DOCUMENT FRONT SHEET

CONOCOBELANAKFIELDDEVELOPMENT
DOCUMENT FRONT SHEET (FOR A4/A3 DOCUMENTS ONLy)

DOCUMENT 705 Operating Manua!


TITLE

TOTAL NO. OF PAGES 21


(INCLUDING FRONT SHEETS)

SUPPLIER'S ORDER NO. STCO587

SUPPLIER'S OWN REV. SUPPLIER'S APPROVAL


DOCUMENT NO. NO. DA TE (NAME AND SIGNATURE)
R02-70S 01 13tnNov 02 DarrenDodd

.
SUBMITTEDFOR:
REVIEW D
CERTIFIED
REVIEW DOES~OT CO~STlTUTEACCEPTANCE
OF DESIGN DETAILS. CALCULATIONS,
D INFO.
TEST
CONOCO
SUPPLIER NAME:
BELANAK FIELD DEVELOPMENT PROJECT

SAAB TANK CONTROL UK L TD


METHODSOR MATERIALSDEVELOPEDOR
SELECTEDBY SUPPLIERNORDOESIT RELIEVE
SUPPLIER FROM FULL COMPLIANCE WITH PACKAGE CARGO & BALLAST MONITORING
CONTRACTUAL OR OTHER OBLIGATIONS. DESCRIPTION: SYSTEM
.
rn( ACCEPTED.
D 2. ACCEPTED.PROCEEDWITH WORK TAG NOS.: MODEL TYPE NOS.:
AND INCORPORATE COMMENTS
AND RE-SUBj~IT.
~ E Eo w ,TH \ N I (/i1-
r;:J
D 3. NOT ACCEPTED.
REVISE AND RE-SUBMIT.

D 4. FORINFORMATIONONLY.
NOSIGNATURE
REQUIRED
SDRLPRIMECODE.
. R02

".' AME . 0~, ".A -v'YYtP.J


(-- PURCHASEORDER NO. SDRLCAT. SEnUENCE
""'"OJ""""""""'"'.' NO.: -ISSUE
DATE: f).P.tc.. t$z. CNCO-BELK-PHIC02 R 0008 01

.I~IIIII
..
. ..'
SAAI~
SaabTankControl(UK) Ud

SDRLCode :
Title :
Instructions

LIST of TAGGED ITEMS

,. . TANK INSTRUMENT DESCRIPTION


\
WBT 1P M 1O-LTZ-11 02 Ballast HiHi Level
WBT 1S M10-L TZ-1202 Ballast HiHi Level
WBT 2P M10-L TZ-21 02 Ballast HiHi Level
WBT 2S M10-L TZ-2202 Ballast HiHi Level
WBT 3P M10-I:.TZ-3102 Ballast HiHi Level
WBT 3S M10-LTZ-3202 Ballast HiHi Level
WBT 4P M10-L TZ-41 02 Ballast HiHi Level
WBT 4S M10-LTZ-4202 Ballast HiHi Level
WBT 5P M1O-LTZ-51 02 Ballast HiHi Level
WBT 5S M1O-LTZ-5202 Ballast HiHi Level
WBT 6P M10-LTZ-61 02 Ballast HiHi Level
WBT 6S M1O-LTZ-6202 Ballast HiHi Level
WBT 7P M10-LTZ-71 02 Ballast HiHi Level
WBT 7S M10-LTZ-7202 Ballast HiHi Level
WBT AFT PEAK P M10-LTZ-81 02 Ballast HiHi Level
WBT AFT PEAK S M1O-LTZ-8202 Ballast HiHi Level
WBT FORE PEAK P M10-LTZ-0102 Ballast HiHi Level
WBT FORE PEAK S M10-LTZ-0202 Ballast HiHi Level
COT 1P M13-LTZ-1108 Cargo Hi Hi Level
COT 1S M13-LTZ-1208 Cargo Hi Hi Level
COT 2P M13-LTZ-21 08 Cargo Hi Hi Level
COT 2S M13-LTZ-2208 Cargo Hi Hi Level
COT 3P M13-LTZ-3108 Cargo Hi Hi Level
COT 3S M 13-LTZ-3208 Cargo Hi Hi Level
COT 4P M13-LTZ-41 08 Cargo Hi Hi Level
COT 4S M13-LTZ-4208 Cargo Hi Hi Level
COT 5P M13-LTZ-5108 Cargo Hi Hi Level
COT 5S M13-LTZ-5208 Cargo Hi Hi Level
COT 6P M13-LTZ-6108 Cargo Hi Hi L-evel
COT 6S M 13-LTZ-6208 Cargo Hi Hi Level
COND TANK P M13-LTZ-7108 Condensate Hi Hi Level
COND TANK S M13-LTZ-7208 Condensate Hi Hi Level
SLOP TANK P M13-LTZ-8108 Slops Hi Hi Level
SLOP TANK S M13-LTZ-8208 Slops Hi Hi Level

705
Installation and Operating Manual

Guided Wave

Radar-based

Level

Measurement















®
UNPACKING

Unpack the instrument carefully. Make sure all components


have been removed from the foam protection. Inspect all
components for damage. Report any concealed damage to
the carrier within 24 hours. Check the contents of the car- Nameplate:
ton/crates against the packing slip and report any discrep- - partnumber
- amplifier
ancies to Magnetrol. Check the nameplate model number - serial n°
(Model number/approvals as per inserted separate sheet) to - tag n°
be sure it agrees with the packing slip and purchase order.
Check and record the serial number for future reference
when ordering parts.

These units have been tested to Partnumber


probe
EN 61000-6-4 and EN 61000-6-2
and are in compliance with the
EMC Directive 89/336/EEC

MOUNTING

Coaxial GWR probe Twin Rod GWR probe

min. 1" - 150 lbs min. 3" - 150 lbs


DN 25 PN 16 DN 80 PN 16
3/4" 2"

Size: 38 mm Size: 47 mm
(1 1/2") or (1 7/8") or
adjustable adjustable
wrench wrench

min. 25 mm (1")
Not important from any metal
object

min 25 mm (1") min 25 mm (1")


from tank bottom from tank bottom

High level shutdown/overfill protection


Special consideration is necessary in any application where Guided Wave Radar is to be used for high level shutdown/overfill
protection. To ensure proper measurement, the Guided Wave Radar probe should be installed so the maximum overfill level is
a minimum of 150 mm (6") below the process connection. This may include utilizing a nozzle or spool piece to raise the probe.
No special precautions are required for the 7MR/7MD probes. Consult factory for further information.

Insulation

Max 150 °C (300 °F)


Do not insulate the
high frequency connector
in case of high temperature
applications

WRONG GOOD

2
Transmitter

Remote
Integral
Max. rotation 270°
360° rotatable: Position for
optimum wiring/viewing

Size: 38 mm (1 1/2") or
adjustable wrench
Recommended torque 20 Nm
(a) (15 foot-pounds) Remove
protection
(b) Remove protection

CAUTION: be careful not to bend or dirty the gold, high frequency


male connector (a) and its female connector (b). Clean with iso-
propyl alcohol and cotton swabs, if necessary

WIRING

CAUTION: power must be switched OFF before wiring the unit.


