KOKM for GIS


Indoor cable current transformers
2 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S
3


Contents

03 Contents

04– 05 KOKM 1 EB, KOKM 1 ED,


KOKM 1 DB

06– 07 KOKM 1 LH, KOKM 1 NJ

08– 09 KOKM 1 CG, KOKM 1 DG, KOKM 1


EG, KOKM 1 GG

10– 11 KOKM 1 GA, KOKM 1 ID,


KOKM 1 IE

12– 13 KOKM 1 FB

14– 15 KOKM 1 DA

16– 17 KOKM 1 LN

18– 19 KOKM 06 LM, KOKM 06 NN

20– 21 KOKM 072 EF

22– 23 KOKM 072 ER


4 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 1 EB, KOKM 1 ED, KOKM 1 DB

KOKM 1 EB, KOKM 1 ED and KOKM 1 DB – are in-


Technical parameters Transformer
type: door, cable, low-voltage current transformers in
KOKM 1 EB resin insulation. These types are suitable for the
KOKM 1 ED measurement of phase currents. A busbar or ca-
KOKM 1 DB
ble serves as the primary conductor. Current
Highest voltage for equipment, Um 1.2 kV transformers from the KOKM series can also be
Rated power-frequency withstand 6 kV used to measure phase currents at voltages
voltage higher than 1.2 kV if the insulation of the
high-voltage primary conductor fulfils the re-
Rated lightning impulse withstand –
voltage quirements of the relevant standards related to
the working voltage. Inner diameter of EB/ED is
Rated frequency fR 50 or 60 Hz
72 mm and DB 60 mm.
Rated primary current, Ipr 50 – 1 250 A

Extended current rating 1.2 × Ipr A


Identification for customer:
KOKM 1 EB RC01
Rated short-time thermal current, Ith max. 50 kA/1s KOKM 1 ED RC02
Rated dynamic current, Idyn 2.5 × Ith kA

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 3


5

— —
KOKM 1 EB KOKM
KOKM 1 ED 1 ED
KOKM 1 EB
74 37
74 27 69 64 3
69 64 3

18
18

32
32

192
0
170 -2
192

72
0
170 -2

72

70
70

A ±1 120 ±1 M6x11 A ±1
100 ±1 M6x11 0 0
B -2 148 ±1 B -2
128 ±1
40

23

40

23
13

M5 40 M5 40

13
58 58

ČÍSLO VÝKRESU / DRAWING NUMBER TYP / TYPE A [mm] B [mm]


1VL4900356R0101 KOKM 1 EB 8 56 80
1VL4900356R0102 KOKM 1 EB 10 76 100 ČÍSLO VÝKRESU / DRAWING NUMBER TYP / TYPE A [mm] B [mm]
1VL4900356R0103 KOKM 1 EB 12 96 120 1VL4900355R0101 KOKM 1 ED 8 56 80
1VL4900356R0104 KOKM 1 EB 14 116 140 1VL4900355R0102 KOKM 1 ED 10 76 100
1VL4900356R0105 KOKM 1 EB 16 136 160 1VL4900355R0103 KOKM 1 ED 12 96 120
1VL4900356R0106 KOKM 1 EB 18 156 180 1VL4900355R0104 KOKM 1 ED 14 116 140
1VL4900356R0107 KOKM 1 EB 20 176 200 1VL4900355R0105 KOKM 1 ED 16 136 160
1VL4900356R0108 KOKM 1 EB 22 196 220 1VL4900355R0106 KOKM 1 ED 18 156 180


KOKM 1 DB V2
6 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 1 LH, KOKM 1 NJ

KOKM 1 LH and KOKM 1 NJ – are the indoor, cable,


Technical parameters Transformer
type: low-voltage current transformers in resin insula-
KOKM 1 LH tion. These types are suitable for the measure-
KOKM 1 NJ ment of phase currents. A busbar or low-voltage
Highest voltage for equipment, Um 1.2 kV cable serves as the primary conductor. Current
transformers from the KOKM series can also be
Rated power-frequency withstand 6 kV
voltage used to measure phase currents at voltages
higher than 1.2 kV if the insulation of the
Rated lightning impulse withstand -
high-voltage primary conductor fulfils the re-
voltage
quirements of the relevant standards related to
Rated frequency fR 50 or 60 Hz the working voltage. Type LH has inner diameter
Rated primary current, Ipr 50 – 1 250 A 130 mm and type NJ has inner diameter 155 mm.

