Vous êtes sur la page 1sur 25

Centrifugal Installation Operation and Maintenance Manual

Modbus Communication Information

Modbus Standard Objects


Read
Network Control
/ Data Type Index Description
Property
Write
Cool Setpoint(9) R/W Holding Register 40002 3~21
Ice Setpoint R/W Holding Register 40051 -9.4~3.4
Heat Setpoint R/W Holding Register 40006 35~55
Capacity Limit Setpoint(10) W Holding Register 40004 0~100%
Chiller Mode Setpoint(2) W Holding Register 40146 1=Ice,2=Cool,3=Heat
Chiller Enable Input(4) R/W Coil 2 0=Off,1=On
0=Off,
Run Enabled R Coil 3
1=Run Allowed
Chiller Local/Remote R Coil 6 0=Remote,1=Local
0=Not Limited,
Chiller Limited R Coil 7
1=Limited
Chiller Mode Output R Holding Register 40148 1=Ice,2=Cool,3=Heat
0=Off,1=Start,
2=Run,
Chiller Status(1) R Holding Register 40147
3=Pre-Shutdown,
4=Service
Active Setpoint R Holding Register 40003 -9.4~55
Actual Capacity(3) R Holding Register 40011 0~125%
Capacity Limit Output R Holding Register 40043 0~100%
Evaporator Entering
R Holding Register 40005 -25~100
Water Temperature(5)
Evaporator Leaving
R Holding Register 40007 -25~100
Water Temperature(6)
Condenser Entering
R Holding Register 40008 -25~100
Water Temperature(7)
Condenser Leaving
R Holding Register 40009 -25~100
Water Temperature(8)
Heat Recovery Entering
R Holding Register 40023 -25~100
Water Temperature
Heat Recovery Leaving
R Holding Register 40024 -25~100
Water Temperature
0=No Flow,
Evaporator Flow Switch Status R Coil 8
1=Flow
0=No Flow,
Condenser Flow Switch Status R Coil 9
1=Flow
0=Pump Off,
Evaporator Pump Status R Coil 30
1=Pump On
0=Pump Off,
Condenser Pump Status R Coil 32
1=Pump On
0=Pump No.1
Pump Select R/W Coil 20
1=Pump No.2
Evaporator Pump Run Hours
Pump Select R Holding Register 40176 0~65,535
Pump#2 Holding Register 40232 0~65,535
Condenser Pump Run Hours R

66 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

Pump Select Holding Register 40177 0~65,535


Pump#2 Holding Register 40233 0~65,535
Comp Select R/W Holding Register 40161 0~65,535
Condenser Refrigerant Pressure
Compressor Select R Holding Register 40022 0~2800kPa
Compressor #2 Holding Register 40094 0~2800kPa
Condenser Saturated
Temperature
R
Compressor Select Holding Register 40021 -25~62
Compressor #2 Holding Register 40093 -25~62
Evaporator Refrigerant Pressure
Compressor Select R Holding Register 40018 0~910kPa
Compressor #2 Holding Register 40091 0~910kPa
Evaporator Saturated
Temperature
R
Compressor Select Holding Register 40017 -25~40
Compressor #2 Holding Register 40090 -25~40
Liquid Line Temperature
Compressor Select R Holding Register 40037 -25~100
Compressor #2 Holding Register 40105 -25~100
Compressor Current(Benshow
Starter)
R
Compressor Select Holding Register 40027 0~65,535Amps
Compressor #2 Holding Register 40096 0~65,535Amps
Compressor Voltage(Benshow
Starter)
R
Compressor Select Holding Register 40030 0~65,535Volts
Compressor #2 Holding Register 40099 0~65,535Volts
Compressor Power(Benshow
Starter)
R
Compressor Select Holding Register 40028 0~65,535kiloWatts
Compressor #2 Holding Register 40097 0~65,535kiloWatts
Compressor Percent RLA
Compressor Select R Holding Register 40026 0~125%
Compressor #2 Holding Register 40095 0~125%
Discharge Temperature
Compressor Select R Holding Register 40020 -25~100
Compressor #2 Holding Register 40092 -25~100
Suction Temperature
Compressor Select R Holding Register 40016 -25~100
Compressor #2 Holding Register 40089 -25~100
Oil Feed Pressure
Compressor Select R Holding Register 40033 0~2800kPa
Compressor #2 Holding Register 40101 0~2800kPa
Oil Sump Pressure
Compressor Select R Holding Register 40034 0~910kPa
Compressor #2 Holding Register 40102 0~910kPa
Oil Feed Temperature
Compressor Select R Holding Register 40035 -25~100
Compressor #2 Holding Register 40103 -25~100
Oil Sump Temperature
R
Compressor Select Holding Register 40036 -25~100

Engineered for Flexibility and performance 67


Centrifugal Installation Operation and Maintenance Manual

Compressor #2 Holding Register 40104 -25~100


Compressor Run Hours
Compressor Select R Holding Register 40175 0~65,535
Compressor #2 Holding Register 40236 0~65,535
Compressor Starts
Compressor Select R Holding Register 40174 0~65,535
Compressor #2 Holding Register 40235 0~65,535

Modbus Alarms Messages


WSC
WDC
Holding
# Description WCC Bit
Register
HSC
TSC
Warnings
Entering Condenser Water Temperature Sensor
1 X 40130 1
Fault
Entering Condenser Water Temperature Sensor
2 X 40130 2
Fault
3 Liquid Line Refrigerant Temperature Sensor Fault X 40130 3
Leaving Condenser Water Temperature Sensor
4 X 40130 4
Fault
Problems
5 NA 40131 0
6 NA 40131 1
7 NA 40131 2
8 NA 40131 3
9 Condenser Water Freeze Protect Comp1 X 40131 4
10 Condenser Water Freeze Protect Comp2 X 40131 5
11 NA 40131 6
12 NA 40131 7
13 Condenser Pump#1 Fault X 40131 8
14 Condenser Pump#2 Fault X 40131 9
15 NA X 40131 10
16 NA X 40131 11
17 NA 40131 12
18 NA 40131 13
Entering Evaporator Temperature Sensor
19 X 40131 14
Fault(EWT reset active)
20 NA 40131 15
21 NA X 40132 0
22 NA X 40132 1
23 NA 40132 2
24 NA 40132 3
25 NA 40132 4
26 NA X 40132 5
27 NA X 40132 6
28 NA 40132 7
29 NA 40132 8
30 NA X 40132 9
31 NA X 40132 10
32 NA 40132 11

68 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

33 NA 40132 12
34 Evaporator Water Freeze Protect Comp 1 X 40132 13
35 Evaporator Water Freeze Protect Comp 2 X 40132 14
36 NA 40132 15
37 NA 40133 0
38 Evaporator Pump 1 Fault X 40133 1
39 Evaporator Pump 2 Fault X 40133 2
40 NA 40133 3
41 NA 40133 4

