Vous êtes sur la page 1sur 17

Eng. & Tech. Journal ,Vol.27, No.

16,2009

Simulation of a Power Transformer Differential


Protective Relay
Mohammed S. Abdulraheem* & Adel Ridha Othman**
Received on:2/4/2008
Accepted on:2/7/2009

Abstract
The aim of this work is to simulate a differential relay, which ensures security
for external fault, inrush, and overexcitation conditions and provides dependability
for internal faults, to protect a single phase power transformer.
This work combines harmonic restraint and blocking methods with a waveshape
recognition technique.
The harmonic based dual slope characteristic differential relay is modeled in
MATLAB (version 7.3) functions. Two approaches are used to simulate the power
transformer transients modeling to evaluate the differential relay performance for
different operation conditions: The first approach has modeled the power
transformer transients in MATLAB functions to simulate the inrush, overexcitation
and external fault conditions, the interfacing of this model with the differential
relay MATLAB functions is accomplished via the sampler model which is
simulated in the environment of SIMULINK. The second approach has modeled
the power transformer transients using the power system blockset to simulate the
internal faults and the sinusoidal inrush current conditions, this model is set to
interact with the differential relay MATLAB functions by the environment of
SIMULINK.

Keywords: Transformer, Inrush, Excitation, Differential, Relaying

‫ﻟﺔ ﺍﻟﻘﺩﺭﺓ‬‫ل ﺤﻤﺎﻴﺔ ﺘﻔﺎﻀﻠﻲ ﻟﻤﺤﻭ‬‫ﻤﺤﺎﻜﺎﺓ ﻤﺭﺤ‬


‫ﺍﻟﺨﻼﺼﺔ‬
‫ﻟﺔ ﺍﻟﻘﺩﺭﺓ ﺍﻟﺫﻱ ﻴﻀﻤﻥ ﺍﻟﺼﻤﻭﺩ ﺃﻤﺎﻡ‬‫ل ﺘﻔﺎﻀﻠﻲ ﻟﺤﻤﺎﻴﺔ ﻤﺤﻭ‬‫ﻴﻬﺩﻑ ﺍﻟﺒﺤﺙ ﺍﻟﻰ ﻤﺤﺎﻜﺎﺓ ﻤﺭﺤ‬
‫ ﻭﻴﻭﻓﺭ ﻭﺜﻭﻗﻴﺔ ﺍﻟﻌﻤل ﻟﻸﻋﻁﺎل‬، ‫ ﺘﻴﺎﺭ ﺍﻻﻨﺩﻓﺎﻉ ﻭﺘﻴﺎﺭ ﺍﻻﺜﺎﺭﺓ ﺍﻟﺘﺸﺒﻌﻲ‬، ‫ﺤﺎﻻﺕ ﺍﻷﻋﻁﺎل ﺍﻟﺨﺎﺭﺠﻴﺔ‬
‫ ﻫﺫﺍ ﺍﻟﺒﺤﺙ ﻴﺠﻤﻊ ﻁﺭﻕ ﻜﺒﺢ ﻭﺤﺠﺯ ﺍﻟﺘﻭﺍﻓﻘﻴﺎﺕ ﻤﻊ ﺘﻘﻨﻴﺔ‬. ‫ﻟﺔ ﺍﻟﻘﺩﺭﺓ ﺍﻻﺤﺎﺩﻴﺔ ﺍﻟﻁﻭﺭ‬‫ﺍﻟﺩﺍﺨﻠﻴﺔ ﻟﻤﺤﻭ‬
. ‫ﺘﻤﻴﻴﺯ ﺍﻟﺸﻜل ﺍﻟﻤﻭﺠﻲ‬
‫ل ﺍﻟﺘﻔﺎﻀﻠﻲ ﺫﻭ ﺍﻟﺨﻭﺍﺹ ﺍﻟﺜﻨﺎﺌﻴﺔ ﺍﻟﻤﻴل ﻭﺍﻟﺫﻱ ﻴﻌﺘﻤﺩ ﺍﺴﺎﺱ ﻋﻤﻠﻪ ﻋﻠـﻰ‬‫ﺘﻡ ﺼﻴﺎﻏﺔ ﻨﻤﻭﺫﺝ ﺍﻟﻤﺭﺤ‬
‫ﻟـﺔ ﺍﻟﻘـﺩﺭﺓ ﻟﺘﻤﺜﻴـل‬‫ ﺘﻡ ﺍﺴﺘﺨﺩﺍﻡ ﻁﺭﻴﻘﺘﻴﻥ ﻟﺼﻴﺎﻏﺔ ﻨﻤﻭﺫﺝ ﻤﺤﻭ‬.MATLAB‫ ﺒﺒﺭﻨﺎﻤﺞ‬,‫ﺍﻟﺘﻭﺍﻓﻘﻴﺎﺕ‬
‫ ﺍﻟﻁﺭﻴﻘﺔ ﺍﻻﻭﻟﻰ ﺘﻡ‬.‫ل ﺍﻟﺘﻔﺎﻀﻠﻲ ﻟﻤﺨﺘﻠﻑ ﻅﺭﻭﻑ ﺍﻟﺘﺸﻐﻴل‬‫ﺍﻟﺤﺎﻻﺕ ﺍﻟﻌﺎﺒﺭﺓ ﻟﻐﺭﺽ ﺘﻘﻴﻴﻡ ﺍﺩﺍﺀ ﺍﻟﻤﺭﺤ‬
‫ ﺍﻟﺘﻴـﺎﺭ‬,‫ ﻟﺘﻤﺜﻴل ﺤﺎﻻﺕ ﺍﻟﺘﻴﺎﺭ ﺍﻻﻨـﺩﻓﺎﻋﻲ‬MATLAB ‫ﻟﺔ ﺍﻟﻘﺩﺭﺓ ﺒﺒﺭﻨﺎﻤﺞ‬‫ﻓﻴﻬﺎ ﺼﻴﺎﻏﺔ ﻨﻤﻭﺫﺝ ﻤﺤﻭ‬
‫ـل‬‫ ﻭﻗﺩ ﺘﻡ ﺘﻌﺸﻴﻕ ﻫﺫﺍ ﺍﻟﻨﻤﻭﺫﺝ ﻤﻊ ﻨﻤـﻭﺫﺝ ﺍﻟﻤﺭﺤ‬.‫ﻟﺔ‬‫ﺍﻻﺜﺎﺭﺓ ﺍﻟﺘﺸﺒﻌﻲ ﻭﺍﻻﻋﻁﺎل ﺍﻟﺨﺎﺭﺠﻴﺔ ﻟﻠﻤﺤﻭ‬
‫ ﺍﻟﻁﺭﻴﻘﺔ ﺍﻟﺜﺎﻨﻴﺔ‬.SIMULINK ‫ ( ﻭﺍﻟﺫﻱ ﺘﻡ ﺘﻤﺜﻴﻠﻪ ﻓﻲ ﺒﻴﺌﺔ‬Sampler) ‫ﺍﻟﺘﻔﺎﻀﻠﻲ ﺒﻭﺍﺴﻁﺔ ﺍﻟﻤﻨﻤﺫﺝ‬
‫ﻟﺔ ﺍﻟﻘﺩﺭﺓ ﺒﺎﺴﺘﺨﺩﺍﻡ ﻤﺠﻤﻭﻋﺔ ﻗﻭﺍﻟﺏ ﻨﻅﻡ ﺍﻟﻘﺩﺭﺓ ﻟﻐﺭﺽ ﺘﻤﺜﻴل ﺤﺎﻻﺕ ﺍﻻﻋﻁﺎل‬‫ﺘﻡ ﻓﻴﻬﺎ ﻨﻤﺫﺠﺔ ﻤﺤﻭ‬

