB 2 = 6


There are 8 lighting MCB
6 power MCB

B. SECOND FLOOR PLAN

I.FOR SDB 1

 MCB 1 ( 1L)

Room/Space No. of bulbs Wattage of each Total Wattage


bulb
Restaurant indoor 16 24 384
outdoor 16 24 384
total 768
WATTAGE = 768W
CURRENT = 768/ (220*0.8) = 4.6A
THEREFORE, IL=6A

 MCB 2 ( 2L)

Room/Space No. of bulbs Wattage of each Total Wattage


bulb
Kitchen 6 24 144
store 4 24 96
wash area 2 24 48
foyer space 4 24 96
total 384

WATTAGE = 384
CURRENT =384/ (220*0.8) 2.18
THEREFORE, 2L= 2.5 A

 MCB 3 -3L

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Kids corner 36 24 864

WATTAGE = 864
CURRENT =864 /(220*0.8)
THEREFORE, 3L = 6A

 MCB 4 - 4L

Room/Space No. of bulbs Wattage of Total Wattage


each bulb
1 meeting room 12 24 288
2.G.M room 4 18 72
3.M. M room 4 18 72
4.library 6 36 216
Stair 2 36 72
Inner corridoor 12 24 288
Total 1008

Wattage = 648
Current =1008/ (220*0.8) = 5.7
THEREFORE, 4l=6A

 MCB 5 - 5L

Room/Space No. of bulbs Wattage of each bulb Total Wattage


FM studio 24 24 576
store 2 12 24
pantry 2 24 48
restroom 6 18 108
Total 756

Wattage = 756
Current = 756/(220*0.8)
THERFORE 5 L = 6 A
Total power socket in dB 1 = 9
Lighting system = 5
For SDB -2

MCB 1 - 1L
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
Computer showroom ( 12 50 600
indoor)
computer showroom ( 9 24 216
outdoor)
maintance room 6 24 144
manager room 4 18 72
Total 1032

wattage =1032
Current l = 1032 / (220*0.8)
1l = 6 A

 MCB 2 = 2L
Room/Space No. of bulbs Wattage of each bulb Total Wattage
Shirting and suiting 14 50 700
tailor 4 40 160
Total 860

Wattage = 860
Current l = 860 / (220*0.8)
2L = 6 A

FOR MCB 3 (3L)

Room/Space No. of bulbs Wattage of each Total Wattage


bulb
Staff room 14 36 504
toilets 2 24 48
control room 8 24 192
Total 744

Wattage = 744
Current l = 744 / (220*0.8)
3L = 6 A
FOR MCB 4 = 4 L
Room/Space No. of bulbs Wattage of each Total Wattage
bulb
News room 6 40 240
broadcasting room 6 24 144
Total 384
wattage = 384
Current l = 384 / (220*0.8)
THEREFORE 4L = 2.5 A

FOR MCB 5 (5L)

Room/Space No. of bulbs Wattage of each bulb Total Wattage


Stair 2 36 72
Lobby 19 24 456
total 528

Wattage = 528
Current l = 538/ (220*0.8)
Therefore 5 l = 6 A

Therefore total no of power socket in SDB 2= 9


Lighting system = 5

10) CALCULATION OF AREA OF CONDUCTOR

For light Circuit: PVC insulated copper conductor of area 1.3 mm2 (3/22), can carry 11A current
safely.
For power sub Circuit: PVC insulated copper conductor of area 4mm2 (2* 7/22+ 1* 3/222).
For MDB to SDB : 3 and ½ core cu conductor.