42 Compressor Current Overload Trip 1 X 40133 5


43 Compressor Current Overload Trip 2 X 40133 6
44 NA 40133 7
45 NA 40133 8
46 Motor Current Imbalance On Compressor 1 X 40133 9
47 Motor Current Imbalance On Compressor 2 X 40133 10
48 NA 40133 11
49 NA 40133 12
50 Low Motor Current Comp 1 X 40133 13
51 Low Motor Current Comp 2 X 40133 14
52 NA 40133 15
53 NA 40134 0
54 NA 40134 1
55 NA 40134 2
56 NA 40134 3
57 High Motor Temperature Comp 1 X 40134 4
58 High Motor Temperature Comp2 X 40134 5
59 NA 40134 6
60 NA 40134 7
61 Phase Loss At Compressor 1 X 40134 8
62 Phase Loss At Compressor 2 X 40134 9
63 NA 40134 10
64 NA 40134 11
65 Phase Reversal At Compressor# 1 X 40134 12
66 Phase Reversal At Compressor# 2 X 40134 13
67 NA 40134 14
68 NA 40134 15
69 Overvoltage On Compressor# 1 X 40135 0
70 Overvoltage On Compressor# 2 X 40135 1
71 NA 40135 2
72 NA 40135 3
73 Under voltage On Compressor# 1 X 40135 4
74 Under voltage On Compressor# 2 X 40135 5
75 NA 40135 6
76 NA 40135 7
77 NA 40135 8
78 Condenser Pressure Sensor Fault Circuit 1 X 40135 9
79 Condenser Pressure Sensor Fault Circuit 2 X 40135 10
80 NA 40135 11
81 NA 40135 12
82 No Condenser Water Flow X 40135 13
83 NA 40135 14

Engineered for Flexibility and performance 69


Centrifugal Installation Operation and Maintenance Manual

84 High Condenser Pressure Circuit 1 X 40135 15


85 High Condenser Pressure Circuit 2 X 40136 0
86 NA 40136 1
87 NA 40136 2
88 No Compressor Stop Comp #1 X 40136 3
89 No Compressor Stop Comp #2 X 40136 4
90 NA 40136 5
91 NA 40136 6
92 Discharge Temperature Sensor Fault Circuit 1 X 40136 7
93 Discharge Temperature Sensor Fault Circuit 2 X 40136 8
94 NA 40136 9
95 NA 40136 10
96 High Discharge Temperature Circuit 1 X 40136 11
97 High Discharge Temperature Circuit 2 X 40136 12
98 NA 40136 13
99 NA 40136 14
100 NA 40136 15
101 No Evaporator Water Flow X 40137 0
102 NA 40137 1
103 NA 40137 2
104 Low Evaporator Pressure Circuit 1 X 40137 3
105 Low Evaporator Pressure Circuit 2 X 40137 4
106 NA 40137 5
107 NA 40137 6
108 NA 40137 7
109 Evaporator Pressure Sensor Fault Circuit 1 X 40137 8
110 Evaporator Pressure Sensor Fault Circuit 2 X 40137 9
111 NA 40137 10
112 NA 40137 11
113 Ground Fault Protection 1 X 40137 12
114 Ground Fault Protection 2 X 40137 13
115 NA 40137 14
116 NA 40137 15
117 Economizer Pressure Sensor Fault 40138 0
118 NA 40138 1
119 IGV Position Sensor Fault 40138 2
120 NA 40138 3
121 DDC Position Sensor Fault 40138 4
122 NA 40138 5
123 Low Discharge Superheat 40138 6
124 NA 40138 7
125 Low Lift Pressure 40138 8
126 NA 40138 9
127 Hot Gas Bypass Position Sensor Fault 40138 10
128 NA 40138 11
129 NA 40138 12
130 NA 40138 13
131 NA 40138 14
132 NA 40138 15
133 NA 40139 0
134 NA 40139 1
135 Leaving Evaporator Water Temperature Sensor X 40139 2

70 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

Fault Comp 1
Leaving Evaporator Water Temperature Sensor 40139
136 X 3
Fault Comp 2
137 NA 40139 4
138 NA 40139 5
139 NA 40139 6
140 Mechanical High Pressure Circuit 1 X 40139 7
141 Mechanical High Pressure Circuit 2 X 40139 8
142 NA 40139 9
143 NA 40139 10
144 Low Oil Net Pressure Comp 1 X 40139 11
145 Low Oil Net Pressure Comp 2 X 40139 12
146 NA 40139 13
147 NA 40139 14
148 High Oil Feed Temperature Comp 1 X 40139 15
149 High Oil Feed Temperature Comp 2 X 40140 0
150 NA 40140 1
151 NA 40140 2
152 Low Oil Feed Temperature Comp 1 X 40140 3
153 Low Oil Feed Temperature Comp 2 X 40140 4
154 NA 40140 5
155 NA 40140 6
156 Oil Feed Temperature Sensor Fault Comp 1 X 40140 7
157 Oil Feed Temperature Sensor Fault Comp 2 X 40140 8
158 NA 40140 9
159 NA 40140 10
160 NA 40140 11
161 NA 40140 12
162 NA 40140 13
163 NA 40140 14
164 NA 40140 15
165 NA 40141 0
166 NA 40141 1
167 NA 40141 2
168 Oil Feed Pressure Sensor Fault Comp 1 X 40141 3
169 Oil Feed Pressure Sensor Fault Comp 2 X 40141 4
170 NA 40141 5
171 NA 40141 6
172 Oil Sump Pressure Sensor Fault Comp 1 X 40141 7
173 Oil Sump Pressure Sensor Fault Comp 2 X 40141 8
174 NA 40141 9
175 NA 40141 10
176 Oil Sump Temperature Sensor Fault Comp 1 X 40141 11
177 Oil Sump Temperature Sensor Fault Comp 2 X 40141 12
178 NA 40141 13
179 NA 40141 14
180 NA 40141 15
181 Starter Fault Compressor 1 X 40142 0
182 Starter Fault Compressor 2 X 40142 1
183 NA 40142 2
184 NA 40142 3
185 No Starter Transition Compressor 1 X 40142 4

Engineered for Flexibility and performance 71


Centrifugal Installation Operation and Maintenance Manual

186 No Starter Transition Compressor 2 X 40142 5


187 NA 40142 6
188 NA 40142 7
189 No Oil Pressure Start Comp 1 X 40142 8
190 No Oil Pressure Start Comp2 X 40142 9
191 NA 40142 10
192 NA 40142 11
193 NA 40142 12
194 NA 40142 13
195 NA 40142 14
196 NA 40142 15
197 Surge High Suct SH-Running Comp 1 X 40143 0
198 Surge High Suct SH-Running Comp 2 X 40143 1
199 NA 40143 2
200 NA 40143 3
201 Surge High Suct SH-Starting Comp 1 X 40143 4
202 Surge High Suct SH-Starting Comp 2 X 40143 5
203 NA 40143 6
204 NA 40143 7
205 Suction Temperature Sensor Fault Comp 1 X 40143 8
206 Suction Temperature Sensor Fault Comp 2 X 40143 9
207 NA 40143 10
208 NA 40143 11
209 Vanes Open No Start Comp 1 X 40143 12
210 Vanes Open No Start Comp 2 X 40143 13
211 NA 40143 14
212 NA 40143 15

72 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

BACnet Communication Information(M350147406)