TB1

Positive supply to (+) terminal/HART connection


IS
Negative supply to (-) terminal/HART connection
IS – + min. 11 V DC required (min. 16 V DC for explosion
P1
Current + proof models)
loop test LOOP
CURRENT
¤

points P2
www.magnetrol.com
Shield wire to green grounding screw (resistance to
ground must be < 1 Ω).

Standard shielded twisted


pair cable

0% 100 %

Customer supplied
local current meter

Ex Ex Ex
Non Ex Non Ex Non Ex

Galvanic Barrier:
max: 28,6 V DC @ 140 mA

ANALOG I/O
or
DIGITAL I/O
(only for units with HART)
Do not connect shield

3
WIRING

LOOP RESISTANCE

1200 1200

1000
20 mA
1000
20 mA
23 mA
800 800

Ω 650

600 600
23 mA
400 400 400

200 200

24 Vdc 24 Vdc
0 0
11 16
0 10 20 30 40 Vdc 0 10 20 30 40 Vdc
GENERAL PURPOSE (GP) EXPLOSION PROOF (XP)
INTRINSICALLY SAFE (IS)

CONFIGURATION

NOTE: When connected to an approved barrier, the intrinsically safe electronics of the Eclipse allow to remove the
covers with power switched on – even if the area is known to be hazardous

2 line – 8 characters LCD


Default display cycles every 5 s through "LEVEL"/"% OUTPUT"/"LOOP"
Returns to default display if after 5 minutes no keystrokes are sensed

Up/Down and Enter pushbuttons

IMPORTANT: The Eclipse amplifier can be bench configured without GWR


probe connected. Ignore the start up message in this case.

Display Comment

Units! Press : The last character on the first line of the display changes to "!". This sign con-
cm firms that the values/choices of the second line can be modified via the and
push buttons.

Units! Press * Scroll through the choices or increase/decrease the values on the second line
cm of the display by and pushbuttons.
* Accept values/choices as selected by pushbutton.

Units Press Scroll through the menu.


cm

4
CONFIGURATION

TERMINOLOGY
Offset = cm or inches
The offset is the distance between reference point (e.g.
bottom of tank) and end of probe. From the reference point
both 4 mA and 20 mA levels are calibrated. When offset is
set at zero, the end of the probe is the reference point.
Inch or cm 4 mA Level = cm or inches
or zero level point, is measured from the reference point.
20 mA Level The unit has a transition zone at the bottom of the probe.
(100%-point) Min. level to enter for media with:
εr = 2.0: 150 mm (6") + Offset
Probe Type
εr = 80: 25 mm (1") + Offset
20 mA Level = cm or inches
Probe Length
or 100 % level point, is measured from the reference point.
Dielectric The unit has a transition zone at the top of the probe.
of medium
Transition zone varies depending on probe type and
media: see probe specifications page13.
4 mA Level Probe length = cm or inches, record the exact probe length as
(0%-point) printed on the nameplate
Offset
Dielectric Select the dielectric scale of the media to measure:
Reference 1.4–1.7 or 1.7–3.0 or 3.0–10.0 or 10.0–100.0 or VARIES.
point
When the dielectric is known, it will enhance the overall
accuracy of the unit but select the dielectric scale ALWAYS
to the lowest expected dielectricum.

PASSWORD

Display Action Comment

Access Menu with Factory default password "1"

Ent Pass Enter 1 with Factory default setting


0

Enter factory default with Menu is activated and


Ent Pass! configuration can be modified.
1
The unit will automatically save all entered modifications.

Changing/Disabling Password

New Pass Toggle with and until screen “New Pass” appears, Changing password
4096➀ press

Ent Pass Enter 1 or old password with and and press Menu is activated and
0 configuration can be modified.

Ent Pass! Enter new password to desired value (between 0-255) Changing or disabling
1 with and or enter value "0" to disable the password password
function
New password is accepted or disabled.

Access Menu with Factory default password "1"

Ent Pass! Display shows an encrypted value, enter your password or Data is protected by a valid
4096 call Magnetrol for assistance to recoop your password Password
if necessary

Protect data by new password Data is not protected


New Pass
0000


encrypted value, can be any value.

5
MENU: STEP BY STEP PROCEDURE

Screen Action Comment

*Level* Transmitter Display Transmitter default display. Level, % Output, and Loop values
1 *%Output*
*Loop* cycle every 5 seconds.
Run mode

2 Level Transmitter Display Transmitter displays Level measurement in cm or in.


xx.x cm

3 %Output Transmitter Display Transmitter displays % Output measurement derived from 20 mA


xx.x% span.

Loop Transmitter Display Transmitter displays Loop measurement (mA).


4
xx.xx mA

Units Select units for level cm or inches.


5
xxx measurement readout.

Prb Type Select the type of probe used. Select Coaxial: 7MA and 7MC
6 Twin Rod: 7MB
probe
HTHPCoax: 7MD
HP Coax: 7MP
CageCoax: 7MR
(See the 3 first digits of the probe part N°).
HTHP 7xS: 7MS

Prb Mount Select the type of probe Select NPT, Flange or BSP.
7
xxx.x mounting.

Probe Ln Enter the exact length of Probe length is printed on the nameplate and order
8 information. It is the last three digits of the model number.
xxx.x probe.

Offset Enter the offset value. When entering configuration values from the end of the probe is
9 cumbersome, an offset can be introduced to determine a new
xxx.x
reference point. This reference point can be either below the
Configuration

probe (positive offset) or at the probe (negative offset). See the


example below.

Dielctrc Enter the dielectric range For 7MC: 1.4–1.7 or 1.7–3.0 ONLY
10
(dlctrc) value of the media. For 7MA/7MR: 1.4–1.7; 1.7–3.0; 10.0–100.0 or Varies
For 7MB/7MP/7MD: 1.7–3.0; 10.0–100.0 or Varies
For 7MS: 10.0–100.0
When dielectric of the process liquid is unknown and/or varies,
select always the lowest expected dielectric range.

Set 4mA Enter the level value for the A small transition zone (0-150 mm) may exist at the bottom of the
11
xxx.x 4 mA point. probe. See Functional Specifications Probe, See page 13.

Set 20mA Enter the level value for the A small transition zone (0-150 mm) may exist at the top of the
12
xxx.x 20 mA point. probe. See Functional Specifications Probe, See page 13.

Damping Enter the damping factor. A Damping factor (1-45 seconds) may be added to smooth a
13 noisy display and/or output due to turbulence.
xx sec

Fault Enter the default value. Select 3.6 mA, 22 mA or HOLD (last value). 3.6 mA is not
14 valid if unit includes both digital display and HART.
Choice

Poll Adr Enter HART ID number. Select a HART poll address (0-15). Enter 0 for a single
15 transmitter installation.
xx

Trim 4 Fine tune the 4 mA point. Attach a mA meter to the output. If the output does not equal
16 4.0 mA, adjust the value on the display to equal 4.00 mA.
xxxx
Fine tune the 20 mA point. Attach a mA meter to the output. If the output does not equal
17 Trim 20
xxxx 20.0 mA, adjust the value on the display to equal 20.00 mA.

