JANUARY 1993: NUMBER 6

Preventive Conservation in Practice


Graham MartinHead of Science Section

Boris PretzelHigher Scientific Officer

Nick Umney20th Century Gallery Conservation Liaison Officer and Senior Conservator,

Introduction
Preventive conservation is now, justifiably, taking a much higher profile in the day to day running of many museums and
other similar institutions. Recent interests in preventive conservation include an international three day symposium hosted
by ARAAFU in Paris.1 (#preventive1) The content of this and similar meetings has been directed towards finding
acceptable solutions to complex problems. This contribution traces the implementation of such preventive solutions to
complex environmental problems in the recently opened Twentieth Century Gallery (rooms 70-74) at the V&A.

The display in this new gallery contains many examples of ephemeral materials used in art and design. These materials are
subject to degradation by several factors among which light and ultra-violet radiation play an important role. One problem
of this display was the many square metres of glazing, subjecting the gallery space to high solar illumination, high uv levels
and considerable solar heat gain. In addition, a design requirement was that the visiting public should still be able to retain
some visual contact with the view through the windows.

The Challenge
The Conservation Department first became involved with the gallery project in March 1992,
by which time the budget and several other design parameters had already been
established. Examination of rooms 70-73 (the group of rooms with east-facing windows)
before development suggested three principal areas of concern: light, heat and dirt. The
environmental conditions required for the gallery can be summarised as;

1. Light levels to be between 50 lux (for fugitive materials) and 250 lux (for
light fast materials)
2. UV power of illumination to be reduced to less than 75 µW/lm and
preferably less than 10 µW/lm using a filter passing the Museum's criteria
3. Peak illumination levels near windows to be less than 1000 lux even during (http://www.vam.ac.uk/imag
the short periods in the mornings in summer when direct sunlight -popup.html)
penetrates the gallery Looking east across the Pirelli
Garden from Room 71 of the 20th
4. Solar gain to be controlled to prevent large fluctuations in temperature in Century Gallery (click image for
the gallery larger version)

In addition the brief from English Heritage was that the view of the windows from the
exterior of the building must not be distorted.

All objects in rooms 70-73 would be enclosed in new Glasbau Hahn cases, except for the furniture, which was to remain on
open display. Logistically, it would be difficult to put the furniture elsewhere than on plinths adjacent to the outside wall. In
addition, the design required that;

1. The garden should be discernible through at least some of the windows for the purpose of visitor
orientation
2. The windows running the full length of one wall in rooms 70-73 should remain openable to allow
maintenance and cleaning should be carried out on the outside of the building
3. The design should be viable for a minimum period of 10 years.
A large proportion of the outside wall is glass. This leads to the possibility of high levels of illumination due to natural light,
direct sun penetration during the early hours of the day and undesirable, uncontrolled heating by the sun. However,
furniture, to be displayed on plinths in window spaces, was not to be exposed to average light levels in excess of 250 lux and
highly light sensitive material was to be displayed at 50 lux. The solution to this problem depended in part on the
unquantified need to reduce solar gain in order to avoid excessive temperature fluctuations in the window spaces. Historical
environmental records for the gallery were not available though some data were collected during April, May and June. Use
of a uv screening film and a grey fabric blind had been proposed but light readings taken in the gallery showed that this
would not provide adequate control of illuminance.

Preliminary measurement of light levels in the gallery suggested that illuminance would need to be controlled to less than
1% of incident light. Small samples of dark sputtered titanium grey film were obtained from Sun-X2 (#preventive2) and
tested in the gallery and in the laboratory to assess their efficacy. This type of film was chosen as it does not introduce
metameric or other problems associated with filtered daylight. The requirements for control of illuminance could be met
using two layers of such a sputtered titanium film on the window with one layer of Mermet Sunscreen 4500 Natte 007 Perle
used as a blind in front of the window. To give adequate protection against uv, a new film, supplied by Sun-X as NDTX20,

http://www.vam.ac.uk/res_cons/conservation/journal/conservation_journal_6/preventive_... 31/01/2011
Preventive Conservation in Practice - Victoria and Albert Museum Página 2 de 3

was suggested which combines the daylight reducing properties of a traditional sputtered titanium film with the uv
filtration properties of a clear uv filtering film, thus nullifying the need for additional filtration.

The use of blackout blinds was considered as an alternative means of controlling the illumination. Such blinds would need
to be raised during the normal opening hours to allow visitors to see through at least some of the windows. The budget
would not allow for blackout blinds in addition to the Mermet Sunscreen blinds and the NDTX20 film, inevitably leading to
higher illumination levels during opening hours. However, as long as peak illumination levels could be maintained below
about 1000 lux, such a system could be used to reduce the overall exposure of objects in the gallery, thereby reducing rates
of degradation.

