Division Functional Chemicals

®
Protectogen
Corrosion inhibitor for closed heating and coo-
ling systems without antifreezing action

Product description
Notes on use *)
Protectogen is a yellowish, water soluble, gly-
col free liquid, which is a highly efficient Product properties
combination of organic and anorganic salts for
sufficient corrosion inhibition. The product is The technical data below describe the product
free of nitrite, amine and heavy metals. and does not constitute of part of the delivery
Furthermore, the product is free of phosphates specification. The mandatory product specifi-
and silicates which can lead to precipitations in cation will be found in the current technical
combination with hard water. data sheet.

Density at 20 °C g/cm³ approx.. 1.10


(DIN 51757)
Refractive index at 20 °C approx. 1.434
(DIN 51423, part 2)
pH value (pure) approx. 10.5
pH value (2 % v/v in water) approx. 8.0
(DIN 51369)
Reserve alkalinity ml 0.1 m HCl min. 60
(ASTM D 1121)
Pour point (pure) °C approx. –30
(DIN 51583)
Kinematic viscosity at 20 °C mm²/s approx. 350
(DIN 51562)
Boiling point at 1013 mbar °C approx. +113
(ASTM D 1120)
Surface tension (2 % v/v) mN/m approx. 47
in deionized water at 20°C
Electrical conductivity (2 % v/v) µS/cm approx. 4800
in deionized water at 20°C

*) The technical data describe the product and does not constitute of part of the delivery specification. The mandatory product specification
will be found in the current technical data sheet. Additional informations on product properties, toxicological, ecological and safety rele-
vant data can be found in the current EG safety data sheet.

= registered trademark Page 1/6

Clariant GmbH
Division Functional Chemicals
D-65840 Sulzbach
Division Functional Chemicals

®
Protectogen

Application properties in winter. For protection from frost, please use


our products ®Antifrogen N, L or KF. The
Protectogen is usually used in a concentration following table shows the relatively low corro-
of 2 Vol-% in mixture with drinking water sion of common used metals caused by Protec-
which has a maximum concentration of 100 togen/water mixtures. The values were deter-
mg/kg chlorides. 2.0 l Protectogen will be ad- mined by the ASTM D 1384 method and show
ded for 100 l ready-made product. This mixtu- the weight loss of the metals in g/m² due to
re does not offer any frost resistance and it is corrosion.
therefore not suitable for outdoor applications

Weight loss in g/m²


Metal Protectogen Mains water
2.0 % (v/v) 14 °dH

Copper (Cu) -0.7 -1.0


Soft solder (WL 30) -1.9 -11
Brass (MS 63) -0.7 -1.0
Steel (St 37) -0.4 -72
Cast iron (GG 25) -0.8 -182
Aluminium (AlSi6Cu3) -4.8 -28

Mixtures of Protectogen with tap water are oxygen access through seals or plastic ele-
dealing with a long lasting corrosion protection ments which can not be avoided. Special addi-
of all common used metals such as copper, tives prevent lime precipitations due to hard
brass, iron metals, soft solder, aluminium al- water. Protectogen can be used in a tempera-
loys and combinations thereof, even in mixed ture range from approx. +5 to +95 °C.
installation. Since zinc may be dissolved – Please note the following tips regarding filling
especially at higher temperatures – please a- of the installation and activity of the product:
void to use galvanized pipelines.
Seals which are commonly used in heating
systems (IT seals and elastomers) have been
found to be resistant. Protectogen is especially
suitable for the use in cold water sets which
do not require frost protection, i.e. in a tempe-
rature range from +5 to +15°C. By adding
Protectogen, the specific heat transfer abilities
of water will not be influenced significantly at
all. Protectogen can be added even in closed
heating systems if there is any possibility of

= registered trademark Page 2/6

Clariant GmbH
Division Functional Chemicals
D-65840 Sulzbach
Division Functional Chemicals

