Académique Documents
Professionnel Documents
Culture Documents
Overview
Description
2
Simplicity in a complex world
Quite simply – SIPROTEC 4
Face the future with confidence and
innovative solutions.
SIPROTEC 4 is a flexible and powerful
solution for protecting your power sys-
tem.
LSP2296-afp.tif
Relay Families
Introduction • In 1976, the first minicomputer (process com-
puter)-based protection system was commis-
Siemens is one of the world’s leading suppliers of sioned: A total of 10 systems for 110/20 kV sub-
protection equipment for power systems. stations was supplied and is still operating
2 satisfactorily today.
Thousands of our relays ensure first-class
performance in transmission and distribution • Since 1985, we have been the first to manufacture
networks on all voltage levels, all over the world, a range of fully numerical relays with standardized
in countries of tropical heat or arctic frost. communication interfaces.
For many years, Siemens has also significantly Today, Siemens offers a complete range of protec-
influenced the development of protection tion relays for all applications including numerical
technology. busbar and machine protection.
To date, more than 600,000 numerical protection
relays from Siemens are providing successful ser-
vice, as stand-alone units in traditional systems or
as components of combined substation protection
Fig. 2/1 and substation control.
Meanwhile, the SIPROTEC 4 series has established
itself right across the market, incorporating many
years of operational experience with thousands of
relays, together with users’ requirements.
LSP2257-afp.tif
State-of-the-art technology
Mechanical and solid-state (static) relays have
been almost completely phased out of our
production because numerical relays are now
preferred by the users due to their decisive
advantages:
• Compact design and lower costs due to integration
SIPROTEC 4 family
of many functions into one relay
• High availability even with less maintenance due
to integral self-monitoring
• No drift (aging) of measuring characteristics due
to fully numerical processing
• High measuring accuracy due to digital filtering
LSP2879.tif
SIPROTEC ‘600
• Many integrated add-on functions, for example,
series for load-monitoring, event/fault recording and
thermal monitoring
• Local operation keypad and display designed to
modern ergonomic criteria
• Easy and reliable read-out of information via serial
LSP2880.tif
SIP053-afp.eps
Modern protection management “One feeder, one relay” concept Fig. 2/2
Numerical relays offer
All the functions, for example, of a line protection Analog protection schemes have been engineered increased information
availability
scheme can be incorporated in one unit: and assembled from individual relays. Interwiring
between these relays and scheme testing has been
• Distance protection with associated add-on and
carried out manually in the workshop.
monitoring functions
Data sharing now allows for the integration of
• Universal teleprotection interface by binary in-
several protection and protection-related tasks
put/contacts or serial interface
into one single numerical relay. Only a few exter-
• Auto-reclosure and synchronism check nal devices may be required for completion of the
total scheme. This has significantly lowered the
Protection-related information can be called up
costs of engineering, assembly, panel wiring, test-
on-line or off-line, such as:
ing and commissioning. Scheme failure probabil-
• Distance to fault ity has also been lowered.
• Fault currents and fault voltages Engineering has moved from schematic diagrams
towards a parameter definition procedure. A pow-
• Relay operation data (fault detector pickup, oper-
erful user-definable logic integrated in SIPROTEC 4
ating times etc.)
allows flexible customized design for protection,
• Set values control and measurement.
• Line load data (kV, A, MW, kVAr) Measuring included
To fulfill vital protection redundancy require- For many applications, the accuracy of the protec-
ments, only those functions which are interde- tion current transformer is sufficient for opera-
pendent and directly associated with each other tional measuring. The additional measuring c.t.
are integrated in the same unit. For back-up pro- was required to protect the measuring instru-
tection, one or more additional units should be ments under short-circuit conditions. Due to the
provided. low thermal withstand capability of the measuring
All relays can stand fully alone. Thus, the tradi- instruments, they could not be connected to the
tional protection concept of separate main and protection c.t.. Consequently, additional measur-
backup protection as well as the external connec- ing core c.t.s and measuring instruments are now
tion to the switchyard remain unchanged. only necessary where high accuracy is required,
e.g. for revenue metering.
