Installation & Maintenance Manual

B. Maintain a distance of at least 30cm between the transmission line (remote control cable and transmission wires) and
power source of the indoor units. If not, the unit can malfunction due to electromagnetic interference (EMI) generated by
incoming power cables from the power source.
C. In systems where multiple indoor units are in synchronized control under a single controller, assign unique refrigerant cycle
Touch Screen Wired Controller (Model:HCWA10NEGQ) numbers and address for indoor units.
D. Refer to Technical Catalog provided with each indoor unit while connecting the wires between the controller and indoor
units to set the refrigerant cycle number and the indoor unit address.
IMPORTANT: E. Ensure that there is no gap between the controller cable and the cable access inlet of the controller box casing. Cover the
READ AND UNDERSTAND THIS MANUAL BEFORE USING THIS WIRED CONTROL SWITCH. gap with vinyl tape sealing if exists. Gap can lead to moisture inside the controller and insect entry, which can cause
KEEP THIS MANUAL FOR FUTURE REFERENCE. degraded performance and/or damage to the unit.
IMPORTANT NOTICE: F. If the wired controller screen stays in initialization mode for a long time (>5 minutes) after power on, power off the system
● No part of this manual can be reproduced without written permission. for 30s and power on again.
● Signal words are used to identify levels of hazard seriousness. Definitions for identifying hazard levels are provided in the
following table with description.
3) Press and hold (mode) and (up) simultaneously for at least
: indicates a hazardous situation, which results in death or serious injury if not avoided.
: indicates a hazardous situation, which can result in death or serious injury if not avoided.
4. Checking Procedures 5 seconds. The controller displays the test run screen.
4) In the test run screen:
: used with the safety alert symbol, indicates a hazardous situation which can result in minor or moderate injury
● Top right corner indicates total number of indoor units connected
if not avoided.
: addresses practices not related to personal injury. 1) Turn ON the power supply for all indoor units. ● The mode and fan icons blink continuously.
: provides useful information for operation and/or maintenance. 2) The addressing is automatically performed ● * Press to select the mode : Cool/Heat/ Ventilation /Dry
approximately after 1-3 minutes and displays ● * Press to select fan speed.
the screen illustrated in the figure. ● * Press to start/stop the test run.
1. Safety Summary
This product has been designed for the air conditioning system.
● DO NOT install the indoor unit, outdoor unit, wired controller and cable in the following places;
1. Where oil vapor or oil is dispersed (It may cause a fire, deformation, corrosion or failure.)
2. Where the hot springs are near (in a sulfuric environment)
3. Where the sea is near (in the salty environment) (It may cause corrosion.)
4. An acid or alkaline environment
5. Where children can touch
6. Where discharge air from the unit directly blows
7. A place with humid atmosphere
8. A place possibility of water wetting
9. A place of poorly ventilated
● In order to protect the unit from malfunction, pay attention to the following points when the unit is installed in a hospital
or other facilities where electromagnetic wave is generated from medical equipment.
1. DO NOT install the indoor unit, outdoor unit, wired controller and cable within approximately 3 meters from strong
electromagnetic wave radiators such as a radio. ● * Press and to select the following run times:
2. In case that the wired controller is installed in a place where electromagnetic wave radiation is generated, shield the wired
30<=>60<=>90<=>120<=>150<=>…<=>600(minute).
controller and cables by covering with the steel box and running the cable through the metal conduit tube.
3. In case that electric noise is applied at the power source for the indoor unit, provide a noise filter. ● NOTE:
● When the function selection of “Thermistor of Wired controller” is used, do NOT install the unit in the following places; * Louver is in auto swing mode
*The settings are available for all units connected to the
1. Where the average room temperature cannot be detected
2. Where it is exposed to the direct sunshine controller.
3. Where it is close to the heat source 5) To cancel the Test Run mode:
4. Where the outside air blows when door is opened/closed * Press and hold both and for at least 5 seconds
or press .

