10 Year VRLA
Battery Periodic
Maintenance
Instructions
41-7546/0213/CD www.cdtechno.com
Table of Contents
General Information
Battery System General Description
Series string .......................................................................................................................3
Parallel string ......................................................................................................................3
Tables
Table 1-Battery System Symptoms and Solutions...............................................................12
Table 2-Battery Parameters by Model Number ...................................................................19
Figures
Figure 1-Series String of VRLA Batteries ............................................................................3
Figure 2-Parallel Strings of VRLA Batteries ........................................................................3
Figure 3-Float Current VS. Float Voltage ............................................................................9
Figure 4-VRLA Battery Impedance VS. Capacity ...............................................................10
Appendices
Appendix 1-VRLA Battery Periodic Maintenance Data Recording Form ............................20
41-7546/0213/CD 2 www.cdtechno.com
C&D VRLA BATTERY SYSTEM For example, as shown in Figure 2, two of each
48 volt 90 ampere hour capacity strings can be
PERIODIC MAINTENANCE AND connected in parallel to provide a nominal 48
TROUBLESHOOTING GUIDE volts at 180 ampere hours.
« « « « « « « « « « « « « « « « «
« « « « « «« « « « « « « « «
« « « « « « « « « « «
-81&7,21
«
« «
%2;
General Information B
« « « « «
« « «
« « «
« « «
« «
§ « «
127(// // « «
« «
10 Year VRLA
Battery System General Description
The 10 Year VRLA battery is a lead acid
In general the battery system is a group of 2, 4, battery which facilitates an oxygen recombination
6, or 12 volt batteries connected in a series string cycle. The net result is that under normal
to provide a total system of higher voltage. For conditions there is minimal gas emission and loss
example, as shown in Figure 1, four of the nominal of water from the electrolyte. The electrolyte is
12 volt batteries may be connected in series to immobilized by absorbing within an absorbent
provide a 24 cell system with a nominal voltage separator between the plates. Consequently, the
of 48 volts. battery is maintenance free in terms of electrolyte
maintenance-that is, there is no requirement nor
« « « « « « « « « « « « « « « « «
« « « « « «« « « « « « « « «
« « « « « « « « « « «
«
B
capacity to add water to the cells or to measure
the electrolyte specific gravity.
&,5&8,7
%5($.(5
« «
«
§
«
41-7546/0213/CD 3 www.cdtechno.com
Electrical Hazards Disposal
Battery systems present a risk of electrical shock Lead acid batteries are to be recycled. Batteries
and high short circuit currents. The following contain lead and dilute sulfuric acid. Dispose of
precautions should be observed when maintaining in accordance with Federal, State and local
VRLA batteries: regulations. Do not dispose of in a landfill, lake or
other unauthorized location.
1. Remove all personal metal objects
(watches, rings, etc.).
Chemical Hazards
2. Use insulated tools.
3. Wear full eye protection and rubber
Any liquid leaking from a VRLA battery is electrolyte
gloves.
which contains dilute sulfuric acid which is harmful
4. Observe circuit polarities.
to the skin and eyes; is electrically conductive;
5. Do not make or break live circuits.
and is corrosive.
6. Prior to handling batteries on a metal
rack, assure the battery is not
If electrolyte contacts the skin, wash immediately
inadvertently grounded by observing the
and thoroughly with water. If electrolyte enters the
ground fault detector indicator. In its
eyes, wash thoroughly for 10 minutes with clean
absence, measure the voltage between
water or a special neutralizing eye wash solution
the battery and the rack. It should be zero.
and seek immediate medical attention.
If not, determine the cause and correct
prior to proceeding.
Neutralize any spilled electrolyte with the special
7. Do not lay metal tools and hardware on
solutions contained in a spill kit or with a solution
top of the batteries.
of 1 lb. bicarbonate of soda to 1 gallon of water.
8. As appropriate, use an insulating
blanket to cover exposed portions of the
battery system when performing extended Fire, Explosion and Heat Hazards
maintenance that could result in personal
or equipment contact with the energized Lead acid batteries can contain an explosive
conductors. mixture of hydrogen gas which can vent under
overcharging conditions.
