SIMOCODE-DP Motor Protection and Control Devices

3UF5

■ Overview
Protection System concept
Thermal overloading can be
caused by unbalanced current
input, failure of a phase or ex-
cessive mechanical loads. The Master computer
3UF50 motor protection and
control devices counteract this
Master level
danger with two protective
mechanisms:
• Monitoring of the three phase
currents by means of inte- Control level SIMATIC R
grated current transformers programmable
ETHERNET controllers
• Thermistor motor protection
by means of evaluation of a
PTC or NTC or KTY thermistor
circuit Automatic level
PROFIBUS-DP Communication-
Furthermore, it is possible to capable
activate an earth-fault protec- low-voltage
tion feature integrated into the controlgear,e.g.
device. The differential current SIMOCODE-DP
is calculated via the three K1 K2 K3 K4
phase currents. If the limit value
(30 % Ie) is exceeded, the load
branch can be disconnected or
a signal can be sent to the con- Motor Motor Motor
trol level. This earth-fault pro-
tection system, however, can Unit control
only be used with loads with a level Fans Conveyer belt Fans
neutral point which is not
tapped. In order to detect an
NSA00139
earth fault with absolute preci-
sion (0.3; 0.5 and 1 A), an exter-
nal summation current trans- Control Communication – Communication –
former (3UL2 20.-.A) can be PROFIBUS-DP standard PROFIBUS-DPV1 standard
Complete, branch-related con-
connected as an alternative expansion
trol functions can be created via The 3UF5 0 motor protection
(unit variant).
the control unit integrated in the and control devices are fitted PROFIBUS-DP has been ex-
For further details on overload device and the four DC 24 V in- with an integrated PROFIBUS- tended with the instruction set
protection, see the Section puts and four floating outputs. In DP interface. for non-cyclic reading and writ-
Overload relays and protective this way, for example, star-delta ing (PROFIBUS-DPV1). This
Connection to the widely imple-
devices. These characteristics or reversing contactor circuits PROFIBUS-DP extension is in-
mented fieldbus system
correspond to those of the can be created without the labor tegrated into the SIMOCODE-
PROFIBUS-DP, rapid and relia-
3RB1 2 electronic overload re- and equipment usually required DP 3UF5 0 system from delivery
ble transmission of control com-
lay. (auxiliary contactors, time re- stage E10 (June 98) onwards.
mands, operational status as
lays, input/output modules of the
EEx e type of protection well as diagnostic, service, sta- This facilitates online parame-
programmable controllers, etc.).
tistical and parameter data to terization, operation, monitor-
The SIMOCODE-DP 3UF5 sys- An expansion module makes it and from the higher-level bus ing and testing with Win-
tem is in accordance with the possible to link in an additional 8 interface is guaranteed. This SIMOCODE-DP/Professional via
regulations for overload protec- outputs and 4 floating outputs to can be a component of a pro- PROFIBUS-DP.
tion of explosion-protected mo- the motor protection and control grammable controller or a proc-
tors of the EEx e "Increased device. In this way more com- ess control system. SIMOCODE Autonomous operation
safety" type of protection to plex control functions can be is easily integrated into a If system faults occur on the
EN 50 019/DIN VDE 0165, created autonomously without PROFIBUS-DP network via the communication path,
DIN VDE 0170/0171 and the involving the automation level. parameterizing and service pro- SIMOCODE-DP automatically
PTB test regulations. gramme of the SIMATIC S5: switches to manual mode.
Safe isolation COM PROFIBUS or
In the case of tripping devices
SIMATIC S7: STEP 7. In this case, either the load
with DC control, isolation by All electric circuits in
feeder is shut down or the oper-
battery or safety transformer in SIMOCODE-DP (from product
ating status is retained. Further
accordance with DIN VDE 0551 ver-sion 12, start of delivery 01/
control is then effected manual-
must be assured. 2000) are safely isolated from
ly.
each other according to DIN
It is recommended to separately
VDE 0100/0106/ 0160, that is, This enables the non-produc-
monitor the control supply volt-
they are designed with double tive times due to faults at the
age if the SIMOCODE-DP 3UF5
leakage paths and clearances. automation and communica-
system that has a parameteriza-
In the event of a fault, therefore, tion level to be considerably re-
ble bistable characteristic of the
no parasitic voltages can be duced. The autonomous struc-
output relay (Order No. 3UF5 0
formed in neighboring circuits. ture of the system permits the
..-3..10-1) is used to protect mo-
In this context, compliance with process to be reliably continued
tors of the "increased safety"
the instructions in the test report with local control through the in-
type.
"Safe isolation" No. 1610a is telligence integrated in the
PTB test report No. necessary. SIMOCODE-DP.
3.53-14605/96.

