Vous êtes sur la page 1sur 7

See discussions, stats, and author profiles for this publication at: https://www.researchgate.

net/publication/263405825

Comparative Study of Protection CT Modeling Under Transient Conditions

Conference Paper · May 2014

CITATIONS READS

0 1,117

5 authors, including:

Aurélio Coelho Paulo Roberto Mattos da Silveira


Universidade Federal de Itajubá (UNIFEI) - Campus Itabira 72 PUBLICATIONS   547 CITATIONS   
28 PUBLICATIONS   44 CITATIONS   
SEE PROFILE
SEE PROFILE

Carlos A. V. Guerrero Benedito Donizeti Bonatto


Universidade Federal de Itajubá (UNIFEI) Universidade Federal de Itajubá (UNIFEI)
10 PUBLICATIONS   30 CITATIONS    74 PUBLICATIONS   236 CITATIONS   

SEE PROFILE SEE PROFILE

Some of the authors of this publication are also working on these related projects:

Impact of Electricity Theft on Power Quality View project

Microgrids: Operation and Control View project

All content following this page was uploaded by Diogo Marujo on 26 June 2014.

The user has requested enhancement of the downloaded file.


Comparative Study of Protection CT Modeling Under
Transient Conditions
Aurélio L. M. Coelho, Paulo M. da Silveira, C. V. Guerrero, B. D. Bonatto and Diogo Marujo
Universidade Federal de Itajubá (UNIFEI)
Centro de Excelência em Redes Inteligente (CERIn)
Itajubá (MG), Brasil

Abstract—This paper presents the results of an investigation Committee) [5,6,9] in order to observe the CT behavior,
about current transformers (CTs) transient behavior and the especially under several fault conditions and secondary
factors that can lead its core to saturate. For this study, two burden.
methodologies are used: CT model implemented in MATLAB
and CT modeling using ATP. The results of this analysis are In section III, a similar approach is performed. It is shown
compared in order to validate the models and the main how to model a CT in ATP in order to examine the factors that
conclusions are presented. cause CT saturation.

Index Terms--Current Transformer, Modeling, Saturation,


Finally, the secondary current waveforms resulting from
Transient Analysis. each model are presented and compared to validate the CT
transient analysis in section IV. The evaluations of these tests
I. INTRODUCTION are based on existing standards [5] and the simulation results.
It is well known that one of the Current Transformer (CT) II. PSRC CT MODEL
functions is provide access to high current of the primary Based on the theory published by IEEE PSRC [9], the
system through reduced replica on its secondary side, allowing algorithm implemented in MATLAB is intended to provide a
timely and correct identification of faults and disturbances by quick indication, not only the existence of CT saturation in a
protective relays. However, the CT core has non-linear particular application, but also an accurate indication of the
magnetic characteristics and, if subjected to high fault secondary current waveform, in such way that the saturation
currents, may achieve high flux values. In this case, the flux degree can be visualized as a function of time.
density may be beyond the core capacity, characterizing the
saturation phenomenon. As a result, the CT primary current is One of the difficulties in using an elaborated model is to
not fully reflected in their secondary side and, depending on obtain the parameters for a particular case in order to
the saturation degree, the current seen by the relay can be implement this model with facility, efficiency and accuracy
considerably reduced and distorted in relation to the ideal [9]. For example, the excitation current in the region below of
secondary signal. So, the relay cannot operate in the desired the knee point is a complex combination of magnetization,
time. For this reason, a fully understanding of the CT transient hysteresis and elements of eddy currents. These parameters are
behavior has great relevance for the study of electrical systems not generally known in a particular case. However, if the
protection. excitation current waveform reaches the saturated region, the
part of the waveform in the region below of the knee point has
Several papers have been published concerning the CTs an insignificant effect on the global solution. For [9], this
modeling and their performance under transient conditions [1- simplifies the solution without much effect on accuracy.
4]. Most of these publications are used the ATP (Alternative Therefore, taking into account this fact, the hysteresis and
Transients Program) software to perform this study. eddy current losses are not considered in the implemented
In order to verify the effectiveness of the ATP CT model, model. When it is desired to evaluate the errors under low
this paper presents an additional tool implemented to analyze current, where the low burden conditions are of interest, a
the CT response under transient conditions. In the section II is more elaborate model should be used, which is not the concern
shown all the mathematical development of the CT model of this work.
implemented in MATLAB that is based in the theory The CT equivalent circuit which generates the mathemati-
published by the IEEE PSRC (Power System Relay cal model (the equations and boundary conditions) to obtain
the current resulting from the algorithm implemented in
This work was supported in part by CAPES, CNPq and FAPEMIG, Brazil. MATLAB is represented in Fig. 1.
in function of time is represented by (3):