Fig. 2/3
PC-aided setting
procedure
The relays may be set in 2 steps. First, all relay Setpoints Relay operations
settings are prepared in the office with the aid of a
local PC and stored on a file. On site, the settings
can then be downloaded from a PC into the relay.
The relay confirms the settings and thus provides
an unquestionable record.
Vice versa, after a system fault, the relay memory
can be uploaded to a PC, and comprehensive fault
2
analysis can then take place in the engineer’s office
if required.
Alternatively, the total relay dialog can be guided
from any remote location via a modem-telephone
connection (Fig. 2/4) or via the utility network.
LSP2260-afp.tif
the reliability of the protection functions (Fig. 2/8).
The following solutions are available within one
relay family:
• Separate control and protection relays
• Feeder protection and remote control of the line
The high processing power of modern numerical circuit-breaker via the serial communication link
units allows further integration of non-protective
• Combined relays for protection, monitoring and
add-on functions.
control
The question as to whether separate or combined
Mixed use of the different relay types is possible
relays should be used for protection and control
Fig. 2/8 on account of the uniform operation and commu-
cannot be uniformly answered. In transmission-
SIPROTEC 4 relays nication procedures.
7SJ61/62/63, 64 type substations, separation into independent
implemented functions hardware units is still preferred, whereas on the
LSP2265-afp.tif
This offers a number of advantages for the user:
• Reduced engineering and testing efforts due to 2
well-suited functions
• Reduced training due to uniform operation and
setting for all relays
• Uniform data management due to a common
operator program
Our 3 product families have a common basis and
with their characteristic features are optimized for
your main area of application.
LSP2329-afpen.tif
A great variety of units ranging from overcurrent-
time protection for medium-voltage applications
to distance and differential protection for extra-
high-voltage applications. All the units have con-
trol functions (partly with graphic display) and of-
fer a great variety of communications possibilities.
They have a large number of integrated protection
functions, from which the user can easily select
those required for his specific case of application.
SIPROTEC 4 relays
Relay Families
SIPROTEC 4 relays are available in 1/3 to 1/1
of 19” wide housings with a standard height of
243 mm. Their size is compatible with that of
other relay families. Therefore, compatible ex-
change is always possible.
All wires (cables) are connected at the rear side of
2 the relay with or without ring cable lugs. A special
LSP2276-afp.tif
relay version with a detached cable-connected op-
erator panel (Fig. 2/13) is also available. It allows,
Fig. 2/10 1/1 of 19”
for example, the installation of the relay itself in
the low-voltage compartment and of the operator
panel separately in the door of the switchgear.
Terminals
Standard relay version with screw-type terminals
Current terminals
Connection Wmax = 12 mm
LSP2266-afp.tif
Voltage terminals
Connection Wmax = 10 mm
Ring cable lugs d1 = 4 mm
LSP2261-afpen.tif
Fig. 2/13
SIPROTEC 4
combined protection,
2-pin or 3-pin
control and connectors
monitoring relay 7SJ63
with detached operator Wire size 0.5 - 1.0 mm2
panel 0.75 - 1.5 mm2
1.0 - 2.5 mm2
Local operation
All operator actions can be executed and informa-
tion displayed via an integrated user interface.
Two alternatives for this interface are available.
On the backlit LCD display, process and device
information can be displayed as text.
2
Freely assignable LEDs are used to display process
or device information. The LEDs can be labelled
according to user requirements. An LED reset key
resets the LEDs and can be used for LED testing.
LSP2284-afpen.eps
4 configurable function keys permit the user to
execute frequently used actions simply and fast. Fig. 2/15
Numerical keys
detection.
Display editor
A display editor is available to design the display
on SIPROTEC 4 units with graphic display. The
predefined symbol sets can be expanded to suit
the user. The drawing of a single-line diagram is
extremely simple. Load monitoring values (analog
values) and any texts or symbols can be placed on 2
the display where required.