= min. required
calibration No offset Positive offset Negative offset
(Offset at 0 cm) (Offset at 10 cm) (Offset at -15 cm)

100 % 20 mA = 75 cm 20 mA = 85 cm 20 mA = 60 cm

75 cm

0% 4 mA = 15 cm 4 mA = 25 cm 4 mA = 0 cm
15 cm
10 cm

6
MENU: STEP BY STEP PROCEDURE

Screen Action Comment

18 Loop Tst Enter a mA Output value. Set mA Output to any given value to perform loop test.
xx.x mA

19 Fid Tick None, do not adjust. Diagnostic, factory setting.

<Window> None, do not adjust. Diagnostic, factory setting.


20
xxx

Range None, do not adjust. Diagnostic, factory setting.


21
xxx

Gain None, do not adjust. Diagnostic, factory setting.


22
xxx
Diagnostics

Conv Fct None, do not adjust. Diagnostic, factory setting.


23
xx.xxx

Scl Offs None, do not adjust. Diagnostic, factory setting.


24
xx.x

# Ticks None, do not adjust. Diagnostic, factory setting.


25
xxxx

Treshold Enter "CFD". Unit default CFD. Only select Fixed in application with low dielectric material
26 Enter "Fixed". over higher dielectric material and unit is reading incorrect level. Example:
xxx
oil over water. Select Dielectric Range of upper material. Adjust-
ment of Offset may be necessary when threshold is changed.

27 Model 705 None, do not adjust. Factory setting. Ver refers to software version.
xxx

28 New Pass Enter new password. Use arrows to select desired value. Values between 0 and 255.
xxx

7
CONFIGURATION USING HART®

CONNECTIONS
- + Connection of your Hart communicator:
• at power terminals (+) and (-) in wiring compartment
• at first junction box between unit and control room.

IMPORTANT: The digital HART® communication is superimposed on the


4-20 mA loop and requires a min. load resistance of 250 Ω and a max load
resistance of 450 Ω.
Junction

CHECK HART®

250 Ω < RL < 450 Ω


Before starting the HART® configuration procedure – check if your HART® commu-
- + nicator (Rosemount Model 275) is equipped with the proper Eclipse Device
Descriptors (DD’s).

I/O start up the communicator


Control
Room Select NO: go offline
Display Select 4: utility
Select 5: simulation
Power Check manufacturer: Magnetrol
Supply

Eclipse software (see “MENU: STEP BY STEP


Current Communicator
Meter PROCEDURE” – page 7, item 27)
Model 705 Ver. 1.x
Model 705 2.x Ver. 2.x
When the proper software version is not found, consult your local HART® Service
Center to load the correct Eclipse DD’s.

HART MENU
I/O Start up the device
1 Enter DEVICE SET UP
Press one of the following alphanumeric keys (if no key is sensed after 5 s, the
unit will automatically jump to RUN mode and alternatively show Level/% Output
and Loop signal
1 for entering the PASSWORD
2 for entering CALIBRATION (see page 5 for additional information)
3 for entering Basic Set Up – general HART
4 for ADVANCED SET UP CONFIGURATION (see page 5 for additional infor-
mation)
5 for entering DIAGNOSTICS (see page 5 for additional information)
6 for entering REVIEW to review all settings.

8
CONFIGURATION USING HART®

1 Enter Password
1 Units 7 4 mA Set Point
1 Device Setup 2 Calibration 2 Probe Type 8 20 mA Set Point
2 Level 3 Probe Mount 9 Damping
3 % Output 4 Probe Length 10 Fault State
4 Loop 5 Offset 11 Date/Time/Initials
6 Dielectric

3 Basic Setup 1 Tag 5 Poll Address


2 Descriptor 6 Burst Mode
3 Message 7 Burst Option
4 Final Asmbly Num

4 Advanced Setup/ 1 Trim 4 mA 5 New Password 1 3.6 mA


Configuration 2 Trim 20 mA 6 Set Magnetrol S/N 2 4 mA
3 4 mA Trim Point 7 Set Serial Number 3 20 mA
4 20 mA Trim Point 4 22 mA
5 Other
5 Diagnostics 1 Loop Test 6 End
2 Error Codes
3 Digital Settings 1 Fiducial Ticks
2 <Window>
6 Review 1 Model 14 Damping 3 Range
2 Manufacturer 15 Fault State 4 Gain
3 Dev Id, S/N 16 Date 5 Conversion Factor
4 Tag 17 Date/Time/Initials 6 Scale Offset
5 Descriptor 18 Final Asmbly Num 7 Treshold
6 Message 19 Universal Rev 8 # of Ticks
7 Units 20 Fld Dev Rev
8 Probe Type 21 Software Rev
9 Probe Length 22 Burst Mode
10 Offset 23 Burst Option
11 Dielectric 24 Poll Address
12 4 mA Set Point 25 Num Req Preams
13 20 mA Set Point

9
MAINTENANCE

TROUBLESHOOTING SYSTEM PROBLEMS

Symptom Problem Solution


LEVEL, % OUTPUT and LOOP values Basic configuration data is Reconfigure the Probe Length and
are all inaccurate. questionable. Offset.
1) Ensure the Level is accurate.
2) Reconfigure Loop values.
LEVEL readings are repeatable but Configuration data does not Ensure proper probe length & probe type.
consistently high or low from actual accurately match tank height. Adjust the Offset value by the
by a fixed amount. amount of noted inaccuracy.

LEVEL, % OUTPUT and LOOP Turbulence. Increase the Damping factor until the
values fluctuate. readings stabilize.

LEVEL, % OUTPUT and LOOP Lower dielectric material over higher Select Fixed Threshold option and/or
values all reading low vs. actual. dielectric material, e.g. oil over water. select dielectric range from top layer.
Coating, clumping or buildup on probe. Expected inaccuracies due to affect on
pulse propagation.

Dense, water based foam. Expected inaccuracies due to affect on


pulse propagation.

LEVEL reading on Display is correct Basic configuration data Set POLL ADR to 0.
but LOOP is stuck on 4 mA is questionable.
LOOP value jittery, usually in tenths Factory settings corrupted. Check # of Ticks. If the number is
or hundredths digit. also jittery, consult the Factory.
HART device only: handheld will only Most current Device Descriptors Contact local HART service center for
read Universal Commands. (DDs) are not installed in handheld. the latest DDs. (see page 8)

Output is unstable. Basic configuration data Check Fid Ticks (max ± 15 ticks and
is questionnable stable) otherwise consult factory.

Improper connection. Ensure proper connection transmitter


onto probe.

ERROR MESSAGES

Symptom Problem Solution


NO FIDUCIAL Poor circuit board/cable/probe Check all of the connections from the
(HART error code = 0x80) connection or malfunctioning cable electronics to the probe.
between electronics and probe.

Replace universal connector.


NO LEVEL SIGNAL Improper dielectric range chosen. Check dielectric of media vs. software
(HART error code = 0x40) choice.

Dielectric too low for probe type. Confirm the probe choice is proper for
the dielectric of the media.
Malfunctioning analog board and/or Replace electronic module.
32 pin connector.
Consult Factory - verify Conversion
Factor and Scale Offset values.
CORRUPT PARAMTRS Microprocessor data corrupted. Check all Configuration parameters.
(HART error code = 0x10)
Verify Probe Type and Probe Length.
OUT OF CALIB Internal parameters corrupted; displays Recalibrate all parameters and/or
(not a fault) with at least 1 parameter has been consult factory
modified after corruption.

