Document: OETC-AMP-O-AMT-A-044:A2

Rev: 0
Standard specification 400/132/33 kV Substations:
Appendix 1, Annex 2, Section 2 HVGIS Technical Data Sheets

Section 2 HVGIS TECHNICAL DATA SHEETS

ABB - Technical Schedule


23488 -DUQM + 23489 - Mahout

24.12.2020

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Appendix 1, Annex 2, Section 2 HVGIS Technical Data Sheets

TDS List:

1. 400 kV GIS
2. 132 kV GIS

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33kV Substations:
Appendix 1, Annex 2, Section 2 400 kV GIS Technical Data Sheets

SECTION 2 400 kV GIS - TECHNICAL DATA SHEETS

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

1 COMMON FEATURES

1.1 Manufacturer name ABB

1.2 Place of Manufacturing Switzerland

1.3 Type ELK 03

1.4 Applicable Standards IEC 62271- IEC 62271-203


203
IEC 62271-1
IEC 62271-1
IEC 62271-100
IEC 62271-
100

1.5 Commercial Operation time of offered Years Minimum 5


Minimum 5
GIS

1.6 Type Test Carried out Yes/ No Yes Yes


2005
1.7 Type Test Date please refer to list of type tests
for more details

1.8 Laboratory in which type Test Carried


out PEHLA

1.9 Operating voltage (U) kV 400 400

1.10 Rated voltage kV 420 420

1.11 Rated frequency Hz 50 50

1.12 Rated short time withstand current (1s) kA 63 63

1.13 Rated peak withstand current kA 160 170

1.14 Lightning Impulse withstand voltage kV p 1425


(phase to phase and phase to earth) at 1425

minimum operating gas pressure

1.15 Switching impulse withstand voltage at kV p 1050 1050


minimum operating gas pressure

1.16 Rated Power frequency withstand voltage kV 650


(1min) (phase to phase and phase to 650
earth) at minimum operating gas
pressure

1.17 Rated Power frequency withstand voltage kV 815 815

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 1 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

(1min) across open switching device or


isolating distance at minimum operating
gas pressure

1.18 Guaranteed SF6 gas losses per % Less than


Less than 0.5%
compartment per year 0.5%
> 1Year
1.19 Design lifetime of moisture absorbers years
Details of AC/DC load documents
1.20 Heat losses per feeder at rated power kW shall be submitted separately

1.21 Rated gas pressure at 20°C in CB bar abs


6.8
compartment

1.22 Rated gas pressure at 20°C in other bar abs 5.3


compartments
CB & VT : 6
1.23 Minimum operating gas pressure at 20°C bar abs Others: 4.5

1.24 Emergency operation at rated voltage Yes/ No Yes


and a gas pressure of 1 bar abs

1.25 Setting of pressure relief devices (20°C) bar abs 12.5

1.26 Insulation medium SF6 SF6

1.27 Type of cooling air natural Air natural

1.28 Conductor material Copper/


Al. Alloy
Aluminum

1.29 Material of enclosures Aluminum Al. Alloy


Alloy/ Steel

1.30 Maximum time of degassing and filling Min after detailed enggineering
of largest compartment stage & finalisation of Layout

1.31 Average thickness of enclosures mm min. 15mm

1.32 Degree of protection of Enclosures IP 65 IP 65

1.33 Weight per feeder (ready for operation) kg 5200 Appx.

1.34 Heaviest part (for crane design) kg 2000 - CB - 1ph

Please refer Layout


1.35 Typical Feeder Dimensions (L x W x H) mm Drawing

1.36 Permissible Maximum Impact (g) during g up to 15 for 11ms


transportation between factory and Site

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 2 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

1.37 Impact Recorder installation and handling Yes/ No Yes Yes - shock Indicators
procedure provided
<48 (no switching
1.38 Noise level dB <48 conditions)

2 CIRCUIT BREAKER

2.1 Manufacturer name ABB

2.2 Place of Manufacturing Switzerland

2.3 Type SP3

IEC 62271
2.4 Applicable Standards

2.5 Electrical Endurance Class E1 E1

2.6 Mechanical Endurance Class M2 M2

2.7 Restrike performance Class C2 C2

2.8 Rated voltage kV 420 420

2.9 Rated Current Bus bars, Bus Section


and Bus Coupler

2.9.1 at 40 0C A 4000 4000

2.9.2 at 50 0C A 4000

2.10 Rated Current Feeders and


transformer bays

2.10.1 at 40 0C A 2500 2500

2.10.2 at 50 0C A 2500

2.11 Rated lightning impulse withstand


voltage

2.11.1 Phase to earth kV p 1425 1425

2.11.2 Across the isolating distance kV p 1425 1425

2.12 Rated power frequency withstand


voltage

2.12.1 Phase to earth kV 650 650

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 3 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