(3)

Thus, the excitation current expressed in (3) must be


defined to determine the secondary current in function of time.
The saturation curve that relates the excitation secondary
Figure 1. Equivalent Circuit of the IEEE PSRC CT Model.
voltage and the excitation current in rms values, presented in
IEEE Std. C57.13 [8], is used in this model. However, for
The parameters of circuit represented in Fig.1 are: simplification, only two parameters are extracted from the
excitation curve: (i) the slope (S) of saturated section and (ii)
Instantaneous primary current; the saturation voltage (Vsat) for which the excitation current is
10 [A] [1].
Instantaneous ideal secondary current;
According to the IEEE Std. C37.110 [7], the saturation
Instantaneous real secondary current; maximum voltage value for a secondary current of 20 times
Instantaneous excitation current; the rated CT is determined for an excitation current of 10 [A].
Instantaneous excitation voltage; In this model, the flux (λ) versus excitation current (ie)
curve has been used to solve the implicit differential equations
Number of CT turns; in the circuit illustrated in Fig. 1. This curve is defined by (4):
Secondary winding resistance;
| | (4)
Burden resistance;
Burden inductance; where “A” is a constant of the model defined in [9].
 radian frequency = 2πf; f = 60Hz. Note in (4) that in order to evaluate the excitation current
effects in the CT saturation it is necessary to determine the
A. PSRC CT Model Implemented in MATLAB flux evolution on CT core. For a computer implementation,
Through of Kirchhoff's Voltage Law, the circuit shown in this flux can be calculated in relation of its variation (Δλ) in
Fig. 1 is described by (1): the time, as well as in function of the remanent flux (λrem)
multiplied by the flux peak value in the saturation point (λsat),
if there is remanence.
( ) ( ) (1)
The implemented algorithm requires an initial flux value to
start the simulation. In mathematical terms, this consideration
where Rt is the total resistance in the CT secondary side, i.e., is expressed by (5):
the sum of the burden resistance with the secondary winding
resistance. ( ) (5)
Considering the circuit shown in Fig. 1 under fault
conditions, the CT instantaneous ideal secondary current, in By Faraday's Law, the flux (λ) is related to the instantane-
function of time (t), has its symmetry and/or asymmetry ous excitation voltage (ve) as given by (6):
expressed by (2):
(6)
√ ( ) (2)
On the other hand, the excitation curve is obtained from a
where Ip is the rms fault current and K is the factor that sinusoidal excitation voltage, given by (7):
determines the characteristics of the secondary current
waveform, so: √ ( ) (7)
 K = 1, when there is asymmetric component in the
fault current. In this case, τ =1/(X/R) is the time con- implying that its flux (λ) will be also sinusoidal.
stant of the system under fault, where X and R are the
reactance and resistance of the power system until the Combining (6) and (7) it is obtained (8), given by:
fault point, respectively;
 √
K = 0, when there is only symmetric component in ( ) (8)
the fault current.
In practice, the excitation current is nonzero and its The flux peak value at the saturation point (λ sat) in this
magnitude determines how much the primary current will be model is defined at the point where the excitation current is 10
reflected erroneously in the CT secondary side. Thus, as [A], i.e., where the excitation voltage (Ve) corresponds to the
shown in the circuit of Fig. 1, the CT actual secondary current saturation voltage (Vsat). Thus, from (8) is obtained (9) given
by: a saturable power transformer in ATP, as illustrated in Fig.2.

√ (9)

The remanent flux (λrem) inserted in this model has its


value defined in per unit (p.u.), as the ratio of a voltage below
the knee point (Vknee) by the saturation voltage (Vsat), as
expressed in (10): Figure 2. Saturable power transformer model in ATP.