● DO NOT pour water into the wired controller (hereafter called “controller”. This product is equipped with electrical
parts. If poured, it will cause a serious electrical shock.
● Prior to the installation work, ensure that foundation is flat, level and sufficiently strong and then fix the unit securely. If
the foundation is not strong enough, it may lead to injuries caused by falling of the product, electrical shock or fire.
● DO NOT install the unit in a place where generation, flowing, staying or leaking of flammable gas is detected.
5. Input/Output
● DO NOT perform installation work and electrical wiring connection by yourself. Contact your distributor or dealer of
YORK and ask them for installation work and electrical wiring by service person.
Setting from Controller
● Perform electrical work according to the Installation Manual and all relevant regulation and standards. If the instructions
are not followed, an electrical shock and fire may occur due to insufficient capacity and inadequate performance.
● Use specified cables to connect between indoor unit and controller. Selecting incorrect cables may lead to fire or
Setting normal screen 2) Press and to select the unit: FF->01->02…FF,
electrical shock. 1) Press and hold both, and for at least 5 “FF” is for default, it indicates that you have selected all
● As for the electrical wiring work and check, turn OFF the main power supply before opening/closing the service cover of indoor units. When you select an unit, the time display area
indoor unit. If service cover is opened with main power supply left on, it may result in an electrical shock. seconds during the normal mode (when the unit is
not being operated). [hours] and [minutes] corresponds to the system number and
Note: The following list serves check list. Tick the checkbox ( □ ) after task completion. Controller displays the unit selection screen if more address number of the unit respectively.
3) Press for confirmation and to enter the input/output
than two units are connected to the controller.
2. Installation Work Otherwise, controller skips the screen and displays
the Input/output setting screen.
option setting screen. Screen displays the option in
[temperature] area and blinks continuously.

2.1 Choosing Place of Installation


Select a suitable place for fixing the controller in agreement
with the customer.
Do not install the controller at following places:
● Reachable to kids
● Where there is direct discharge of air from air conditioner
More than 50mm
2.2 Before Installation
The package contains the following components:
[A] Wired Controller (Q’ty: 1, For Operation Control)
[B] Screw <M4x16L> (Q’ty: 2, For Fixing the Holding Bracket
onto the Wall)
[C] Installation & Maintenance & Operation Manual (Q’ty: 2)
[D] Terminal (Q’ty: 1, For fixing cable)

2.3 Installation Procedures 4) Press or to choose the option: Option Description


-> -> -> ->
1) Insert the edge of the slotted screwdriver into the groove at the bottom of the bracket holder. Rotate the Press to confirm the option and to select the parameters. Input option 1
5)
screwdriver to remove the controller from the bracket holder. The screen displays the parameter in [minutes] area. Input option 2
6) Press or to select the parameters:
00->01->02->03->04->05->06->07->08->01 Output option 1
7) Press for confirmation.
Rear cover Output option 2
8) Press and hold both and for at least 5 seconds or
press to cancel and to return to normal mode. Output option 3
Approx. 6mm View from the bottom
• Table A Input and Output Number Display and Connectors

Input/output Factory Setting


Port
Groove for attaching Indication Setting Features Indication
controller
Input 1 CN3 1-2# Remote ON/OFF 1 03
2) Attach the controller to the bracket holder and connect the cable as shown:
Input 2 CN3 3-2# Prohibiting Remote Control after Manual Stopping 06
1. Prepare field-supplied Implanted Switch Box (GB standard 86*86 Box).
2. Lead the cable through the conduit tube inside the wall. Output 1 CN7 1-2# Operation 01
3. Connect to the wired controller through the terminal provided.
Output 2 CN7 1-3# Alarm 02
Output 3 CN8 1-2# Thermo-ON for Heating 06

• Table B Input and Output Settings and Display Codes


Indication Input Output

00 Not Set Not Set


Terminal
01 Room thermo(for cooling) Operation

02 Room thermo (for heating) Alarm


M4 Screws 03 Remote ON/OFF 1 Cooling
(Field-supplied)
04 Remote ON/OFF 2 (Operation) Thermo-ON for Cooling

Remove the 05 Remote ON/OFF 2 (Stoppage) Heating


protection film
06 Forbidding Remote Control after Manual Stoppage Thermo-ON for Heating
07 Remote Cooling / Heating Change Not Set
3) Attach the wired controller to the bracket holder.
Note: Be careful not to pinch the cable while attaching it.

4) Remove the protection film on the liquid crystal display.


6. Function Setting
Setting from normal screen 3) Press and to select the unit: FF->01->02…FF,
“FF”: displayed by default, indicates that you have
3. Electrical Wiring 1) Press and hold both, and for at least 5
seconds in the normal mode (when unit is not selected all indoor units. When you select an unit, the time
operational). display area [hours] and [minutes] corresponds to the
2) Controller displays the unit selection screen if you system number and address number of the unit respectively.
ATTENTION: 4) Press for confirmation and go to function paramter
have connected more than two units. Otherwise,
Ensure to disconnect power at the main source before initiating electrical work. Failure can cause fire, it skips this screen and displays the function setting screen. The parameter item displays in [temperature]
damage to internal components damage and severe/fatal electrical shock. setting screen. area and its value displays in [minutes] area.

