STAR ELECTRONIC CONCEPTS

WLD System
Do’s
1. Connect only one sensor cable per zone.
2. Remove 4.7KΩ / ¼ W resistor from zone and connect sensor cable for
used zone only.
3. Make all connections to wld system such as
a. Sensor cable wiring.
b. Hooter connection.
c. Potential free contact.
d. Modbus communication cable.
Then power on wld system.
4. Connect NAC (Hooter, Sounder) which has operating power
12Vdc / 0.25A.
5. Connect proper connection of batter terminals
a. Red battery probe to (+) terminal of battery.
b. Black battery probe to (-) terminal of battery.
6. Connect only one (12V / 7Ah) sealed lead battery to panel.
7. After installation do dry cleaning of wld system board.
8. Program used zone as sensing mode via keypad of wld system.
9. Program unused zone as isolate mode via keypad of wld system.

Don’ts
1. Do not place wld sensor cable on any electric conductive material.
2. Do not connect / disconnect any connections to wld system while the
system is ON.
3. For unused zone don’t remove 4.7KΩ / ¼ W resistor.
4. Do not connect NAC (Hooter, Sounder) which requires operating power
more than 12Vdc / 0.25A.
5. Do not connect
a. Red battery probe to (-) terminal of battery.
b. Black battery probe to (+) terminal of battery.
6. Do not change power supply connections.
7. Do not remove fuse or change it.
8. Do not make any extra holes (do not drill) on wld panel.