There is a fairly short critical time after the Museum opens and before the sun passes over the building when sunlight
penetrates directly into the gallery. To test whether maximum illumination levels in the gallery could be adequately
controlled using just the double layer of NDTX20 film even during these times, the following approximate measurements
were taken in room 72 at 10.00 hours on the 19th May:

1. Direct sunlight through glass next to window: in excess of 19,000 lux


2. At window through two layers of dark sputtered titanium film: 2,0001ux
3. At window, two layers of dark sputtered titanium film and Mermet blind: 223 lux
Direct sun penetration had stopped by 11.30 hours and at this time the light measured at the window, without filtration, had
dropped to 5,0001ux. Even on a bright day it appeared that two layers of film would be adequate once the gallery was out of
direct sun.

The option involving movable blackouts would need to have resulted in a significant reduction of annual exposure in order
to be preferred to the potentially more reliable low maintenance option of fixed blinds. A rough calculation suggested that
this would not be the case. However this calculation did not take into account the question of solar gain.

Consultants were engaged to assess the likely need for measures to combat solar gain. Their proposal was to estimate the
likely degree of sun penetration into the building, using an approximate analysis of the degree of external obstructions to
the window. From this and an approximate measurement of the thermal capacity of the building they proposed to calculate
the likely temperature rise in the gallery under four different solar control situations. These were (1) without protection (2)
with solar film (3) with blinds (4) with no window at all. In the end, mainly because of the levels of reduction in energy
transmission provided by the film and the results of our own environmental monitoring in the gallery, we did not pursue
this interesting avenue.

Two approaches were taken to testing the effect of the film and the blind materials. In one, a test rig was built and used for
carrying out measurements in the gallery. The test rig consisted of a light-proof box in two parts that allowed measurements
to be taken through various combinations of layers of film and blind via a light meter inserted through a small flap at the
back. The other method involved the use of uv-vis-nir spectroscopy to measure the transmission characteristics of the film.
There was close agreement in the results obtained using these two different methods.

The Solution
The final system chosen was a combination of films and a blind. A single layer of the darkest available sputtered titanium
film has daylight transmittance of 22% and a solar transmittance of 21%. As over 25000 lux may be incident at times, this is
insufficient. Therefore a double layer (daylight transmittance of 5%, solar transmittance of 4%) was used and combined
with a blind of Mermet Natte 4500 (007 Perle). This combination provides a bright appearance and a pleasant view of the
Museum's garden while substantially reducing light levels. The combination has a daylight transmittance of 0.6% (and solar
transmittance of 0.7%).

Lighting in the rooms is supplemented with ultra-low voltage tungsten-halogen lamps. As these inherently produce large
amounts of uv, they are filtered using Optivex cover glass filters, reducing uv levels to less than 1 µW/lm. The spotlights are
further supplemented with bare tungsten-halogen uplighters, illuminating the ceiling.

Glossary
Daylight transmittance: percentage illumination intensity of filtered D65 reference daylight as compared to unfiltered
D65.

D65: D illuminants are standard illuminants having defined relative spectral power distributions that represent phases of
daylight with different correlated colour temperature. D65 represents daylight with a correlated colour temperature of
approximately 6500 Kelvin; this is used to represent average indoor daylight (daylight with only small contributions from
the sun directly).

Illumination intensity: the integral of the power distribution of the illumination weighted by the sensitivity of human
eye to the various frequencies (400nm - 760nm).

Metamerism: colours which match in one set of viewing conditions but not in others are said to be metameric.

Solar transmittance: percentage energy of filtered D65 (340nm to 1800nm) as compared to unfiltered D65.

http://www.vam.ac.uk/res_cons/conservation/journal/conservation_journal_6/preventive_... 31/01/2011
Preventive Conservation in Practice - Victoria and Albert Museum Página 3 de 3

Sputtered coating: a metallised coating produced by bombardment of the metal with high energy particles at low
pressure.

All spectral measurements in accordance with ISO 9050

References
1. La Conservation Preventive, Paris 8, 9 and 10 October 1992, organised by the Association des Restaurateurs d'Art et
d'Archeologie de Formation Universtaire, 3, rue Michelet, 75006 Paris.
2. Combined light reducing and uv filtering film supplied and fitted by Sun-X.

Film manufacturer: Deposition Technologies Inc., USA. This fihn has a titanium sputtered coating for reducing illumination
levels without degrading colour rendition or changing correlated colour temperature (ie. warmness or coolness) of light.
This film does not introduce metameric problems. The sputtered coating on the film produces only partially reflective film
therefore it does not change externalappearance too greatly. The film also has uv filter incorporated, filtering D65 ref.
daylight to less than 10µW/Im.