Example for Communication Cabling:


Max.16 Indoor Units

Electrical Box Electrical Box


Controller of Indoor Unit of Indoor Unit
Terminal Board Terminal Board
A B M3.5 A B M3.5
A B
Screws Screws

5) Press and and select the parameters.


6) Press to confirm the parameter.
7) Press and to select the parameter value.
8) Press to confirm the parameter value.
Twist Pair Cable with Shield Tube: 1P-0.75mm² or more 9) Press and hold both and for at least 5
seconds or press to cancel this mode and
NOTICE : return to normal mode.
A. Use 0.3 to 0.75mm2 cable for wired connection. The maximum cable length is 30m. If the total cable length exceeds
30m, use twisted pair cable with shield tube (1P - 0.75 mm2). In that case, the maximum total cable length is 500m.
Usage of cable outside this specifications can cause damage from electronic interference (EMI).
• Table C: Optional Functions for Setting Parameters
*1: Parts of Indoor Unit can’ t set“02”.
Parameter Individual Setting *2: For RPI models:
No. Value Optional Function Setting Condition Contents 00: Increasing fan speed 1 (standard)
00 Standard (+7℉/+4℃) 01: Increasing fan speed 2 (high static pressure)
Cancellation of Heating 01 Removal 02: Standard (low static pressure)
1 b1 Temperature Compensation O 02 Set Temp. +2℃/3℉ *3: If the set temperature changes within the set time“F4”, the temperature automatically changes to“F5”and“F6”. If the
due to Uneven Heat Load
03 Set Temp. +3℃/5℉ set temperature is out of range at“F5”and“F6”, it is applied within upper and lower limit for the set temperature.
Set Temp. +1℃/2℉(*1) *4: Applicable for fan, cooling, and dry operation modes
04
Not Available *5: Applicable for heating operation mode
Circulator Function at Heating 00
2 b2 Thermo-Off O Available
*6: Sensor temperature can be showed by setting “C8” item
01
Enforced 3 Minutes Minimum 00 Not Available
3 b3
Operation Time of Compressor
O NOTES: * The screen displays and in place of letters “J” and “K” respectively.
01 Available
00 Standard

7. Louver Setting
01 100 hrs
4 b4 Change of Filter Cleaning Time O 02 1,200 hrs
03 2,500 hrs
04 No Indication This setting is available only for the indoor units that adopt the individual louver. Set the angle for each louver individually
following this procedure:
5 b5 Fixing of Operation Mode ×
1) Press and hold the for 5 seconds in normal 3) Press both, and for at least 5 seconds to enter the
mode the louver setting screen is displayed. individual louver setting screen.
6 b6 Fixing of Setting Temperature × 2) Press to select the louver angle. 4) If you have connected multiple indoor units, press or
7 b7 Fixing of Operation as Exclusive Cooling Unit - to select the required indoor unit.
8 b8 Automatic COOL/HEAT Operation × 5) Press to confirm and enter individual louver setting
screen.
9 b9 × 6) Otherwise, go to individual louver setting directly.
Fixing of Fan Speed
10 bA Not Prepared -
Cooling Temperature Compensation
11 bb O
due to Uneven Heat Load

12 bC Not Prepared
13 bd Not Prepared
14 bE Not Prepared
15 C1 Not Prepared
16 C2 Not Prepared
17 C3 Not Prepared
18 C4 Not Prepared On individual louver setting screen, the
Hi-Speed(Except for Hi-Speed number shows the index of louver .
19 C5 O 7) Press to select the required louver:
at Heating Thermo-OFF)
[01->02->03->04] represents 4 ways’ louver
20 C6 Hi Speed at Heating Thermo-OFF O 8) 8. Press to change the angle for the selected louver.
9) 9. Press to confirm and go to back to normal screen.
Canceling of Enforced 3 Minutes
21 C7 O
Minimum Operation Time of Compressor

22 C8 Thermistor of Remote Control Switch O

23 C9 Not Prepared
24 CA Not Prepared

25 Cb Selection of Forced Stoppage Logic ×


26 CC Not Prepared
27 Cd Not Prepared
00
28 CE Fan Stop at Heating Thermo-OFF O
01

8. Adjust Data/Time
29 CF Change of Louver Swing Angle O
On the normal screen, you need to press both and for at least 5 seconds to adjust the date and time.
30 d1 Power Supply ON/OFF 1 O
1) Press and to set the year. 3) Press and to set the month.
31 d2 Not Prepared 2) Press to confirm and switch to set the month 4) Press to confirm and switch to set the date.
32 d3 Power Supply ON/OFF 2
O

