INSTRUMENT DATA SHEETS FOR MANUAL ALARM CALL POINT Page 2 of 3

CLIENT APPROVAL
REV DATE DESCRIPTION PREPARED CHECKED APPROVED
BY DATE
A 28-Sep-12 IFR AP DTS IWP
0 28-Sep-12 IFB AP DTS IWP

GENERAL NOTES :

1. Reference Documents :

- Instrument and Control Design Basis (SLS-00-INS-DB-001)


- Instrumentation Specification-fire&gas detector (SLS-00-INS-SPC-008)
Jasa Konsultansi Perancangan & Feasibility Study
Jalur Pipa Transmisi Gas Arun - Belawan

INSTRUMENT DATA SHEETS FOR MANUAL ALARM CALL POINT Page 3 of 3

CLIENT APPROVAL
REV DATE DESCRIPTION PREPARED CHECKED APPROVED BY DATE
A 28-Sep-12 IFR AP DTS IWP
0 28-Sep-12 IFB AP DTS IWP

ITEM QUANTITY DESCRIPTION


4 4 Tag No. See note.
Break Glass Type . The actuating mechanism shall be equipped with a strain limit preventing
Type
permanent deformation of button and contacts.
Operation By Hummer
Housing Material UV resistant GRP for Break Glass station (for Indoor)
Degree of Protection IP 42 for Indoor an IP 65 for outdoor
Certification General purpose
Operating Enviroment Suitable for service in indoor and outdoor onshore marine enviroment
Mounting Shall be supplied with 316 SS bolt and other accessories for surface mounting.
Output Double change over 2A (resistive load), 24 VDC, Gold plated, NO, Close in Alarm condition.

Integral termination compartment with 2 x 1/2"NPT x 1.5 ISO thread cable entries, Left and
Cabling Right Hand Side. Screw clamp terminals are to be suitable for up to 2.5mm 2 conductors with
at least 5 terminals.
Housing Colour Red. Paint shall be two pack epoxy type suitable for tropical onshore service.
Manufacturer Refer to Vendor List
Model No. Refer to Vendor List
Each station shall have an 316SS duty label with wording "MANUAL ALARM CALL
Duty Label
STATION". The letter height to be 10 mm (minimum).
Tag Label Each station shall have an 316 ss tag label. The letter height to be 6mm (minimum).

Notes :

No Tag Number Service Drawing Number

1 RPN-MAC-001 Compressor Area SLS-10-INS-DRW-015


2 RPN-MAC-002 Near Exit Office Building SLS-10-INS-DRW-015
3 RPN-MAC-003 Beside Lab Room SLS-10-INS-DRW-016
Beside Marshalling Cabinet
4 RPN-MAC-004 Room SLS-10-INS-DRW-016