BAD CAL PARAMTRS Probe Length entered in software is Verify Probe Length and Probe Type
(HART error code = 0x20) ot equal to value measured by entered in software is correct.
electronics; possible media build-up
on probe. Clean media off probe.

Improper dielectric range selected. Select proper dielectric range. (Select


always to the lowest expected dielectricum).

“Water bottom”. Select fixed treshold.

NOTE: When consulting the factory concerning improper operation, use the table on page 19. Enter all data when the
transmitter is working correctly and incorrectly.

10
MAINTENANCE

TROUBLESHOOTING APPLICATIONS

Most frequent application problems that may occur, media • Bridging


buildup on the probe and stratification, are covered here. Media that is viscous or solid enough to form a clog, or
Media buildup on the probe is not a problem in most bridge, between the elements causes the greatest
cases–Eclipse circuitry typically works very effectively. degradation in performance. High dielectric media (eg.
Media buildup should be viewed as two types – Film water-based) will show as level at the location of the
Coating and Bridging. bridging.
A twin rod probe should always be chosen if media buildup
• Stratification/Interface
is a possibility.
The Eclipse transmitter is designed to measure the first
• Continuous Film Coating air/media interface it detects. It will not measure further
The most typical of coating problems where the media liquid/liquid interfaces. However, a low dielectric over a
forms a continuous coating on the probe. Eclipse will high dielectric application can cause a measurement
continue to measure effectively with some small degra- problem if the net level of the low dielectric medium
dation in performance. A problem can develop if the becomes small enough (a few inches) to cause the elec-
product begins to buildup on the spacers that separate tronics to trigger on the high dielectric medium that lies
the probe elements. High dielectric media (e.g., water- beneath it.
based) will cause the greatest error.

Bridging

Film
Coating

REPLACEMENT PARTS

No. Description Part Number


1 Electronic module
Display and HART® - English 31-2808-001
Display and HART® - Spanish 31-2808-021
Display and HART® - French 31-2808-031
4
Display and HART® - German 31-2808-041
HART® only 31-2808-002
3 Display only - English 31-2808-003
5 Display only - Spanish 31-2808-023
2 Display only - French 31-2808-033
Display only - German 31-2808-043
3 2 Terminal board
General Purpose (GP) 30-9106-003
Intrinsically Safe (IS) 30-9106-003
1
Explosion Proof (XP) 30-9106-004
3 O-Ring (neoprene) 12-2201-237
4 Housing cover without glass ➀ 04-9193-003
5 Housing cover with glass ➀ 36-4410-001
➀ For stainless steel housing covers – consult factory.

11
TRANSMITTER SPECIFICATIONS

FUNCTIONAL/PHYSICAL
Description Specification
Power (at terminals) General Purpose: 11 to 36 V DC
ATEX Intrinsically Safe: 11 to 28.6 V DC
ATEX Explosion Proof (with Intrinsically Safe electronics) 16 to 36 V DC
Signal Output 4-20 mA or 4-20 mA with HART®
3,8 to 20,5 mA useable (meets NAMUR NE 43)
Span 150 to 6100 mm (6 to 240")
Resolution Analog: 0,01 mA
Display: 0,1 cm (inch)
Loop Resistance CENELEC Intrinsically Safe/General Purpose: 620 Ω @ 20,5 mA - 24 V DC
(see tables at page 12) Explosion Proof (with Intrinsically Safe electronics): 390 Ω @ 20,5 mA - 24 V DC
Damping Adjustable 0-45 s
Diagnostic Alarm Adjustable 3,6 mA, 22 mA, HOLD (3,6 mA is not valid if unit includes both digital display and HART®)
User Interface 3-button keypad and/or HART® communicator
Display 2-line x 8-character LCD
Menu Language English/Spanish/French/German
Housing Material IP 66/Aluminium A356T6 (< 0.25% copper) or stainless steel
Approvals ATEX II 1G EEx ia II C T4, ATEX II 1/2G EEx d(ia) II C T4,
ATEX II 3G EEx nA II T6, FM and CSA
STOOMWEZEN – Secondary level safety device for steamdrums
TÜV – WHG § 19, VLAREM II 5.17-7
LRS – Lloyds Register of Shipment (marine applications)
GOST/GOSGORTECHNADZOR – Russian Authorisation Standards
Electrical Data Ui = 28,6 V, li = 140 mA, Pi = 1 W
Equivalent Data Ci = 2,1 nF, Li = 37 µH
Shock/Vibration Class ANSI/ISA-571.03 SA1 (Shock), ANSI/ISA-571.03 VC2 (Vibration)
Net and Gross Weight 2,70 kg net; 3,20 kg gross
Overall Dimensions H 214 mm (8.43") x W 111 mm (4.38") x D 188 mm (7.40")

PERFORMANCE
Description Specification
Reference Conditions Reflection from liquid, with dielectric in center of selected
range, at +20 °C (70 °F) with CFD treshold➀
Linearity Better than 0,1 % of probe length➁
Accuracy 2,5 mm (0.1") or ± 0,1 % probe length (whichever is greater)➁
Resolution ± 2,5 mm (0.1")
Repeatability < 2,5 mm (0.1")
Hysteresis < 2,5 mm (0.1")
Response Time < 1 second
Warm-up Time < 5 seconds
Ambient Temp. -40 °C to +80 °C (-40 °F to +175 °F) – blind transmitter
-20 °C to +70 °C (-5 °F to +160 °F) – with digital display and keypad
Process Dielectric Effect < 7,5 mm (0.3") within selected range
Operating Temp. Effect Approx. +0,02 % of probe length/°C
Humidity 0-99 %, non-condensing
Electromagnetic Compatibility Meets CE requirements (EN-61000-6-4, EN 61000-6-2)
(Twin-Rod probe must be used in metallic vessel or stillwell)
➀ May degrade for 7MD probe or with fixed treshold. ➁ Top 600 mm (24") of twin rod probe: 7,5 mm (0.3").

TEMPERATURE-PRESSURE RATING FOR ECLIPSE PROBE SEALS

350
Process Pressure (bar)

50
300
Process Pressure (bar)

40
250
30
200
20
150
10
100
0
-40 -20 0 20 40 60 80 100 120 140 160 180 200
50
Process Temperature (°C) 0
-150 -100 -50 0 50 100 150 200 250 300 350 400

7MA: coaxial GWR probe Process Temperature (°C)


7MB: standard twin rod GWR probe 7MD: high temperature / high pressure GWR probe
7MR: overfill prevention GWR probe 7MP: high pressure GWR probe
7MS: saturated steam GWR probe