Rated secondary current, Isr 1 or 5 A


Identification for customer:
Extended current rating 1.2 × Ipr A KOKM 1 LH RC05
KOKM 1 NJ RC06
Rated short-time thermal current, Ith max. 50 kA/1s

Rated dynamic current, Idyn 2.5 × Ith kA

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 5


7


— KOKM 1 NJ
KOKM 1 NJ V2
V2
KOKM
KOKM 1 LH
1 LH V2 V2 130 52,5
130 35 103 56 3
103 56 3

22
22

55
35

155

282
130

0
255 -2
272
0
245 -2

0
127,5 -1
0
127,5 -1

5
5

0 A
235 -1 M8x16 0
0 A B -2
200 -1 0
M8x16 B -2

10 10

25

25
ČÍSLO VÝKRESU
DRAWING NUMBER TYP / TYPE A [mm] B [mm]
ČÍSLO VÝKRESU
TYP / TYPE A [mm] B [mm]
DRAWING NUMBER
1VL4900372R0101 KOKM 1 LH 6 V2 30 60
330 ±0,3

1VL4900375R0101 KOKM 1 NJ 6 V2 30 60

330 ±0,3
1VL4900372R0102 KOKM 1 LH 9 V2 60 90
360

360
1VL4900375R0102 KOKM 1 NJ 9 V2 60 90
1VL4900372R0103 KOKM 1 LH 12 V2 90 120

1VL4900372R0104 KOKM 1 LH 14 V2 110 140 1VL4900375R0103 KOKM 1 NJ 12 V2 90 120

1VL4900372R0105 KOKM 1 LH 16 V2 130 160 1VL4900375R0104 KOKM 1 NJ 14 V2 110 140

1VL4900372R0106 KOKM 1 LH 18 V2 150 180 1VL4900375R0105 KOKM 1 NJ 16 V2 130 160


51

13 23

1VL4900372R0107 KOKM 1 LH 20 V2 170 200 1VL4900375R0106 KOKM 1 NJ 18 V2 150 180


51

13 23
1VL4900372R0108 KOKM 1 LH 22 V2 190 220 1VL4900375R0107 KOKM 1 NJ 20 V2 170 200
M5 20
1VL4900372R0109 KOKM 1 LH 24 V2 210 240
30

1VL4900375R0108 KOKM 1 NJ 22 V2 190 220


15

M5 20
30

1VL4900372R0110 KOKM 1 LH 26 V2 230 260 1VL4900375R0109 KOKM 1 NJ 24 V2 210 240


98

15
170 ±1 1VL4900372R0111 KOKM 1 LH 28 V2 250 280 1VL4900375R0110 KOKM 1 NJ 26 V2 230 260
98
1VL4900372R0112 KOKM 1 LH 30 V2 270 300
205 ±1 1VL4900375R0111 KOKM 1 NJ 28 V2 250 280

1VL4900375R0112 KOKM 1 NJ 30 V2 270 300


8 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 1 CG, KOKM 1 DG, KOKM 1 EG, KOKM 1 GG

KOKM 1 CG, KOKM 1 DG, KOKM 1 EG and KOKM 1


Technical parameters Transformer
type: GG – are indoor, cable, low-voltage current trans-
KOKM 1 CG formers in resin insulation. These types are suit-
KOKM 1 DG able for the measurement of phase currents.
KOKM 1 EG
KOKM 1 GG A busbar or low-voltage cable serves as the pri-
mary conductor. Current transformers from the
Highest voltage for equipment, Um 1.2 kV
KOKM series can also be used to measure phase
Rated power-frequency withstand 6 kV currents at voltages higher than 1.2 kV if the insu-
voltage lation of the high-voltage primary conductor ful-
Rated lightning impulse withstand - fils the requirements of the relevant standards re-
voltage lated to the working voltage. Inner diameter of
Rated frequency fR 50 or 60 Hz CG is 50 mm, DG 60 mm, EG 70 mm and GG
90 mm.
Rated primary current, Ipr 50 – 2 500 A