2.12.2 Across the isolating distance kV 815 815

2.13 Rated short-circuit breaking Current

2.13.1 AC component, r.m.s. value kA >63 63

2.13.2 Percentage of DC component % 60

2.14 Rated short time withstand current (1s) kA 63

2.15 Rated short-circuit making current kA 170

2.16 Rated cable charging breaking current A 400

2.17 Rated Line charging breaking current A 400

2.18 Maximum capacitive breaking current A as per IEC

2.19 Rated small inductive breaking current A 100 100

2.20 Rated out-of-phase breaking current kA 15.8

2.21 Breaking current for shunt reactors A 315 315

2.22 First-pole-to-clear-factor 1.3 1.3

2.23 Rated operating sequence O-0.3s-CO-3m O-0.3s-CO-1min-CO


in-CO

2.24 Operating time

2.24.1 Opening ms <30 18 (0/-5)

2.24.2 Closing ms 60 (0/-15)

2.24.3 Maximum total break time (trip initiation ms 60


to final arc extinction) <40

2.24.4 Maximum time interval between opening ms 3


<=2
of first and last phase of three phase
circuit breakers

2.24.5 Dead Time Minimum time from ms 300


extinction of arc to contact make during 300
auto-reclosing duty)

2.25 Number of full short-circuit breakings No >15 20


per pole till next maintenance

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 4 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

2.26 Suitable for single-phase auto reclosure Yes Yes

2.27 Type of operating mechanism Hydraulic or spring charged


spring Hydraulic operated
charged

2.28 Operation counter for each phase Yes/ No Yes Yes

2.29 Mechanical position Indicator for main Yes/ No Yes Yes


contacts

2.30 Emergency tripping facilities - Yes/ No


Yes
Mechanical

2.31 Emergency tripping facilities - Electrical Yes/ No Yes

2.32 Capacitor in parallel to the main contact Yes/ No Yes

2.33 Number of breaks in series per phase SP3: 2


During detailed engineer-
2.34 Gas pressure ing as per SLD Layout

2.34.1 Monitoring of R, Y, B phase separate Yes/ No Yes Yes

2.34.2 Combined gas sensor system for Yes/ No Yes


remote monitoring provided

2.34.3 Rated pressure at 20°C bar 6.8 (abs)

2.34.4 Minimum pressure at 20°C bar 6.0 (abs)

2.34.5 Lockout pressure at 20°C bar 6.0 (abs)

2.34.6 Setting pressure of relief device bar 12.5 (abs)

2.35 Spring charged operating mechanism

2.35.1 spring charging time s 30

2.35.2 Motor nominal Voltage V 110 DC 110V DC

2.35.3 Rated motor power W 1100

2.35.4 Hand operating facility Yes/ No Yes Yes

2.35.5 Hand charging facility Yes/ No Yes Yes

2.35.6 Manual spring release Yes/ No Yes Yes

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 5 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

2.35.7 Mechanical spring charge / discharge Yes/ No Yes Yes


indication

2.36 Hydraulic operating mechanism

2.36.1 Motor nominal voltage V 110 DC please refer to 2.35.2

2.36.2 Rated motor power W please refer to 2.35.3

2.36.3 operating counter for motor operation Yes/ No Yes Yes

2.36.4 motor running hour meter Yes/ No Yes No

2.36.5 Rated pressure at 20°C bar n.a.

2.36.6 Motor Stop pressure bar n.a.

2.36.7 Motor start pressure bar n.a.

2.36.8 Auto reclose lockout bar 6.0 bar (abs)

2.36.9 Close lock out bar 6.0 bar (abs)

2.36.10 Operation lock out bar 6.0 bar (abs)

2.37 Number of opening coils 2 2

2.38 Number of close coils 1 1

2.39 Closing coil nominal voltage V 110 DC 110V DC

2.40 Opening coil nominal voltage V 110 DC 110V DC

2.41 Nominal control and operating voltage V 110 DC 110V DC

2.42 Nominal heater voltage V 240 AC 240V AC

2.43 Rated power of opening coil W 550

2.44 Rated power of close coil W 550

2.45 Total load of heaters for circuit breaker W 70

2.46 Mass of circuit breaker complete (three kg


5000
pole)

2.47 Mass of single phase of circuit breaker kg - 1680

2.48 Emergency Trip Facility during failure of Yes/ No Yes

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 6 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

