Académique Documents
Professionnel Documents
Culture Documents
net/publication/263405825
CITATIONS READS
0 1,117
5 authors, including:
Some of the authors of this publication are also working on these related projects:
All content following this page was uploaded by Diogo Marujo on 26 June 2014.
Abstract—This paper presents the results of an investigation Committee) [5,6,9] in order to observe the CT behavior,
about current transformers (CTs) transient behavior and the especially under several fault conditions and secondary
factors that can lead its core to saturate. For this study, two burden.
methodologies are used: CT model implemented in MATLAB
and CT modeling using ATP. The results of this analysis are In section III, a similar approach is performed. It is shown
compared in order to validate the models and the main how to model a CT in ATP in order to examine the factors that
conclusions are presented. cause CT saturation.
(3)
√ (9)
Finally the flux variation (Δλ) is obtained from the : Number of turns of the primary winding;
derivative of the excitation current as a function of time, : Number of turns of the secondary winding;
present in (1). This current can be decomposed, as shown in
(11): : Primary winding resistance;
: Secondary winding resistance;
| | (11) : Primary winding inductance;
: Secondary winding inductance;
Thus, replacing (6) and (11) in (1), and manipulating them,
the flux is a function of time, as expressed by (12): : Magnetization resistance.
To reproduce a CT, C-class, based on the power trans-
former shown in Fig. 2, the following considerations about the
(12) CT parameterization on ATP should be observed [10]:
| |
The CT secondary side is modeled in the primary
winding of the power transformer;
where dips/dt is defined from the derived of the ideal
On the secondary winding of the power transformer,
secondary current (ips) expressed in (2).
set the resistor RS equals to zero and the inductance
LS to a value slightly greater than zero (10e-6, for
With the initial flux value obtained from (5), the initial example);
values of the excitation current and flux variation, expressed
Set the inductor LP of the primary winding of the
in (4) and (12), respectively, are also determined.
power transformer to a value equals to zero, whereas
a C-class CT has leakage inductance almost negligi-
After obtaining the initial values, the flux evolution (λ) in ble;
the core as a function of time becomes given by its previous
Set the resistor RP of the power transformer primary
values, as expressed in (13):
to a value equal to the resistance of the CT secondary
winding;
λ λ Δλ (13) It should be add a circuit to represent the resistance
and inductance of CT burden;
where (n) is the index that indicates the actual flux position Set the magnetization resistance RMAG to infinity,
and (n-1) is the previous position. since RMAG is very large. Enter "0" in the model of
ATP to a RMAG infinite;
Select ten points of excitation current versus excita-
The implemented algorithm can solve all the presented
tion voltage from the CT saturation curve, to include
equations, and the following input data must be provided by
saturation in the model;
the program user: i) the rms value of symmetrical fault current
(Ip); ii) the presence or not of the asymmetry factor (K) in the Convert these current versus voltage points into
fault current; iii) the X/R ratio of the power system until the current versus flux points using the ATP supporting
failure point, when K=1; iv) the burden values (Rb and Lb); v) routine called SATURA.
the secondary winding resistance (Rs ); vi) the turns ratio (N); A. ATP CT Model in a Power System
vii) the saturation voltage (Vsat); viii) the slope (S) of the
As well as the models presented in previous sections, the
saturated region of the excitation curve and ix) the remanent
data of CT saturation curve shown in IEEE Std C57.13 [8]
flux (λrem ) if necessary.
may be used in this model. From these curves are obtained the
With the correct information, the implemented program secondary winding resistance and the CT saturation voltage.
will provide as a result the CT secondary current waveform
Initially, it creates an *.atp file with the pairs of current
for several transient conditions.
and voltage obtained from the saturation curve. It is selected a
III. ATP CT MODEL point at the lower end of the curve, many points in the knee
region, and a point at the upper end of the curve. An example
This section shows how to perform the CT modeling from
of *.atp file with these points, is presented in Fig. 3. of R and L, it is possible to control the X/R ratio, which
determines the time constant of the primary circuit, as well as
the asymmetry degree of the CT current waveform.
With respect to the CT burden, this is represented in the
ATPDraw model by a impedance which can be easily varied
to check its influence on the CT secondary current.
IV. RESULTS AND DISCUSSION
This section presents the CT transient behavior for the two
presented CT models. For this study, the following CT
saturation factors are analyzed:
a) symmetrical fault current and burden value;
Figure 3. Example of *.atp file with data of CT saturation curve. b) asymmetric fault current and X/R ratio.
In order to examine these items it is used a CT C-class
The file illustrated in Fig. 3 is compiled and it generates a
300/5 [A], with the standard features presented in the guide
*.pch file, as shown in Fig. 4, which contains pairs of current
IEEE Std. C57.13 [8].
versus flux and also define the CT characteristic used in the
magnetization branch of the power transformer model used in A. Symmetric fault current and burden effects in CT transient
this study. response
High values of burden connected to the CT secondary side
result in increased core saturation and thus cause errors in the
current reflected in its secondary side. The reason for this is
that a given secondary current demands greater CT voltage for
Current an increase in the burden value. The flux density is
x proportional to this voltage.
Voltage
With respect to the fault current, it is fully symmetrical
when the angle of fault incidence in the voltage signal
Current waveform corresponds to the current crossing through zero.
x Theoretically, in an inductive purely circuit, this condition
Flux occurs when the voltage is maximum, i.e., the voltage angle
equals 90°.