LSP2285-afpen.tif
ting groups can be activated via binary inputs, via
DIGSI 4 (local or remote), via the integrated key-
pad or via the serial substation control interface.
Relay Families
SIPROTEC 4 relays
LSP2273-afpen.tif
switching sequences can be configured simply via
drag and drop of logic symbols; no special knowl-
edge of programming is required. Logical ele-
ments, such as AND, OR, flip-flops and timer
Fig. 2/20
elements are available. The user can also generate CFC logic with module library
user-defined annunciations and logical combina-
tions of internal or external signals.
Retrofitting: communication modules
Communication interfaces It is possible that the relays are supplied directly
with two communication modules for the service
With respect to communication, particular em- and substation control interfaces or to retrofit the
phasis has been placed on high levels of flexibility, communication modules at a later stage. The
data integrity and utilization of standards com- modules are mounted on the rear side of the relay.
mon in energy automation. The design of the As standard, the time synchronization interface is
communication modules permits interchange- always supplied.
ability on the one hand, and on the other hand The communication modules are available for the
provides openness for future standards. entire SIPROTEC 4 relay range. Depending on the
relay type the following protocols are available:
LSP2261-afpen.tif
RS232, RS485
Note:
For further details of communication features, please refer
to Part 4.
Indication derivation
LSP2277-afp.tif
Navigation keys
8 configurable LEDs
Battery cover
Fig. 2/30
SIPROTEC Compact overcurrent relay
Relay Families
Terminals
Current terminals:
Single conductors:
Conductor cross-section 2.0 – 4.0 mm2 (AWG 14-11)
Insulation skipping length 15 mm
Voltage terminals:
LSP2878.tif
Single conductors:
Conductor cross-section 0.5 – 2.5 mm2 (AWG 20-13)
Insulation skipping length 12 mm
Fig. 2/32a
Voltage terminals
LSP2876.tif
Fig. 2/33
Power supply
Two versions will cover the whole range:
a) 24/48 V DC
Fig. 2/32b b) 60 to 250 V DC, 115 and 230 V AC
Current terminals
Fault analysis
The SlPROTEC ‘600 relays supply detailed data for
the analysis of faults and for checking of operating Four configurable LEDs
conditions
• Fault records Two line 8-digit display
The last 8 fault records can always be displayed. If
a new fault occurs, the oldest will be overwritten.
• Operational indications
This log records up to 30 internal events in the relay Keys for navigation and entering of settings
with 1 ms resolution.
• Fault event logs
LSP2278-afp.tif
The last 8 faults are stored. All fault event logs are
time-stamped with a resolution of 1 ms.
Typical Protection
Schemes
Application Circuit Circuit equipment protected Page
number
2 Cables and overhead lines Radial feeder circuit 2/22
1
2 Ring-main circuit 2/22
3 Switch-onto-fault protection 2/23
4 Directional comparison protection (cross-coupling) 2/23
5 Distribution feeder with reclosers 2/23
6 3-pole multishot auto-reclosure (AR, ANSI 79) 2/24
7 Parallel feeder circuit 2/24
8 Reverse power monitoring at double infeed 2/25
9 Synchronization function 2/25
10 Cables or short overhead lines with infeed from both ends 2/26
11 Overhead lines or longer cables with infeed from both ends 2/26
12 Subtransmission line 2/26
13 Transmission line with reactor 2/28
14 Transmission line or cable (with wide-band communication) 2/29
15 Transmission line, breaker-and-a-half terminal 2/30
Transformer Notes:
2 protection 1) Auto-reclosure 79 only with overhead lines.
see Fig. 2/52
2) Negative sequence overcurrent protection 46 as
sensitive backup protection against unsymmet-
rical faults.
General hints:
• The relay at the far end (D) is set with shortest
operating time.
Relays further upstream have to be time-graded
against the next downstream relay in steps of
about 0.3 seconds.