12
PROBE SPECIFICATIONS

Description 7MR: overfill protection coaxial probe 7MA: coaxial


Materials Probe 316/316L (1.4401/1.4404)
Hastelloy C® (2.4819) or Monel® (2.4360)
Process seal TFE with Viton GFLT, EPDM or Kalrez 4079 (Consult factory for alternatives)
Probe diameter Inside rod: 8 mm (0.3125") – Outer tube: 22 mm (0.875")
Mounting In-tank mounting / external cage mounting In-tank mounting only
(WHG approved)
Process Connection Threaded: 3/4" NPT or 1" BSP (G1)
Flanged: Various ANSI, DIN or torque tube mating flanges
Probe length From 600 mm to 6100 mm (24 to 240"), selectable per 10 mm
Transition Zone➀ Top 0 mm (0") εr: 2,0 = 25 mm (1")/εr: 80 = 150 mm (6")
Bottom εr: 2,0 = 150 mm (6")/εr: 80 = 25 mm (1") εr: 2,0 = 150 mm (6")/εr: 80 = 25 mm (1")
Max. Process Temp. 200 °C @ 13 bar (400 °F @ 200 psi) 150 °C @ 20 bar (250 °F @ 300 psi)
Max. Process Pressure 50 bar @ 20 °C (750 psi @ 70 °F) – see table at page 12
Max. Viscosity 500 cP
Dielectric Range 1,4 to 100

Description 7MD: high pressure/high temperature 7MS: saturated steam GWR probe
GWR probe
Materials Probe 316/316L (1.4401/1.4404)
Process seal Borosilicate/inconel X750 PEEK with Aegis PF 128
Spacers Ceramic
Probe diameter Inside rod: 8 mm (0.125") – Outer tube: 22 mm (0.875")
Mounting In-tank mounting / external cage mounting (7MD – WHG / 7MS – Stoomwezen approved)
Process Connection Threaded: 3/4" NPT or 1" BSP (G1)
Flanged: Various ANSI, DIN or “proprietary” mating flanges
Probe length From 600 mm to 6100 mm (24 to 240"), selectable per 10 mm
Transition Zone➀ Top 25 mm (1")
Bottom εr: 2,0 = 150 mm (6") / εr: 80 = 25 mm (1") εr: 10 = 150 mm (6") / εr: 80 = 25 mm (1")
Process Temp. Max 400 °C @ 135 bar (750 °F @ 2000 psi) 320 °C @ 110 bar (605 °F @ 1585 psi)
Min -150 °C @ 135 bar (-230 °F @ 2000 psi) -40 °C @ 110 bar (-40 °F @ 1585 psi)
Max. Process Pressure 345 bar @ 20 °C (5000 psig @ 70 °F) 110 bar @ 320 °C (1585 psi @ 605 °F)
Max. Viscosity 500 cP
Dielectric Range 2 to 100 10 to 100
Vacuum service Full vacuum Negative pressure but not up to full vacuum
(Helium leak < 10-8 cc/s @ 1 atmosphere vacuum)

Description 7MP: high pressure GWR probe 7MB: standard twin rod GWR probe
Materials Probe 316/316L (1.4401/1.4404)
Hastelloy C® (2.4819) or Monel® (2.4360)
Process seal Borosilicate/inconel X750 TFE with Viton GFLT, EPDM or
Kalrez 4079 (Consult factory for alternatives)
Spacers Teflon
Probe diameter Inside rod: 8 mm (0.3125") – Two 13 mm (0.5") Ø rods –
Outer tube: 22 mm (0.875") 22 mm (0.875") CL to CL
Mounting In-tank mounting only. Twin rod probe must be used in metallic vessel or stillwell > 25 mm
(1") from any surface or obstruction
Process Connection Threaded: 3/4" NPT or 1" BSP (G1) Threaded: 2" NPT or 2" BSP (G2)
Flanged: Various ANSI, DIN or “proprietary” Flanged: Various ANSI, DIN or “proprietary”
mating flanges mating flanges
Probe length From 600 mm to 6100 mm (24 to 240"), selectable per 10 mm
Transition Zone➀ Top εr: 2,0 = 25 mm (1")/εr: 80 = 150 mm (6") 50 mm (2") + 102 mm (4") inactive length
Bottom εr: 2,0 = 150 mm (6")/εr: 80 = 25 mm (1") εr: 2,0 = 150 mm (6")/εr: 80 = 25 mm (1")
Process Temp. Max 200 °C @ 290 bar (400 °F @ 4000 psi) 150 °C @ 20 bar (250 °F @ 300 psi) /
200 °C @ 30 °C (400 °F @ 86 °F) ambient
temp.
Min - integral electr. -40 °C @ 345 bar ( -40 °F @ 5000 psi) -40 °C @ 50 bar (-40 °F @ 750 psi)
Min - remote electr. -150 °C @ 135 bar (-230 °F @ 2000 psi) -40 °C @ 50 bar (-40 °F @ 750 psi)
Max. Process Pressure 345 bar @ 20 °C (5000 psig @ 70 °F) 50 bar @ 20 °C (750 psi @ 70 °F)
– see table at page 12 – see table at page 12
Max. Viscosity 500 cP 1500 cP
Dielectric Range 1,7 to 100 2,0 to 100
Vacuum service Full vacuum Negative pressure but not up to full vacuum
(Helium leak < 10-8 cc/s @ 1 atmosphere vacuum)
Media coating Not recommended in case of media coating Film: 3% error of coated length,
bridging not recommended➁
➀ ε
Transition Zone (zone with reduced accuracy) is dielectric dependent; r ➁ Bridging is defined as continuous accumulation of material between the
= dielectric permitivity. It is recommended to set 4-20 mA signal outside probe elements.
transition zones.
13
PROBE SPECIFICATIONS

“O”-ring material max process min process max process not recommended for recommended for applications
temperature temperature pressure applications
Viton 200°C @ 16 bar -40 °C (-40 °F) 50 bar @ 20 °C ketones (MEK, acetone), skydrol fluids, general purpose, steam, ethylene
GFLT (400 °F @ 230 psi) (750 psi @ 70 °F) amines, anhydrous ammonia,
low molecular weight esters and ethers,
hot hydrofluoric or chlorosulfonic acids,
sour hydrocarbons
Neoprene 150 °C @ 20 bar -55 °C (-65 °F) 50 bar @ 20 °C phosphate ester fluids, refrigerants, high anline point
(300 °F @ 290 psi) (750 psi @ 70 °F) ketones (MEK, acetone) petroleum oils,
silicate ester lubricants
EPDM 125 °C @14 bar -50 °C (-60 °F) 50 bar @ 20 °C petroleum oils, di-ester base acetone, MEK, skydrol fluids,
(250 °F @ 200 psi) (750 psi @ 70 °F) lubricant, steam anhydrous ammonia
Kalrez 4079 200 °C @ 14 bar -40 °C (-40 °F) 50 bar @ 20 °C hot water/steam, hot aliphatic inorganic and organic acids (including
(400 °F @ 200 psi) (750 psi @ 70 °F) amines, ethylene oxide, propylene hydro fluids and nitric), aldehydes,
oxide ethylene, organic oils, glycols, silicone
oils, vinegar, sour hydrocarbons
Chemraz 505 200 °C @ 14 bar -30 °C (-20 °F) 50 bar @ 20 °C acetaldehyde, ammonia + lithium inorganic and organic acids,
(400 °F @ 200 psi) (750 psi @ 70 °F) metal solution, butyraldehyde, alkalines, ketones, esters, aldehydes,
di-water, freon, ethylene oxide, fuels, steam, hot water
liquors, isobutyraldehyde
Buna-N 135 °C @ 22 bar -20 °C (-4 °F) 50 bar @ 20 °C halogenated hydrocarbons, nitro general purpose sealing, petroleum
(275 °F @ 320 psi) (750 psi @ 70 °F) hydrocarbons, phosphate ester oils and fluids, cold water, silicone
hydraulic fluids, ketones (MEK, greases and oils, di-ester base
acetone), strong acids, ozone, lubricants, ethylene glycol base
automotive brake fluid fluids
Polyurethane 95 °C @29 bar -55 °C (-65 °F) 50 bar @ 20 °C acids, ketones, chlorinated hydraulic systems, petroleum
(200 °F @ 420 psi) (750 psi @ 70 °F) hydrocarbons oils, hydrocarbon fuel, oxygen,
ozone
HSN 135 °C @ 22 bar -20 °C (-4 °F) 50 bar @ 20 °C halogenated hydrocarbons, nitro NACE applications
(Highly Saturated (275 °F @ 320 psi) (750 psi @ 70 °F) hydrocarbons, phosphate ester
Nitrile) hydraulic fluids, ketones (MEK,
acetone), strong acids, ozone,
automotive brake fluid, steam
Aegis PF128 200 °C @ 14 bar -20 °C (-4 °F) 50 bar @ 20 °C black liquor, freon 43, freon 75, inorganic and organic acids (including
(400 °F @ 200 psi) (750 psi @ 70 °F) galden, KEL-F liquid, molten potassium, hydro fluids and nitric), aldehydes,
molten sodium ethylene, organic oils, glycols, silicone
oils, vinegar, sour hydrocarbons, steam,
amines, ethylene oxide, propylene oxide