BACnet Standard Objects


Network Control Property Units Object Name Description

Object Instance
Keypad attributes available as

Object Type
BACnet Standard Objects for

W = Write
R = Read
network control of the unit

Active Setpoint R AI 7 °F ActiveLvgWaterTarg -40° 199°F


et
*Actual Capacity (3) R AI 9 NA ChillerCapacity 0 160%
Actual RPM R 0-32678
AI 56 RPM Comp1ActualRPM
AI 60 RPM Comp2ActualRPM
*Capacity Limit (Output) (10) R AI 8 NA ActiveCapacityLimit 0 160%
*Capacity Limit Setpoint (10) W AO 32 NA NetworkCapacityLimi 0 to 160%; Default=100%
*Chiller Enable (Input) (4) W BV 41 NA ChillerEnable 0=Request Chiller Off,
1=Request Chiller On,
Chiller Limited R BI 39 NA ChillerLimited 0=Not Limited, 1=Limited
Chiller Local/Remote R BI 38 NA ChillerLocalRemote 0=Remote, 1=Local
Chiller Mode Output R MSI 44 NA ActiveMode 1=Ice, 2=Cool, 3=Heat,
Chiller Mode Setpoint W MSO 45 NA ChillerOperationMod 1=Ice, 2=Cool, 3=Heat,
Chiller On Off R BI 33 NA UnitOFF 0=Chiller Off, 1=Chiller On
Chiller Power R AI 67 NA TotalChillerKW Totalized compressor
*Chiller Status BACnet (1) R MSI 43 NA UnitStatus 1=Off, 2=Start,3=Run,
4=Pre Shutdown,
Chiller Type R MSI 48 NA DAIKIN ChillerType 1=AGZS, 2=AGZD,
3=WGZD/TGZD,
4=WSC/WDC/HTS/HTD,
5=AGSU, 6=ACZS,
7=ACZD, 8=HTM/HTMXE,
9=WGSD,
10=AGSD, 11=AGZS,
12=AGZDU, 13=WGZU,
Compressor 2 Active Capacity R AI 88 Percent Comp2ActiveCapLimi
Compressor 2 VFD Speed R AI 80 Percent Comp2Speed
Compressor Current R Amperes 0 65,535
AI 51 Current
AI 76 Comp2Current
AI 95 Comp3Current
AI 103 Comp4Current
AI 111 Comp5Current
AI 117 Comp6Current
Compressor Discharge R °F
Temperature AI 18 DischargeTemp -460° 621°F
AI 72 Comp2DischargeTm -460° 621°F
Compressor Percent RLA R Percent -3276.8 3276.7
AI 24 CompMotorCurrentP
AI 75 Comp2CurrentPercen
AI 94 Comp3CurrentPercen
AI 102 Comp4CurrentPercen
AI 110 Comp5CurrentPercen
AI 116 Comp6CurrentPercen
Compressor Power R kiloWatts 0 65,535
AI 54 Kilowatts
AI 77 Comp2Kilowatts
AI 96 Comp3Kilowatts
AI 104 Comp4Kilowatts
AI 112 Comp5Kilowatts
AI 118 Comp6Kilowatts
Compressor Run Hours R Hours

Engineered for Flexibility and performance 73


Centrifugal Installation Operation and Maintenance Manual

Network Control Property Units Object Name Description

Object Instance
Keypad attributes available as

Object Type
BACnet Standard Objects for

W = Write
R = Read
network control of the unit

Compressor Select AI 26 NA CompHours


AI 93 Comp2Hours
AI 101 Comp3Hours
AI 109 Comp4Hours
Compressor Select W MSO 46 NA CompSelect 1=Comp1, 2=Comp2,
3=Comp3, 4=Comp4,
Compressor Starts R NA
Compressor Select AI 25 CompStarts 0 65,535
AI 92 Comp2Starts
AI 100 Comp3Starts
AI 108 Comp4Starts
Compressor Status R NA Bitwise logic:
Compressor Select AI 123 CompressorStatus Bit 0=Off
AI 91 Comp2Status Bit 1=Start Oil Pump,
AI 99 Comp3Status Bit
AI 107 2=Interlock/Prelube,
Comp4Status
Bit 3=Run
AI 115 Comp5Status Bit 4=Shutdown
AI 121 Comp6Status Bit 5=Postlube
Suction Line Temperature R °F -40° 244°F
Compressor Select AI 15 SuctionTemp
AI 69 Comp2SuctTemp
Compressor Voltage R VAC 0 65,535
Compressor Select AI 52 Voltage
AI 79 Comp2Voltage
AI 98 Comp3Voltage
AI 106 Comp4Voltage
AI 114 Comp5Voltage
AI 120 Comp6Voltage
*Condenser Entering Water R AI 3 °F EntCondWaterTemp -40° 244°F
Temperature (7)

Condenser Flow Switch Status R BI 35 NA CondWaterFlowStatus 0=No Flow, 1=Flow


*Condenser Leaving Water R AI 4 °F LvgCondWaterTemp -40° 244°F
Condenser Pump Run Hours R NA
AI 28 CondPumpOperHours 0 65,535
AI 90 CondPmp2Hrs 0 65,535.
Condenser Refrigerant Pressure R psi
Compressor Select AI 16 CondPressure -3276.8 3276.7
AI 74 Comp2CondPress -3276.8 3276.7
Condenser Saturated Refrigerant R °F
Temperature AI 17 CondSatTemp -40° 244°F
AI 73 Comp2CondSatTemp -40° 244°F
Condenser Water Flow Rate R AI 50 GP CondWaterFlowRat Flow Rate in GPM
M e Centrifugals Only
Condenser Water Pump Status R BI 37 NA CondPumpState 0=No Flow, 1=Flow
*Cool Setpoint (9) W AO 29 °F NetworkCoolTempSetp 10 120°F;
Design RPM R RPM 0-32678
AI 63 Comp1DesignRPM
AI 64 Comp2DesignRPM
*Evaporator Entering Water R AI 1 °F EntEvapWaterTem -
Temperature (5) p 4
Evaporator Flow Switch Status R BI 34 NA EvapWaterFlowSta 0=No Flow, 1=Flow
*Evaporator Leaving Water R AI 2 °F LvgEvapWaterTem -
Temperature for Unit (6) pUnit 4
Evaporator Leaving Water R °F
Temperature for AI 23 LvgEvapWaterTem -40° 244°F

74 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

Compressor AI 68 Comp2EvapLvgWT -40° 244°

Engineered for Flexibility and performance 75


Centrifugal Installation Operation and Maintenance Manual

Network Control Property Units Object Name Description

Object Instance
Keypad attributes available

Object Type
W = Write
R = Read
as BACnet Standard Objects
for network control of the unit

