MOTOR LOGIC PLUS™ Overload Relay

in Model 6 Motor Control Centers

The SQUARE D® MOTOR LOGIC PLUS Features


solid state overload relay is available as • 4.5:1 adjustment
a selection in Model 6 MCC starter
• Automatic, network,
units. The overload is one of the most
electronic or manual reset
advanced relays of its kind on the
market today. • 19.2K baud MODBUS
RS485
• Fully programmable
Data and Diagnostics
• Current, voltage, and
The MOTOR LOGIC PLUS can be
trip indication via alpha-
provided with optional communications
numeric LED display
capability in Model 6 MCCs. When
selected, a wealth of motor information • Local programming via external 9V power source
is available to the host device. This data, • For manual reset, a through-the-door reset is replaced
which includes motor current and volt- by a push button mounted on the control station plate
age among others, provides you with a • Software available for data acquisition, monitoring and
view into your process, allowing you to configuration
maintain your system and keep your
process running smoothly.
Advanced Protection
With the communications option, cabling • Overload, underload, jam • High/Low voltage
is installed in the MCC to connect the
overload relays via MODBUS®, making • Single and reverse phasing • Ground fault
the data available to a host PC running • Voltage and current unbalance • Rapid cycling
SQUARE D POWERLOGIC® SMS
software or SQUARE D 9999 MLPS
Solutions software for overload monitoring. MCC MOTOR LOGIC PLUS Applications for FVNR, FVR, RVAT
Network bridges are available for other Amp Range HP@ HP@ HP @ HP@ NEMA
networks. The MOTOR LOGIC PLUS 208V 240V 48OV 600V Size
can be implemented with the control
wiring method of your choice. An inte- 0.5-2.3 NA 0.5 0.5-1 0.5-1.5 1*
grated solution is available, OMNI 2-9 0.5-1.5 0.75-2 1.5-3 2-5 1*
CENTER Enhanced, which features
MOTOR LOGIC PLUS overloads along 6-27 2-7.5 3-7.5 5-10 7.5-10 1
with a MOMENTUM® I/O base in each
unit. This base provides control and data 10-45 10 10-15 15-25 15-25 2
acquisition over one network cable.
20-90 15-25 20-30 30-50 30-50 3
Network options include DEVICENET®,
MODBUS PLUS, and PROFIBUS®. 60-135 30-40 40-50 60-100 60-100 4

120-270 50-75 60-100 125-200 125-200 5

240-540 100-150 125-200 250-400 250-400 6

* NEMA Size 1 is standard


MOTOR LOGIC PLUS™ Overload Relay
in Model 6 Motor Control Centers

Commands and Parameters Available over a Network


Read/Write Read Only
• Commands: Stop, Reset/Run*, Display Lock, Display Unlock, Network Lock, • Average Voltage
Network Unlock, Config Enable • Average Current
*The network reset replaces the Reset/Program push button. It does not perform a system
reset or a power-on reset of the SSOLR. Thermal memory is not affected.
• Error and Trip Indicators
• L1 Current (A)
• Trip class and jam detection (TC)
• L2 Current (B)
• Current transformer effective turns ratio (MULT)
• L3 Current (C)
• Low-voltage trip point (LV) and high-voltage trip point (HV)
• L1-L2 Voltage
• Voltage unbalance trip point (VUB)
• L2-L3 Voltage
• Overcurrent trip point (OC) and undercurrent trip point (UC)
• L1-L3 Voltage
• Current unbalance trip point (CUB)
• Voltage Unbalance
• Ground fault trip point (GF)
• Current Unbalance
• Rapid cycle timer (RD1)
• Power Factor Angle
• Overload and phase loss/unbalance restart delay, motor cool-down timer (RD2)
• Thermal Capacity Remaining
• Undercurrent restart delay, dry well recovery timer (RD3)
• Ground Fault Current
• Number of restarts after an overload (manual or automatic) (#RF)
• Fault History (last 4 faults)
• Number of restarts after an undercurrent (manual or automatic) (#RU)
• RD1 Elapsed Time
• Undercurrent trip delay (UCTD)
• RD2 Elapsed Time
• RD3 Elapsed Time

Application Notes
• When MOTOR LOGIC PLUS is selected, a “Reset” pilot device push button eliminates the reset in the door option.
• MODBUS cabling is furnished when the MODBUS Communication Option is selected. When selected, vertical wireway
trunkline cabling, and drop connection to overload is furnished.

Motor Logic Plus Programming and Monitoring


Local Programming:
Local programming should rarely be used unless the overload is not tied
to a network. Local programming is accomplished by applying 9Vdc to
the “P” and “G” terminals of the communication module. Configuration
of parameters is an easy process. By using the Mode Select switch,
Program/Display dial and Reset/Program push button on the face of the
overload, parameter setting can be made without a network connection or
hand-held programmer.
Remote Programming and Monitoring:
The MOTOR LOGIC PLUS is a fully programmable electronic overload
with a communication port (2-wire or 4-wire configuration). Three distinct
methods of remote monitoring and programming are available.
• 9999MLPS Solutions software is available to monitor up to 99 overloads Solutions Software Information screen on a
via MODBUS on a Windows® platform. Windows PC platform.The information screen
• Use various types of automation and control products such as PLCs to allows you to monitor real-time motor information
monitor data and change set points via MODBUS. OMNI-Enhanced from your PC. Software functionality also includes
supports MODBUS PLUS, DEVICENET, and PROFIBUS as well.
data logging, trip limits read/write, and fault listing.
• POWERLOGIC software may be used to monitor data from the overload
via MODBUS.