DIMENSIONS in mm (inches)

45° View
83 105 83 105 83 105
(3.28) (4.12) (3.28) (4.12) (3.28) (4.12)

102 102 102


(4.00) (4.00) (4.00)

214
(8.43) 256 256 256
(10.08) (10.08) (10.08)

126 45° 45°


45°
(4.94)
2 cable 2 cable 2 cable
entries entries entries

142 135 (5.31)


(5.31) 166 (6.55)
111 Mounting 315 (12.40)
(4.38) Flange

143 (5.62)
Eclipse Housing,
Probe Insertion
(45° View) Probe Insertion Length Probe
Length 1" BSP (G1) Insertion
3/4" NPT Process Conn. Length
Process Conn. Add 143 (5.62)
for complete
probe insertion
length

83 105 7MR 7MR


(3.28) (4.12) with threaded with flanged connection
98
connection 7MR
(3.85)
with top hat flanged
connection

60 2 cable
(2.37) entries 45°

76 95 840
51 (3.00) (3.75) (33.00)
(2.00)
89 2 holes 108 Ø 22 O.D.
(3.50) (4.25) (0.88)
22 (0.88)
Ø 13 (0.50) Ø 8 (0.31")
Rods

10 (0.38)

Twin Rod GWR Probe, Coaxial GWR Probe,


End View End View

14
DIMENSIONS in mm (inches)

83 105
(3.28) (4.12)
83 105 83 105
(3.28) (4.12) (3.28) (4.12) Proprietary flanges
102
(4.00)
102 102 Ø 229 Ø 184
(4.00) (4.00) (9.0) (7.25)

256
(10.08) 45°
256 256
(10.08) (10.08)
45°

45° 45° 2 cable Ø 22


entries (.875)
2 cable 2 cable
entries entries 32
(1.125)

40 (1.57) Mounting 219 (8.62)


59 (2.31) 71 (2.80)
Flange 143 (5.62) 133
(5.23) 6
(.22)
Probe Insertion Fisher 249B/259B (600 lbs), carbon steel
Probe Insertion Length Probe
Length 1" BSP (G1) Insertion Add 143 (5.62)
3/4" NPT Process Conn. Length for complete
Process Conn.
probe insertion
length

7MA 7MA Ø 143 Ø 121


with threaded with flanged 7MA (5.625) (4.750)

connection connection with top hat flanged


connection
45°
83 105
83 105 83 105 (3.28) (4.12)
(3.28) (4.12) (3.28) (4.12)
Ø 11
102
(.438)
102 102 (4.00)
(4.00) (4.00) 29
(1.125)

256 86
256 (10.08) (3.375) 5
256 (.188)
(10.08)
(10.08) Fisher 249C (600 lbs), 316 stainless steel
45°
45° 2 cable
45°
2 cable 2 cable entries
entries entries

Mounting
Flange
54 (2.13) 47 (1.85) 190
77 (3.03) Ø 191 Ø 149
143 (7.48)
(5.62) (7.50) (5.875)

102 (4.00) 135 (5.31)


Probe Inactive Probe Insertion Inactive
Insertion Length Length Length 45°
Length Probe
2" BSP (G2) Insertion
2" NPT Process Conn.
Process Length
Add 143 (5.62) for
Conn.
complete probe Ø 22
insertion length (.875)
29
(1.125)

7MB 7MB 102


6
with threaded with flanged 7MB with top hat
(4.00)
(.25)
2" NPT connection connection flanged connection Masoneilan (600 lbs), 316 carbon steel

83 105
83 105 (3.28) (4.12) 83 105
83 105 (3.28) (4.12) (3.28) (4.12)
(3.28) (4.12)
102
102 (4.00) 102
(4.00) (4.00)
102
(4.00)

256
256 (10.08) 256
(10.08) (10.08)
256
(10.08) 45°
45° 45°
2 cable
45° 2 cable entries 2 cable
entries entries
2 cable
entries

7MD: 218 (8.58)


218 7MS: 177 (6.97)
88 (3.00)
59 (2.31) (8.58)

7MD: 277 (10.90)


166 (6.52) 7MS: 240 (9.45)
Probe Insertion
Probe Insertion Length
Length Mounting Probe Insertion Mounting
1" BSP (G1) Probe Insertion
3/4" NPT Flange Length Flange
Process Conn. Length
Process Conn. 1" BSP (G1)
3/4" NPT Process Conn.
Process Conn. Probe
Probe
Insertion Insertion
Length Length

7MP 7MD/7MS
with threaded 7MP with threaded 7MD/7MS
connection with flanged connection connection with flanged connection

15
MODEL IDENTIFICATION

Code for ECLIPSE transmitter head/electronics

BASIC MODEL NUMBER


7 0 5 Eclipse guided wave radar transmitter

POWER
5 24 V DC, two wire

SIGNAL OUTPUT
1 4-20 mA with HART® communication
0 4-20 mA only (requires local display and keypad - Accessories code A)

MENU LANGUAGE (HART® communication is only available in English)


1 English – default selection for blind transmitters
2 Spanish
3 French
4 German

ACCESSORIES
A Digital display and keypad
0 Blind transmitter (no display/keypad) – only available for units with HART® communication

MOUNTING/CLASSIFICATION (Consult factory for FM/CSA approvals)


1 Integral, General Purpose (& I.S. FM/CSA)
2 Remote, General Purpose (& I.S. FM/CSA)
A Integral, ATEX II 1 G EEx ia IIC T4
B Remote, ATEX II 1 G EEx ia IIC T4
C Integral, ATEX II 1/2 G EEx d(ia) IIC T4
D Remote, ATEX II 1/2 G EEx d(ia) IIC T4
E Integral, ATEX II 3 G EEx nA II T6
F Remote, ATEX II 3 G EEx nA II T6