Certain types of rectifier circuits used in charging
the VRLA battery may not include a line isolating Do not smoke or introduce sparks in the vicinity
transformer. In these cases extreme caution of the battery.
should be exercised when maintaining and
collecting data on the battery system. Prior to handling the batteries, touch a grounded
metal object, such as the rack, to dissipate any
The VRLA battery is sometimes enclosed in static charge that may have developed on
cabinets with very limited access. Again, extreme your body.
caution must be exercised when maintaining and
collecting data on the battery system. Do not charge batteries in a sealed container.
The individual batteries should have 0.5 inches
of space between the batteries to allow for
convection cooling. If contained, assure the
container or cabinet and room have adequate
ventilation to prevent an accumulation of
potentially vented gas.
41-7546/0213/CD 4 www.cdtechno.com
Caution A test of the individual unit resistance, impedance
or conductance, while optional, is also recommended
Do not attempt to remove the vents (valves) from on a periodic basis. This data and its trend can be
the 10 YEAR VRLA battery or add water. This a valuable aid in troubleshooting the system and
presents a safety hazard and voids the warranty. predicting the need for a system capacity test.
41-7546/0213/CD 5 www.cdtechno.com
Quarterly Maintenance 3. Optionally perform the 10 sec. high rate
(e.g. 100 amp) load test to assure the
The following checks should be completed individual batteries are functional.
quarterly. 4. Optionally measure and record the
resistance/impedance/conductance of
1. Assure the battery room is clean, free of the individual units to trend the condition of
debris and well lighted. the individual units over time and to detect
2. Assure that all facility safety equipment is dramatic differences between individual
available and functional. units and the norm.
3. Measure and record the air temperature
within the battery room. Annual Maintenance
4. Visually inspect the battery for:
a. cleanliness. 1. Repeat the semi-annual checks.
b. terminal damage or evidence of 2. Retorque all the interunit connecting
heating. hardware to the values noted in tables
c. container or cover damage. listed in the Table of Contents.
d. evidence of overheating This can be omitted if the connection
5. Measure and record the battery system resistance is measured and found to have
DC float charging voltage at the battery. not increased more than 20% from the
Optionally measure and record the AC value at installation.
ripple voltage at this time also.
6. Measure the DC voltage from each
Bi-Annual Maintenance
polarity of the battery to ground to detect
any ground faults.
The battery should be capacity tested every two
7. If possible, measure and record the battery
years at the service load or at the battery rating
system DC and AC float charging current.
related to the service requirements. Ideally, this
8. Measure and record the temperature of
will be the same rate at which it was acceptance
the battery pilot unit. Measure the
tested when originally installed. Once the battery
temperature on the side of the unit in the
is found to be at 85% of rating, it should be
center or at the negative terminal of
capacity tested annually. Capacity testing instructions
the unit.
are found in the bulletin "Acceptance and
9. Measure and record the individual unit
Capacity Testing" #41-7135.
DC float charging voltage.
10. Measure and record the System
Equalization Voltage. Data Analysis and Corrective Actions
41-7546/0213/CD 6 www.cdtechno.com
Environment Ambient and open circuit. For cleaning, use a cloth moistened
Battery Temperature in a solution of bicarbonate of soda and water.
Do not use cleaners of unknown solutions such
While the VRLA battery will function at extremes as window or glass cleaners and solvents. Use of
of temperature, it is rated at 77°F (25°C) and the certain petroleum based cleaners will damage the
ideal operating temperature range for the 10 battery plastic containers and could cause them
Year VRLA battery is 70°F (21°C) to 80°F (27°C). to crack and craze.
Operation at cooler temperatures will reduce the
anticipated standby operating time while Container and Cover Damage
operation at warmer temperatures will detract
from the battery life and will increase the Should a crack or other penetration of the
potential of a thermal runaway condition. container or cover of a battery be noted, it should
be replaced. A crack in the container could allow
The battery will experience a 50% reduction of conductive electrolyte to wick from the battery and
life for each 18°F (10°C) above 77°F (25°C). create a ground fault. A ground fault could lead to
High ambient room temperature should be corrected melting and burning of the container.
through the use of appropriate ventilation and air
conditioning. A hole in the cover, even without wicking of the
electrolyte, can also be a serious situation.
The VRLA battery should not be charged at The hole will allow drying of the electrolyte in the
temperatures exceeding 122°F (50°C). A thermal subject cell resulting in an eventual high resistance
runaway condition could result. and heating of the subject cell.