* College of Electrical and Electronic Techniques/ Baghdad


** Electromechanical Engineering Department, University of Technology /Baghdad
3076

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

‫ل ﺍﻟﺘﻔﺎﻀﻠﻲ ﻤﻥ ﺨﻼل‬‫ ﻫﺫﺍ ﺍﻟﻨﻤﻭﺫﺝ ﺘﻡ ﺘﻌﺸﻴﻘﻪ ﻤﻊ ﺒﺭﻨﺎﻤﺞ ﺍﻟﻤﺭﺤ‬,‫ﺍﻟﺩﺍﺨﻠﻴﺔ ﻭﺍﻟﺘﻴﺎﺭ ﺍﻻﻨﺩﻓﺎﻋﻲ ﺍﻟﺠﻴﺒﻲ‬
.SIMULINK ‫ﺒﻴﺌﺔ‬
NEGHALF Negative half cycle
Nomenclature d. c. content.
2HB1 Second
harmonic blocking signal.
5HB1 Fifth POSHALF Positive half cycle d.
harmonic blocking signal. c. content.
DCBL1 Direct current SLP1 First slope of
blocking signal. differential relay characteristic.
DCR1 Direct current ratio. SLP2 Second slope of
E1 Enable differential relay characteristic
signal. T Restraint trip
Id Differential current. signal.
IOP1 Differential T1 Relay
relay operation current. differential element 1 trip signal.
IOP1F2 Second harmonic UR1 Unrestraint trip
restraint current. signal.
IOP1F5 Fifth harmonic spc Samples per cycle
restraint current. r Sequence of samples
IOV Relay maximum 0,1,2,3,………..
overcurrent threshold. 1. Introduction
IP.U Relay minimum The power system protection relay
pick up current threshold. has experienced many important
IRS1 Differential relay changes, from purely
characteristic break point. electromechanical type to the mixture
IRT1 Differential of electronic and electromechanical
relay restraint current. type, then to fully static and now
I1W1 Transformer fully numerical relays based on
scaled primary current. microprocessors.
I1W2 Transformer The most important protection
scaled secondary current. scheme is the differential protection.
I1W1F1 Fundamental Two trip criteria are used; the first
component of scaled primary current. trip criterion is based on unrestrained
I1W2F1 Fundamental component of differential trip algorithm for heavy
scaled secondary current. internal faults which will produce a
I1W1F2 Second harmonic of scaled very high differential current so that
primary current. it is not necessary to check whether it
I I1W2F2Second harmonic of is inrush or not. The second trip
scaled secondary current. criterion is the through fault current
I1W1F5 Fifth harmonic of restrained differential algorithm
scaled primary current. which also includes the waveform
I1W2F5 Fifth harmonic of blocking criterion in combination
scaled secondary current. criteria of second harmonic restrain-
block for inrush and fifth harmonic

3077

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

block for overexcitation [1]. Some R. Gutierrez, and P. J. Mckenny [6]


researches that have been presented used lumped R-L-C circuit to
to develop the protection relays are represent the transformer winding.
outlined in the following paragraphs: This method requires knowledge of
A. G. Phadke, and J. S. Thorp [2]. the details of the transformer
Proposed a flux-restrained current construction to get these parameters,
differential relay. This relay and these parameters are very
calculates the rate of change of flux difficult to estimate from an external
with respect to the differential testing. S. B. Wilkinson [7] Proposed
current and uses it as a restraint. a method based on waveshape
However, the relay uses the winding recognition to
current, which is unavailable for a distinguish faults from inrush and
transformer with a delta winding. has applied this method in
B.W. Garrett, H.W. Dommel, K.H. transformer relays. However, this
Engelhardt [3] developed a technique do not identify transformer
protection system model under overexcitation conditions. M.
transient conditions, and showed how Kezunovic, Q. Chen [8] combined
both near-operation and near mis- EMTP and MATLAB to model
operation of relays could be made protective relays. Relays were
visible from simulations. A. modeled in the MATLAB simulation
Keyhani, H. Tsai, and A. Abur [4] software and connected to EMTP
proposed a method to establish a through an interaction buffer.
multisection network model for study Harlowe, James H., ed. [9] presented
of high frequency transient behavior the calculations of the harmonics to
of the transformer and machine restrain/block the relay on a
winding. The winding with equally differential basis, i.e. subtracts the
divided sections is considered in this low voltage harmonics from the high
paper. That will make the number of voltage harmonics. This calculation
sections be large if this method is is necessary to separate the
used for simulating the small turn-to- harmonics generated in load from the
turn fault of transformer. A. harmonics generated within the
Giuliante, and G. Clough [5] transformer.
suggested a technique based on the Yong-Cheol Kang, En-Shu Jin and
length of the time intervals when the Sung-Ho Won[10] proposed a
differential current is close to zero. modified-current-differential relay
During for transformer protection. The
magnetic inrush, the low current relay calculates the core-loss
intervals are greater than one-quarter current from the induced voltage
of a cycle and the relay is blocked. and the core-loss resistance as well
For internal faults, the low current as the magnetizing current from the
intervals are less than one-quarter of core flux and the magnetization
a cycle and the relay operates. curve. Finally, the relay obtains the
However, waveshape recognition modified differential current by
techniques fail to identify subtracting the core-loss and the
overexcitation. R. C. Degeneff, M.