MATERIAL OF CONSTRUCTION
1 Cast aluminium dual compartiment housing
2 Stainless steel dual compartiment housing

CABLE ENTRY
1 M20 x 1.5 (2 entries - one plugged)
0 3/4" NPT (2 entries - one plugged)
2 PG 13.5 (2 entries - one plugged) – not available for explosion proof version
3 PG 16 (2 entries - one plugged) – not available for explosion proof version

7 0 5 5 complete code for ECLIPSE 705 transmitter head/electronics

AMBIENT TEMPERATURE VERSUS PROCESS TEMPERATURE


Ambient Temperature °C

100
80
60
40
20
0
0 20 40 60 80 100 120 140 160 180 200

Process Temperature (°C)

16
Code for ECLIPSE GWR probe

BASIC MODEL NUMBER


GWR probe suited for external cage and/or in-tank mounting
7 M R Overfill prevention Coaxial GWR probe (dielectric range: ≥ 1,4) - WHG approved
GWR probes for in-tank mounting only (probes should not be used in overfill applications)
7 M A Coaxial GWR probe (dielectric range: ≥ 1,4)
7 M B Twin Rod GWR probe (dielectric range: ≥ 2,0)

MATERIAL OF CONSTRUCTION - wetted parts (including process connection flange when applicable)
A 316/316L (1.4401/1.4404) stainless steel
B Hastelloy C (2.4819)
C Monel (2.4360)

PROCESS CONNECTION - SIZE/TYPE (consult factory for other process connections)


Threaded
1 1 3/4" NPT thread 4 1 2" NPT thread
2 2 1" BSP (G1) thread 4 2 2" BSP (G2) thread
ANSI flanges
2 3 1" 150 lbs. ANSI RF 5 3 3" 150 lbs. ANSI RF
2 4 1" 300 lbs. ANSI RF 5 4 3" 300 lbs. ANSI RF
3 3 1 1/2" 150 lbs. ANSI RF 6 3 4" 150 lbs. ANSI RF
3 4 1 1/2" 300 lbs. ANSI RF 6 4 4" 300 lbs. ANSI RF
4 3 2" 150 lbs. ANSI RF
4 4 2" 300 lbs. ANSI RF

DIN flanges
B A DN 25, PN 16 DIN 2527 form B E A DN 80, PN 16 DIN 2527 form B
B B DN 25, PN 25/40 DIN 2527 form B E B DN 80, PN 25/40 DIN 2527 form B
B C DN 25, PN 64/100 DIN 2527 form E E D DN 80, PN 64 DIN 2527 form E
C A DN 40, PN 16 DIN 2527 form B E E DN 80, PN 100 DIN 2527 form E
C B DN 40, PN 25/40 DIN 2527 form B F A DN 100, PN 16 DIN 2527 form B
C C DN 40, PN 64/100 DIN 2527 form E F B DN 100, PN 25/40 DIN 2527 form B
D A DN 50, PN 16 DIN 2527 form B F D DN 100, PN 64 DIN 2527 form E
D B DN 50, PN 25/40 DIN 2527 form B F E DN 100, PN 100 DIN 2527 form E
D D DN 50, PN 64 DIN 2527 form E
D E DN 50, PN 100 DIN 2527 form E

Top Hat (Modulevel type) flanges in carbon steel Top Hat (Modulevel type) flanges in stainless steel
4 R 2" 150 lbs ANSI Raised Face flange 4 W 2" 150 lbs ANSI Raised Face flange
4 S 2" 300 lbs ANSI Raised Face flange 4 Y 2" 300 lbs ANSI Raised Face flange
5 R 3" 150 lbs ANSI Raised Face flange 5 W 3" 150 lbs ANSI Raised Face flange
5 S 3" 300 lbs ANSI Raised Face flange 5 Y 3" 300 lbs ANSI Raised Face flange
Torque tube mating flanges with top hat Torque tube mating flanges
T V 600 lbs Fisher (249B/259B) with top hat in carbon steel T T 600 lbs Fisher (249B/259B) in carbon steel
T W 600 lbs Fisher (249C) with top hat in stainless steel T U 600 lbs Fisher (249C) in stainless steel
U V 600 lbs Masoneilan flange with top hat in carbon steel U T 600 lbs Masoneilan flange in carbon steel
U W 600 lbs Masoneilan flange with top hat in stainless steel U U 600 lbs Masoneilan flange in stainless steel

PROCESS SEAL - MATERIAL ➀


0 Viton GFLT seal 4 Buna-N seal 7 Cast Polyurethane seal
1 EPDM (Ethylene Propylene) 5 Neoprene seal 8 Aegis PF 128 seal
2 Kalrez 4079 seal 6 Chemraz seal 9 Kalrez 2035 seal
3 HSN seal
➀ Viton GFLT and Kalrez are rated to a max. process temperature of 200 °C (400 °F) / EPDM is rated to 125 °C (250 °F).

INSERTION LENGTH – specify per 1 cm (0.39") increments


0 6 0 min 0.6 m (24") insertion length
6 1 0 max 6.1 m (240") insertion length
Note: Add 143 mm (5.62") to the probe insertion length to obtain the complete GWR probe length for units with top
hat process connection.

7 M complete code for ECLIPSE 705 Coaxial GWR probe

17
Code for ECLIPSE High Pressure Coaxial GWR probe

BASIC MODEL NUMBER


GWR probe suited for external cage and/or in-tank mounting
7 M D High Temp / High Pressure (HTHP) Coaxial GWR probe (dielectric range: ≥ 2.0) - WHG approved
7 M S Saturated steam – Coaxial GWR probe (dielectric range: ≥ 10) - Stoomwezen approved
GWR probes for in-tank mounting only (probe should not be used in overfill applications)
7 M P High Pressure High Integrity (HP) Coaxial GWR probe (dielectric range: ≥ 1.7)

MATERIAL OF CONSTRUCTION - wetted parts (including process connection flange when applicable)
A 316/316L (1.4401/1.4404) stainless steel
B Hastelloy C (2.4819) - not for 7MD/7MS GWR probes
C Monel (2.4360) - not for 7MD/7MS GWR probes

PROCESS CONNECTION - SIZE/TYPE (consult factory for other process connections)