Evaporator Pump Run Hours R NA


AI 27 EvapPumpOperHours 0 65,535
AI 89 EvapPmp2Hrs 0 65,535.
Evaporator Refrigerant R psi
Pressure AI 13 EvapPressure -3276.8 3276.7
AI 71 Comp2EvapPress -3276.8 3276.7
Evaporator Saturated R °F
Refrigerant Temperature AI 14 EvapSatTemp -40° 244°F
AI 70 Comp2EvapSatRTmp -40° 244°F
Evaporator Water Flow Rate R AI 49 GPM EvapWaterFlowRate Flow Rate in GPM
Evaporator Water Pump R BI 36 NA EvapPumpState 0=No Flow, 1=Flow
Heat Recovery Entering R AI 5 °F HeatRecEntWaterTemp -40° 244°F
Heat Recovery Leaving R AI 6 °F HeatRecLvgWaterTemp -40° 244°F
Heat Setpoint W AO 31 °F NetworkHeatTempSetpoint 50 150°F,
Ice Setpoint W AO 30 °F NetworkIceTempSetpoint 15 35°F,
IGV Percentage Open R % 0-110%
AI 58 Comp1IGVPercentOpen
AI 62 Comp2IGVPercentOpen
Inverter Temperature R °F
AI 66 Comp1InverterTmp
AI 87 Comp2InverterTmp
Liquid Line Refrigerant R AI 12 psi LiquidLinePress -22592 22591 psi
Liquid Line Refrigerant R °F
Temperature AI 11 LiquidLineTemp -40° 244°F
AI 85 Comp2LiqLineTemp -40° 244°F
Maximum RPM R RPM 0-32678
AI 55 Comp1MaxRPM
AI 59 Comp2MaxRPM
Minimum RPM R RPM 0-32678
AI Comp1MinRPM
AI Comp2MinRPM
Motor Cavity Temperature R °F
AI 65 Comp1MotorCavityTmp
AI 86 Comp1MotorCavityTmp
Oil Feed Pressure R psi
AI 19 OilFeedPressure -22592 22591 psi
AI 81 Comp2OilFeedPress -22592 22591 psi
Oil Feed Temperature R °F
AI 21 OilFeedTemp -40° 244°F
AI 83 Comp2OilFeedTemp -40° 244°F
Oil Sump Pressure R psi
AI 20 OilSumpPressure -22592 22591 psi
AI 82 Comp2OilSumpPress -22592 22591 psi
Oil Sump Temperature R °F
AI 22 OilSumpTemp -40° 244°F
AI 84 Comp2OilSumpTemp -40° 244°F
Outdoor Air Temperature R AI 10 °F OutdoorAirTemp -40° 244°F
Power Factor R Power -99 - +100
AI 53 PowerFactor
AI 78 Comp2PowerFactor
AI 97 Comp3PowerFactor
AI 105 Comp4PowerFactor
AI 113 Comp5PowerFactor
AI 119 Comp6PowerFactor
Pump Select W MSO 47 NA PumpSelect 1=Pump No. 1,
2=Pump No. 2;
Default=1

76 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

Network Control Property Units Object Name Description

Object Instance
Keypad attributes

Object Type
available as BACnet

W = Write
R = Read
Standard Objects for
network control of the unit

Run Enabled R BI 33 NA UnitOFF 0=OFF, 1=Run Allowed


*Boldface denotes data points for typical minimum integration.

Chiller Alarm Objects


Network Control Property Object Name Description

Object Instance
Object Type
Keypad attributes available as
W = Write
R = Read

BACnet Standard Objects for network


control of the unit

Warning Alarms, Analog Input Object R AI 902 AIWarningAlarm Alarm Index


Problem Alarms, Analog Input Object R AI 900 AIProblemAlarm Alarm Index
Fault Alarms, Analog Input Object (11) R AI 901 AIFaultAlarm Alarm Index
Warning Alarms, Multi-state Input R MSI 902 MSIWarningAlarm Alarm Index and Alarm Text
Problem Alarms, Multi-state Input R MSI 900 MSIProblemAlarm Alarm Index and Alarm Text
Fault Alarms, Multi-state Input Object R MSI 901 MSIFaultAlarm Alarm Index and Alarm Text
Alarm Digital Output (11) R BI 40 AlarmDigitalOutput 0-No Alarm, 1=Alarm
BACnet Clear Alarm (12) W BV 42 ClearAlarm 0= Normal, 1=Clear Alarm

BACnet Alarm Messages


The following table identifies each alarm, class, whether an acknowledgement
is required, the alarm text, and indicates system parameters at the time of the
alarm.

HTS/
Alarm Class Description Event Values
HTD/HTC

1 W NO ACTION - Condenser Entering Water Temperature Sensor 1,2,3,4,9 X


Failure
2 W NO ACTION - Evaporator Entering Water Temperature Sensor 1,2,3,4,9,10 X
Failure
3 W NO ACTION - Liquid Line Refrigerant Temperature Sensor Failure 1,2,3,4,9 X

NO ACTION (STOP if Heat) - Condenser Leaving Water


4 W 1,2,3,4,9 X
Temperature Sensor Failure

5 P RESTART DELAYED - Power Loss While Running #1 1,2,9,10

6 P RESTART DELAYED - Power Loss While Running #2 1,2,9,10

7 P RESTART DELAYED - Power Loss While Running #3 1,2,9,10

9 W Expansion Alarm Warning 1,2,9,10

10 P START INHIBITED - Ambient Temperature Low 1,2,3,4,9,10

11 P INHIBIT LOAD - Condenser Pressure High #1 1,2,9,10

Engineered for Flexibility and performance 77


Centrifugal Installation Operation and Maintenance Manual

HTS/
Alarm Class Description Event Values
HTD/HTC

12 P INHIBIT LOAD - Condenser Pressure High #2 1,2,9,10

13 P INHIBIT LOAD - Condenser Pressure High #3 1,2,9,10

15 P UNLOAD - Condenser Pressure High 1,2,9,10

16 P UNLOAD - Condenser Pressure High #1 1,2,3,4,9,10

17 P UNLOAD - Condenser Pressure High #2 1,2,3,4,9,10

18 P UNLOAD - Condenser Pressure High #3 1,2,9,10

20 P CONDENSER PUMP ON - Condenser Water Freeze Protection #1 1,2,3,4,9 X

21 P CONDENSER PUMP ON - Condenser Water Freeze Protection #2 1,2,3,4,9 X

24 P PUMP #2 START ATTEMPTED - Condenser Pump #1 Failure 1,2,3,4,9 X

25 P PUMP #1 START ATTEMPTED - Condenser Pump #2 Failure 1,2,3,4,9 X

26 P LOAD - Discharge Temperature High #1 1,2,3,4,9 X

27 P LOAD - Discharge Temperature High #2 1,2,3,4,9 X

30 P NO EWT RESET - Entering Evaporator Temperature Sensor 1,2,3,4,9 X


Failure
31 P INHIBIT LOAD - Evaporator Pressure Low 1,2,3,4,9,10

32 P INHIBIT LOAD - Evaporator Pressure Low #1 1,2,3,4,9,10 X

33 P INHIBIT LOAD - Evaporator Pressure Low #2 1,2,3,4,9,10 X

34 P INHIBIT LOAD - Evaporator Pressure Low #3 1,2,9,10

36 P UNLOAD - Evaporator Pressure Low 1,2,3,4,9,10

37 P UNLOAD - Evaporator Pressure Low #1 1,2,3,4,9,10 X

38 P UNLOAD - Evaporator Pressure Low #2 1,2,3,4,9,10 X

39 P UNLOAD - Evaporator Pressure Low #3 1,2,9,10

41 P UNLOAD - Compressor Motor Current High #1 1,2,3,4,9,10 X

42 P UNLOAD - Compressor Motor Current High #2 1,2,3,4,9,10 X

43 P UNLOAD - Compressor Motor Current High #3 1,2,9,10

45 P EVAPORATOR PUMP ON - Evaporator Water Freeze Protection 1,2,3,4,9 X


Comp #1
46 P EVAPORATOR PUMP ON - Evaporator Water Freeze Protection 1,2,3,4,9 X
Comp #2
49 P PUMP #2 START ATTEMPTED - Evaporator Pump #1 Failure 1,2,3,4,9 X