The individual batteries within the string should Containers which are severely swollen and
not exceed the ambient temperature by more permanently deformed have been overheated and
than 18°F (10°C). If the entire battery or individual experienced thermal runaway. Thermal runaway
units temperatures are excessively high, the will also cause the batteries to gas and dry out
respective units may be experiencing thermal and will damage the plates. In this case the entire
runaway. In this situation the charging current battery string should be replaced.
should be terminated by disconnecting the
Charger/Rectifier and the cause of the situation Terminals
should be determined and corrected.
Bent or otherwise damaged terminals can
If thermal runaway has occurred, the battery produce high resistance connections or can
system should be capacity tested and replaced hide a fracture that could fuse open under load.
if necessary. Batteries with damaged terminals should be
replaced.
Battery Visual Inspection
Container Cleanliness If the protective grease at a termination has
melted and flowed onto the cover, it is an
It is important that the individual batteries be indication that the connection has been hot and
clean and properly spaced. An accumulation this is, in all probability, the result of a loose or
of dirt or dust and moisture on the covers can high resistance connection. In this situation the
produce a conductive path between the connection should be disassembled, inspected
terminals or to ground which could result in for damage, cleaned and properly reassembled.
short circuits or ground faults.
41-7546/0213/CD 7 www.cdtechno.com
Battery System Float Extended overcharging will cause excessive
Charging Voltage float current, corrosion of the plate grids,
gassing and drying of the limited amount of electrolyte.
The recommended battery system float This constitutes premature aging of the battery
charging voltage for the 10 Year VRLA and loss of capacity.
Batteries with a specific gravity of 1.280 to 1.300
is equal to the number of cells in the system Severe overcharging for extended periods can
multiplied by the range of 2.25 to 2.30 volts per induce a thermal runaway condition. This would
cell at 77°F (25°C). For example, a string of 30 also necessitate replacement of the battery system.
each 12 volt (6 cell) batteries should be float
charged within the range of 405 to 414 VDC While measuring the battery system DC float
(180 cells x 2.25 v/c minimum and 180 cells x charging voltage it may also be convenient to
2.30 v/c maximum) at 77°F (25°C). measure the AC ripple voltage appearing across
the battery system. If the AC ripple voltage is a
When temperature extremes are encountered sinusoidal waveform the maximum reading should
the float charging voltage should be be less than 0.5% Vrms of the DC float voltage.
temperature compensated. The temperature In the case of 180 cell string floating at 414 VDC,
compensation coefficient is -0.0028 v/c per this is 2.07 Vrms. When measuring the ripple with
degree F (-0.005 v/c per degree C). an oscilloscope, the maximum p-p value should
be 1.5% of the float voltage or 6.2 Vp-p when
For example, if the battery normal temperature floating at 414 VDC.
is 90°F (13° above 77°F) the average float
charging voltage range should be reduced Excessive AC ripple voltage across the battery
0.036 v/c (13° x 0.0028 v/c per °F) to between could cause gassing and heating of the battery
2.21 and 2.26 v/c. For a 180 cell battery this which would result in reduced life.
would be 397.8 to 408.6 VDC. This will help
reduce the potential for thermal runaway at Battery System
elevated temperatures. Ground Fault Detection
If the battery operates at cold temperatures, If the rectifier used to charge the battery has a
for example 60°F (17° below 77°F), the charging ground fault detection capability, the indicator
voltage can be increased to improve recharge time. should be observed to determine the safety of the
For example, the charging voltage range could system. If a ground fault is indicated, it should be
be increased by (17° x -0.0028 v/c per °F) or isolated and corrected prior to further
0.048 v/c. The float voltage range would be maintenance on the battery system.
2.298 to 2.348 v/c. For the 180 cell string this
would be 413.6 to 422.6 VDC. If the rectifier does not have a ground fault
detection circuit, use the digital voltmeter and
If the battery is undercharged for a period during measure the voltage from each polarity of the
which there have been multiple discharges, battery to ground (the grounded rack or cabinet).
the battery will not fully recharge following each A detected voltage would indicate a short or
discharge and it will provide progressively lower leakage current from the battery to ground.
capacity. This condition may be correctable with The approximate location of the cell with the
an extended equalization charge (eg. 48 to 72 ground fault, from the battery system output terminal,
hours). However, if the situation has continued would be the measured voltage divided by the
for too long a time, irreversible sulfation of the average per cell charging voltage. For example,
plates may have occurred and the battery may if the measured voltage to ground was 135 VDC
have to be replaced. and the charging voltage.
