CLIENT : DESIGN BY :
JOB NO. : DATE : REVIEW BY :
Light Gage Truss Design Based on AISI S100/SI-10 & ESR-3064P
CONTINUED TOP CHORD (from 0 to 6 & from 6 to 11) 2 x 1200S250-97 (33 ksi) < == (TOTAL SECTION: 12 in Ht. x 5 in Thk.)
CONTINUED BOTTOM CHORD (from 0 to 11) 2 x 600S250-54 (33 ksi) < == (TOTAL SECTION: 6 in Ht. x 5 in Thk.)
ALL WEB MEMBER SIZE 600S162-54 (33 ksi) SLOPED DEAD LOADS DL = 300 lbs / ft
PROJECTED LIVE LOADS LL = 240 lbs / ft
TRUSS SPAN LENGTH L= 24 ft
TRUSS DEPTH H= 4 ft POINT DEAD LOADS P2-DL = P10-DL = 0.5 kips
P4-DL = P8-DL = 0.4 kips
THE TRUSS DESIGN IS ADEQUATE.
ANALYSIS
DESIGN CRITERIA
1. The intermediate finite element analysis include shear deformations using E & G equal to 29500 ksi & 11300 ksi.
2. There are different rotations at same joint of web to chord, since web pinned to continued chord.
3. Top chord shall be fastened to sheathing before vertical load added.
HEIGHT h = 4.21637021 ft
ANALYSIS
SECTION PROPERTIES OF EACH VERTICAL STUD (SSMA page 8 to 14)
thk = 0.1017 in Fy = 33 ksi Ixx = 34.016 in4 Mn/Wb = 102.52 in-kips
t = 12 in Wt = 6.05 lb/ft Sxx = 5.496 in3 Vn/Wv = 7411 lbs
A = 1.779 in2 rx = 4.373 in ry = 0.794 in xo = -1.329 in
CHECK COMPRESSION CAPACITY WITH, AT LEAST, ONE FLANGE THROUGH-FASTENED TO SHEATHING (AISI D6.1.3)
Pn/Wc = 18.54 kips > P [Satisfactory]
Where Wc = 1.8
Pn = C1C2C3 AE / 29500 = 33.37 kips
C1 = (0.79 x + 0.54) = 0.942
C2 = (1.17 a t + 0.93) = 1.049
C3 = a (2.5b - 1.63d) + 22.8 = 9.490
E= 29500 ksi (AISI pg xiv)
P= 0.05 kips (included studs weight.)
CHECK CAPACITY COMBINED BENDING & SHEAR AT ANY SAME SECTION (AISI C3.3.1)
2 2
bM vV
= 0 < 1.0 [Satisfactory]
Mn Vn
M V
0.6 b v = 0 < 1.3 [Satisfactory]
Mn Vn
(cont'd)
CHECK CAPACITY COMBINED AXIAL LOAD & BENDING (AISI C5.2.1)
cP b C mM
0.00 < 1.0 [Satisfactory]
Pn M n
Where M= 0.00 ft-kips, (1/1.4 included)
P= 0.05 kips
Pn/Wc = 18.54 kips
Mn/Wb = 17.09 in-kips
Cm = 1.0
2E I x
P Ex 7737.40 kips
K xL x 2
cP
1 1.000
P Ex
CHECK DEFLECTION
5w L4
0.00 in < h /240 = 0.21 in [Satisfactory]
384 EI
NOTE : 1. STUD FLANGES SHALL BE FASTENED TO SHEATHING AT EACH SIDE OF WALL BEFORE VERTICAL LOAD ADDED.
Technical References:
1. AISI S100/SI-10, North American Specification for the Design of Cold-formed Steel Structural Members, with Supplement 1, 2010.
2. SSMA_Product_Technical_Guide, ESR-3064P, Steel Stud Manufactures Association, 2015.
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE: REVIEW BY :
Brace Design Based on AISI S100/SI-10 & ESR-3064P
ANALYSIS
NOTE : THE LATERAL LOADS MAY BE REDUCED BY (1/1.4) PER AISI APPENDIX A.4.1.2 .
Technical References:
1. AISI S100/SI-10, North American Specification for the Design of Cold-formed Steel Structural Members, with Supplement 1, 2010.
2. SSMA_Product_Technical_Guide, ESR-3064P, Steel Stud Manufactures Association, 2015.
PROJECT : PAGE :
CLIENT : DESIGN BY :
JOB NO. : DATE: REVIEW BY :
Jamb/Column Design Based on AISI S100/SI-10 & ESR-3064P
HEIGHT h= 24 ft
ANALYSIS
SECTION PROPERTIES OF EACH VERTICAL STUD (SSMA page 8 to 14)
thk = 0.0566 in Fy = 33 ksi Ixx = 3.819 in4 Mn/Wb = 21.9 in-kips
t = 6 in Wt = 2.28 lb/ft Sxx = 1.159 in3 Vn/Wv = 1890 lbs
A = 0.67 in2 rx = 2.388 in ry = 0.917 in xo = -1.86 in
J = 0.000715 in 4 Cw = 4.194 in 6
CHECK COMPRESSION CAPACITY WITH, AT LEAST, ONE FLANGE THROUGH-FASTENED TO SHEATHING (AISI D6.1.3)
Tn/Wt = 22.11 kips > T [Satisfactory]
Where Wc = 2
Pn = C1C2C3 AE / 29500 = 44.22 kips
C1 = (0.79 x + 0.54) = 0.949
C2 = (1.17 a t + 0.93) = 0.996
C3 = a (2.5b - 1.63d) + 22.8 = 19.270
E= 29500 ksi (AISI pg xiv)
T= 12.86 kips (included studs weight.)
CHECK CAPACITY COMBINED BENDING & SHEAR AT ANY SAME SECTION (AISI C3.3.1)
2 2
bM vV
= 0.2958 < 1.0 [Satisfactory]
Mn Vn
M V
0.6 b v = 0.24193 < 1.3 [Satisfactory]
Mn Vn
(cont'd)
CHECK CAPACITY COMBINED AXIAL LOAD & BENDING (AISI C5.2.1)
cP b C mM
0.87 < 1.0 [Satisfactory]
Pn M n
Where M= 0.75 ft-kips, (1/1.4 included)
P= 12.86 kips
Pn/Wc = 22.11 kips
Mn/Wb = 3.65 in-kips
Cm = 1.0
2E I x
P Ex 26.81 kips
K xL x 2
cP
1 0.041
P Ex
CHECK DEFLECTION
5w L4
0.00 in < h /240 = 1.20 in [Satisfactory]
384 EI
NOTE : 1. STUD FLANGES SHALL BE FASTENED TO SHEATHING AT EACH SIDE OF WALL BEFORE VERTICAL LOAD ADDED.
Technical References:
1. AISI S100/SI-10, North American Specification for the Design of Cold-formed Steel Structural Members, with Supplement 1, 2010.
2. SSMA_Product_Technical_Guide, ESR-3064P, Steel Stud Manufactures Association, 2015.