The parameters of the equivalent circuit of the saturable


(10) power transformer model of ATP, shown in Fig. 2, are
specified by:

Finally the flux variation (Δλ) is obtained from the : Number of turns of the primary winding;
derivative of the excitation current as a function of time, : Number of turns of the secondary winding;
present in (1). This current can be decomposed, as shown in
(11): : Primary winding resistance;
: Secondary winding resistance;
| | (11) : Primary winding inductance;
: Secondary winding inductance;
Thus, replacing (6) and (11) in (1), and manipulating them,
the flux is a function of time, as expressed by (12): : Magnetization resistance.
To reproduce a CT, C-class, based on the power trans-
former shown in Fig. 2, the following considerations about the
(12) CT parameterization on ATP should be observed [10]:
| |
 The CT secondary side is modeled in the primary
winding of the power transformer;
where dips/dt is defined from the derived of the ideal
 On the secondary winding of the power transformer,
secondary current (ips) expressed in (2).
set the resistor RS equals to zero and the inductance
LS to a value slightly greater than zero (10e-6, for
With the initial flux value obtained from (5), the initial example);
values of the excitation current and flux variation, expressed
 Set the inductor LP of the primary winding of the
in (4) and (12), respectively, are also determined.
power transformer to a value equals to zero, whereas
a C-class CT has leakage inductance almost negligi-
After obtaining the initial values, the flux evolution (λ) in ble;
the core as a function of time becomes given by its previous
 Set the resistor RP of the power transformer primary
values, as expressed in (13):
to a value equal to the resistance of the CT secondary
winding;
λ λ Δλ (13)  It should be add a circuit to represent the resistance
and inductance of CT burden;
where (n) is the index that indicates the actual flux position  Set the magnetization resistance RMAG to infinity,
and (n-1) is the previous position. since RMAG is very large. Enter "0" in the model of
ATP to a RMAG infinite;
 Select ten points of excitation current versus excita-
The implemented algorithm can solve all the presented
tion voltage from the CT saturation curve, to include
equations, and the following input data must be provided by
saturation in the model;
the program user: i) the rms value of symmetrical fault current
(Ip); ii) the presence or not of the asymmetry factor (K) in the  Convert these current versus voltage points into
fault current; iii) the X/R ratio of the power system until the current versus flux points using the ATP supporting
failure point, when K=1; iv) the burden values (Rb and Lb); v) routine called SATURA.
the secondary winding resistance (Rs ); vi) the turns ratio (N); A. ATP CT Model in a Power System
vii) the saturation voltage (Vsat); viii) the slope (S) of the
As well as the models presented in previous sections, the
saturated region of the excitation curve and ix) the remanent
data of CT saturation curve shown in IEEE Std C57.13 [8]
flux (λrem ) if necessary.
may be used in this model. From these curves are obtained the
With the correct information, the implemented program secondary winding resistance and the CT saturation voltage.
will provide as a result the CT secondary current waveform
Initially, it creates an *.atp file with the pairs of current
for several transient conditions.
and voltage obtained from the saturation curve. It is selected a
III. ATP CT MODEL point at the lower end of the curve, many points in the knee
region, and a point at the upper end of the curve. An example
This section shows how to perform the CT modeling from
of *.atp file with these points, is presented in Fig. 3. of R and L, it is possible to control the X/R ratio, which
determines the time constant of the primary circuit, as well as
the asymmetry degree of the CT current waveform.
With respect to the CT burden, this is represented in the
ATPDraw model by a impedance which can be easily varied
to check its influence on the CT secondary current.
IV. RESULTS AND DISCUSSION
This section presents the CT transient behavior for the two
presented CT models. For this study, the following CT
saturation factors are analyzed:
a) symmetrical fault current and burden value;
Figure 3. Example of *.atp file with data of CT saturation curve. b) asymmetric fault current and X/R ratio.
In order to examine these items it is used a CT C-class
The file illustrated in Fig. 3 is compiled and it generates a
300/5 [A], with the standard features presented in the guide
*.pch file, as shown in Fig. 4, which contains pairs of current
IEEE Std. C57.13 [8].
versus flux and also define the CT characteristic used in the
magnetization branch of the power transformer model used in A. Symmetric fault current and burden effects in CT transient
this study. response
High values of burden connected to the CT secondary side
result in increased core saturation and thus cause errors in the
current reflected in its secondary side. The reason for this is
that a given secondary current demands greater CT voltage for
Current an increase in the burden value. The flux density is
x proportional to this voltage.
Voltage
With respect to the fault current, it is fully symmetrical
when the angle of fault incidence in the voltage signal
Current waveform corresponds to the current crossing through zero.
x Theoretically, in an inductive purely circuit, this condition
Flux occurs when the voltage is maximum, i.e., the voltage angle
equals 90°.
The IEEE Std. C37.110 guide [7] suggests that CTs used
Figure 4. Example of *.pch file with data of CT saturation curve (current
versus flux) obtained from *.atp file. with protective relays be selected considering that maximum
symmetrical fault current does not exceed 20 times the CT
The circuit for analysis of the CT transient response may rated current and that load voltage does not exceed the voltage
be prepared in ATPDraw (*. adp file) as shown in Fig. 5. For of their accuracy class. Mathematically, the AC saturation can
the study purpose, this circuit is composed of five main be prevented from (7):
components: a primary voltage source (in this modeling, the
primary side of the power transformer is used as the CT (14)
secondary side, and vice-versa); a saturable transformer
model; a load that represents the CT burden; a load that where if is the maximum fault current in per unit of rating CT
represents the CT primary impedance and a switch for and zb is the CT burden in per unit of standard burden.
applying disturbances.
Two cases are selected to show the effects of the symmet-
ric fault current magnitude and burden values in CT
saturation, as indicated in Table I.