3078

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

magnetizing currents from the All terms have fixed values except
conventional differential current. the permeance P. The following
2. Transformer Modeling expression determines the permeance
Accurate modeling of the power of a given transformer core:
transformer is very necessary to µ.A
evaluate protective relay P= ....(4)
performance and leads to the
l
The ratio of the incremental value of
transformer protection improvement.
the flux density to the incremental
The transformer model simulates
value of the magnetic field intensity
current signals for different operating
determines the permeability µ.
and fault conditions, these signals are
∆B
applied to the differential relay to µ= ...(5)
analyze its performance. ∆H
The following expressions determine In this case, three differential
the relationship between voltages, equations must be solved. These
currents, and mutual flux in the equations can be solved with the
transformer core [11]. fourth-order Runge-Kutta numerical
∆I1 ∆φ method.
E1 = R1 . I1 + L1 + N1 ...(1)
∆t ∆t The empirical Frolich Equation
models the S shape of the
∆I 2 ∆φ
E 2 = R2 . I 2 + L2 + N2 ...(2) anhysteretic B-H curve.
∆t ∆t The following equations determine
the empirical b and c constants
∆φ = P . N1 . ∆I1 + P . N2 . ∆I 2 ....(3) H
B=
c + b. H
Whereas figure 2 shows the variation
1 of permeability µ with magnetic field
1− intensity H calculated from the
µi
b= ....(7) transformer modeling
BSAT algorithm according to Frolich
equation (equation 6).
1 .....(8)
c=
µi . µ0 2.1 Transformer Modeling in
SIMULINK
The anhysteretic curve modeled by Figure 3 shows a schematic diagram
the Frolich equation is used to of a SIMULINK model, which is
determine the permeability values for used to
the different magnetic flux simulate the transformer normal
conditions presented in transformer operation condition (no fault
operation. situation), internal faults conditions
Figure 1 shows the anhysteretic B-H and the transformer energization with
curve of ferromagnetic material sinusoidal inrush current condition to
calculated from the transformer evaluate the differential relay
modeling algorithm according to performance
Frolich equation (equation 6).

3079

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

3. Differential Relay Modeling


Figure 4 shows a schematic diagram IOP1 > SLP * IRT1 + IOP1F2 ....(9)
of one of the percentage differential
elements (Element 1 of three phase Comparator 3 enables the relay by E1
differential relay) with 2nd harmonic signal if the operating current IOP1 is
restraint-blocking, 5th harmonic greater than a threshold value IPU,
blocking, and D.C. blocking, this Comparators 5 and 6 compare the
diagram is simulated by MATLAB operating current to the second- and
functions. Input to the differential fifth-harmonic restraint currents to
element are the filtered, scaled, and generate the second harmonic 2HB1
compensated sets of samples and fifth harmonic 5HB1 blocking
corresponding to the fundamental signals according to equations 10 and
component, second and fifth 11
harmonics of the transformer primary IOP1 < IOP1F2 ........ (10)
and secondary currents. IOP1 < IOP1F5 .....(11)
The magnitude of the sum of the The differential relay includes an
fundamental component of the unrestrained instantaneous
primary and secondary currents differential overcurrent trip function
(I1W1F1 and I1W2F1 respectively) forms by Comparator 2 which compares the
the operating current IOP1 . operating current IOP1 with a
The scaled magnitude of the threshold value IOV to provide the
difference of the fundamental unrestrained differential overcurrent
component currents forms the trip signal UR1.
restraint current IRT1. Comparator 7 compares the d.c. ratio
Comparator 1 and switch S1 select DCR1 with a 0.1 threshold to
the slope according to the value of generate the relay d.c. blocking
the restraint current to provide a signal DCBL1.
dual-slope percentage characteristic The inputs to the AND gate are: E1,
to calculate the restraint current IRT1 R1, 2HB1, 5HB1, and DCBL1.
f(slp). The output of the AND gate is the
The scaled magnitude of the sum of restraint trip signal T .
the second harmonic of the The restraint trip signal T is ORed
transformer primary and secondary with the unrestraint trip signal UR1 to
currents (I1W1F2 and I1W2F2 generate the final trip signal T1.
respectively) represent the second The settings of the differential relay
harmonic restraint current IOP1F2 the which is simulated in MATLAB
scaling factor is PCT2 functions are as follows:
The scaled magnitude of the sum of The relay minimum pick up current
the fifth harmonic of the transformer threshold IPU = 0.3 p.u.
primary and secondary currents The relay maximum overcurrent
(I1W1F5 and I1W2F5 respectively) threshold IOV = 30 p.u.
represents the fifth harmonic restraint First slope of differential relay
current IOP1F5 . characteristic SLP 1 = 25%
Comparator 4 compares the Second slope of differential relay
operating current IOP1 with the sum characteristic SLP 2 = 60%
of the fundamental and second Differential relay dual slope
harmonic restraint currents IR1, to characteristic break point IRS1 = 3 p.u
generate R1 signal, the comparator Second harmonic scaling factor PCT2
asserts for fulfillment of equation 9. = 1/0.16