The IEEE Std. C37.110 guide [7] suggests that CTs used
Figure 4. Example of *.pch file with data of CT saturation curve (current
versus flux) obtained from *.atp file. with protective relays be selected considering that maximum
symmetrical fault current does not exceed 20 times the CT
The circuit for analysis of the CT transient response may rated current and that load voltage does not exceed the voltage
be prepared in ATPDraw (*. adp file) as shown in Fig. 5. For of their accuracy class. Mathematically, the AC saturation can
the study purpose, this circuit is composed of five main be prevented from (7):
components: a primary voltage source (in this modeling, the
primary side of the power transformer is used as the CT (14)
secondary side, and vice-versa); a saturable transformer
model; a load that represents the CT burden; a load that where if is the maximum fault current in per unit of rating CT
represents the CT primary impedance and a switch for and zb is the CT burden in per unit of standard burden.
applying disturbances.
Two cases are selected to show the effects of the symmet-
ric fault current magnitude and burden values in CT
saturation, as indicated in Table I.
20 60
Secondary Current (A)
40
-30 -60
-40 -80
-0.02 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Time (s)
-100
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Time (s)
Figure 6. Secondary signals resulting of the case 1 presented in Table I -
PSRC CT modeling in MATLAB.
Figure 9. Secondary signals resulting of the case 2 presented in Table I -
ATP CT Model - Case 1
CT modeling in ATPDraw.
40
Ideal
Actual
In case 2, as previously mentioned, the CT does not enter
30
in the saturation state, since the fault current is within the
20 limits determined in (14) and it is used a standard CT burden.
It is observed in Figs 12 to 14 that the primary current is
Secondary Current (A)
10
reflected without errors in its secondary side.
0
From the presented graphics, it is observed that the
-10 secondary waveforms responses for the two CT models are
almost identical for both analyzed cases.
-20
B. Asymmetric fault current and X/R ratio in CT transient
-30 response
-40 An important consideration in the fault current is that it
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Time (s) can provide a continuous aperiodic component (DC offset),
leading to asymmetry, which depends on the value of the
Figure 7. Secondary signals resulting of the case 1 presented in Table I - voltage at the instant of its occurrence (point-on-wave). If the
CT modeling in ATPDraw.
voltage at the time of fault is null, the asymmetry is maximum
In the case 1 it is applied a small fault current in compari- for inductive purely circuits. The DC component of the fault
son with the maximum current supportable by the CT defined current, responsible for this asymmetry, decays exponentially
in (14). However, a high CT burden value is used compared with a time constant in function of the X/R ratio [6].
with its standard value, which explains the high saturation It is important to note that the criterion of 20 times of the
degree which reduced and distorted the actual secondary rated current as the limit for the CT does not exceed its
current, as illustrated in Figs. 6 and 7. accuracy class is only valid for symmetrical purely fault
Figs. 8 and 9 shows the same analysis for the case 2 currents. In the presence of continuous aperiodic component in
present in Table I. the fault current, the CT can really saturate for a fault current
below 20 times of the rated current, depending of the X/R
100
IEEE PSRC CT Model - Case 2 ratio.
Ideal
80 Actual In order to avoid CT saturation from an asymmetrical fault
60 current, the IEEE Std. C37.110 guide [7] suggests that the
40
secondary voltage be less than the saturation voltage, now
given by (15):
Secondary Current (A)
20
-20 | | (15)
-40
100
phenomenon, the secondary current signals resulting from the
simulations can be converted to COMTRADE format and
50
loaded into a injection test device to evaluate the response of
protection relays under these events.
0
REFERENCES
-50
Periodicals:
[1] Kezunovic, M. et al. (1994). Experimental Evaluation of EMTP-Based
-100 Current Transformer Models for Protective Relay Transient Study. IEEE
-0.02 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16
Time (s) Transactions on Power Delivery, Vol. 9, No. 1, pp. 405- 413.
[2] Tziouvaras, D.A. et al. (2000). Mathematical Models for Current,
Voltage, and Coupling Capacitor Voltage Transformers. IEEE
Figure 10. Secondary signals resulting of the case with asymmetric fault Transactions on Power Delivery, Vol. 15, No. 1, pp. 62- 72.
current and X/R =19 - PSRC CT modeling in MATLAB.
[3] Guerra, F. C. F. and Mota, W. S. (2007). Current Transformer Model.
IEEE Transactions on Power Delivery, Vol. 22, No. 1, pp. 187- 194.
ATP CT Model ; X/R = 19
200
Ideal Papers from Conference Proceedings (Published):
Actual [4] Kojovic, Lj. A., July 2002b, “Comparison of Different Current
150 Transformer Modeling Techniques for Protection System Studies” –
IEEE Power Engineering Society Summer Meeting, vol. 3, no., pp.
1084- 1089.
Secondary Current (A)
100
[5] A. L. M. Coelho; P. M. da Silveira; F. N. Belchior; C. V. Guerrero.
“Algorithm for CT Transient Analysis and Evaluation of the Effects on
50 Numerical Overcurrent Relays,” XIX Automatic Brazilian Conference -
CBA, Campina Grande, 2012.
0
Dissertations:
[6] A. L. M. Coelho; “Analysis of Current Transformer Transient Response
-50 and the Impact on Numerical Protection Relays,” MSc. dissertation,
Dept. Electrical Eng., UNIFEI, Itajubá, 2011.
-100
0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 Standards:
Time (s) [7] IEEE Guide for the Application of Current Transformers Used for
Protective Relaying Purposes, IEEE Standard C37.110-2007, 2007.
Figure 11. Secondary signals resulting of the case with asymmetric fault [8] IEEE Requirements for Instrument Transformers. IEEE Standard
current and X/R =19 - CT modeling in ATPDraw. C57.13-2008, 2008.