50 P PUMP #1 START ATTEMPTED - Evaporator Pump #2 Failure 1,2,3,4,9 X

52 F COMPRESSOR SHUTDOWN - Outside Air Temperature Sensor 1,2,3,4,9,10


Fault
53 F COMPRESSOR SHUTDOWN - Current Overload Trip #1 1,2,3,4,9,10 X

54 F COMPRESSOR SHUTDOWN Current Overload Trip #2 1,2,3,4,9,10 X

55 F COMPRESSOR SHUTDOWN Current Overload Trip #3 1,2,9,10

57 F COMPRESSOR SHUTDOWN Motor Current Imbalance #1 1,2,9,10 X

58 F COMPRESSOR SHUTDOWN Motor Current Imbalance #2 1,2,9,10 X

61 F COMPRESSOR SHUTDOWN Low Motor Current #1 1,2,9,10 X

62 F COMPRESSOR SHUTDOWN Low Motor Current #2 1,2,9,10 X

HTS/
Alarm Class Description Event Values HTD/
HTC

78 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

65 F UNIT SHUTDOWN - Motor Protector Trip 1,2,3,4,9,10

66 F COMPRESSOR SHUTDOWN - Motor Protector Trip #1 1,2,3,4,9,10

67 F COMPRESSOR SHUTDOWN - Motor Protector Trip #2 1,2,3,4,9,10

68 F COMPRESSOR SHUTDOWN - Motor Temperature High #1 1,2,3,4,9,10 X

69 F COMPRESSOR SHUTDOWN - Motor Temperature High #2 1,2,3,4,9,10 X

70 F COMPRESSOR SHUTDOWN - Motor Temperature High #3 1,2,9,10

72 F COMPRESSOR SHUTDOWN - Phase Loss #1 1,2,3,4,9,10

73 F COMPRESSOR SHUTDOWN - Phase Loss #2 1,2,3,4,9,10

74 F COMPRESSOR SHUTDOWN - Phase Loss #3 1,2,9,10

76 F COMPRESSOR SHUTDOWN - Phase Reversal #1 1,2,3,4,9,10

77 F COMPRESSOR SHUTDOWN - Phase Reversal #2 1,2,3,4,9,10

78 F COMPRESSOR SHUTDOWN - Phase Reversal #3 1,2,9,10

80 F COMPRESSOR SHUTDOWN - Overvoltage #1 1,2,3,4,9,10

81 F COMPRESSOR SHUTDOWN - Overvoltage #2 1,2,3,4,9,10

82 F COMPRESSOR SHUTDOWN - Overvoltage #3 1,2,9,10

84 F COMPRESSOR SHUTDOWN - Undervoltage #1 1,2,3,4,9,10

85 F COMPRESSOR SHUTDOWN - Undervoltage #2 1,2,3,4,9,10

86 F COMPRESSOR SHUTDOWN - Undervoltage #3 1,2,9,10

88 F COMPRESSOR SHUTDOWN - Condenser Pressure Sensor Fault 1,2,3,4,9,10

89 F COMPRESSOR SHUTDOWN - Condenser Pressure Sensor Fault 1,2,3,4,9,10 X


#1
90 F COMPRESSOR SHUTDOWN - Condenser Pressure Sensor Fault 1,2,3,4,9,10 X
#2
91 F COMPRESSOR SHUTDOWN - Condenser Pressure Sensor Fault 1,2,9,10
#3
93 F COMPRESSOR SHUTDOWN - Condenser Water Flow Loss 1,2,3,4,9 X

94 F COMPRESSOR SHUTDOWN - Condenser Pressure High 1,2,3,4,9,10 X

95 F COMPRESSOR SHUTDOWN - Condenser Pressure High #1 1,2,3,4,9,10 X

96 F COMPRESSOR SHUTDOWN - Condenser Pressure High #2 1,2,3,4,9,10 X

97 F COMPRESSOR SHUTDOWN - Condenser Pressure High #3 1,2,9,10

99 F COMPRESSOR OFF - Current High with Compressor OFF #1 1,2,3,4,9 X

100 F COMPRESSOR OFF - Current High with Compressor OFF #2 1,2,3,4,9 X

103 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor 1,2,3,4,9,10 X


Fault #1
104 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor 1,2,3,4,9,10 X
Fault #2
105 F COMPRESSOR SHUTDOWN Discharge Temperature Sensor 1,2,9,10
Fault #3
107 F COMPRESSOR SHUTDOWN Discharge Temperature High #1 1,2,3,4,9,10 X

108 F COMPRESSOR SHUTDOWN Discharge Temperature High #2 1,2,3,4,9,10 X

HTS/
Alarm Class Description Event Values
HTD/HTC

109 F COMPRESSOR SHUTDOWN - Discharge 1,2,9,10


Temperature High #3

Engineered for Flexibility and performance 79


Centrifugal Installation Operation and Maintenance Manual

111 F COMPRESSOR SHUTDOWN - Condenser Entering Water 1,2,3,4,9,10


Temperature Sensor Fault
112 F COMPRESSOR SHUTDOWN - Evaporator Water Flow Loss 1,2,3,4,9,10 X

113 F COMPRESSOR SHUTDOWN - Evaporator Leaving Water Temperature 1,2,3,4,9,10


Low (Freeze)
114 F COMPRESSOR SHUTDOWN - Evaporator Pressure Low 1,2,3,4,9,10

115 F COMPRESSOR SHUTDOWN - Evaporator Pressure Low #1 1,2,3,4,9,10 X

116 F COMPRESSOR SHUTDOWN - Evaporator Pressure Low #2 1,2,3,4,9,10 X

117 F COMPRESSOR SHUTDOWN - Evaporator Pressure Low #3 1,2,9,10

119 F COMPRESSOR SHUTDOWN - Evaporator Pressure Sensor Fault 1,2,3,4,9,10

120 F COMPRESSOR SHUTDOWN - Evaporator Pressure Sensor Fault #1 1,2,3,4,9,10 X

121 F COMPRESSOR SHUTDOWN - Evaporator Pressure Sensor Fault #2 1,2,3,4,9,10 X

122 F COMPRESSOR SHUTDOWN - Evaporator Pressure Sensor Fault #3 1,2,9,10

124 F COMPRESSOR SHUTDOWN - Ground Fault Trip #1 1,2,3,4,9,10


125 F COMPRESSOR SHUTDOWN - Ground Fault Trip #2 1,2,3,4,9,10
126 F COMPRESSOR SHUTDOWN - Ground Fault Trip #3 1,2,9,10
128 F COMPRESSOR SHUTDOWN - Lift Pressure Low #1 1,2,9,10
129 F COMPRESSOR SHUTDOWN - Lift Pressure Low #2 1,2,9,10
130 F COMPRESSOR SHUTDOWN - Lift Pressure Low #3 1,2,9,10
132 F COMPRESSOR SHUTDOWN - Liquid Line Pressure Sensor Fault #1 1,2,9,10

133 F COMPRESSOR SHUTDOWN - Liquid Line Pressure Sensor Fault #2 1,2,9,10

134 F COMPRESSOR SHUTDOWN - Liquid Line Pressure Sensor Fault #3 1,2,9,10

136 F COMPRESSOR SHUTDOWN - Liquid Line Temperature Sensor Fault #1 1,2,9,10

137 F COMPRESSOR SHUTDOWN - Liquid Line Temperature Sensor Fault #2 1,2,9,10

138 F COMPRESSOR SHUTDOWN - Liquid Line Temperature Sensor Fault #3 1,2,9,10

140 F UNIT LOCKOUT - Number of Allowed Re-Starts Exceeded 1,2,9,10

141 F COMPRESSOR LOCKOUT - Number of Allowed Re- Starts Exceeded #1 1,2,3,4,9,10

142 F COMPRESSOR LOCKOUT - Number of Allowed Re- Starts Exceeded #2 1,2,3,4,9,10

143 F COMPRESSOR LOCKOUT - Number of Allowed Re- Starts Exceeded #3 1,2,9,10

145 F COMPRESSOR SHUTDOWN - Evaporator Leaving Water Temperature 1,2,3,4,9,10


Sensor Fault
146 F COMPRESSOR SHUTDOWN - Evaporator Leaving Water Temperature 1,2,3,4,9 X
Sensor Fault #1
147 F COMPRESSOR SHUTDOWN - Evaporator Leaving Water Temperature 1,2,3,4,9 X
Sensor Fault #2
150 F UNIT STOP - Mechanical High Pressure Trip 1,2,9,10

