Académique Documents
Professionnel Documents
Culture Documents
TOTAL 7
Panel Size - 5.6 Mtr 5600
11 KV Switchgear Panel -
I/C FOR 11KV 1 0 1
O/G - 11/3.3KV TXF 1000KVA 1 1 2
O/G - 11/0.433KV TXF 3000KVA 1 0 1
APFC - 300KVA 1 1 2
BUS PT 1 0 1
TOTAL 7
Panel Size - 5.6 Mtr 5600
HINDUSTAN DORR-OLIVER LTD.
MUMBAI. ENGINEERING DIVISION DATE 18/10/2010
CLIENT ONGC ASSAM PROJ. NO. BYE IT00900
PLANT ETP + WIP (GELKI) CAL. NO.
CONSULTANT REVISION P0
TITLE TRANSFORMER SIZING CACULATION SHT. NO.
497.27
HENCE, KVA = = 621.58 KVA
0.8
TOTAL LOAD IN KVA AT 0.8 P.F. LAG = (KVA X COS F) + j (KVA X SIN F)
= 497.27 + j 372.95 KVA ………….[1]
TOTAL MOTOR LOAD IN KVA AT 0.8 P.F. LA = (KVA X COS F) + j (KVA X SIN F)
= 45 + j 26.70 KVA ………….[2]
SO, THE INCOMER AS WELL AS THE BUSDUCT RATING OF 1600 AMP IS RECOMMENDED.
H. G. PATEL T N MERCHANT
PREPARED BY APPROVED BY
HINDUSTAN DORR-OLIVER LTD.
MUMBAI. ENGINEERING DIVISION DATE 18/10/2010
CLIENT ONGC ASSAM PROJ. NO. BYE IT00900
PLANT ETP + WIP (GELKI) CAL. NO.
CONSULTANT REVISION P0
TITLE TRANSFORMER SIZING CACULATION SHT. NO.
1364.00
HENCE, KVA = = 1705.00 KVA
0.8
TOTAL LOAD IN KVA AT 0.8 P.F. LAG = (KVA X COS F) + j (KVA X SIN F)
= 1364.00 + j 1023.00 KVA ………….[1]
TOTAL MOTOR LOAD IN KVA AT 0.8 P.F. LA = (KVA X COS F) + j (KVA X SIN F)
= 450 + j 290.67 KVA ………….[2]
SO, THE INCOMER AS WELL AS THE BUSDUCT RATING OF 600 AMP IS RECOMMENDED.
H. G. PATEL T N MERCHANT
PREPARED BY APPROVED BY