Vous êtes sur la page 1sur 4

Actual Output for F&A Capacity

F&A Cap 1000 kg/hr


Boiler Op. Pressure 10.5 Kcal/kg
Enthalpy at Op. Pr. 663 Kcal/kg
Feed water temp. 40 deg C
Actual Output 867 kg/hr
Calculation of Fuel Consumption & Chimney
Height
F&A Cap 4000 kg/hr
Sulphur 4 %
Cal. Value 9650 Kcal/kg
Efficiency 83 %
Fuel Conspn. 269.68 kg/hr
Chimney Height 35.18 m
Steam Consumption at Op. Pressure

Net Steam
Consumption 500 kg/hr

Enth at Op Pr 663 Kcal/kg

Feedwater Temp 50 Deg C

NCV 9650 Kcal/kg

Effi. 88 %

Sp density of fuel 0.95

Fuel Conspn 36.09 kg/hr

or 37.99 l/hr
Steam Consumption at F&A 100 Deg

F&A rating 1000 kg/hr

Enth at 100 Deg C 540 Kcal/kg

NCV 9650 Kcal/kg

Effi. 89 %

Sp density of fuel 0.95

Fuel Conspn 62.87 kg/hr

or 66.18 l/hr