41-7546/0213/CD 8 www.cdtechno.com
was 2.25 v/c, the ground fault would be will not float at 13.8 VDC but may vary from 13.3
approximately 60 cells (ten 12 volt units) from to 14.5 and still be normal. If the system is equalized
the battery system output terminal. for 24 hours upon installation, or after with an
extended time in float service, this spread in float
Battery System voltage will normally decrease.
Float Charging Current
Refer to table 1, Electrical Characteristics, for
If the DC float current can be measured, it can each series battery as listed in the documents
provide an indication of the proper current noted in the table of contents, which lists the
acceptance of the battery system. Depending on minimum and maximum DC float voltages to be
the charging voltage per string and the temperature, measured across batteries in a series string. If an
the float current per string should be approximately individual battery measures too low, it may be an
that shown in Figure 3. The float current will indication of a shorted cell.
approximately double for each 18°F (10°C)
above 77°F (25°C). If an individual unit measures too high, it may be
an indication of increased resistance within the
5
cell. If one unit measures very high while the
Milliampere Float Current Per Ampere Hour Capacity
While the battery string may be charged at an A battery suspected of having a shorted or open
average of between 2.25 and 2.3 volts per cell, cell should be removed and replaced immediately.
ot all cells will float at the exact average voltage.
Each cell has a somewhat different impedance More information concerning the measurement
and rate of oxygen recombination and will therefore and interpretation of individual battery float
exhibit a slightly different float voltage at the voltages is contained in the Technical Bulletin
same float current. For example, all the 12 volt "Integrity Testing" #41-7264.
batteries in a string charged at 2.3 volts per cell
41-7546/0213/CD 9 www.cdtechno.com
High Rate Momentary Load Test When an AC ripple voltage appears across a
string of batteries it will be subdivided across the
The high rate momentary load test is a functional
test of the individual battery within the series
100
string. It does not replace a capacity test but it
% rated capacity
75
does indicate if the battery is functional at least 50
% Original Value
120
100
batteries respectively) or the battery should be 90
70
of very high resistance and low capacity. 0 10 20 30 40 50
% LIFE
60 70 80 90 100
Never perform the high rate momentary load Figure 4 - VRLA Battery Impedance and
test on a battery suspected of having a shorted Conductance Vs. Capacity and Age
or open cell. Full face protection should always
individual units in the string proportional to their
be worn during this test, since a spark internal
relative resistance. Therefore in the absence of
to a cell could ignite the residual gasses within
an impedance, resistance or conductance test
the cell.
set, the AC ripple voltage across the individual
units can be measured with a DVM and compared
More information concerning this test and
to each other and the norm as an indication of
the minimum voltages to be expected by part
their relative resistance and condition.
number is contained in the Technical Bulletin
If the resistance of the batteries has increased by
"Integrity Testing" #41-7664.
30% over that when it was new, the battery
should be further tested to determine the cause
Impedance Testing and if necessary the battery or system should be
capacity tested to assure reliability.
The normal wear out mode of the VRLA More information on this topic is contained in the
battery includes corrosion of the plate grids, Technical Bulletin "Impedance and Conductance
deterioration of the plate active material and Testing" #41-7271.
some drying of the electrolyte. Abnormal failure
modes would include deterioration of the
Interunit Connecting Resistance
conductive path and excessive drying of the
electrolyte. These processes will all increase the
High resistance in the interunit connections and
resistance of the affected cells and periodic
loose connecting hardware can cause excessive
measurement of the impedance, resistance or
voltage drop during discharge resulting in reduced
conductance of the cells and trending of this data
operating time and in the extreme case even
can indicate string uniform gradual degradation
cause melting of the battery terminals and
and loss of capacity with time. This is shown in
potentially a fire.
Figure 4.
The contacting surfaces of all connections should
Rapid changes in individual units may indicate
be brushed clean, removing all lead oxide and
shorted, open and drying cells and cells with
contamination, protected with a special
deteriorating conductive paths.
antioxidation grease, and tighten.