• Inverse time or definite time can be selected
according to the following criteria:
Definite time:
Source impedance large compared to the line
impedance, i.e. small current variation between
near and far end faults
Inverse time:
Longer lines, where the fault current is much
Fig. 2/35 *) Alternatives: less at the far end of the line than at the local
7SJ45/46, 7SJ61 end.
Very or extremely inverse time:
Lines where the line impedance is large com-
pared to the source impedance (high difference
Transformer
protection for close-in and remote faults) or lines, where
see Fig. 2/55 coordination with fuses or reclosers is neces-
sary. Steeper characteristics also provide higher
stability on service restoration (cold load pickup
and transformer inrush currents).
2 Ring-main circuit
General hints:
• Operating time of overcurrent relays to be coordi-
nated with downstream fuses of load transformers.
(Preferably very inverse-time characteristic with
about 0.2 s grading-time delay)
• Thermal overload protection for the cables
(option)
• Negative sequence overcurrent protection 46 as
sensitive protection against unsymmetrical faults
(option).
Fig. 2/36
*) Alternatives:
7SJ45/46, 7SJ61, 7SJ80
3 Switch-onto-fault protection
If switched onto a fault, instantaneous tripping
can be effected. If the internal control function is
used (local, via binary input or via serial inter-
face), the manual closing function is available
without any additional wiring. If the control
switch is connected to a circuit-breaker bypassing 2
the internal control function, manual detection
using a binary input is implemented.
Fig. 2/37
Fig. 2/38
Fig. 2/39
*) Alternatives:
7SJ60, 7SJ62/63/64, 7SJ80
Fig. 2/40
Fig. 2/41
*) Alternatives:
7SJ62, 7SJ80
Fig. 2/42
9 Synchronization function
Note:
1) Also available in relays 7SA6, 7SD5, 7SA522,
7VK61.
General hints:
• When two subnetworks must be interconnected,
the synchronization function monitors whether
the subnetworks are synchronous and can be con-
nected without risk of loosing stability.
• This synchronization function can be applied in
conjunction with the auto-reclosure function as
well as with the control function CLOSE com-
mands (local/remote). Fig. 2/43
12 Subtransmission line
Note:
Fig. 2/45 1) Connection to open delta winding if available.
Relays 7SA6/522 and 7SJ62 can, however, also
be set to calculate the zero-sequence voltage
internally.
General hints:
• Distance teleprotection is proposed as main, and
time-graded directional overcurrent as backup
protection.
• The 67N function of 7SA6/522 provides addi-
tional high-resistance earth-fault protection.
It can be used in parallel with the 21/21N function.
• Recommended teleprotection schemes:
PUTT on medium and long lines with phase shift
carrier or other secure communication channel
POTT on short lines.
BLOCKING with On/Off carrier (all line lengths).
Fig. 2/46
Fig. 2/47
Fig. 2/50
Fig. 2/51
Transformers
Typical Protection
Schemes
16 Small transformer infeed
General hints:
2 • Earth faults on the secondary side are detected by
current relay 51N which, however, has to be time-
graded against downstream feeder protection re-
lays.
The restricted earth-fault relay 87N can optionally
be applied to achieve fast clearance of earth faults
in the transformer secondary winding.
Relay 7VH60 is of the high-impedance type and
requires class X CTs with equal transformation
ratio.
• Primary circuit-breaker and relay may be replaced
by fuses.
Fig. 2/52
Fig. 2/53
Fig. 2/54
Fig. 2/55
Fig. 2/56
22 Autotransformer
Notes:
1) 87N high-impedance protection requires spe-
cial class X current transformer cores with
equal transformation ratio.
2) The 7SJ60 relay can alternatively be connected
in series with the 7UT613 relay to save this CT
core.