HTS/
Alarm Class Description Event Values
HTD/HTC

151 F COMPRESSOR SHUTDOWN - Mechanical High Pressure Trip #1 1,2,3,4,9,10 X

80 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

152 F COMPRESSOR SHUTDOWN - Mechanical High Pressure Trip #2 1,2,3,4,9,10 X

153 F COMPRESSOR SHUTDOWN - Mechanical High Pressure Trip #3 1,2,9,10

155 F COMPRESSOR SHUTDOWN - Oil Net Pressure Low #1 1,2,3,4,9 X

156 F COMPRESSOR SHUTDOWN - Oil Net Pressure Low #2 1,2,3,4,9 X

159 F COMPRESSOR SHUTDOWN - Oil Feed Temperature High #1 1,2,3,4,9 X

160 F COMPRESSOR SHUTDOWN - Oil Feed Temperature High #2 1,2,3,4,9 X

163 F COMPRESSOR SHUTDOWN - Oil Feed Temperature Low #1 1,2,3,4,9 X

164 F COMPRESSOR SHUTDOWN - Oil Feed Temperature Low #2 1,2,3,4,9 X

167 F COMPRESSOR SHUTDOWN - Oil Feed Temperature Sensor Fault #1 1,2,3,4,9 X

168 F COMPRESSOR SHUTDOWN - Oil Feed Temperature Sensor Fault #2 1,2,3,4,9 X

171 F COMPRESSOR SHUTDOWN - Oil Level Low #1 1,2,9,10

172 F COMPRESSOR SHUTDOWN - Oil Level Low #2 1,2,9,10

173 F COMPRESSOR SHUTDOWN - Oil Level Low #3 1,2,9,10

175 F COMPRESSOR SHUTDOWN - Oil Filter Delta Pressure High #1 1,2,9,10

176 F COMPRESSOR SHUTDOWN - Oil Filter Delta Pressure High #2 1,2,9,10

177 F COMPRESSOR SHUTDOWN - Oil Filter Delta Pressure High #3 1,2,9,10

179 F COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor Fault #1 1,2,3,4,9 X

180 F COMPRESSOR SHUTDOWN - Oil Feed Pressure Sensor Fault #2 1,2,3,4,9 X

183 F COMPRESSOR SHUTDOWN - Oil Sump Pressure Sensor Fault #1 1,2,3,4,9 X

184 F COMPRESSOR SHUTDOWN - Oil Sump Pressure Sensor Fault #2 1,2,3,4,9 X

187 F COMPRESSOR SHUTDOWN - Oil Sump Temperature Sensor Fault #1 1,2,3,4,9 X

188 F COMPRESSOR SHUTDOWN - Oil Sump Temperature Sensor Fault #2 1,2,3,4,9 X

191 F SHUTDOWN Phase Voltage Protection 1,2,3,4,9

192 F COMPRESSOR SHUTDOWN - Starter Fault Compressor #1 1,2,3,4,9,10 X

193 F COMPRESSOR SHUTDOWN - Starter Fault Compressor #2 1,2,3,4,9,10 X

194 F COMPRESSOR SHUTDOWN - Starter Fault Compressor #3 1,2,9,10

196 F COMPRESSOR SHUTDOWN - No Starter Transition #1 1,2,3,4,9 X

197 F COMPRESSOR SHUTDOWN - No Starter Transition #2 1,2,3,4,9 X

200 F COMPRESSOR START ABORT - Oil Pressure Low #1 1,2,3,4,9 X

201 F COMPRESSOR START ABORT - Oil Pressure Low #2 1,2,3,4,9 X

204 F COMPRESSOR SHUTDOWN - Subcooling Low #1 1,2,9,10

HTS/
Alarm Class Description Event Values
HTD/HTC

205 F COMPRESSOR SHUTDOWN - Subcooling Low #2 1,2,9,10

Engineered for Flexibility and performance 81


Centrifugal Installation Operation and Maintenance Manual

206 F COMPRESSOR SHUTDOWN - Subcooling Low #3 1,2,9,10


COMPRESSOR SHUTDOWN - Surge Suction Superheat High-Running
208 F 1,2,3,4,9 X
#1
COMPRESSOR SHUTDOWN - Surge Suction Superheat High-Running
209 F 1,2,3,4,9 X
#2
212 F COMPRESSOR SHUTDOWN - Surge Suction Superheat High-Starting #1 1,2,3,4,9 X

213 F COMPRESSOR SHUTDOWN - Surge Suction Superheat High-Starting #2 1,2,3,4,9 X

216 F COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault #1 1,2,3,4,9,10 X

217 F COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault #2 1,2,3,4,9,10 X

218 F COMPRESSOR SHUTDOWN - Suction Temperature Sensor Fault #3 1,2,9,10


COMPRESSOR START ABORT - Vanes Open OR No Start Interlock
220 F 1,2,3,4,9 X
Switch #1
COMPRESSOR START ABORT - Vanes Open OR No Start Interlock
221 F 1,2,3,4,9 X
Switch #2
224 F COMPRESSOR SHUTDOWN - (Check Chiller Display for Cause) 1,2,3,4,9,10 X

225 F C-Stop - General Comp Fault#1 1,2,3,4,9,10 X


226 F C-Stop - General Comp Fault#2 1,2,3,4,9,10 X
227 F C-Stop - Communication Fault #1 1,2,3,4,9,10 X
228 F C-Stop - Communication Fault #2 1,2,3,4,9,10 X
229 F C-Stop - Interlock Fault #1 1,2,3,4,9,10 X
230 F C-Stop - Interlock Fault #2 1,2,3,4,9,10 X
231 F C-Stop - Bearing Fault #1 1,2,3,4,9,10 X
232 F C-Stop - Bearing Fault #2 1,2,3,4,9,10 X
233 F C-Stop - Motor Fault #1 1,2,3,4,9,10 X
234 F C-Stop - Motor Fault #2 1,2,3,4,9,10 X
235 F C-Stop - Drive Fault #1 1,2,3,4,9,10 X
236 F C-Stop - Drive Fault #2 1,2,3,4,9,10 X
237 F C-Stop - Internal Control Err#1 1,2,3,4,9,10 X
238 F C-Stop - Internal Control Err#2 1,2,3,4,9,10 X
239 W Warn-Chiller Capacity Limited 1,2,3,4,9,10 X
240 F U-Stop - Check Valve Fault #1 1,2,3,4,9,10 X
241 F U-Stop - Check Valve Fault #2 1,2,3,4,9,10 X
242 F U-Stop - LB Valve Fault #1 1,2,3,4,9,10 X
243 F U-Stop - LB Valve Fault #2 1,2,3,4,9,10 X