Rated secondary current, Isr 1 or 5 A Identification for customer:


KOKM 1 CG RC17
Extended current rating 1.2 × Ipr A
KOKM 1 DG RC18
Rated short-time thermal current, Ith max. 63 kA/1s KOKM 1 EG RC04
Rated dynamic current, Idyn 2.5 × Ith kA
KOKM 1 GG RC19

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 4


9

— —
KOKM 1 CG KOKM 1 DG

— —
KOKM 1 EG KOKM 1 GG
10 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 1 GA, KOKM 1 ID, KOKM 1 IE

KOKM 1 GA, KOKM 1 ID, KOKM 1 IE – are indoor,


Technical parameters Transformer
type: cable, low-voltage current transformers in resin
KOKM 1 GA insulation. These types are suitable for the mea-
KOKM 1 ID surement of phase currents. A busbar or low-volt-
KOKM 1 IE
age cable serves as the primary conductor. Cur-
Highest voltage for equipment, Um 1.2 kV rent transformers from the KOKM series can also
Rated power-frequency withstand 6 kV be used to measure phase currents at voltages
voltage higher than 1.2 kV if the insulation of the
high-voltage primary conductor fulfils the re-
Rated lightning impulse withstand -
voltage quirements of the relevant standards related to
the working voltage. Inner diameter of ID/IE is 110
Rated frequency fR 50 or 60 Hz
mm, GA 90 mm.
Rated primary current, Ipr 50 - 1250 A

Rated secondary current, Isr 1 or 5 A


Identification for customer:
KOKM 1 IE RC13
Extended current rating 1.2 × Ipr A KOKM 1 GA RC15
Rated short-time thermal current, Ith max. 63 kA/1s KOKM 1 ID RC16

Rated dynamic current, Idyn 2.5 × Ith kA

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 4


11

— —
KOKM 1 GA KOKM 1 ID


KOKM 1 IE
12 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 1 FB

KOKM 1 FB – is indoor, cable, low-voltage current


Technical parameters Transformer
type: transformer in resin insulation. This type is suit-
KOKM 1 FB able for the measurement of phase currents.
Highest voltage for equipment, Um 1.2 kV
A busbar or low-voltage cable serves as the pri-
mary conductor. Current transformers from the
Rated power-frequency withstand 6 kV KOKM series can also be used to measure phase
voltage
currents at voltages higher than 1.2 kV if the insu-
Rated lightning impulse withstand - lation of the high-voltage primary conductor ful-
voltage
fils the requirements of the relevant standards re-
Rated frequency fR 50 or 60 Hz lated to the working voltage. Inner diameter is
72 mm.
Rated primary current, Ipr 50 - 1250 A

Rated secondary current, Isr 1 or 5 A Identification for customer:


Extended current rating 1.2 × Ipr A KOKM 1 FB RC12

Rated short-time thermal current, Ith max. 63 kA/1s

Rated dynamic current, Idyn 2.5 × Ith kA

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 4


13


KOKM 1 FB
14 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 1 DA

KOKM 1 DA – is indoor, cable, low-voltage current


Technical parameters Transformer
type: transformer in resin insulation. This type is suit-
KOKM 1 DA able for the measurement of phase currents.
Highest voltage for equipment, Um 1.2 kV
A busbar or low-voltage cable serves as the pri-
mary conductor. Current transformers from the
Rated power-frequency withstand 6 kV KOKM series can also be used to measure phase
voltage
currents at voltages higher than 1.2 kV if the insu-
Rated lightning impulse withstand - lation of the high-voltage primary conductor ful-
voltage
fils the requirements of the relevant standards re-
Rated frequency fR 50 or 60 Hz lated to the working voltage. Inner diameter is
65 mm.
Rated primary current, Ipr 50 - 1250 A

Rated secondary current, Isr 1 or 5 A Identification for customer:


Extended current rating 1.2 × Ipr A KOKM 1 DA RC14

Rated short-time thermal current, Ith max. 63 kA/1s

Rated dynamic current, Idyn 2.5 × Ith kA

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 4


15


KOKM 1 DA
16 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 1 LN

KOKM 1 LN – is indoor, cable, low-voltage current


Technical parameters Transformer
type: transformer in resin insulation. This type is are
KOKM 1 LN suitable for the measurement of phase currents.
Highest voltage for equipment, Um 1.2 kV
A busbar or low-voltage cable serves as the pri-
mary conductor. Current transformers from the
Rated power-frequency withstand 6 kV KOKM series can also be used to measure phase
voltage
currents at voltages higher than 1.2 kV if the insu-
Rated lightning impulse withstand - lation of the high-voltage primary conductor ful-
voltage
fils the requirements of the relevant standards re-
Rated frequency fR 50 or 60 Hz lated to the working voltage.
Rated primary current, Ipr 50 - 1250 A
Identification for customer:
Rated secondary current, Isr 1 or 5 A KOKM 1 LN RC07
Extended current rating 1.2 × Ipr A

Rated short-time thermal current, Ith max. 63 kA/1s

Rated dynamic current, Idyn 2.5 × Ith kA

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 4


17


KOKM 1 LN
18 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 06 LM, KOKM 06 NN

KOKM 1 LH and KOKM 1 NJ – are window types of


Technical parameters Transformer
type: indoor, cable, low-voltage current transformers in
KOKM 06 LM resin insulation. These types are suitable for the
KOKM 06 NN measurement of phase currents and alternatively
Highest voltage for equipment, Um 0.72 kV for three phase currents measurement. A non-in-
sulated busbar or cable serves as the primary
Rated power-frequency withstand 3 kV
voltage conductor. Current transformers from the KOKM
series can also be used to measure phase cur-
Rated lightning impulse withstand -
rents at voltages higher than 0.72 kV if the insula-
voltage
tion of the high-voltage primary conductor fulfils
Rated frequency fR 50 or 60 Hz the requirements of the relevant standards re-
Rated primary current, Ipr 50 – 1 500 A lated to the working voltage.

Rated secondary current, Isr 1 or 5 A


Identification for customer:
Extended current rating 1.2 × Ipr A KOKM 06 LM RC08
KOKM 06 NN RC09
Rated short-time thermal current, Ith max. 50 kA/1s

Rated dynamic current, Idyn 2.5 × Ith kA

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 5


19

— —
KOKM
KOKM 06 LM 06 LM KOKM
KOKM 06
06 NN NN
145 65 65 103 65 56 4
103 56 4

22
22
15

55

55
60
55
15 15

309 min.

446
0
420 -2
280 min.

425
0
400 -2

154 min.
130 min.

2x
9

55
2x
9
55

65 15

15
0
0 0 A -2
65 15
15

A -2 235 -1
0
210 -1

51

23
51

23

M5

14,5
20
M5 20 98
14,5

98
ČÍSLO VÝKRESU / DRAWING NUMBER TYP / TYPE A [mm]
ČÍSLO VÝKRESU / DRAWING NUMBER TYP / TYPE A [mm] 1VL4900396R0101 KOKM 06 NN 6 60
1VL4900396R0102 KOKM 06 NN 9 90
1VL4900369R0101 KOKM 06 LM 6 60 1VL4900396R0103 KOKM 06 NN 12 120
1VL4900369R0102 KOKM 06 LM 9 90 1VL4900396R0104 KOKM 06 NN 14 140
1VL4900396R0105 KOKM 06 NN 16 160
1VL4900369R0103 KOKM 06 LM 12 120 1VL4900396R0106 KOKM 06 NN 18 180
1VL4900369R0104 KOKM 06 LM 14 140 1VL4900396R0107 KOKM 06 NN 20 200
1VL4900369R0105 KOKM 06 LM 16 160 1VL4900396R0108 KOKM 06 NN 22 220
1VL4900396R0109 KOKM 06 NN 24 240
1VL4900369R0106 KOKM 06 LM 18 180 1VL4900396R0110 KOKM 06 NN 26 260
20 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 072 EF