General hint:
• Two different protection schemes are provided:
87T is chosen as low-impedance three-winding
version (7UT613). 87N is a single-phase high-
impedance relay (7VH60) connected as restricted
earth-fault protection. (In this example, it is as-
Fig. 2/58 sumed that the phase ends of the transformer
winding are not accessible on the neutral side, i.e.
there exists a CT only in the neutral earthing con-
nection.)
Fig. 2/59
Motors 1)
Fig. 2/62
Fig. 2/63
Generators
Fig. 2/66
29 Generators > 1–3 MW
(Fig. 2/67)
Notes:
1) Functions 81 and 59 are only required where
prime mover can assume excess speed and the
voltage regulator may permit rise of output
voltage above upper limit.
2) Differential relaying options:
– Low-impedance differential protection 87.
– Restricted earth-fault protection with low ohmic
resistance-earthed neutral (see Fig. 2/65).
Fig. 2/64
With solidly-
earthed neutral
Fig. 2/67
Fig. 2/65
With resistance-earthed neutral
Fig. 2/68
Fig. 2/69
Fig. 2/70
Busbars
Fig. 2/71
Fig. 2/72
Fig. 2/73
Fig. 2/74
Siemens SIP · 2008 2/41
2 Overview
Networks
Typical Protection
37 Load shedding
Schemes (Fig. 2/75)
In unstable networks (e.g. solitary networks,
emergency power supply in hospitals), it may be
necessary to isolate selected loads from the net-
2 work to prevent overload of the overall network.
The overcurrent-time protection functions are
effective only in the case of a short-circuit.
Overloading of the generator can be measured as
a frequency or voltage drop.
(Protection functions 27 and 81 available in
7RW600 and 7SJ6..)
Fig. 2/75
38 Load shedding
with rate-of-frequency-change protection
(Fig. 2/76)
The rate-of-frequency-change protection calcu-
lates, from the measured frequency, the gradient
or frequency change df/dt. It is thus possible to de-
tect and record any major active power loss in the
power system, to disconnect certain consumers
accordingly, and to restore the system to stability.
Unlike frequency protection, rate-of-frequency-
change protection already reacts before the fre-
quency threshold is undershot. To ensure effective
protection settings, it is recommended to consider
Fig. 2/76 requirements throughout the power system as a
whole. The rate-of-frequency-change protection
function can also be used for the purposes of sys-
tem decoupling.
Rate-of-frequency-change protection can also be
enabled by an underfrequency state.
Fig. 2/77
Notes:
1) The transformer is protected by differential
protection and inverse or definite-time
overcurrent-time protection functions for the
phase currents. In the event of a fault, the
circuit-breaker CB1 on the utility side is tripped
by a remote link. Circuit-breaker CB2 is tripped
additionally.
2) Overcurrent-time protection functions protect
feeders 1 and 2 against short-circuits and over-
load caused by the connected loads. Both the
phase currents and the zero currents of the
feeders can be protected by inverse and defi-
nite-time overcurrent-time stages. The circuit-
breakers CB4 and CB5 are tripped in the event
of a fault.
Transformer feeders
The energizing of transformers causes inrush cur-
rents that may last for seconds, depending on their
size (Fig. 2/79).
Selection of the pickup current and assigned time
delay have to be coordinated so that the inrush
current decreases below the relay o/c reset value
before the set operating time has elapsed.
The inrush current typically contains only about
50 % fundamental frequency component.
Numerical relays that filter out harmonics and the
DC component of the inrush current can there-
fore be set more sensitive. The inrush current peak
values of Fig. 2/79 will be reduced more than to
Time constant of inrush current one half in this case.
Nominal power 0.5 … 1.0 1.0 … 10 > 10 Some digital relay types have an inrush detection
(MVA) function which may block the trip of the over-
Time constant 0.16 … 0.2 0.2 … 1.2 1.2 … 720 current protection resulting from inrush currents.
(s)
Fig. 2/79 Earth-fault protection relays
Earth-current relays enable a much more sensitive
Typical applications and functions setting, as load currents do not have to be consid-
ered (except 4-wire circuits with single-phase load).