41-7546/0213/CD 10 www.cdtechno.com
The connection hardware may loosen somewhat Continuous operation at elevated temperatures
with time and repeated cycling of the battery system. will result in accelerated aging of the battery.
The connection hardware should be retorqued to For each 18° (10°C) above 77°F (25°C) the
the value indicated for the battery part number battery will age at twice the normal rate. Additional
as shown on the relevant data sheet. A summary information on this topic is found in the Technical
of the battery terminal types and the recommended Bulletin "Life Expectancy and Temperature"
torque values is given in Table 2. #41-7329.
41-7546/0213/CD 11 www.cdtechno.com
TABLE 1-VRLA Battery Symptoms and Solutions
Reduced operating Individual low Reversed cells during Replace the isolated
time at 77°F with capacity cells. discharge-reversed cells low capacity batteries.
step voltage decline will become very hot
or voltage plateaus. and will not fully recharge.
Excessive initial Battery is cold. Excessive voltage drop. Heat the battery.
voltage drop even to Cabling is too small. Run parallel cables.
the point of dropping Excessive voltage drop.
High resistance Add required parallel
load in the first Cells will become hot,
connections. strings.
several seconds. could develop thermal
Battery is undersized. Replace isolated units
runaway; internal arcing
with shorts and evaluate
Shorted cells. could result in explosion.
entire string.
TEMPERATURE
CHECKS
Elevated room Lack of adequate air Reduced battery life. Cool the room or
temperature. conditioning/ventilation. accept reduced
battery life.
Elevated battery Elevated room Reduced life and Improve room air
temperature. temperature. potential thermal conditioning.
Inadequate cabinet runaway.
Improve cabinet
ventilation. Reduced life and ventilation and
potential thermal temperature.
Discharge-Charge
runaway.
cycle Limit recharge current.
Can be normal if not
AC ripple current
exceeding 18°F (10°C) Determine cause of
greater than 5
increase. excessive AC ripple
amperes
Reduced life and current and correct.
rms/100Ah battery
capacity. potential thermal
runaway.
41-7546/0213/CD 12 www.cdtechno.com
TABLE 1-VRLA Battery Symptoms and Solutions (Continued)
High current High charging This combination can Limit recharge current.
recharge. voltage. lead to thermal Reduce to within
runaway. specifications.
Shorted cells.
Replace shorted cells
and evaluate total string.
VISUAL BATTERY
CHECKS
Cover/container Handling or impact Cell dryout or ground Replace damaged unit.
crack. damage. fault. Potential internal
gas ignition.
41-7546/0213/CD 13 www.cdtechno.com
TABLE 1-VRLA Battery Symptoms and Solutions (Continued)
Rotten egg odor. Possibly caused by Odor is a product of Replace the battery
high temperature extended thermal system and correct the
environment, runaway. items leading to the
overcharging, thermal runaway.
excessively high
recharge
current,shorted
cells or a ground
fault or a combination
of these items.
Melted grease at Connections were Excessive voltage drop Clean and reassemble
terminals. hot probably due perhaps leading to short the connection if
to excessive operating time or undamaged.
resistance damaged terminals.
caused by loose
connection, dirty In extreme case could Replace any battery
contact surfaces or lead to melted terminal with damaged terminals.
corrosion within the and ignition of the
connection. battery cover.
Corrosion at There is possibly Increased connection Disassemble connection,
terminals. either residual resistance and resulting clean, coat connecting
electrolyte from increase in the surfaces and terminal
manufacturing or connection heating and area and seal with
electrolyte leaking voltage drop at high rate antioxidation grease
from the battery discharge. and appropriately
terminal seal reassemble the connection.
that is attacking the If leakage about the
interunit connector. terminal area is
obvious, the battery
should be replaced.
Burned area on Crack in container Could result in personal Clear the ground fault
container. wicking electrolyte hazard due conductive and replace defective
to grounded rack, path to rack, etc. unit. Evaluate balance
etc. of the string.
Ground fault.
VISUAL BATTERY
CHECKS
System float voltage Charger output set Overcharging will cause Reset the charger
greater than 2.3 v/c incorrectly. excessive gassing and output voltage to the
average at 77°F drying of the electrolyte recommended value.
(25°C). and will contribute to
potential thermal
runaway.
