Académique Documents
Professionnel Documents
Culture Documents
557F/S
010824 4022 339 01861
Class Code: 4
INTRODUCTION
Improvements have been carried out to the Generator Control Board on new MPPCs. The triggering frequency
measuring circuit on this board has been changed to give greater accuracy when reading the actual frequency./
The consequences of this change in the accuracy of the triggering frequency measurement are that changes are need to
the diagnostic procedures contained in the service manuals.
When carrying out diagnostic procedures the tables included in this XRA need to be referred to. The version of the
Generator Control Board must be checked before using the information given in the tables and the correct table must be
used for the MPPC under test.
Also additional diagnostics procedures are provided which are not included in the service manuals.
The following tables provide the triggering frequencies for both versions of HT Generator installed in instruments in the
field. provides information for the earlier version and provides information for the recent version. To identify which
version is applicable, check the identity of the Generator Control Board fitted to the MPPC, the later version is
identified as 4022 332 8522 version b as shown in Figure 1 Generator Control Board - Version Label.
Version
Label
Voltage 20 24 30 32 35 40 45 50 55 60
(kV)
10 2.6 2.7 2.9 2.9 3.0 3.2 3.5 3.8 4.3 5.1
NOTE: a. All the figures included in the above table have a tolerance of ±10%.
b The figures in the shaded boxes reflect the additional triggering frequencies for the 4kW version,
010824 XRA 557/F/S Page 3
Voltage 20 24 30 32 35 40 45 50 55 60
(kV)
10 3.1 3.2 3.4 3.5 3.6 3.7 4.1 4.5 5.0 6.0
NOTE: a. All the figures included in the above table have a tolerance of ±10%.
b The figures in the shaded boxes reflect the additional triggering frequencies for the 4kW version,
When there is problem with the HT generation circuit use the TDS to find the reason of the problem. In the subsystem
>> x-ray Tube and generator
Page 4 XRA 557/F/S 010824
On this screen the status of the HT generator are given and also the reason of the last error. The information on this
screen can be very helpful to identify the problem.
• Safety errors
Safety Errors
On the TDS screen there are three main fields giving information about the HT generator status. The first field gives
information about the safety circuit, the second field information about the cooling water and the last field information
about the MPPC status. If one of the signals monitored by these fields is not indicating OK then the HT will turn off and
the reason will be displayed in the tube status field. Other safety circuit errors which are not indicated in the three status
fields will be reported in the message field of TDS together with a code for the error. For interpretation of the error code
refer to Appendix B.
When this error message is generated the cause of the fault can be found in one of the HT generator components i.e
♦ The MPPC
♦ The HT tank
♦ The HT cable
♦ The X-ray Tube
To find which component is faulty carry out the following tests. The flow diagram for these tests is shown in Figure 2
kV Ready Time Out Error - Flow Diagram.
010824 XRA 557/F/S Page 5
Kv Ready
time out
NO
HT = 20 kV
No mA HT Cable faulty
No kV YES
No mA MPPC short circuited 0 kHz
0 kHz internally
YES
NO
HT Tube faulty
Short circuit the MPPC
resonator output
Switch On the HT
Check the triggering frequency
Trigger NO
Frequency < 32 kHz MPPC Faulty
YES
HT 20 kV NO
No mA Tank Faulty
0 kHz
YES
Test 1:
Disconnect the MPPC resonator cable from the tank (X400), shown in Figure 3 HT Resonator Cable - Disconnected,
switch on the HT and monitor the kV, mA and the triggering frequency on the screen. If the MPPC is short circuited
then the triggering frequency will not be 0 kHz and the kV will increase. If this case then replace the MPPC.
Test 2:
Short circuit the MPPC resonator outputs, these are connection sockets 1 and 4 on the female connector of the resonant
cable. Make sure that the short circuit is not connected between the wrong connection sockets by checking the resistance
between the short circuit and ground, this should be open circuit.
Switch the HT generator on and monitor the triggering frequency. If the frequency is greater than 32 kHz (version a) or
greater than 36 kHz (version b),, then the MPPC is faulty and should be replaced. If the frequency is less than 32 kHz
(version a), or less than 36kHz (version b), then proceed with the next test.
Test 3:
Reconnect the MPPC resonant cable and disconnect the HT cable from the tank. Switch on the HT. If the voltage rises
to 20 kV and 0 mA then proceed with the next test. If not then the tank is short circuited and must be replaced.
Test 4:
Reconnect the HT cable to the tank and disconnect it this time from the tube side, shown in Figure 4 Tube HT
Connector - Disconnected. Maximum care must be taken here because a voltage of 20 kV will be present on the cable
end therefore make sure that the cable is kept well away from any metal objects to avoid arcs
If the voltage rises to 20 kV and 0 mA that means the HT cable is faulty. If not that means that the tube is faulty.
mA ready timeout
When this error is generated by the TDS then there is a fault in the current generation circuit. Carry out the following
tests to find out which component is faulty. The flow diagram for these tests is shown in Figure 5 mA Ready Time Out
Error - Flow Diagram.
010824 XRA 557/F/S Page 7
mA Ready
time out
NO NO
YES
V = 130 Vac Replace the tank
NO
Test 1:
Disconnect the filament cable from the tube side. Switch on the HT. Measure the DC voltage on the cable if the voltage
rises to 30 V, the HT switches off and the error mA ready time out is generated. This means that the current generation
is OK but the tube is faulty. Check the tube filament by measuring the filament resistance this should be about 0.2 Ohm
under normal conditions. If the measured voltage is 0 V that means the current circuit is not working. Carry out the next
test.
Test 2:
First check that the fuse on the card is not blown. If the fuse is still working make two test points on the filament supply
card by soldering two wires on the output contacts, refer to Figure 6.
Refit the card and switch the HT on. If the voltage across the transformer output is 130 V ac then the Filament Supply
(mA control) card is not defective and the fault lies in the HT tank rectifier circuit. In this case, replace the tank.