®
Protectogen

Filling, operation and activity duration


with Protectogen 5. Performance check
Due to the danger of corrosion, low concentra-
1. Checking of the installation tions of Protectogen/water mixtures should be
Before filling the system with Protecto- avoided.
gen/water the pipe connections, vessels and If the system is topped up with liquid the per-
circulating pumps should be checked for tight- formance of the mixture should be checked, at
ness. Especially regarding older systems it is least on a yearly basis. This service (for free) is
recommended to renew all sealants. Suitable offered by: Clariant GmbH, Werk Gendorf,
for this purpose are common IT- and rubber Division FUN, R&D, Bau 300, D-84504
sealants. In order to seal the pipe connections, Burgkirchen, Germany, Tel.: +49 - (0) 86 79 -
a combination of hemp with (R)Fermit or 7 22 72.
(R)Fermitol (Nissen & Volk, Hamburg) or
(R)Loctite has been carried out. During system The data in our service report relate solely to
construction only chloride-free solvents shall the sample sent to us. Guidance on further use
be used. of the product tested assumes that the system is
in proper condition and properly operated. We
2. Identifying content of the system and would expressly point out that, particularly
flushing where corrosion or scale is already present in
Simultaneously to checking the tightness of the the system, interactions with the product may
system, the needed water amount should be occur with unpredictable consequences. We
determined by use of a hydrometer. The instal- accept no liability whatsoever for any damage
lation should be drained again to get rid of rust resulting from the improper condition or opera-
and other pollutions. Older systems which tion of the system.
were running without corrosion protective
additives, must be thoroughly inspected and 6. Draining
cleaned well; this can be achieved by use of The system should be left drained only for a
inhibited acid. short time.

3. Dosage
Protectogen should be diluted with tap water or
deionized water. The dosage for sufficient
corrosion protection is 2 % v/v, i.e. 2 l Protec-
togen for 100 l water capacity. The tap water 7. Duration of activity
used for diluting Protectogen should have a The activity of the corrosion inhibitors strongly
middle grade of hardness and it should not depends on the individual application conditi-
contain more than 100 ppm (mg/kg) chlorides ons. Therefore, the systems should be designed
(this can be requested at your local water- as closed circuits with expansion tanks. By
treatment plant). using the recommended concentration of Pro-
tectogen the corrosion inhibitors will have a
4. Filling the installation long-lasting effect. Regarding open systems
Only clean, thoroughly rinsed and rust-free the inhibitor activity may decrease significant-
systems should be filled with Protectogen. ly faster, especially at higher temperatures.
After checking the tightness the system should
be filled right away with Protectogen/water in
order to avoid corrosion damages.

= registered trademark Page 3/6

Clariant GmbH
Division Functional Chemicals
D-65840 Sulzbach
Division Functional Chemicals

®
Protectogen

8. Mixing with other products


Any mixture of Protectogen with other pro-
ducts – particularly with salt or glycole based
products – can lead to incompatibilities.

Safety, Toxicology and


Ecology Transport and Storage
Protectogen is harmful to humans and animals Protectogen is supplied in non-returnable
if swallowed. Consult a doctor immediately if drums (240 kg). Smaller canisters are available
the product is swallowed inadvertently. from our dealers. The storage stability of Pro-
The water hazard class of the pure product is tectogen at room temperature in its original
WGK 1, the ready-made Protectogen/water sealed container is limited to 2 years.
mixture is rated as being not water-polluting.
Undiluted Protectogen can be disposed of in a
special waste incineration plant in accordance
with local regulations. The biodegradability of
Protectogen/water mixtures is very good; the Appendix
mixtures can therefore be taken to a biological
treatment plant for biodegradation, after con- The following diagrams show the most impor-
sultation with the operator, provided the rele- tant physical properties of Protectogen/water
vant legal provisions on water and waste allow mixtures.
this. The product contains organic and anorga-
nic salts which act as corrosion inhibiting a-
gents for a long time. Protectogen is free of
amines, nitrates, phosphates and heavy metals.

Further information will be found in the cur-


rent EG safety data sheet.

= registered trademark Page 4/6

Clariant GmbH
Division Functional Chemicals
D-65840 Sulzbach
Division Functional Chemicals

®
Protectogen

Density (0-3 %)

Protectogen
Dependency of Density and Concentration

1,005

1,004

1,003
density at 20°C ( g/cm³ )

1,002

1,001

1,000

0,999

0,998

0,997
0 0,5 1 1,5 2 2,5 3
concentration ( % v/v )

Refractice index (0-3 %)

Protectogen
Dependency of Refractive Index and Concentration

1,3375

1,3370

1,3365

1,3360
refractive index at 2O °C

1,3355

1,3350

1,3345

1,3340

1,3335

1,3330

1,3325
0 0,5 1 1,5 2 2,5 3
concentration ( % v/v )

= registered trademark Page 5/6

Clariant GmbH
Division Functional Chemicals
D-65840 Sulzbach
Division Functional Chemicals

®
Protectogen

This information is based on our present state would expressly point out that, particularly
of knowledge and is intended to provide gene- where corrosion or scale is already present in
ral notes on our products and their uses. It the system, interactions with the product may
should not therefore be construed as guaran- occur with unpredictable consequences. We
teeing specific properties application. accept no liability whatsoever for any damage
Any existing industrial property rights must be resulting from the improper condition or opera-
observed. The quality of our product is guaran- tion of the system.
teed under our General Conditions of Sale. We

Issued: April 2002


Th 20855 d

= registered trademark Page 6/6