Leading from main DB to various floors


1.Leading from main DB to Basement floor

2.Leading from main DB to Ground floor


a) For TPMCCB 1
A≥ (1.5* I * k * L)/ (Permissible voltage drop)
L = 4m+23m
k = 0.02
I = 30 A
Permissible voltage = 2% of 220 V = 4.4 V

A≥(1.5* 30*0.02*27)

A≥ 24.3 mm2
Hence,
A≥ 24.3mm2
From table, nearest conductor size is 25 mm2 having the current carrying capacity of 68 A
for Cu conductor laid in duct. Hence the size of conductor used is of 25 mm2 having current
carrying capacity 68A.

b) For TPMCCB 2
A≥ (1.5* I * k * L)/ (Permissible voltage drop)
L= 4m
k = 0.02
I = 30A
Permissible voltage = 2% of 220
= 4.4 V
Hence,
A≥ (1.5*30*0.02*4) mm2
A≥ 3.6 mm2

From table, nearest conductor size is 4 mm2 having the current carrying capacity of 30 A
for Cu conductor laid in duct. Hence the size of conductor used is of 4 mm2 having current
carrying capacity 30A.

3.Leading from main DB to First floor


a) For TPMCCB 1
A≥ (1.5* I * k * L)/ (Permissible voltage drop)
L = 8m+23m
k = 0.02
I = 30 A
Permissible voltage = 2% of 220 V = 4.4 V

A≥ (1.5* 30*0.02*31)

A≥ 27.9 mm2
Hence,
A≥ 27.9mm2
From table, nearest conductor size is 35 mm2 having the current carrying capacity of 99 A
for Cu conductor laid in duct. Hence the size of conductor used is of 35 mm2 having current
carrying capacity 99A.

b) For TPMCCB 2
A≥ (1.5* I * k * L)/ (Permissible voltage drop)
L= 8m
k = 0.02
I = 30A
Permissible voltage = 2% of 220
= 4.4 V
Hence,
A≥ (1.5*30*0.02*8) mm2
A≥ 7.2 mm2

From table, nearest conductor size is 10mm2 having the current carrying capacity of 50 A
for Cu conductor laid in duct. Hence the size of conductor used is of 10 mm2 having current
carrying capacity 50A.

4.Leading from main DB to Second floor


a) For TPMCCB 1
A≥ (1.5* I * k * L)/ (Permissible voltage drop)
L = 12m+23m
k = 0.02
I = 30 A
Permissible voltage = 2% of 220 V = 4.4 V

A≥ (1.5* 30*0.02*35)

A≥ 31.5 mm2
Hence,
A≥ 35mm2
From table, nearest conductor size is 35 mm2 having the current carrying capacity of 99 A
for Cu conductor laid in duct. Hence the size of conductor used is of 35 mm2 having current
carrying capacity 99A.

b) For TPMCCB 2
A≥ (1.5* I * k * L)/ (Permissible voltage drop)
L= 12m
k = 0.02
I = 30A
Permissible voltage = 2% of 220
= 4.4 V
Hence,
A≥ (1.5*30*0.02*12) mm2
A≥ 10.8 mm2

From table, nearest conductor size is 16mm2 having the current carrying capacity of 64 A
for Cu conductor laid in duct. Hence the size of conductor used is of 16mm2 having current
carrying capacity 64A.

11) TRANSFORMER SELECTION

Current through the MDB = 100A


Power = 3*Vp*Ip
=3* 220 *100
= 66 KVA
Hence, we select the Transformer of 66 KVA.
Voltage ratio: 11/0.4 KV
Transformer type: Three phase single Unit

12) COMMENTS AND CONCLUSION


The lighting design is completed for a semipublic complex with considering all possible factors to
fulfill lighting necessity of the health club complex. The complex is supplied by 66KVA, 11/0.4 KV 3
phase step down transformer to MDB placed inside the electrical room in the . From MDB 3
phases is supplied to each SDB from where single phase is supplied to each sub-circuit in each room. Care
has been given to balance the load in each phase as far as possible.
Though this project does not fulfill every requirement for complete electrification, however it
covers most of the design and can be taken as a base for electrification for the particular complex.

Bibliography

1. Course Manual on Building Services II, By Narad Muni Bhandari


2. Class Notes, By Er. Sangeet Lal Nakarmi
3. www.gelightings.com
4. Reports, By seniors
5. www.google.com
6. Different types of lighting manual