Siemens Energy & Automation, Inc. 16/141


Industrial Controls Catalog
16_Sec (129-160).qxd 07/28/03 03:36 PM Page 16/142

SIMOCODE-DP Motor Protection and Control Devices

3UF5
Actuator Sensor Interface

■ Overview
Parameterization and SIMOCODE-DP parameterizing locations
configuration software
PC or programming device with SIMATIC S5/S7/C7/M7 and PCS7 with
Specific software packages are
Win-SIMOCODE-DP/Professional PROFIBUS-DP communication processor
available for the different pa-
rameter setting areas and inter-
facing possibilities:

NSA00140b
COM-PROFIBUS
COM-PROFIBUS can be used PC or programming with
Win-SIMOCODE-DP/Smart
to integrate SIMOCODE-DP into PROFIBUS-DP cyclic data exchange
PROFIBUS-DP
SIMATIC S5 as a standard extension to standard
of controk and alarm data, as well as exchange
slave. The parameterization can of diagnostics data in the event of modifications
Online parameterization,
and parameterization on PLC startup
be created with COM- diagnostics, control,
and test via aczyclic
PROFIBUS and written to reading and writing
SIMOCODE-DP when the auto- of data
mation system starts up.

STEP 7
Point-to-point parameterization,
STEP 7 allows SIMOCODE-DP SIMOCODE-DP SIMOCODE-DP SIMOCODE-DP diagnostics, control, and test
via RS-232 interface
to be integrated into
SIMATIC S7 as a standard
slave. The parameterization can
Parameterization, operation, monitoring, and testing with Win-SIMOCODE-DP/Professional
be created with STEP 7 and
written to SIMOCODE-DP when
the automation system starts
up.

Win-SIMOCODE-DP/Profes-
sional
Software for online parameteri-
zation, operation, monitoring
and testing via PROFIBUS-DP
or point-to-point via the RS-232
system interface. Online means
that, apart from the normal cy-
clic transfer of data to the PLC,
non-cyclic parameter, control,
alarm and statistical data can
be read/written from/to
SIMOCODE-DP via a communi-
cations processor of Class 2,
e. g. CP5511 that is plugged in-
to the PC or programming de-
vice. This means no more run-
ning from switchgear room to
switchgear room to parameter-
ize the motor branches.
To modify parameters via
PROFIBUS-DP, it used to be
necessary to bring the plant to
a standstill. If Win-SIMOCODE-
DP/Professional is used, param-
eters can now be modified dur-
ing operation.
Unplanned standstill times for
maintaining the switching de-
vices are also a thing of the Win-SIMOCODE-DP/Smart OM-SIMOCODE-DP PCS7-FB SIMOCODE-DP
past. The plant operator is able Software for point-to-point pa- The SIMOCODE-DP object The PCS7 function block
to read all statistical data such rameterization, operation, moni- manager (OM) allows SIMOCODE-DP allows stand-
as the number of starts and op- toring and testing of SIMOCODE-DP to be integrated ard integration of SIMOCODE-
erating hours at the press of a SIMOCODE-DP via the RS-232 as an S7 slave into SIMATIC S7. DP into the PCS7 application
button from a central point via system interface. This means that parameter data programme as well as visualiza-
PROFIBUS-DP. created with Win-SIMOCODE- tion of SIMOCODE-DP-specific
DP/Professional can be loaded operating, diagnostics and sta-
offline into the SIMATIC S7 sys- tistical data in a PCS7 face-
tem data blocks (SDB) and can plate.
be written to SIMOCODE-DP
when the automation system
starts up. The user now only has
to operate a single parameteri-
zation interface: Win-
SIMOCODE-DP/Professional.

16/142 Siemens Energy & Automation, Inc.


