17. A hydroelectric generating station is supplied from a reservoir of capacity 5 × 108 cubic meters at a head of
200 meters. Find the total energy available in KWHR if the overall efficiency is 75%.
a) 1.044 × 108 b) 2.044 × 108 c) 3.044 × 108 d) 4.044 × 108
18. A direct lightning fixture directs at least .
a) 90% of the light downward b) 85% of the light downward
c) 85% of the light upward d) 80% of the light downward
19. One decibels represent a power ratio of .
a) 10 : 1 b) 20 : 1 c) 2 : 1 d) 1.26 : 1
20. A generating station is to supply four regions of load whose peak loads are 10 MW, 5 MW, 8 MW, and
7 MW. The diversity factor at the station is 1.5 and the average annual load factor is 60%. Calculate the
annual energy supplied by the substation.
a) 150.12 × 106 KWHR b) 10.512 × 106 KWHR
c) 15.012 × 106 KWHR d) 105.12 × 106 KWHR
21. Calculate the distance from a normal placed screen a 30 candela lamp be placed in order that the illumination
be 5 lux.
a) 2.45 m b) 4.45 m c) 5.25 m d) 3.66 m
22. Semiconductors like silicon and germanium are .
a) tetravalent b) monovalent c) trivalent d) pentavalent
23. In a 13.8 kV, 10 MVA base three phase system, a phase to phase fault occurs. If the Thevenin’s equivalent
impedance of the system is 2.63%, what is the magnitude of the fault current?
a) 13,800 A b) 15,900 A c) 27,600 A d) 7,970 A
24. A 50 KVA single phase transformer has a full-load copper loss of 560 W and iron loss of 500 W. Calculate
the efficiency at 25% of full load for a power factor of 0.8 lagging.
a) 93.9% b) 94.9% c) 95.9% d) 96.9%
25. A three-phase induction motor is taking 40 kW, the slip being 4%, stator losses amount to 800 W. Calculate
the total power developed.
a) 39,200 kW b) 40,800 kW c) 37,632 kW d) 36,732 kW
26. A 500 V 1 phase synchronous motor is taking 50 A at a power factor of 0.8 leading. The output is 25 hp and
the effective resistance of the armature is 0.25Ω. Find the iron and friction losses
a) 0.896 b) 0.846 c) 0.796 d) 0.916
27. What is the copper loss at full-load of a transformer if its copper loss at 7/8 of full-load is 4,900 W?
a) 5,600 W b) 3,750 W c) 6,400 W d) 375 W
28. If three transformers in ∆ − ∆ are delivering rated load and one transformer is removed, then overload on
each remaining transformer is percent.
a) 66.6 b) 173.2 c) 57.7 d) 73.2
29. The output of a 200 V single phase synchronous motor, taking a current of 20 A is 4 hp. Its effective
resistance is 0.5Ω. The iron and friction losses amount to 400 W. What is the motor power factor?
a) 0.896 b) 0.846 c) 0.796 d) 0.916
30. In a half-wave rectifier, if AC supply is 60 Hz, then ac ripple is .
a) 120 Hz b) 60 Hz c) 30 Hz d) 15 Hz
31. The three unbalanced currents are: Ia = 10cis(−30◦ ), Ib = 0, Ic = 10cis(150◦ ). Find the phase C positive
sequence current.
3
a) 5.77 A b) 5.77 cis 120◦ A c) 8.66 cis 120◦ A d) 5.77 cis 240◦ A
32. A coil of inductance 10 H and resistance 2 Ωis being supplied by 20 V source. Find the average emf induced
when the circuit is opened if the current falls to zero in 0.5 sec.
a) 20 V b) 10 V c) 100 V d) 200 V
33. A 200 V, three phase source is connectd to two equal impedances of 7.07 + j7.07 Ωin parallel and with both
connected in wye configuration. What is the current per phase of the combination?
a) −16.26 − j16.26 A b) 16.26 + j16.26 A
c) 16.26 − j16.26 A d) −16.26 + j16.26 A
34. A dc machine has 8 poles and a rated current of 100 A. How much current will flow in each conductor at
rated condition if the armature is simplex lap wound?
a) 6.25 A b) 50 A c) 25 A d) 12.5 A
35. A 2 µF capacitor, with initial charge of 100 µC is connected across a 100 Ω resistor at t = 0. Calculate the
time at which the transient voltage across the resistor drops from 40 to 10 V.