Prevention for Cooling Discharge


33 d4 O
Air Temp. Decrease
Prevention for Heating Discharge
34 d5 O
Air Temp. Decrease
35 d6 Room Temp. Control for Energy Saving
36 d7 Fall Distance of Elevating Panel
37 E1 Ventilation Mode
38 E2 Increasing Supply Air Volume
39 E3 Not Prepared
40 E4 Precooling / Preheating Period
41 E5 Not Prepared

Indoor Fan Operation Time After


42 E6 O
Cooling Operation Stoppage 5) Press and to set the date. 7) Press and to set the hour.
6) Press to confirm and switch to set the hour. 8) Press to confirm and to switch to set the minute.
43 E7 Not Prepared
Fan Operation Control at
44 E8 Heating Thermo-OFF O
45 E9 Not Prepared
46 EA Not Prepared

Fan Operation Control at


47 Eb Cooling Thermo-OFF O

48 EC Forced Thermo-ON Stoppage at Cooling O


49 Ed Not Prepared

50 EE Automatic Fan Speed Control O


Automatic Fan Speed control
51 EF (Compatible with High 2) O
9) Press and to set the minute.
52 F0 Not Prepared 10) Press to confirm and back to normal screen.
53 F1 Automatic OFF Timer Setting
54 F2 Wired Controller Main-Sub Setting
55 F3 Automatic Reset of Setting Temperature (*3) ×

56 F4 Automatic Reset Time ×

Automatic Reset Temperature


57 F5 for Cooling (*4) ×

58 F6 Automatic Reset Temperature


for Heating (*5)
×
Operation Stoppage Prevention by
59 F7
60 F8
Wired Controller Operational Error
Lock Function for Operation Mode Selection 9. Check Function
61 F9 Lock Function for Temperature Setting
62 FA Lock Function for Fan Speed Selection Following table describes the functionalities of each “Check Function” :
63 Fb Lock Function for Swing Louver Operation
Function Description Operation
Cooling Lower Limit for
64 FC Setting Temperature (*4)
× Check 1
Monitors and indicates the sensor
condition of air conditioner
Press and hold both, and at least for 5 seconds on
normal mode to enter the check screen and choose [01].

Monitors and indicates sensor data of air Press and hold both, and at least for 5 seconds on
Check 2
conditioner prior to alarm occurrence normal mode to enter the check screen and choose [02].
Heating Upper Limit for
65 Fd
Setting Temperature (*5)
×
Alarm History Displays previous alarm record Press at least for 5 seconds on normal mode to enter
Display*1 (Indoor Unit address, alarm index, alarm code) alarm history query screen.
66 FE Not Prepared
67 FF Not Prepared *1: Refer to the manuals of indoor unit for the details of the alarm code, press and hold both and for
68 H1 Not Prepared at least 5 seconds to clear the alarm history.
69 H2 Indication of Hot Start
70 H3 Not Prepared
71 H4 Not Prepared
10. Supported Indoor Unit
72 J1 Temperature Indication (*6) ×
73 J2 Not Prepared Wired controller is compatible* with the indoor units and models listed in the following table:
74 J3 Run Indicator Color
No. Indoor Unit Model Name Connectivity
75 J4 Not Prepared
76 J5 Not Prepared 1 Fresh Air Ducted RPI-***KFNQ One controller can only control
77 J6 Not Prepared 2 Floor Concealed RPFI-***FSNQ one indoor unit listed, not both.
78 J7 Not Prepared
3 Wall Mounted (Small) RPK-***FSNQS
79 J8 Eco-operation
80 J9 4 2-way Cassette RCD-***FSN3
Not Prepared
81 JA Not Prepared Compact Ducted (AC) RPIZ-***HNGUAQ
5 (New)
82 Jb Not Prepared RPIZ-***HNGTAQ
83 K1 Not Prepared One controller can control up to
Mid-ESP Ducted (AC) RPIM-***HNGUAQ
84 K2 Not Prepared 6 16 indoor unit types listed.
(New) RPIM-***HNGTAQ
85 K3 Not Prepared
86 K4 Not Prepared RPIH-***HNGUAQ
High-ESP Ducted (AC)
87 K5 Not Prepared 7 RPIH-***HEGTAQ
(New)
RPIH-***HNGUEQ
88 P1 Temperature Step Unit Setting ×
8 Round-way Cassette (New) RCIR-***HNGTAQ
89 P2 ℃/℉ × * Controller may or may not work with the units not specified in the above table.