Industrial Controls Catalog
16_Sec (129-160).qxd 07/28/03 03:36 PM Page 16/143

SIMOCODE-DP Motor Protection and Control Devices

3UF5

■ Overview
Installation Win-SIMOCODE-DP/Professional "Totally Integrated" in STEP 7 via the OM-SIMOCODE-DP
The current transformers are al-
ready integrated into the hous-
ing of all versions of the 3UF5 0
motor protection and control
devices.
The units with current setting
ranges ≤100 A (mounting width:
70 mm) are designed for instal-
lation as single units due to the
push-through installation tech-
nique.
Here, the main current conduc-
tors with rated motor currents of
1.25 A to 100 A are pushed
through the current converters
integrated in the housing. By
means of multiple loops, loads
with motor rated currents be-
tween 0.25 A and 1.25 A can al-
so be protected.
With the help of this push-
through technique, additional
installation work is reduced and
power losses at the transfer re-
sistors of the terminal points
that would otherwise be neces-
sary are avoided.
The 70 mm wide devices are ei-
ther snapped onto a 35 mm
standard mounting rail in ac-
cordance with EN 50 022 or
screwed onto a mounting plate
by means of plug-in clips which System manual Standards
can be supplied as accesso-
For selection of equipment IEC 60 947-4-1/DIN VDE 0660
ries.
and for planning, it is recom- Part 102;IEC 60 947-5-1/
With current setting ranges be- mended that the 3UF5 7 sys- DIN VDE 0680 Part 200
tween 100 A and 820 A (mount- tem manual is consulted (see
ing widths:120 mm,145 mm Selection and Ordering Data).
and 230 mm), the devices can
Further information is available
be directly fitted to the contac-
on the Internet at:
tor via connecting bars.
http://www.siemens.de/
A screw fastening for these de-
simocode-dp
vices is integrated in the hous-
ing.
For the 3UF5 0 devices (overall
width:120 mm), a baseplate for
snap-on attachment on a
75 mm standard mounting rail
is available.

Siemens Energy & Automation, Inc. 16/143


Industrial Controls Catalog
16_Sec (129-160).qxd 07/28/03 03:36 PM Page 16/144

SIMOCODE-DP Motor Protection and Control Devices

3UF5

■ Overview
Intelligent Communication with a Acquisition of operating Evaluation of statistical Controlling a load feeder
motor protection programmable controller data data
(automatic level)
SIMOCODE-DP protects SIMOCODE-DP offers pow- SIMOCODE-DP collects SIMOCODE-DP evaluates SIMOCODE-DP makes it pos-
electrical equipment such as erful communication operating data and makes statistical data and makes sible to control a motor via the
single-phase, three-phase between individual control them available for the user them available for the user bus, manually (3UF5 2 control
motors and transformers level and automatic level via via the bus, via the hand- via the bus, via the hand- module or locally) via the
PROFIBUS-DP and the held terminal or by means of held terminal or by means of hand-held terminal or be
PROFIBUS-DP extension to the Win-SIMOCODE-DP/ the Win-SIMOCODE-DP/ means of the Win-SIMOC-
the standard (DPV1) Smart or Professional soft- Smart or Professional soft- ODE-DP/Smart or Profes-
ware ware sional software
For rated currents from Data volume: Maximum phase current in % Maximum motor current of Parameterizable control
0.25 A to 820 A 4/12 bytes I/O cyclic of the current setting Ie the last overload trip Features:
20 bytes diagnostics in % of the current setting Ie • Direct on-line starter
Release classes 213 bytes of parameter data Alarm/tripping • Reversing starters
CLASS 5/10/15/20/25/30 • Overload Cause of the last tripping • Start-delta starting
Parameterization of the • Current unbalance • Dahlander circuit
Overload, phase failure, cur- device via the bus. • Threshold thermistor motor Operating hours • Pole reversal
rent unbalance and earth- protection overrange • Solenoid valve control
fault detection as well as Transfer rate, address and • Earth fault Number of starts • Gate valve control
locked-rotor protection and basic type must always be • Current limit value out of • SIKOSTART 3RW22
PTC, KTY or NTC thermistor set with Win-SIMOCODE-DP/ range Number of overload trip- • Individual control functions
motor protection Smart or Professional via the pings by means of logic blocks
system interface (RS 232). such as:
Protection of EEx e motors 4 truth tables, 2 timers,
All operating and diagnostic 2 counters and,
Two overload setting ranges data are available for the 4 signal matching blocks
for two-speed motors superordinated automatic
level. Monitoring of
Programmable current limit process signals:
value for process protection In case of a bus failure, fail- • Running time monitoring
ure of the communication when starting and stopping
Recovery time processor or failure of the • Interlocking, e.g. in reversing
5 min fixed-setting, extension programmable controller motors between clockwise
up to 60 min possible CPU, SIMOCODE-DP and counterclockwise rota-
switches off or retains its tion
Emergency start operational status (program- • Current-dependent change-
mable). over switching from star to
Combined Test/Reset button delta with star-delta starting
Manual/automatic RESET Manual control is enabled!
Control commands with man-
Remote Reset via the bus or Control commands can be ual operation:
external button given from the automatic • From the switchboard using
level. the 3UF5 2
High tripping precision • Locally e.g. with
Self monitoring enclosed pushbuttons
• Via the system interface by
Temperature range using the Win-
–25 to +60 °C SIMOCODE-DP/Smart
or Professional software

Control commands with auto-


matic operation:
• Via the bus from the applica-
tion programme
• whereby operator enables
can be issued and a key
switch for Manual/Automatic
changeover can be inte-
grated.