TABLE I. SIMULATED CASES TO VERIFY THE INFLUENCE OF THE SYMMETRIC


FAULT CURRENT MAGNITUDE AND BURDEN VALUES IN CT SATURATION.

Case if (p.u) zb (p.u) Equation (14)


Figure 5. CT circuit model implemented in ATPDraw. 1 8 10 20,0 < 80,0
2 20 1 20,0 = 20,0
In order to provide a fully symmetrical primary current for
the CT of the circuit shown in Fig.5, the RLC impedance According to the criteria defined in (14), there is only CT
value of the primary system should be set without reactive saturation in the case 1 presented in Table I. Figs. 6 and 7
portion. resulting of the implemented model in MATLAB and model
simulated in ATPDraw, respectively, for the case 1 present in
To provide an asymmetry primary current for the CT, the Table I.
RLC impedance value of the primary system should be set
considering the inductive reactive portion. From the variation
IEEE PSRC CT Model - Case 1 ATP CT Model - Case 2
40 100
Ideal
Ideal
30 Actual 80 Actual

20 60
Secondary Current (A)

40

Secondary Current (A)


10
20
0
0
-10
-20
-20
-40

-30 -60

-40 -80
-0.02 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Time (s)
-100
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Time (s)
Figure 6. Secondary signals resulting of the case 1 presented in Table I -
PSRC CT modeling in MATLAB.
Figure 9. Secondary signals resulting of the case 2 presented in Table I -
ATP CT Model - Case 1
CT modeling in ATPDraw.
40
Ideal
Actual
In case 2, as previously mentioned, the CT does not enter
30
in the saturation state, since the fault current is within the
20 limits determined in (14) and it is used a standard CT burden.
It is observed in Figs 12 to 14 that the primary current is
Secondary Current (A)

10
reflected without errors in its secondary side.
0
From the presented graphics, it is observed that the
-10 secondary waveforms responses for the two CT models are
almost identical for both analyzed cases.
-20
B. Asymmetric fault current and X/R ratio in CT transient
-30 response
-40 An important consideration in the fault current is that it
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Time (s) can provide a continuous aperiodic component (DC offset),
leading to asymmetry, which depends on the value of the
Figure 7. Secondary signals resulting of the case 1 presented in Table I - voltage at the instant of its occurrence (point-on-wave). If the
CT modeling in ATPDraw.
voltage at the time of fault is null, the asymmetry is maximum
In the case 1 it is applied a small fault current in compari- for inductive purely circuits. The DC component of the fault
son with the maximum current supportable by the CT defined current, responsible for this asymmetry, decays exponentially
in (14). However, a high CT burden value is used compared with a time constant in function of the X/R ratio [6].
with its standard value, which explains the high saturation It is important to note that the criterion of 20 times of the
degree which reduced and distorted the actual secondary rated current as the limit for the CT does not exceed its
current, as illustrated in Figs. 6 and 7. accuracy class is only valid for symmetrical purely fault
Figs. 8 and 9 shows the same analysis for the case 2 currents. In the presence of continuous aperiodic component in
present in Table I. the fault current, the CT can really saturate for a fault current
below 20 times of the rated current, depending of the X/R
100
IEEE PSRC CT Model - Case 2 ratio.
Ideal
80 Actual In order to avoid CT saturation from an asymmetrical fault
60 current, the IEEE Std. C37.110 guide [7] suggests that the
40
secondary voltage be less than the saturation voltage, now
given by (15):
Secondary Current (A)