KOKM 072 EF – is the indoor, cable, low-voltage


Technical parameters Transformer
type: current transformer in resin insulation. This type
KOKM 072 EF is suitable for the measurement of phase cur-
Highest voltage for equipment, Um 0.72 kV
rents. A busbar or cable serve as the primary con-
ductor. Current transformers from the KOKM se-
Rated power-frequency withstand 3 kV ries can also be used to measure phase currents
voltage
at voltages higher than 0.72 kV if the insulation of
Rated lightning impulse withstand - the high-voltage primary conductor fulfils the re-
voltage
quirements of the relevant standards related to
Rated frequency fR 50 or 60 Hz the working voltage. KOKM 072 EF has inner di-
ameter 72 mm.
Rated primary current, Ipr 50 – 2 500 A

Rated secondary current, Isr 1 or 5 A Identification for customer:


Extended current rating 1.2 × Ipr A KOKM 072 EF RC10

Rated short-time thermal current, Ith max. 50 kA/1s

Rated dynamic current, Idyn 2.5 × Ith kA

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 5


21


KOKM 072
KOKM 072 EF
EF
114 37
103 56 3

22
79

227

75
0
-2
202
94
65

120 ±1 A ±1
153 M8x12 0
0
B -2
188 -1
51

23

20 20
13

M5
98

ČÍSLO VÝKRESU / DRAWING NUMBER TYP / TYPE A [mm] B [mm]


1VL4900391R0108 KOKM 072 EF 12 90 120
1VL4900391R0109 KOKM 072 EF 14 110 140
1VL4900391R0110 KOKM 072 EF 15 120 150
1VL4900391R0111 KOKM 072 EF 16 130 160
1VL4900391R0112 KOKM 072 EF 18 150 180
1VL4900391R0113 KOKM 072 EF 20 170 200
1VL4900391R0114 KOKM 072 EF 22 190 220
22 KO K M F O R G I S I N D O O R C A B L E C U R R E N T T R A N S F O R M E R S


KOKM 072 ER

KOKM 072 ER – is the indoor, cable, low-voltage


Technical parameters Transformer
type: current transformer in resin insulation. This type
KOKM 072 ER is suitable for the measurement of phase cur-
Highest voltage for equipment, Um 0.72 kV
rents. A busbar or cable serve as the primary con-
ductor. Current transformers from the KOKM se-
Rated power-frequency withstand 3 kV ries can also be used to measure phase currents
voltage
at voltages higher than 0.72 kV if the insulation of
Rated lightning impulse withstand - the high-voltage primary conductor fulfils the re-
voltage
quirements of the relevant standards related to
Rated frequency fR 50 or 60 Hz the working voltage. KOKM 072 ER is double
holed transformer with inner diameter 75 mm.
Rated primary current, Ipr 50 – 2 500 A

Rated secondary current, Isr 1 or 5 A Identification for customer:


Extended current rating 1.2 × Ipr A KOKM 072 ER RC11

Rated short-time thermal current, Ith max. 50 kA/1s

Rated dynamic current, Idyn 2.5 × Ith kA

Conformity with standards IEC, ANSI, GOST,


others on
request

Maximal number of cores 5


23


KOKM 072
KOKM 072 ER
ER
64 250
103 56 3
32

22
75 75

226
200
94

190 A ±1
310 ±1 0
M8x12 B -2
378 ±2
51

23

M5 20 20
13

98

ČÍSLO VÝKRESU / DRAWING NUMBER TYP / TYPE A [mm] B [mm]


1VL4900370R0101 KOKM 072 ER 16 130 160
1VL4900370R0102 KOKM 072 ER 22 190 220
— —
C O N TA C T U S NOTE We reserve all rights in this document and in
1VLC000609 Rev.4, en 2017.06.01

ABB s.r.o. We reserve the right to make technical the subject matter and illustrations con-
EPMV Brno changes or modify the contents of this docu- tained therein. Any reproduction, disclosure
Videnska 117, 619 00 Brno, ment without prior notice. With regard to to third parties or utilization of its contents -
Czech Republic purchase orders, the agreed particulars shall in whole or in parts - is forbidden without
Tel.: +420 547 152 021 prevail. ABB does not accept any responsibil- prior written consent of ABB.
+420 547 152 614 ity whatsoever for potential errors or possi-
Fax: +420 547 152 626 ble lack of information in this document. Copyright© 2017 ABB
E-mail: info.ejf@cz.abb.com All rights reserved

www.abb.com