DC supply

3 ISOLATORS

3.1 Manufacturer name ABB

3.2 Place of Manufacturing Switzerland

3.3 Type designation TK3

3.4 Type of operating mechanism Motor Motor

3.5 Standards IEC 62271- IEC 62271-102,


102, IEC IEC 62271-1,
62271-1, IEC62271-203
62271-203

3.6 Rated normal current Bus bars, Bus


Section and Bus Coupler / Incomer /
Feeder

3.6.1 Required current at 40oC A 4000-Busbar /2500-


Feeder
3.6.2 at 50oC A 4000-Busbar/2500-
Feeder
3.7 Mechanical Endurance Class M2 M2

3.8 Rated short time withstand current (1 s) kA 63 63

3.9 Rated peak withstand current kA p 160 170

3.10 Total time from initiation of opening s


operation to isolator in fully open 0.4 - 0.9
position

3.11 Total time from initiation of opening s


operation to time when isolator gap can 0.4 - 0.9
withstand phase voltage

3.12 Hand operating facility Yes/ No Yes Yes

3.13 Locking arrangement in on/off position Yes/ No Yes Yes

3.14 Nominal control and operating voltage V 110 DC 110V DC

3.15 Automatic isolation of control supplies Yes/ No Yes Yes


when lock off

3.16 Accessibility to operating mechanism Yes/ No Yes Yes

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 7 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

from ground level or catwalk

3.17 Nominal heater voltage V 240 AC 240V AC


Details of AC/DC load
3.18 Rated power of operation coil W documents shall be
submitted separately

3.19 Rated motor power W 500

3.20 Total load of heaters for isolator W 16

3.21 Total mass of three phase isolator kg


600 Approx.
complete

3.22 Mass of single phase isolator kg 183 Approx.

4 EARTH SWITCHES

4.1 Manufacturer name ABB

4.2 Place of Manufacturing Switzerland

4.3 Type designation TK3

4.4 Type of operating mechanism Motor Motor

4.5 Standards IEC 62271- IEC 62271-102,


102, 62271-1, IEC 62271-1,
62271-203 IEC 62271-203

4.6 Rated short time withstand current (1s) kA 63 63

4.7 Rated peak withstand current kA 160 170

4.8 Continuous current rating (for CT A 4000/2500


primary injection purpose)

4.9 Continuous voltage rating (across kV 10 AC


isolated earthing link, for CT primary 10
injection purpose)

4.10 Hand operating facility Yes/ No Yes Yes

4.11 Locking arrangement in on/off position Yes/ No Yes Yes

4.12 Nominal control and operating voltage V 110 DC 110 DC

4.13 Automatic isolation of control supplies Yes/ No Yes Yes


when lock off

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 8 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

4.14 Accessibility to operating mechanism Yes/ No Yes Yes


from ground level or catwalk

4.15 Nominal heater voltage V 240 AC 240V AC


Details of AC/DC load
4.16 Rated power of operating coil W documents shall be
submitted separately

4.17 Rated motor power W 500

4.18 Total load of heaters for earthing switch W 16

5 HIGH SPEED EARTH SWITCH

5.1 Manufacturer name ABB

5.2 Place of Manufacturing Switzerland

5.3 Type designation EB3

5.4 Type of operating mechanism Motor-spring Motor-spring

IEC 62271- 102,


5.5 Standards IEC 62271-
IEC 62271-1,
102, 62271-1, IEC 62271-203
62271-203

5.6 Rated short time withstand current (1 s) kA 63 63

5.7 Rated peak withstand current kA p 160 170

5.8 Rated short-circuit making current kA p 160 170

5.9 Continuous current rating (for CT A 4000/2500


primary injection purpose)
5.10 Continuous voltage rating (across kV 10 AC
isolated earthing link, for CT primary 10
injection purpose)

5.11 Total time from initiation of opening ms


operation to earth switch in fully open <2 S
position

5.12 Charging time s 4s - motor running time

5.13 Hand operating facility Yes/ No yes Yes

5.14 Locking arrangement in on/off position Yes/ No yes Yes

5.15 Nominal control and operating voltage V 110 DC 110V DC

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 9 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

5.16 Automatic isolation of control supplies Yes/ No Yes Yes


when lock off

5.17 Accessibility to operating mechanism Yes/ No Yes


Yes
from ground level or catwalk

5.18 Nominal heater voltage V 240 AC 240V AC

5.19 Rated power of operation coil W 500

5.20 Rated motor power W 500

5.21 Total load of heaters for earthing switch W 16

5.22 Total mass of earthing switch complete kg 700 Approx.

6 LOCAL CONTROL CUBICLE

6.1 Manufacturer name ABB

6.2 Place of Manufacturing Switzerland

6.3 Type freestanding

6.4 Standard IEC

6.5 Steel thickness (minimum)

6.5.1 door mm >=2mm

6.5.2 Side/ top / rear of the cubicle mm >=1.5mm

6.5.3 Gland plate mm 3 mm

6.6 Paint thickness minimum m 80 80

6.7 Dimensions of LCC (Length x Width x mm


1600(L)X800(D)X2200(H)
Height)