Relay operating characteristics and their setting In solidly and low-resistance earthed systems a set-
must be carefully coordinated in order to achieve ting of 10 to 20 % rated load current can generally
selectivity. The aim is basically to switch off only be applied. High-resistance earthing requires much
the faulted component and to leave the rest of the more sensitive setting in the order of some amperes
power system in service in order to minimize sup- primary. The earth-fault current of motors and
ply interruptions and to assure stability. generators, for example, should be limited to values
below 10 A in order to avoid iron burning.
Sensitivity
Residual-current relays in the star point connection
Protection should be as sensitive as possible to of CTs can in this case not be used, in particular
detect faults at the lowest possible current level. with rated CT primary currents higher than 200 A.
At the same time, however, it should remain The pickup value of the zero-sequence relay would
stable under all permissible load, overload and in this case be in the order of the error currents of
through-fault conditions. For further information the CTs. A special core-balance CT is therefore
see: http://www.siemens.com/systemplanning. used in this case as earth-current sensor. The
The Siemens engineering programs SINCAL and core-balance CT 7XR96 is designed for a ratio of
SIGRADE are especially designed for selective 60/1 A. The detection of 6 A primary would then
protection grading of protection relay systems. require a relay pickup setting of 0.1 A secondary.
They provide short-circuit calculations, interna- An even more sensitive setting is applied in isolated
tional standard characteristics of relays, fuses and or Petersoncoil-earthed networks where very low
circuit-breakers for easy protection grading with earth currents occur with single-phase-to-earth
respect to motor starting, inrush phenomena and faults. Settings of 20 mA and less may then be
equipment damage curves. required depending on the minimum earth-fault
current. Sensitive directional earth-fault relays
(integrated in the relays 7SJ62, 63, 64, 7SJ80,
7SK80, 7SA6) allow settings as low as 5 mA.
Motor feeders
The energization of motors causes a starting
current of initially 5 to 6 times the rated current
(locked rotor current).
A typical time-current curve for an induction mo-
tor is shown in Fig. 2/80.
2
In the first 100 ms, a fast decaying asymmetrical
inrush current appears additionally. With conven-
tional relays it was common practice to set the in-
stantaneous overcurrent stage of the short-
circuit protection 20 to 30 % above the locked-
rotor current with a short time delay of 50 to
100 ms to override the asymmetrical inrush
period.
Numerical relays are able to filter out the asym-
metrical current component very rapidly so that
the setting of an additional time delay is no longer
Fig. 2/80
applicable.
Typical motor current-time
The overload protection characteristic should fol- characteristics
low the thermal motor characteristic as closely as
possible. The adaptation is made by setting the Differential relay (87)
pickup value and the thermal time constant, using
the data supplied by the motor manufacturer. Transformer differential relays are normally set to
Further, the locked-rotor protection timer has to pickup values between 20 and 30 % of the rated
be set according to the characteristic motor value. current. The higher value has to be chosen when
the transformer is fitted with a tap changer.
Time grading of o/c relays (51) Restricted earth-fault relays and high-resistance
motor / generator differential relays are, as a rule,
The selectivity of overcurrent protection is based set to about 10 % of the rated current.
on time grading of the relay operating characteris-
tics. The relay closer to the infeed (upstream relay)
lnstantaneous overcurrent protection (50)
is time-delayed against the relay further away
from the infeed (downstream relay). The calcula- This is typically applied on the final supply load or
tion of necessary grading times is shown in on any protection relay with sufficient circuit im-
Fig. 2/82 by an example for definite-time pedance between itself and the next downstream
overcurrent relays. protection relay. The setting at transformers, for
The overshoot times take into account the fact example, must be chosen about 20 to 30 % higher
that the measuring relay continues to operate due than the maximum through-fault current. The re-
to its inertia, even when the fault current is inter- lay must remain stable during energization of the
rupted. This may be high for mechanical relays transformer.
(about 0.1 s) and negligible for numerical relays
(20 ms).