82 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

BACnet Communication Information(E8211212/3)

BACnet Data Points


Chiller Variables
Network Control Read/
Data Type Index Description
Property Write
Cool Setpoint(9) R/W AV 1 3~21
Ice Setpoint R/W AV 50 -9.4~3.4
Heat Setpoint R/W AV 5 35~55
Capacity Limit AV
W 3 0~100%
Setpoint(10)
Chiller Mode AV
W 1017 1=Ice,2=Cool,3=Heat
Setpoint(2)
Chiller Enable
R/W BV 1 0=Off,1=On
Input(4)
BV 0=Off,
Run Enabled R 2
1=Run Allowed
Chiller Local/Remote R BV 5 0=Remote,1=Local
BV 0=Not Limited,
Chiller Limited R 6
1=Limited
Chiller Mode AV
R 1019 1=Ice,2=Cool,3=Heat
Output
AV 1=Off,2=Start,
3=Run,
Chiller Status(1) R 1018
4=Pre-Shutdown,
5=Service
Active Setpoint R AV 2 -9.4~55
Actual Capacity(3) R AV 10 0~125%
Capacity Limit AV
R 42 0~100%
Output
Evaporator Entering AV
R 4 -25~100
Water Temperature(5)
Evaporator Leaving AV
R 6 -25~100
Water Temperature(6)
Condenser Entering AV
R 7 -25~100
Water Temperature(7)
Condenser Leaving AV
R 8 -25~100
Water Temperature(8)
Heat Recovery Entering AV
R 22 -25~100
Water Temperature
Heat Recovery Leaving AV
R 23 -25~100
Water Temperature
Evaporator Flow Switch 0=No Flow,
R BV 7
Status 1=Flow
Condenser Flow Switch 0=No Flow,
R BV 8
Status 1=Flow
0=Pump Off,
Evaporator Pump Status R BV 29
1=Pump On
0=Pump Off,
Condenser Pump Status R BV 31
1=Pump On
Pump Select R/W BV 19 0=Pump No.1

Engineered for Flexibility and performance 83


Centrifugal Installation Operation and Maintenance Manual

1=Pump No.2
Evaporator Pump
Run Hours
R
Pump Select AV 1047 0~65,535
Pump#2 AV 1103 0~65,535
Condenser Pump Run Hours
Pump Select R AV 1048 0~65,535
Pump#2 AV 1104 0~65,535
Comp Select R/W AV 1032 0~65,535
Condenser Refrigerant
Pressure
AV 0~2800kP
Compressor Select R 21
a
AV 0~2800kP
Compressor #2 93
a
Condenser Saturated
Temperature
R
Compressor Select AV 20 -25~62
Compressor #2 AV 92 -25~62
Evaporator Refrigerant
Pressure
R
Compressor Select AV 17 0~910kPa
Compressor #2 AV 90 0~910kPa
Evaporator Saturated
Temperature
R
Compressor Select AV 16 -25~40
Compressor #2 AV 89 -25~40
Liquid Line
Refrigerant Temperature
AV -
Compressor Select R 36
25~100
AV -
Compressor #2 104
25~100
Compressor
Current(Benshow Starter)
AV 0~65,535
Compressor Select R 26
Amps
AV 0~65,535
Compressor #2 95
Amps
Compressor
Voltage(Benshow Starter)
AV 0~65,535
Compressor Select R 29
Volts
AV 0~65,535
Compressor #2 98
Volts
Compressor Power(Benshow
Starter)
AV 0~65,535k
Compressor Select R 27
iloWatts
AV 0~65,535k
Compressor #2 96
iloWatts
Compressor
R
Percent RLA

84 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

Compressor Select AV 25 0~125%


Compressor #2 AV 94 0~125%
Discharge Temperature
AV -
Compressor Select 19
R 25~100
AV -
Compressor #2 91
25~100
Suction Temperature
AV -
Compressor Select 15
R 25~100
AV -
Compressor #2 88
25~100
Oil Feed Pressure
AV 0~2800kP
Compressor Select 32
R a
AV 0~2800kP
Compressor #2 100
a
Oil Sump Pressure
Compressor Select R AV 33 0~910kPa
Compressor #2 AV 101 0~910kPa
Oil Feed Temperature
AV -
Compressor Select 34
R 25~100
AV -
Compressor #2 102
25~100
Oil Sump Temperature
AV -
Compressor Select 35
R 25~100
AV -
Compressor #2 103
25~100
Compressor Run Hours
Compressor Select R AV 1046 0~65,535
Compressor #2 AV 1107 0~65,535
Compressor Starts
Compressor Select R AV 1045 0~65,535
Compressor #2 AV 1106 0~65,535
Chiller Alarm Variables
Network Control Read/
Data Type Index Description
Property Write
0=No Alarm,
Alarm Digital Output(11) R BV 3
1=Alarm
0=Normal,
Clear Alarm(12) R/W BV 24
1=Clear Alarm
1001~ 16Holding Registers:
Active Alarms(13) R AV 1014(MV/ Each bit representing
AV) an alarm condition
Modbus Alarms
WSC
WDC
Holding
# Description WCC WMC WT C Bit
Register
HSC
TSC

Engineered for Flexibility and performance 85


Centrifugal Installation Operation and Maintenance Manual

Warnings
1 Entering Condenser Water Temperature Sensor Fault X X X 1001 1
2 Entering Condenser Water Temperature Sensor Fault X X X 1001 2
3 Liquid Line Refrigerant Temperature Sensor Fault X X X 1001 3
4 Leaving Condenser Water Temperature Sensor Fault X X X 1001 4
Problems
5 NA 1002 0
6 NA 1002 1
7 NA 1002 2
8 NA 1002 3
9 Condenser Water Freeze Protect Comp1 X X X 1002 4
10 Condenser Water Freeze Protect Comp2 X X X 1002 5
11 NA 1002 6
12 NA 1002 7
13 Condenser Pump#1 Fault X X X 1002 8
14 Condenser Pump#2 Fault X X X 1002 9
15 NA X X X 1002 10
16 NA X X 1002 11
17 NA 1002 12
18 NA 1002 13
19 Entering Evaporator Temperature Sensor Fault(EWT reset active) X X X 1002 14
20 NA 1002 15
21 NA X X X 1003 0
22 NA X X 1003 1
23 NA 1003 2
24 NA 1003 3
25 NA 1003 4
26 NA X X X 1003 5
27 NA X X 1003 6
28 NA 1003 7
29 NA 1003 8
30 NA X X X 1003 9
31 NA X X 1003 10
32 NA 1003 11
33 NA 1003 12
34 Evaporator Water Freeze Protect Comp 1 X X X 1003 13
35 Evaporator Water Freeze Protect Comp 2 X X 1003 14
36 NA 1003 15
37 NA 1004 0
38 Evaporator Pump 1 Fault X X X 1004 1
39 Evaporator Pump 2 Fault X X 1004 2
40 NA 1004 3
41 NA 1004 4
Faults
42 Compressor Current Overload Trip 1 X X X 1004 5
43 Compressor Current Overload Trip 2 X X 1004 6
44 NA 1004 7
45 NA 1004 8
46 Motor Current Imbalance On Compressor 1 X X X 1004 9
47 Motor Current Imbalance On Compressor 2 X X 1004 10
48 NA 1004 11
49 NA 1004 12