3080

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

Fifth harmonic scaling factor PCT5 = modeling functions with MATLAB


1/0.3 differential relay functions.
3.1 Digital Filter Modeling The transformer primary and
A 16 sample/cycle full cycle window secondary currents (I1W1 and I1W2,
is used in this work, while extracting respectively) obtained from the
the wanted components; the filter MATLAB transformer modeling
rejects all other harmonics including functions must be sampled before
the decaying exponential. The filter they can be used by the MATLAB
in equation form appears as follows: relay functions.
The filter cosine coefficients are:- The anti aliasing analog low – pass
 2π n  filter is a second order butterworth of
CFCn = cos   ... (12) 400 Hz cutoff frequency.
 N  The zero order hold sampling time is
The filter sine coefficients 0.00125 second corresponding to a
 2π n  sampling rate of 16 samples per
SFCn = sin 
 N 
....(13) cycle.
The quantization interval is set to
1/4096
The real part of the filter output is:- 5. Cases Simulation in MATLAB
2 N−1 (a) Energization Condition
filtc= ∑Ir+spc−n .CFCn
spcn=0
...(14) The transformer is energized from
the high side with a rated voltage of
230 volts, the transformer primary
The imaginary part of the filter and secondary currents are shown in
output is:- figure 6a and figure 6b, respectively.
2 N−1 The primary inrush current I1W1
filts= ∑Ir+spc−n .SFCn
spcn=0
... (15) initial value is about 30 p.u times the
rated value with a decaying dc offset.
The secondary current I1W2 is a rated
The output filter phasor magnitude current of magnitude 1 p.u.
is:- As shown in figure 6c the differential
relay enters the operating zone where
( filtc)2 + ( filts)2 ..(16) IOP1 is greater than IRT1 but lesser than
IOP1F2, so IOP1 is lesser than IR1 and
thus the trip signal T1 is not activated
The phase is:- as shown in figure 6d, and the relay
filts
φ = arctan ... (17) displays good security against the
filtc inrush current.
In equation 14 and equation 15, any (b) Overexcitation Condition
value of r indicates that 16 samples This case is simulated by applying
of the current have been stored. The 150% overvoltage to the high side of
index n ranges from 0 to 15 to apply the transformer model with full load,
the coefficients and sum the samples figure 7a and figure 7b show the
to produce the output [12]. primary and secondary currents
4. The sampler respectively.
Figure 5 shows the sampler used to The peak value of the excitation
interface MATLAB transformer current shown in figure 7c is
approximately 10 p.u. of the rated
current. Figure 7d shows that IOP1 is

3081

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

greater than IR1, so the relay enters its 6. Differential Relay Sensitivity
operating zone. However, the The differential relay sensitivity to
blocking signal 5HB1 is issued due to detect the transformer internal faults
IOP1F5 is greater than IOP1 and thus the depends on its security, i.e.
differential relay does not declare a increasing the security of the relay
trip as shown in figure 7e, T1 is not decreasing the sensitivity and vice
activated. versa. Increasing the second
harmonic scaling factor PCT2
increasing the relay security against
(c) External Fault Condition inrush currents but this causes
An external fault (phase-to-ground) increasing the minimum percentage
is simulated at the low side of the of the transformer winding turns
transformer model. Figure 8a and which is protected by the relay.
figure 8b show high and low side Table 1 shows variation of relay
currents respectively. From figure 8c, sensitivity with PCT2.
IOP1F2 is greater than IOP1 and then IR1 7. Differential Relay Operation
is greater than IOP1, so the restraint R1 Speed
and the blocking 2HB1 signals are The differential relay speed of
produced. The differential relay does operation (trip time) to activate a trip
not declare a trip condition as shown signal after an internal fault
in figure 8d and T1 is not activated. incidence depends on its security, i.e.
(d) Sinusoidal Inrush Condition increasing the security of the relay
The transformer is energized with increasing the trip time and vice
rated load with sinusoidal inrush versa. Increasing the second
current with decaying d.c. offset. harmonic scaling factor PCT2
Figure 9a show the transformer increasing the relay security against
primary current. Figure 9b shows the inrush currents but this causes
differential relay current signals, decreasing of its speed to detect and
it is clear that IOP1 is greater than isolate the faulted transformer.
restraint and blocking current signals. Table 2 shows variation of relay trip
For this situation the relay must time with PCT2 .
declare a trip, but the blocking signal 8. Discussion
DCBL1 has an objection on this The model of the percentage restraint
declaration and the relay trip signal differential relay consisted in setting
T1 is not activated as shown in figure the values of the slopes of the
9c. differential characteristic (SLP1 and
(e) Internal Fault Condition SLP2) to achieve a correct operation
This case is simulated by Short of the differential relay during
circuiting 25% of the transformer normal operation and in the event of
secondary turns to ground. Short a fault. Figure 11a shows zooming of
circuit incidence is during the differential relay currents during
transformer normal operation with normal operation and figure 11b
rated load. Figure 10a, figure 10b shows zooming of the differential
and figure 10c show the current relay currents after occurrence of a
signals. Figure 10d shows phase to ground fault ring at time of t
the trip signal T1 which is activated = 0.1 seconds at 25% of the
by the relay. transformer winding turns. Equations
Trip time is 16.3 msec. after fault 18 and 19 were employed to
incidence.