The setting values for the relay at station B are: The normal way
• Pickup current: Ip/IN = 1.1 To prove the selectivity over the whole range of
• Time multiplier Tp = 0.11 possible short-circuit currents, it is normal
practice to draw the set of operating curves in a
Given these settings, we can also check the operat- common diagram with double log scales. These
ing time of the relay in B for a close-in fault in F3: diagrams can be calculated manually and drawn
The short-circuit current increases in this case to point-by-point or constructed by using templates.
2690 A (see Fig. 2/83). 2
The corresponding I/Ip value is 12.23. Today, computer programs are also available for
this purpose. Fig. 2/85 shows the relay coordina-
• With this value and the set value of Tp = 0.11 tion diagram for the example selected, as calcu-
we obtain again an operating time of 0.3 s lated by the Siemens program SIGRADE
(see Fig. 2/84). (Siemens Grading Program). For further
information please see:
Station A: http://www.siemens.com/systemplanning
• We add the time grading interval of 0.3 s
and find the desired operating time Note:
tA = 0.3 + 0.3 = 0.6 s. To simplify calculations, only inverse-time char-
Following the same procedure as for the relay in acteristics have been used for this example. About
station B, we obtain the following values for the 0.1 s shorter operating times could have been
relay in station A: reached for high-current faults by additionally
applying the instantaneous zones I>> of the 7SJ60
• Pickup current: Ip/IN = 1.0 relays.
• Time multiplier Tp = 0.17
• For the close-in fault at location F4 we obtain an Coordination of o/c relays with fuses
operating time of 0.48 s. and low-voltage trip devices
The procedure is similar to the above-described
Normal inverse grading of o/c relays. A time interval between 0.1
0.14 and 0.2 seconds is usually sufficient for a safe time
t= ⋅ Tp ( s) coordination.
(I I )
0 .02
p −1
Very and extremely inverse characteristics are of-
ten more suitable than normal inverse characteris-
tics in this case. Fig. 2/86 shows typical examples.
Simple distribution grid stations use a power fuse
on the secondary side of the supply transformers
(Fig. 2/86a).
In this case, the operating characteristic of the
o/c relay at the infeed has to be coordinated with
the fuse curve.
Very inverse characteristics may be used with ex-
pulsion-type fuses (fuse cutouts) while extremely
inverse versions adapt better to current limiting
fuses.
In any case, the final decision should be made by
plotting the curves in the log-log coordination
diagram.
Electronic trip devices of LV breakers have long-
delay, short-delay and instantaneous zones.
Numerical o/c relays with one inverse-time and
two definite-time zones can closely be adapted to
this (Fig. 2/86b).
Fig. 2/84
Normal inverse-time
characteristic of the 7SJ60 relay
Protection Coordination
a) b)
Fig. 2/86
Coordination of an o/c relay with an MV fuse
and low-voltage breaker trip device
X Prim Min
l min =
′
X Line
Fig. 2/88
Operating characteristics
of Siemens distance relays
Protection Coordination The reset time is 1 cycle for EHV relays (7SA6/52,
7VK61) and 1.5 to 2 cycles for distribution type
relays (7SJ***).
Fig. 2/90 shows the time chart for a typical breaker
failure protection scheme. The stated times in
parentheses apply for transmission system protec-
tion and the times in square brackets for distribu-
2 tion system protection.
Setting
The setting is always a trade-off between sensitiv-
ity and stability. A higher voltage setting leads not
only to enhanced through-fault stability, but also
to higher CT magnetizing and varistor leakage
currents resulting consequently in a higher pri-
mary pickup current.