86 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

50 Low Motor Current Comp 1 X X X 1004 13


51 Low Motor Current Comp 2 X X 1004 14
52 NA 1004 15
53 NA 1005 0
54 NA 1005 1
55 NA 1005 2
56 NA 1005 3
57 High Motor Temperature Comp 1 X X X 1005 4
58 High Motor Temperature Comp2 X X 1005 5
59 NA 1005 6
60 NA 1005 7
61 Phase Loss At Compressor 1 X1 1005 8
62 Phase Loss At Compressor 2 X1 1005 9
63 NA 1005 10
64 NA 1005 11
65 Phase Reversal At Compressor# 1 X1 1005 12
66 Phase Reversal At Compressor# 2 X1 1005 13
67 NA 1005 14
68 NA 1005 15
69 Overvoltage On Compressor# 1 X1 1006 0
70 Overvoltage On Compressor# 2 X1 1006 1
71 NA 1006 2
72 NA 1006 3
73 Under voltage On Compressor# 1 X1 1006 4
74 Under voltage On Compressor# 2 X1 1006 5
75 NA 1006 6
76 NA 1006 7
77 NA 1006 8
78 Condenser Pressure Sensor Fault Circuit 1 X X X 1006 9
79 Condenser Pressure Sensor Fault Circuit 2 X X 1006 10
80 NA 1006 11
81 NA 1006 12
82 No Condenser Water Flow X X X 1006 13
83 NA 1006 14
84 High Condenser Pressure Circuit 1 X X X 1006 15
85 High Condenser Pressure Circuit 2 X X 1007 0
86 NA 1007 1
87 NA 1007 2
88 No Compressor Stop Comp #1 X X X 1007 3
89 No Compressor Stop Comp #2 X X 1007 4
90 NA 1007 5
91 NA 1007 6
92 Discharge Temperature Sensor Fault Circuit 1 X X X 1007 7
93 Discharge Temperature Sensor Fault Circuit 2 X X 1007 8
94 NA 1007 9
95 NA 1007 10
96 High Discharge Temperature Circuit 1 X X X 1007 11
97 High Discharge Temperature Circuit 2 X X 1007 12
98 NA 1007 13
99 NA 1007 14
100 NA 1007 15
101 No Evaporator Water Flow X X X 1008 0

Engineered for Flexibility and performance 87


Centrifugal Installation Operation and Maintenance Manual

102 NA 1008 1
103 NA 1008 2
104 Low Evaporator Pressure Circuit 1 X X X 1008 3
105 Low Evaporator Pressure Circuit 2 X X 1008 4
106 NA 1008 5
107 NA 1008 6
108 NA 1008 7
109 Evaporator Pressure Sensor Fault Circuit 1 X X X 1008 8
110 Evaporator Pressure Sensor Fault Circuit 2 X X 1008 9
111 NA 1008 10
112 NA 1008 11
113 Ground Fault Protection 1 X1 1008 12
114 Ground Fault Protection 2 X1 1008 13
115 NA 1008 14
116 NA 1008 15
117 Economizer Pressure Sensor Fault X 1009 0
118 NA 1009 1
119 IGV Position Sensor Fault X 1009 2
120 NA 1009 3
121 DDC Position Sensor Fault X 1009 4
122 NA 1009 5
123 Low Discharge Superheat X 1009 6
124 NA 1009 7
125 Low Lift Pressure X 1009 8
126 NA 1009 9
127 Hot Gas Bypass Position Sensor Fault X 1009 10
128 NA 1009 11
129 NA 1009 12
130 NA 1009 13
131 NA 1009 14
132 NA 1009 15
133 NA 1010 0
134 NA 1010 1
135 Leaving Evaporator Water Temperature Sensor Fault Comp 1 X X X 1010 2
136 Leaving Evaporator Water Temperature Sensor Fault Comp 2 X X 1010 3
137 NA 1010 4
138 NA 1010 5
139 NA 1010 6
140 Mechanical High Pressure Circuit 1 X X X 1010 7
141 Mechanical High Pressure Circuit 2 X X 1010 8
142 NA 1010 9
143 NA 1010 10
144 Low Oil Net Pressure Comp 1 X X 1010 11
145 Low Oil Net Pressure Comp 2 X 1010 12
146 NA 1010 13
147 NA 1010 14
148 High Oil Feed Temperature Comp 1 X X 1010 15
149 High Oil Feed Temperature Comp 2 X 1011 0
150 NA 1011 1
151 NA 1011 2
152 Low Oil Feed Temperature Comp 1 X X 1011 3
153 Low Oil Feed Temperature Comp 2 X 1011 4

88 Engineered for Flexibility and performance


Centrifugal Installation Operation and Maintenance Manual

154 NA 1011 5
155 NA 1011 6
156 Oil Feed Temperature Sensor Fault Comp 1 X X 1011 7
157 Oil Feed Temperature Sensor Fault Comp 2 X 1011 8
158 NA 1011 9
159 NA 1011 10
160 NA 1011 11
161 NA 1011 12
162 NA 1011 13
163 NA 1011 14
164 NA 1011 15
165 NA 1012 0
166 NA 1012 1
167 NA 1012 2
168 Oil Feed Pressure Sensor Fault Comp 1 X X 1012 3
169 Oil Feed Pressure Sensor Fault Comp 2 X 1012 4
170 NA 1012 5
171 NA 1012 6
172 Oil Sump Pressure Sensor Fault Comp 1 X X 1012 7
173 Oil Sump Pressure Sensor Fault Comp 2 X 1012 8
174 NA 1012 9
175 NA 1012 10
176 Oil Sump Temperature Sensor Fault Comp 1 X X 1012 11
177 Oil Sump Temperature Sensor Fault Comp 2 X 1012 12
178 NA 1012 13
179 NA 1012 14
180 NA 1012 15
181 Starter Fault Compressor 1 X X X 1013 0
182 Starter Fault Compressor 2 X X 1013 1
183 NA 1013 2
184 NA 1013 3
185 No Starter Transition Compressor 1 X X 1013 4
186 No Starter Transition Compressor 2 X 1013 5
187 NA 1013 6
188 NA 1013 7
189 No Oil Pressure Start Comp 1 X X 1013 8
190 No Oil Pressure Start Comp2 X 1013 9
191 NA 1013 10
192 NA 1013 11
193 NA 1013 12
194 NA 1013 13
195 NA 1013 14
196 NA 1013 15
197 Surge High Suct SH-Running Comp 1 X X X 1014 0
198 Surge High Suct SH-Running Comp 2 X X 1014 1
199 NA 1014 2
200 NA 1014 3
201 Surge High Suct SH-Starting Comp 1 X X X 1014 4
202 Surge High Suct SH-Starting Comp 2 X X 1014 5
203 NA 1014 6
204 NA 1014 7
205 Suction Temperature Sensor Fault Comp 1 X X X 1014 8

Engineered for Flexibility and performance 89


Centrifugal Installation Operation and Maintenance Manual

206 Suction Temperature Sensor Fault Comp 2 X X 1014 9


207 NA 1014 10
208 NA 1014 11
209 Vanes Open No Start Comp 1 X X2 X 1014 12
210 Vanes Open No Start Comp 2 X X2 1014 13
211 NA 1014 14
212 NA 1014 15
1
_Solid State Starter Option required. Not available on WMC.
2
_Should be No Start- Interlock Switch on WMC chiller.

90 Engineered for Flexibility and performance

Vous aimerez peut-être aussi