7 SURGE ARRESTERS (GI AND


OUTDOOR TYPE) NA for this project

7.1 Manufacturer name

7.2 Place of manufacturing

7.3 Type

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 10 of
17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

7.4 Standard IEC 60099-4,


60099-1
60099-5,
62271-1

7.5 Rated/system voltage kV

7.6 Maximum overvoltage factor on the pu 2.3


system due to any switching duty

7.7 Rated system frequency Hz 50

7.8 Condition of system neutral Solid

7.9 Nominal Discharge current kA crest 20

7.10 Rated voltage kV 336 360


7.11 Maximum continuous operating voltage kV 269 288
288
7.12 Discharge class as per IEC 60099-4 4

7.13 Nominal Discharge current kA 20

7.14 Temporary Over Voltage (TOV)


withstand capability

7.14.1 1 sec kV 390

7.14.2 10 sec kV 370

7.15 Maximum residual voltage with current


wave

7.15.1 Switching Surges

7.15.1.1 2 kA kV 680

7.15.1.2 3 kA kV 700

7.15.2 lightning impulse (8/20 wave)

7.15.2.1 10kA kV 780

7.15.2.2 20kA kV 850

7.15.2.3 40kA kV

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 11 of
17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

7.16 Discharge Current withstand strength

7.16.1 High surge current (4/10 wave) kA 100

7.16.2 Long-wave surge current (2000 µs) A 1600

7.16.3 Short circuit strength (0.2 s) kA

7.17 Pressure relief capability

7.18 Rating of earth connections kA/sec 50/1

7.19 Surge counter provided Yes/ No Yes

7.20 Equipped with leakage current indicator Yes/ No Yes

7.21 GI Type SA - Other Data


7.21.1 First commercial operation of the
offered unit

7.21.2 Reference list attached Yes/ No Yes


7.22 Outdoor Type SA - Other Data

7.22.1 First commercial operation of the


offered unit

7.22.2 Reference list attached Yes/ No Yes

7.23 GI Type SA - supporting documents


7.23.1 Type test reports enclosed Yes/ No Yes

7.23.2 Technical literature enclosed Yes/ No Yes

7.23.3 Standard conditions of installation Yes/ No Yes


enclosed

7.23.4 Relevant drawings enclosed Yes/ No Yes

7.24 Outdoor Type SA - supporting


documents

7.24.1 Type test reports enclosed Yes/ No Yes

7.24.2 Technical literature enclosed Yes/ No Yes

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 12 of
17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

7.24.3 Standard conditions of installation Yes/ No Yes


enclosed

7.24.4 Relevant drawings enclosed Yes/ No Yes

8 OUTDOOR BUSHINGS ( SILICON


RUBBER POLYMER TYPE)

8.1 Manufacturer name LAPP/ SAVER

8.2 Place of Manufacturing Germany/ Italy

8.3 Type HB3/420

8.4 Standards

8.5 Operating voltage (U0/U) kV 230 / 400 400

8.6 Rated voltage kV 420 420

8.7 Rated short-circuit withstand current kA/1sec 63 63

8.8 Rated peak withstand current kA 160 170

8.9 Insulation medium SF6 SF6

8.10 Material of enclosures polymer Composite

8.11 Insulator Creepage distance (minimum) mm/kV 55 >55


at rated voltage (line to earth)
8.12 Lightning impulse withstand voltage kV 1425
(peak) (phase to phase and phase to 1425
earth) at minimum operating gas
pressure

8.13 Switching impulse withstand voltage kV 1050


1050
(Phase to Phase) at minimum operating
gas pressure

8.14 Rated Power frequency withstand voltage kV 650


(1min) (phase to phase and phase to 650

earth) at minimum operating gas


pressure

8.15 Rated Current

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 13 of
17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