3082

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

calculate the operating and restraint 9. conclusions


currents, respectively. (a) The relay model provides a
IOP1 = |I1W1F1 + I1W2F1 | (18) valuable insight into the internal
IRT1 = 0.5 |I1W1F1 - I1W2F1 | (19) behaviour of a relay in a wide range
During normal operation, the of field events and application.
operating current IOP1 must be (b) Harmonic restraint or blocking
smaller than the restraining current increases differential relay security,
IRT1 and consequently smaller than but could delay relay operation for
total restraining current IR1, and in a internal faults combined with inrush
fault, the operating current must be current.
larger than the restraining currents. (c) Harmonic blocking and harmonic
In normal operation shown in figure restraint techniques may not be
11a, it is observed that these adequate to prevent differential relay
differential currents fulfilled the operation for unique cases with very
requirements of a correct operation. low harmonic content in the
After the fault inception, as shown in operating current. Some form of
figure 11b, it is only in the transitory waveshape recognition may be
part that the relay currents did not required to ensure security for these
fulfill the requirements of a correct unique conditions without sacrificing
operation. fast and dependable operation when
The harmonic-restrained differential energizing a faulted transformer.
relay employs the second harmonic 10. References
of the operating current to overcome [1] J. Wang, Z. Gajic and S. Holst,
the problems in the protection of “The Multifunctional Numerical
power transformers due to the Transformer Protection and
presence of inrush current. Equation Control System with Adaptive
9, suggests that the second harmonic and Flexible Features”, ABB
restraint current IOP1F2 must be added Automation Products AB,
to the restraint current IRT1 to Sweden, 2001.
constitute the total restraint current [2] A. G. Phadke, and J. S. Thorp, “A
IR1, this current is assured to be larger New Computer-Based Flux-
than the operating current during the Restrained Current-Differential
time of the inrush current effect. Relay for Power Transformer
However, the previous action had a Protection,” IEEE Trans. on
temporary negative effect in the PAS, Vol. 102, No. 11, pp. 3624-
operation of the differential relay 3629, Nov. 1983.
after fault inception. Figure 11b [3] B. W. Garrett, H. W. Dommel, K.
shows the zooming of the differential H. Engelhardt, “Digital
currents just after the fault inception, Simulation of Protection Systems
It is observed that the second Under Transient Conditions,”
harmonic of the operating current Proceedings of the Ninth Power
had pick value from the time of the Systems Computation
fault inception t = 0.1 seconds up to t Conference, Cascais, Portugal,
= 0.1163 seconds where the relay September 1987, Butterworths
initiate a trip signal. Although this (London), pp. 291-297.
pick value causes a delaying in the [4] A. A. Keyhani, H. Tsai, and
identification of the fault condition, Abur, “Maximum likelihood
the differential relay showed correct estimation of
operation for the simulated fault.