Function blocks Communication Transfer rate Transmission media Number of stations


interface max. distance
• Time-graded starting after PROFIBUS-DP 9.6; 45.45; 93.75; 187.5; • twisted, shielded two-wire • per segment 32
failure of the voltage in the PROFIBUS-DPV1 500; 1500 kbit/s cable • when using an RS 485
main circuit DIN (E) 19 245 Part 3/ • via optical link modules with repeater up to 122
• System protection OFF EN 50 170 Version 1.0 plastic or glass-fiber optic
• Ready to close cables
• Test mode (cold startup) RS 485 interface type • 9.6 km with two-wire cables
• Evaluation of external error • 425 m with plastic fibers
• Watchdog for undervoltage Connection via terminals • 93 km with glass fibers
OFF (conductor cross-sections as
• Evaluation of external alarm for auxiliary contacts or 9-
• Emergency start pole SUB-D socket

16/144 Siemens Energy & Automation, Inc.


Industrial Controls Catalog
16_Sec (129-160).qxd 07/28/03 03:36 PM Page 16/145

SIMOCODE-DP Motor Protection and Control Devices

3UF5

■ Operation
The motor current flowing at any 3UF5 0 basic unit, front view
particular time is detected in
each phase via current trans- $ Connection of a thermistor detector circuit for full motor
1 6
formers and continuously protection

NSA00141a
checked by a microprocessor. 2
Optimal: Connection of a summation current transformer
SIEMENS for earth fault monitoring
If there is an overload of Ready % Connection of the control supply voltage DC 24 V/
> 110 % of the set current Ie, a 7
3 Bus AC 115 V /AC 230 V
current imbalance of > 40 % Ie Gen. Fault & 3 LED displays
or a phase failure, the unit is ( Unit test, manual reset:
tripped in accordance with the 4 Automatic reset parameterizable
set tripping characteristic 8
Remote reset via bus or input
) 3 + 1 relay outputs: Function assignment parameterizable
(CLASS 5/10/15/20/25/30 * 4 optocoupler inputs:
see Section Characteristics) DC 24 V internally supplied, function assignment parame-
Resetting, either by pressing 5 terizable
+ System interface: Connection of expansion module, con-
the TEST/RESET button on the trol module, hand-held terminal or PC
unit or by remote or automatic , Bus connection PROFIBUS-DP:
RESET, is only possible when standard 9-pole SUB-D socket,
the recovery time of 5 minutes terminal for withdrawable units
has elapsed. An extension of
the recovery time and an emer-
gency start are possible.
If the thermistor sensor re- 3UF5 1 expansion module, front view
sponds or an earth-fault occurs,
the unit is tripped without any $ System interface:
3
delay. Connection to the basic unit
Supply from the basic unit
If the thermistor is tripped, re- % 3 + 1 relay outputs: Function assignment parameterizable
setting is only possible when & 8 optocoupler inputs:
the temperature in the motor DC 24 V/AC 115 V /AC 230 V externally supplied
coil has fallen to 5 K below the 1 4 ( System interface: Connection of control module or PC
response temperature of the
thermistor.
When an earth-fault causes trip-
ping, the unit can be reset im-
NSA00142

mediately after clearing the


fault. 2

A test of the current detection


function of the unit, the thermis-
tor and earth-fault inputs and 3UF5 2 control module, front view
the tripping function of the aux-
iliary contacts can be initiated 4 $ 2 status LEDs
by pressing the TEST/ RESET % 3 LED displays: Function assignment parameterizable
button (> 5 s). SIEMENS & Unit test, manual reset
Ready ( Control buttons, function assignment parameterizable
The integrated self-monitoring 1 5
Gen. Fault ) 3 LED displays: Function assignment parameterizable
system ensures that the unit is * System interface: Connection of control module or PC
2
also tripped when an internal
6
fault occurs.
A 3UF50 unit is operated (e. g. 3
switched on and off) either from
the local control points connect- NSA00143

ed to the inputs, the automatic


level via the bus, the 3UF5 2
control unit, or a personal com-
puter.

Siemens Energy & Automation, Inc. 16/145


Industrial Controls Catalog