8.15.1 Feeder

8.15.1.1 at 40°C A 2500 4000

8.15.1.2 at 50°C A >3150

8.15.2 Transformer

8.15.2.1 at 40°C A 4000

8.15.2.2 at 50°C A >3150

8.15.3 Reactor

8.15.3.1 at 40°C A 4000

8.15.3.2 at 50°C A >3150

8.16 Rated gas pressure at 20°C bar abs. 5.3

8.17 Minimum gas pressure at 20°C bar abs. 4.5

8.18 Gas quantity of complete bushing kg 447 liters

8.19 Weight of bushing kg 262

8.20 First commercial operation of the


same as GIS
offered unit

8.21 Supporting Documents

8.21.1 Reference list attached Yes/ No During Detail Engineering

8.21.2 Type test reports enclosed Yes/ No Yes Yes

8.21.3 Technical literature enclosed Yes/ No Yes During Detail Engineering

8.21.4 Standard conditions of installation Yes/ No Yes


enclosed During Detail Engineering

8.21.5 Relevant drawings enclosed Yes/ No Yes Yes

9 OUTDOOR BUSHINGS (SILICON


RUBBER)

9.1 Insulator Creepage distance (minimum) mm/kV 55


at rated voltage (line to line)

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 14 of
17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

10 CURRENT TRANSFORMERS

10.1 Manufacturer name ABB/Pfiffner/Trench

10.2 Place of Manufacturing CZ/CH/DE

10.3 Type Toroidal toroidal


-core or type
bar

10.4 Standards IEC 61869-2 IEC 61869-2

10.5 core insulation Cast resin cast resin

10.6 Insulation class E or better E

10.7 Permissible Maximum Impact (g) during g


transportation between factory and Site

10.8 Impact Recorder installation and Yes Yes - shock indicator


handling procedure provided

10.9 Mounting arrangement Both side of CB

10.10 Inside SF6 duct Yes/ No NO

10.11 Outside SF6 duct Yes/ No Yes

10.12 Operating Voltage on Primary side of kV 400 400


the CT

10.13 Rated frequency Hz 50 50

10.14 Rated short-circuit withstand current 1 kA 63


63
sec

10.15 Rated peak withstand current kA 160 170

10.16 Continuous Overloading

10.16.1 For transformer feeder % 150% 150%

10.16.2 For Bus Couplers and Bus sections % 150% 150%

10.16.3 Minimum (for normal application) % 120% 120%

10.17 Supporting Documents

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 15 of 17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

10.17.1 Type test reports enclosed Yes/ No Yes Yes

10.17.2 Technical literature enclosed Yes/ No Yes Yes

10.17.3 Standard conditions of installation Yes/ No Yes Yes


enclosed

10.17.4 Relevant drawings enclosed Yes/ No Yes Yes

11 VOLTAGE TRANSFORMERS
Ritz/Trench/Pfiffner
11.1 Manufacturer name

DE/DE/CH
11.2 Place of Manufacturing

11.3 Type Inductive, SF6 Inductive,


gas insulated, SF6 Gas insulated
enclosed enclosed

11.4 Standards IEC 61869-3, IEC 61869-3,


IEC 62271-1,
62271-1,
IEC 62271-203
62271-203

11.5 Permissible Maximum Impact (g) during g


transportation between factory and Site

11.6 Impact Recorder installation and Yes


Yes
handling procedure provided

11.7 Rated voltage kV 420 420

11.8 Rated frequency Hz 50 50

11.9 Rated lightning impulse phase to earth kV p 1425 1425

11.10 Rated power frequency withstand kV 650 650


voltage phase to earth

11.11 Maximum permissible partial discharge pC <5


level Um

11.12 Maximum permissible partial discharge pC <5


level 1.2Um / 3

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 16 of
17
Document: OETC-AMP-O-AMT-A-044:A2
Rev: 0
Standard specification 400/132/33 kV Substations:
Annex 2, Section 2 400 kV GIS Technical Data Sheets

TECHNICAL DATA SHEET


400kV SF6 Gas Insulated Switchgear
(To be Completed, Signed and Stamped by the Tenderer)

Item No Description Unit Required Tendered

11.13 Maximum capacitive current discharge A


During Detail engineering
rating

11.14 Rated over voltage factors

11.14.1 continuously 1.2 1.2

11.14.2 for 30 s (solidly grounded) 1.5 1.5

11.14.3 for 8 hrs. (ungrounded - DELTA 1.9 1.9


connection)

11.15 Method of suppressing ferroresonance


phenomena During Detail Engineering

11.16 Line bay voltage transformer Yes

11.17 Number of secondaries 2 2

400/sqrt(3) /
11.18 Rated transformation ratio kV 400/ 3 /
0.11/sqrt(3),
0.11/ 3, 0.11/sqrt(3)
0.11/ 3

Post Box: 1389, Postal Code: 132, Al Khoud, Sultanate of Oman. website: www.omangrid.com Page 17 of
17