3083

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

high frequency machine and Washington, “Transformer


transformer winding Modeling as Applied to
parameters,” IEEE Differential Protection”, 22nd
Trans. on Power Delivery, vol. 5, Annual Western Protective Relay
No. 1, pp. 212–219, Jan. 1990. Conference, Spokane, WA,
[5] A. Giuliante, and G. Clough, October 24-26, 1995.
“Advances in the Design of [12] Stanley E. Zocholl and Gabriel
Differential Protection for Power Bemouyal, Schweitzer Engineering
Transformers”, 1991 Georgia Laboratories, Inc., Pullman, WA,
Tech. Protective Relaying USA, “How Microprocessor Relays
Conference, Atlanta, GA, pp. 1- Respond to Harmonics, Saturation
12, May 13, 1991. and other Wave Distort
[6] R. C. Degeneff, M. R. Gutierrez,
and P. J. Mckenny, “A Method
for Constructing Reduced Order
Transformer Models for System
Studies from Detailed Lumped
Parameter Models,” IEEE Trans.
on Power Delivery, Vol. 7, No.
2, pp. 649–655, Apr. 1992.
[7] S. B. Wilkinson, “Transformer
Differential Relay”, U.S. Patent
No 5627712, May 6, 1997.
[8] M. Kezunovic, Q. Chen, “A
Novel Approach for Interactive
Protection System Simulation,”
IEEE Trans. on Power Delivery,
Vol. 12, No.2, April 1997, pp.
668-674.
[9] Harlowe, James H., ed., “Electric
Power Transformer
Engineering”, Boca Raton, FL:
CRC Press, 2004.
[10] Yong-Cheol Kang, En-Shu Jin
and Sung-Ho Won, “Modified
Current Differential Relay for
Transformer Protection”, KIEE
International Transaction on
Power Engineering, Vol. 5-A
No. 1, PP. 1~8, 2005.
[11] Stanley E. Zocholl, Armando
Guzman and Daqing Hou,
Schweitzer Engineering
Laboratories, Inc., Pullman,

3084

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

Table (1) Variation of Relay Sensitivity with PCT 2

Table( 2) Variation of Relay Trip Time with PCT2

3085

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

1.5

0.5

B (Tesla)
0

-0.5

-1

-1.5

-2
-2000 -1500 -1000 -500 0 500 1000 1500 2000
H (Amp-turn/m)

Figure (1) Anhysteretic B-H Curve of Ferromagnetic


Materials Calculated by the Transformer Modeling Algorithm.

0.02

0.018

0.016

0.014

0.012
u (H/m)

0.01

0.008

0.006

0.004

0.002

0
-2000 -1500 -1000 -500 0 500 1000 1500 2000
H (Amp-turn/m)

Figure (2) Permeability µ (H/m) versus Field Intensity H (Amp-turn/m)


Calculated by the Transformer Modeling Algorithm.

Series RLC Load


Breaker
AC Voltage Source
+2
1+ 2
+3 Breaker1
3
+4
1
4

Multi-Winding
Transformer
I1W1.mat

To File
-K-

Gain1

Continuous 2 Scope
pow ergui
Multimeter
-K-

Gain I1W2.mat

To File1

Figure (3) Schematic Diagram of Transformer Modeling in SIMULINK.

3086

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

I1W1F1
| I1W1F1 + I1W2F1 | IOP1 UR1
I1W2F1 + +2
-
Iov
T1
+3 E1
Ipu -

IRT1 S1 SLP1
1 (SLP1-SLP2) *
- | I1W1F1 - I1W2F1 | 2 + IRS1
-1
IRS1
IR1 T
+ R1
4
+
I1W1F2
IOP1F2 IOP1
+ | I1W1F2 + I1W2F2 |
I1W2F2

-5 2HB1
IOP1 +

I1W1F5
IOP1F5
+ | I1W1F5 + I1W2F5| PCT5 - 5 HB1
I1W2F5 6
IOP1 +

POSHALF
I1W1
Min DCR1
I1W2 + Max +7 DCBL1
0.1 -

NEGHAL
F
Figure (4) Schematic Diagram of Differential Relay
Modeling in MATLAB

3087

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

butte
r - I1w1.m
K- at
Gain Zero- Quantiz To
Analo 2 Hol
Order er File2
Filter
g d
Design
butte
tes r
t - I1W2.m
From K- at
File Gain Zero- Quantize To
Analo 1 Hold
Order r1 File1
Filter
g 1
Design1

Scope Scope Scop


1 2 e

Figure (5) Sampler Schematic Diagram


I1W1 I1W 2
35 1

30

0.5
25

20
0
P.U.

P.U.