2
A higher voltage setting also requires a higher
Fig. 2/91
knee-point voltage of the CTs and therefore
Principal connection
greater size of the CTs. diagram
A sensitivity of 10 to 20 % IN is normal for motor
and transformer differential protection, or for Sensitivity:
restricted earth-fault protection. IFmin = N ⋅ (IR + IVar + n · ImR)
Stability:
RR
IF max Through <N ⋅ ⋅ IR
Rlead + RCT
600 10 ,000
IF max Through < ⋅ ⋅ 0.02
1 3+ 4
IF max Through < 17 kA (28 x IN)
Relay type Transient dimensioning factor Ktd Min. required sym. short- Min. required kneepoint voltage VK
circuit current factor K’ssc
I High set point I High set point
Overcurrent-time and motor – K'ssc ≥ VK ≥ · (Rct + R'b) · Isn
protection I pn . ⋅ I pn
13
7SJ511, 512, 531 20
7SJ45, 46, 60 at least: 20 at least: · (Rct + R'b) · Isn
7SJ61, 62, 63, 64 13
.
7SJ80, 7SK80
I scc max (ext. fault) I scc max (ext. fault)
Line differential protection – K'ssc ≥ VK ≥ · (Rct + R'b) · Isn
(pilot wire) I pn 13. ⋅ I pn
7SD600
and: and:
Protection Coordination
The CT requirements mentioned in Table 2/1 on page 2/53 are simplified in order to allow fast CT
calculations on the safe side. More accurate dimensioning can be done by more intensive calculation
with Siemens’ CTDIM (V 3.21) program. Results of CTDIM are released by the relay manufacturer.
2 Adaption factor for 7UT6, 7UM62 relays (limited resolution of measurement)
(also 7SD52, 53, 610, when transformer inside protected zone)
with
InO = rated current of the protected object
VnO = rated voltage of the protected object
INrelay = rated current of the relay
SN max = maximum load of the protected object (for transformers: winding with max. load)
Attention: when low impedance REF is used, the request for the REF side (3-phase) is:
¼ ≤ FAdap ≤ 4, (for the neutral CT: ¼8 ≤ FAdap ≤ 8
Further condition for 7SD52x, 53x, 610 relays
(when used as line differential protection without transformer inside protected zone)
Maximum ratio between primary currents of CTs at the end of the protected line:
I pn max
≤8
I pn min
Fig. 2/92
Example 1 (continued)
Verification of the numerical differential protection
Ktd = 5 (from Table 2/1) Ktd = 3 (from Table 2/1) Ktd = 3 (from Table 2/1) Ktd = 1.2 (from Table 2/1)
I scc max (ext. fault) I scc max (ext. fault) I 2
K'ssc ≥ Ktd · K'ssc ≥ Ktd · K'ssc ≥ Ktd · scc max (ext. fault)
I pn I pn I pn
31378 A 35860 A 7498 A
=5· = 28.8 =3· = 17.9 =3· = 18.7
6000 A 6000 A 1200 A
Sn 20 VA Sn 20 VA Sn 50 VA
Rb = = = 20 Ω Rb = = = 20 Ω Rb = = =2Ω
I 2 sn 1 A 2 I 2 sn 1 A 2 I 2 sn 5 A 2
R'b = Rlead + Rrelay R'b = Rlead + Rrelay R'b = Rlead + Rrelay R'b = Rlead + Rrelay
= 111.8 V
K'ssc required = 28.8, K'ssc required = 17.9, K'ssc required = 18.7, VK required = 111.8 V,
K'ssc effective = 40.8 K'ssc effective = 41.2 K'ssc effective = 30.6 VK effective = 200 V
28.8 < 40.8 17.9 < 41.2 18.7 < 30.6 111.8 V < 200 V
Q CT dimensioning is ok Q CT dimensioning is ok Q CT dimensioning is ok Q CT dimensioning is ok
ANSI CT definition
K ssc
Vs.t.max = 20 ⋅ 5 A ⋅ Rb ⋅
20
with
Pb
Rb = 2
and I Nsn = 5 A , we get
I sn
Vs.t.max Pb ⋅ K ssc
=
5A
Example:
IEC 600/5, 5P20, 25 VA
60044:
ANSI
C57.13: Vs.t.max =
(25 VA ⋅ 20) = 100 V, acc. to class C100
5A