20

-20 | | (15)
-40

-60 where X and R represent the reactance and resistance of the


-80 primary system, respectively, up to the failure point.
-100
-0.02 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Time (s) It is adopted the case 2 of the Table I in order to show the
Figure 8. Secondary signals resulting of the case 2 presented in Table I -
effects of the asymmetric fault current and X/R ratio in CT
PSRC CT modeling in MATLAB. saturation, but now considering asymmetric fault current with
high values of the X/R ratio (X/R = 19).
The Figs. 10 and 11 shows the ideal and actual CT
secondary signals resulting of the implemented model in not fully equals.
MATLAB and CT model simulated in ATPDraw,
respectively, for this case. From these models comparison, it was demonstrated that
the CT saturation degree is dependent of factors such as: the
IEEE PSRC CT Model ; X/R = 19 level and type of fault current, the X/R ratio and the CT
200
Ideal
burden value. These factors may cause the magnitude
Actual reduction and distortion of the secondary current and then may
150 result in problems in the protection devices connected to it
In addition to a better understanding of the saturation
Secondary Current (A)

100
phenomenon, the secondary current signals resulting from the
simulations can be converted to COMTRADE format and
50
loaded into a injection test device to evaluate the response of
protection relays under these events.
0

REFERENCES
-50
Periodicals:
[1] Kezunovic, M. et al. (1994). Experimental Evaluation of EMTP-Based
-100 Current Transformer Models for Protective Relay Transient Study. IEEE
-0.02 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Time (s) Transactions on Power Delivery, Vol. 9, No. 1, pp. 405- 413.
[2] Tziouvaras, D.A. et al. (2000). Mathematical Models for Current,
Voltage, and Coupling Capacitor Voltage Transformers. IEEE
Figure 10. Secondary signals resulting of the case with asymmetric fault Transactions on Power Delivery, Vol. 15, No. 1, pp. 62- 72.
current and X/R =19 - PSRC CT modeling in MATLAB.
[3] Guerra, F. C. F. and Mota, W. S. (2007). Current Transformer Model.
IEEE Transactions on Power Delivery, Vol. 22, No. 1, pp. 187- 194.
ATP CT Model ; X/R = 19
200
Ideal Papers from Conference Proceedings (Published):
Actual [4] Kojovic, Lj. A., July 2002b, “Comparison of Different Current
150 Transformer Modeling Techniques for Protection System Studies” –
IEEE Power Engineering Society Summer Meeting, vol. 3, no., pp.
1084- 1089.
Secondary Current (A)

100
[5] A. L. M. Coelho; P. M. da Silveira; F. N. Belchior; C. V. Guerrero.
“Algorithm for CT Transient Analysis and Evaluation of the Effects on
50 Numerical Overcurrent Relays,” XIX Automatic Brazilian Conference -
CBA, Campina Grande, 2012.

0
Dissertations:
[6] A. L. M. Coelho; “Analysis of Current Transformer Transient Response
-50 and the Impact on Numerical Protection Relays,” MSc. dissertation,
Dept. Electrical Eng., UNIFEI, Itajubá, 2011.

-100
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 Standards:
Time (s) [7] IEEE Guide for the Application of Current Transformers Used for
Protective Relaying Purposes, IEEE Standard C37.110-2007, 2007.
Figure 11. Secondary signals resulting of the case with asymmetric fault [8] IEEE Requirements for Instrument Transformers. IEEE Standard
current and X/R =19 - CT modeling in ATPDraw. C57.13-2008, 2008.

By the criterion defined in (15), there is CT saturation Technical Reports:


when considering a fault with asymmetry and high X/R ratio. [9] G. Swift (2003). “CT Saturation Theory and Calculator,” IEEE Power
System Relay Committee (PSRC). Available: http://www.pes-
From Figs. 10 to 11 it is observed that, differently of the psrc.org/Reports/CT_SAT%2010-01-03.zip.
case 2 shown in Figs. 8 to 9, the CT enter in saturation state [10] Ralph Folkers. “Determine Current Transformer Suitability Using
due to the asymmetric component presented in the fault EMTP Models,” Schweitzer Engineering Laboratories, Inc. Pullman,
WA, USA, 1999.
current. From the graphics presented, it is observed that the
secondary waveforms for the two CT models are very similar.
V. CONCLUSIONS
First, an efficient and accurate CT model, based on the
theory published by IEEE PSRC was implemented in
MATLAB. The program implemented proved to be a
convenient tool to evaluate the CT transient behavior under
different fault conditions and secondary load. This model
showed a satisfactory response when compared with the
transient behavior of the CT modeled in ATPDraw, which was
configured with the same parameters, presented similar
secondary waveforms. The small difference observed in the
models is acceptable, because the mathematical CT models are

View publication stats

Vous aimerez peut-être aussi