a) 27.7 ms b) 0.277 ms c) 2.77 ms d) 277 ms
36. In a parallel RC circuit, as the value of frequency increases, the power factor .
38. If C1 = 100µF and C2 = 50µF are connected in series, find the maximum energy stored when a 220 V dc
supply is applied across the combination.
a) 0.107 J b) 0.507 J c) 0.807 J d) 1.107 J
39. A 2-element series circuit consumes 700 W and has a power factor of 0.707 leading. If the applied voltage is
141sin(314t + 30◦ ), find the circuit constants.
a) R = 7.14Ω, C = 44.6µF b) R = 7.14Ω, C = 446µF
c) R = 71.4Ω, C = 44.6µF d) R = 71.4Ω, C = 44.6µF
40. Two electrons in a vacuum experience a force of 2 × 10−15 N. How far apart are the electrons?
42. It is desired to correct the 2400 KVA 0.65 lagging power factor load in a plant to unity by the installation of
a synchronous condenser. Calculate the KVA rating of the latter.
a) 2,400 b) 1,825 c) 1,560 d) 1,960
43. For a 36-slot 4-pole three-phase full-pitch distributed winding, what is the percent reduction in the generated
voltage?
a) 4 b) 3 c) 6 d) 5
44. Three 10 : 1 transformers are connected ∆/Y for stepping up the 2,300 V three-phase source. Calculate the
secondary line voltage.
45. A transformer is rated at 550 / 220 V. with the low voltage winding shorted, it requires 25 V across the
550 V winding to permit rated current through both windings of the transformer. Calculate the percent
impedance.
a) 4.55% b) 6.55% c) 3.55% d) 5.55%
46. A three-phase overhead transmission line is being supported by three disc insulators. The potentials across
the top unit and the middle unit are 8 KV and 11 KV, respectively. Calculate the ratio of capacitance
between the pin and the earth to the self-capacitance of each unit.
a) 0.475 b) 0.775 c) 0.375 d) 0.275
47. This device is used to reflect back surges into the line.
a) choke coil b) arc horns c) surge depressors d) deion gaps
48. A 50 kW carrier is to be modulated to a level of 85%. What is the carrier power after modulation?
a) 58.8 kW b) 18 kW c) 50 kW d) 42.5 kW
49. What is the device function number of overvoltage relay?
a) 59 b) 76 c) 27 d) 67
50. A short 3-phase line with an impedance of 6 + j8Ω per line has sending and receiving end line voltages of 120
kV and 110 kV respectively for some receiving end load at a power factor of 0.9 lagging. The active power
at the receiving end is nearest to .
a) 100,000 kW b) 200,000 kW c) 120,000 kW d) 110,200 kW
51. A farmer has a small stream on his property which he thinks might supply enough power to light his buildings.
The stream is gauged and found out to be flowing 0.03 cubic meters per second. The available falls is 2.1
m. A small hydraulic turbine and generator will have a combined efficiency of 70%. Taking the transmission
line efficiency of 80%, how many 50-W lamps can be connected to the generator simultaneously?
a) 5 b) 6 c) 7 d) 8
52. Two long straight conductors each carrying an electric current of 5 A, are kept parallel to each other at a
separation of 2.5 cm. Calculate the magnitude of the magnetic force experienced by 10 cm of a conductor.
a) 2 × 10−3 N b) 2 × 10−4 N c) 2 × 10−5 N d) 2 × 10−6 N
53. A 400 V, 10 kW series motor drives a fan when running at 800 rpm. The motor draws 50 A from the
supply. The resistance of the armature and series field are 0.2 Ω and 0.1 Ω, respectively. Determine the
electromagnetic torque developed by the motor.
a) 255 Nm b) 230 Nm c) 235 Nm d) 240 Nm
54. If the load of a certain transformer is reduced to 50%, the copper loss would become .
a) 0.25 times b) 0.5 times c) 2 times d) same as before
55. At a slip of 4%, the maximum possible speed of a 3-phase 60 Hz squirrel cage induction motor is .
a) 3,600 rpm b) 3,456 rpm c) 3,200 rpm d) 2,000 rpm
56. An electric heater develops a power of 1 kW when run on 230 V supply. If the resistance wire of the heater
has a diameter of 0.5 mm and a resistivity of 60 × 10−8 Ωm, find the minimum length of the wire required.
a) 11.3 m b) 13.3 m c) 15.3 m d) 17.3 m
57. Each conductor of a horizontally arrange two-conductor bundle line is ACSR, 1,272 MCM Pheasant. The
spacing between bundle centers is 8 m, 8 m, and 16 m, and between bundle conductors is 45 cm. Find the
inductive reactance of the line in ohms per km per phase if GMR of each conductor is 0.0466 ft.