ANSI flanges
2 3 1" 150 lbs. ANSI RF 4 N 2" 2500 lbs. ANSI RJ
2 4 1" 300 lbs. ANSI RF 5 3 3" 150 lbs. ANSI RF
2 5 1" 600 lbs. ANSI RF 5 4 3" 300 lbs. ANSI RF
2 K 1" 600 lbs. ANSI RJ 5 5 3" 600 lbs. ANSI RF
2 L 1" 900 lbs. ANSI RJ 5 K 3" 600 lbs. ANSI RJ
3 3 1 1/2" 150 lbs. ANSI RF 5 L 3" 900 lbs. ANSI RJ
3 4 1 1/2" 300 lbs. ANSI RF 5 M 3" 1500 lbs. ANSI RJ
3 5 1 1/2" 600 lbs. ANSI RF 5 N 3" 2500 lbs. ANSI RJ
3 K 1 1/2" 600 lbs. ANSI RJ 6 3 4" 150 lbs. ANSI RF
3 M 1 1/2" 900/1500 lbs. ANSI RJ 6 4 4" 300 lbs. ANSI RF
3 N 1 1/2" 2500 lbs. ANSI RJ 6 5 4" 600 lbs. ANSI RF
4 3 2" 150 lbs. ANSI RF 6 K 4" 600 lbs. ANSI RJ
4 4 2" 300 lbs. ANSI RF 6 L 4" 900 lbs. ANSI RJ
4 5 2" 600 lbs. ANSI RF 6 M 4" 1500 lbs. ANSI RJ
4 K 2" 600 lbs. ANSI RJ 6 N 4" 2500 lbs. ANSI RJ
4 M 2" 900/1500 lbs. ANSI RJ
DIN flanges
B A DN 25, PN 16 DIN 2527 form B D G DN 50, PN 250 DIN 2527 form E
B B DN 25, PN 25/40 DIN 2527 form B D H DN 50, PN 320 DIN 2527 form E
B C DN 25, PN 64/100 DIN 2527 form E D J DN 50, PN 400 DIN 2527 form E
B F DN 25, PN 160 DIN 2527 form E E A DN 80, PN 16 DIN 2527 form B
B G DN 25, PN 250 DIN 2527 form E E B DN 80, PN 25/40 DIN 2527 form B
B H DN 25, PN 320 DIN 2527 form E E D DN 80, PN 64 DIN 2527 form E
B J DN 25, PN 400 DIN 2527 form E E E DN 80, PN 100 DIN 2527 form E
C A DN 40, PN 16 DIN 2527 form B E F DN 80, PN 160 DIN 2527 form E
C B DN 40, PN 25/40 DIN 2527 form B E G DN 80, PN 250 DIN 2527 form E
C C DN 40, PN 64/100 DIN 2527 form E E H DN 80, PN 320 DIN 2527 form E
C F DN 40, PN 160 DIN 2527 form E E J DN 80, PN 400 DIN 2527 form E
C G DN 40, PN 250 DIN 2527 form E F A DN 100, PN 16 DIN 2527 form B
C H DN 40, PN 320 DIN 2527 form E F B DN 100, PN 25/40 DIN 2527 form B
C J DN 40, PN 400 DIN 2527 form E F D DN 100, PN 64 DIN 2527 form E
D A DN 50, PN 16 DIN 2527 form B F E DN 100, PN 100 DIN 2527 form E
D B DN 50, PN 25/40 DIN 2527 form B F F DN 100, PN 160 DIN 2527 form E
D D DN 50, PN 64 DIN 2527 form E F G DN 100, PN 250 DIN 2527 form E
D E DN 50, PN 100 DIN 2527 form E F H DN 100, PN 320 DIN 2527 form E
D F DN 50, PN 160 DIN 2527 form E F J DN 100, PN 400 DIN 2527 form E

Torque tube mating flanges


T T 600 lbs Fisher (249B/259B) in carbon steel U T 600 lbs Masoneilan flange in carbon steel
T U 600 lbs Fisher (249C) in stainless steel U U 600 lbs Masoneilan flange in stainless steel

PROCESS SEAL MATERIAL


N Borosilicate seal – for high temp / pressure non condensing applications min -150 °C (-230 °F)
8 Saturated steam seal (PEEK / Aegis PF 128) – for saturated steam applications min -40 °C (-40 °F)

INSERTION LENGTH – specify per 1 cm (0.39") increments


0 6 0 min 0.6 m (24") insertion length
6 1 0 max 6.1 m (240") insertion length

complete code for ECLIPSE 705 High Temperature / High Pressure Coaxial
7 M
GWR probe - for non steam applications

18
®

705 Eclipse Guided Wave Radar Transmitter


Configuration Data Sheet

Copy blank page and store calibration data for future reference and troubleshooting.
Item Value Value Value
Vessel Name
Vessel #
Media & Dielectric
Tag #
Electronics Serial # TROUBLESHOOTING
Probe Serial # Correct Value Incorrect Value
Level
Units
Probe Type
Probe Mount
Probe Length
Offset
Dielectric
4mA point
20mA point
Damping
Fault Choice
HART Poll Address
Trim 4mA
Trim 20mA
Fiducial Tick
<Window>
Range
Gain
Conversion Factor
Scale Offset
# of Ticks
Threshold
Software Version
New Password
Name
Date
Time

19
IMPORTANT
SERVICE POLICY
Owners of Magnetrol products may request the return of a control; or, any part of a control for complete rebuilding or
replacement. They will be rebuilt or replaced promptly. Magnetrol International will repair or replace the control, at no cost to
the purchaser, (or owner) other than transportation cost if:

a. Returned within the warranty period; and,


b. The factory inspection finds the cause of the malfunction to be defective material or workmanship.

If the trouble is the result of conditions beyond our control; or, is NOT covered by the warranty, there will be charges for labour
and the parts required to rebuild or replace the equipment.
In some cases, it may be expedient to ship replacement parts; or, in extreme cases a complete new control, to replace the
original equipment before it is returned. If this is desired, notify the factory of both the model and serial numbers of the
control to be replaced. In such cases, credit for the materials returned, will be determined on the basis of the applicability of
our warranty.
No claims for misapplication, labour, direct or consequential damage will be allowed.

RETURNED MATERIAL PROCEDURE


So that we may efficiently process any materials that are returned, it is essential that a “Return Material Authorisation” (RMA)
form will be obtained from the factory. It is mandatory that this form will be attached to each material returned. This form is
available through Magnetrol’s local representative or by contacting the factory. Please supply the following information:

1. Purchaser Name
2. Description of Material
3. Serial Number and Ref Number
4. Desired Action
5. Reason for Return
6. Process details

All shipments returned to the factory must be by prepaid transportation. Magnetrol will not accept collect shipments.

All replacements will be shipped FOB factory.

BULLETIN N°: BE 57-600.6


EFFECTIVE: MAY 2002
UNDER RESERVE OF MODIFICATIONS SUPERSEDES: January 2002
www.magnetrol.com

BENELUX Heikensstraat 6, 9240 Zele, België


Tel. +32 (0)52.45.11.11 • Fax. +32 (0)52.45.09.93 • E-Mail: info@magnetrol.be
®
DEUTSCHLAND Schloßstraße 76, D-51429 Bergisch Gladbach-Bensberg
Tel. 02204 / 9536-0 • Fax. 02204 / 9536-53 • E-Mail: vertrieb@magnetrol.de
FRANCE Le Vinci 6 - Parc d’activités de Mitry Compans, 1, rue Becquerel, 77290 Mitry Mory
Tél. 01.60.93.99.50 • Fax. 01.60.93.99.51 • E-Mail: magnetrolfrance@magnetrol.fr
ITALIA Via Arese 12, I-20159 Milano
Tel. (02) 607.22.98 (R.A.) • Fax. (02) 668.66.52 • E-Mail: mit.gen@magnetrol.it
UNITED Unit 1 Regent Business Centre, Jubilee Road Burgess Hill West Sussex RH 15 9TL
KINGDOM Tel. (01444) 871313 • Fax (01444) 871317 • E-Mail: sales@magnetrol.co.uk
INDIA B4/115 Safdurjung Enclave, New Delhi 110 029
Tel. 91 (11) 6186211 • Fax 91 (11) 6186418 • E-Mail: magnetrolindia@vsnl.com

Vous aimerez peut-être aussi