41-7546/0213/CD 14 www.cdtechno.com
TABLE 1-VRLA Battery Symptoms and Solutions (Continued)
41-7546/0213/CD 15 www.cdtechno.com
TABLE 1-VRLA Battery Symptoms and Solutions (Continued)
41-7546/0213/CD 16 www.cdtechno.com
TABLE 1-VRLA Battery Symptoms and Solutions (Continued)
Float current to the A battery or Failure to support the Replace the battery with
string is zero. connection in the load. If an internal arc the open cell or repair
series string is open. should occur during the open/loose external
This can be verified discharge, it could ignite connection.
via the float voltage the gasses internal to
check or AC ripple to the cell.
voltage or impedance If there is a open/loose
check of the connection in the external
individual batteries. conductive path, it could
damage the termination
under load.
Float current Batteries are not Not at 100% of Determine the
exceeds 3.0 yet fully recharged. capability. specific cause and
milliamperes per Batteries are above Conducive to thermal take necessary
ampere hour of rated 77°F (25°C). runaway. corrective action.
capacity at 77°F Potentially shorted Conducive to thermal
(25°C) at float cells in battery. runaway.
voltage. Depending on the Thermal runaway
degree, results in eventual
the battery may be meltdown of the
entering or in battery and the potential
thermal runaway. of hydrogen sulfide
emissions and fire.
AC ripple current Poor filtering of the Excessive AC ripple Improve the charger
exceeds 5 amperes charger. current will result in output filtering.
per 100 Ah rated battery heating, reduced
battery capacity service life and potential
thermal runaway.
HIGH RATE 10 SEC.
LOAD TEST
41-7546/0213/CD 17 www.cdtechno.com
TABLE 1-VRLA Battery Symptoms and Solutions (Continued)
BATTERY
IMPEDANCE/
CONDUCTANCE
TEST
Impedance/ Battery is discharged Reduced Charge and retest
resistance or Battery conductive operating time. battery or replace as
increase by 50% path, plate grid or required.
from original values active material Conducive to
when new or or electrolyte thermal runaway.
conductance decline volume deterioration. Will not support load.
to 50% or the value Shorted cells.
when new.
Open cells.
CONNECTION
HARDWARE
RESISTANCE/
TIGHTNESS CHECK
41-7546/0213/CD 18 www.cdtechno.com
TABLE 1-VRLA Battery Symptoms and Solutions (Continued)
Please refer to 12-1110 and 12-1111 for additional Ohmic reference values.
41-7546/0213/CD 19 www.cdtechno.com
C&D Valve Regulated
Lead Acid Batteries
Historical Data and System Status
Company: System Float Changing Voltage: VDC
Location: Date Batteries Installed:
Supervisor in Charge: Phone: Load (K.W. or Ampere):
Type Charger/Load: System Equalize Voltage: Amps:
Unit Part Number: Cells /Unit:
Date: Date:
Unit Charging Impedance 10 Sec. Vmin Connection Unit Charging Impedance 10 Sec. Vmin Connection
No. Volt&Unit Conductance o 100 Amps. Resistance No. Volts- Unit Conductance o 100 Amps. Resistance
AC Millivolts AC Millivolts
1 31
2 32
3 33
4 34
5 35
6 36
7 37
8 38
9 39
10 40
11 41
12 42
13 43
14 44
15 45
16 46
17 47
18 48
19 49
20 50
21 51
22 52
23 53
24 54
25 55
26 56
27 57
28 58
29 59
30 60
Any data, descriptions or specifications presented herein are subject to revision by C&D Technologies, Inc.
without notice. While such information is believed to be accurate as indicated herein, C&D Technologies, Inc.
makes no warranty and hereby disclaims all warranties, express or implied, with regard to the accuracy or
1400 Union Meeting Road completeness of such information. Further, because the product(s) featured herein may be used under conditions
P.O. Box 3053 • Blue Bell, PA 19422-0858 beyond its control, C&D Technologies, Inc. hereby disclaims all warranties, either express or implied, concerning
the fitness or suitability of such product(s) for any particular use or in any specific application or arising from any
(215) 619-2700 • Fax (215) 619-7899 • (800) 543-8630 course of dealing or usage of trade. The user is solely responsible for determining the suitability of the product(s)
customersvc@cdtechno.com featured herein for user’s intended purpose and in user’s specific application.
www.cdtechno.com