15

10 -0.5

5
-1
0

-5 -1.5
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time (sec) Time (sec )
T
1
IOP1, IRT1, IOP1F2, IOP1F5, IR1
60
0.8

IR1
0.6
50
IOP1F2 0.4

40 0.2

0
P.U.

30
-0.2

20 -0.4

IOP 1 -0.6
10
-0.8
IRT1

IOP1F5 -1
0 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
0 0.05 0. 1 0.15 0.2 0. 25 0.3 0. 35 0.4
Time (sec) Time (sec)

Figure (6) [ Energization Condition: (a. Primary Current, b. Secondary


Current. c. Relay Current Signals, d. Relay Trip Signal.)]

3088

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

I1W1 I1W 2
15 2

1.5

10
1

0.5
5
P.U.

P.U.
0

0
-0.5

-1
-5

-1.5

-10 -2
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time (sec) Time (sec)

Id IOP1, IRT1, IOP1F2, IOP1F5, IR1


10 6

8 IOP1F5
5
6
IOP1

4 4
IR1

2
P.U.

P.U.

3
IOP1F2
0

-2 2

-4 IRT1
1
-6

-8 0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time (sec) Time (sec)

T1
1

0.8

0.6

0.4

0.2

-0.2

-0.4

-0.6

-0.8

-1
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time (sec)

Figure (7) [ Overexcitation Condition: (a. Primary Current, b. Secondary


Current, c. Differential Current, d. Relay Current signals, e.
Relay Trip Signal.)]

3089

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

I1W 1 I1W1
50 50

40 40

30
30
P.U.

20

P.U.
20

10
10

0
0

-10
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
-10
Time (sec) 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
IOP1, IRT1, IOP1F2, IOP1F5, IR1 Time (sec)
T1
14 1

IR1 0.8
12
0.6
IOP1F2
10 0.4

0.2
8
P.U.

0
6
-0.2

4 -0.4
IRT1
-0.6
2 IOP1
-0.8
IOP1F5
0 -1
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time (sec) Time (sec)

Figure (8) [ External Fault Condition: ( a. Primary Current, b. Secondary


Current, c. Relay Current signals, d. Relay Trip Signal.)]
I1W 1 IOP1, IRT1, IOP1F2, IOP1F5, IR1
10 3.5
IOP1

3
8

2.5
6 IR1

2
P.U.

P.U.

4
IOP1F2
1.5

2
1

IRT1
0
0.5
IOP1F5

-2 0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time (sec) Time (sec)

3090

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

T1
1

0.8

0.6

0.4

0.2

-0.2

-0.4

-0.6

-0.8

-1
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time (sec)

Figure (9) [Sinusoidal Inrush Condition: (a. Primary Current, b. Relay


Current signals, c. Relay Trip Signal.)]

I1W1 I1W2
6 1.5

5
1
4

3 0.5

2
P.U.

P.U.

0
1

0 -0.5

-1
-1
-2

-3 -1.5
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time (sec) Time (sec)
IOP1, IRT1, IOP1F2, IOP1F5, IR1 T1
8 1

0.9
7
0.8
6
0.7
5
0.6
P.U.

4 0.5

0.4
3 IOP1
0.3
2
0.2
1 IR1
0.1
IRT1
IOP1F2
0 IOP1F5 0
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Time (sec) Time (sec)

Figure (10) [ Internal Fault Condition: (a. Primary Current, b. Secondary


Current, c. Relay Current Signals, d. Relay Trip Signal.)]

3091

PDF created with pdfFactory Pro trial version www.pdffactory.com


Eng. & Tech. Journal ,Vol.27, No.16,2009 Simulation of a Power Transformer
Differential Protective Relay

IOP1, IRT1, IOP1F2, IOP1F5, IR1


IOP1, IRT1, IOP1F2, IOP 1F5, IR1
0.5
8

0.45
7
IR1
0.4
6
0.35 IR1 IOP1F2

0.3 5
P.U.

P.U.
0.25 4

0.2 IRT1
3 IOP1
0.15
2
0.1
IOP1F5 IOP1F2 IOP 1F5 IRT1
IOP1 1
0.05

0 0
0.01 0.02 0.03 0.04 0.05 0.06 0.07 0.08 0.09 0.1 0 0.02 0.04 0.06 0.08 0.1 0.12 0.14 0.16 0.18
Time (sec) Time (sec)

Figure (11) [a.Zooming of the Relay Currents During Normal


Operation,b.Zooming of the Relay Currents after Fault Inception.]

3092

PDF created with pdfFactory Pro trial version www.pdffactory.com

Vous aimerez peut-être aussi