a) 0.165 b) 0.265 c) 0.365 d) 0.465
58. Shunt generators are used where the main requirement is constant .
a) current and voltage b) current
c) voltage over a narrow load range d) voltage over a wide load range
5
59. A 4-pole lap-wound armature has 480 conductors and a flux per pole of 25 mWb. What is the emf generated,
when running at 600 rpm?
a) 240 V b) 120 V c) 60 V d) 30 V
62. When a line to ground fault occurs, the current in a faulted phase is 100 A. The zero sequence current in
this case will be .
a) zero b) 66.6 A c) 33.3 A d) 100 A
63. In which type of faults given below, all the 3 components Ia0 , Ia1 , Ia2 are equal?
66. When the relative permeability of a material is slightly less than 1, it is called a material.
a) non-magnetic b) paramagnetic c) ferromagnetic d) diamagnetic
67. A coil of 50 turns having a mean diameter of 3 cm is placed coaxially at the center of a solenoid 60 cm long
would with 2500 turns and carrying a current of 2 A. What is the mutual inductance of the arrangement?
77. What is the nature of the current flowing in the armature of dc machine?
a) pulsating dc b) pure dc c) rectified ac d) alternating current
78. The current in a circuit is given by i = 50sin(ωt). If the frequency is 25 Hz, how long will it take for the
current to rise to 25 A.
80. The resistance of the field coil is 200 Ω at 15◦ C. After the motor worked for a few hour on full load, the
resistance increases to 240 Ω. Calculate the temperature rise of the field coil assuming the temperature
coefficient of resistance is 0.0042 per ◦ C at 0◦ C
a) 20.6◦ C b) 30.6◦ C c) 40.6◦ C d) 50.6◦ C
83. A power plant is said to have had a use factor of 48.5% and a capacity factor of 42.4%. How many hours did
it operate during the year?
a) 7,660 b) 8,660 c) 5,660 d) 6,660
84. Surge impedance of a transmission line is given by .
p √ √ p
a) C/L b) CL c) 1/ CL d) L/C
85. In a radio, a gang condenser is given by .
a) air capacitor b) paper capacitor c) ceramic capacitor d) electrolytic capacitor
86. A single-phase transmission line has a total resistance of 1.5 Ω and a loop resistance of 0.3 Ω. It delivers 2
MW at 11 kV at a power factor of 0.8 lagging. Calculate the line voltage at the sending end.
a) 11.21 kV b) 11.11 kV c) 11.41 kV d) 11.31 kV
87. Three 40 Ω non-inductive resistances are connected in delta across 200 V, 3-phase lines. Calculate the power
taken from the mains if one of the three resistors is disconnected.
88. Power in a balanced three-phase system is measured by the two-wattmeter method and it is found that the
ratio of the two readings is 2 : 1. What is the power factor of the system?
a) 0.5 b) 0.8 c) 0.866 d) 1
92. Calculate the self-inductance of an air-cored solenoid, 40 cm long, having a cross-section of 20 cm2 and 800
turns.
a) 2.42 mH b) 4.02 mH c) 5.20 mH d) 6.40 mH
93. A three-phase induction motor having an input power of 30 kW is running at a slip of 4%. The stator loss
is 1 kW and friction and windage loss is 1.5 kW. Determine the motor efficiency.
a) 86.8% b) 87.8% c) 88.8% d) 89.8%
94. An iron core has a cross-section of 500 mm2 and having a length of 100 cm. A magnetizing force of 500 AT
in it produces a magnetic flux of 400 µWb. Determine the relative permeability of the material.
96. The reactance of a generator is given as 0.25 per unit based on its nameplate rating of 18 kW, 500 MVA.
The base for calculations are 20 KW, 100 MV. Find the reactance on the new base.
a) 0.0500 pu b) 0.1050 pu c) 0.0250 pu d) 0.0405 pu
97. A synchronous generator having a subtransient reactance of 0.15 pu and operating at 5% above its rated
voltage supplies a synchronous motor having a 0.2 subtransient reactance. The motor is connected to the
generator by a transmission line and a transformer of total reactance of 0.305 pu.A sudden three-phase short
circuit occurs at the generator terminals. Determine the per unit subtransient fault current.
a) −j6.443 pu b) −j7.443 pu c) −j9.079 pu d) −j10.079 pu