Académique Documents
Professionnel Documents
Culture Documents
• V=IR
– Higher the voltage lesser the Voltage drop
– Voltage drop proportional to the ratio of voltages
• Power loss = I2R
– Higher the voltage, lesser the current and lesser the
power loss
• For ex. If voltage is raised from 11 kV to 33 kV
the voltage drop would be lowered by a figure of
1/3 and line loss would be lowered by (1/3)2
• Higher voltage can also bring down the conductor
sizes on account of lower currents handled
Central Pulp & Paper Research Institute, Saharanpur
G e n e r a t io n E ffic ie n c y r a n g e s 2 8 - 3 5 % w it h r e s p e c t t o s iz e o f t h e r m a l
E ffic ie n c y η 1 p la n t , a g e o f p la n t a n d c a p a c it y u t ilis a t io n
S t e p - u p S t a t io n S t e p - u p t o 4 0 0 / 8 0 0 k V t o e n a b le E H V t r a n s m is s io n .
η2 E n v is a g e d m a x . lo s s e s 0 .5 % o r e ffic ie n c y o f 9 9 .5 %
EHV E H V t r a n s m is s io n a n d s u b s t a t io n s a t 4 0 0 k V / 8 0 0 k V .
T r a n s m is s io n & E n v is a g e d m a x im u m lo s s e s 1 .0 % o r e ffic ie n c y o f 9 9 %
η 3 S t a t io n
HV H V t r a n s m is s io n & S u b s t a t io n s fo r 2 2 0 / 4 0 0 k V .
T r a n s m is s io n & E n v is a g e d m a x im u m lo s s e s 2 .5 % o r e ffic ie n c y o f 9 7 .5 %
S t a t io n η 4
S ub- S u b - t r a n s m is s io n a t 6 6 / 1 3 2 k V
t r a n s m is s io n η 5 E n v is a g e d m a x im u m lo s s e s 4 % o r e ffic ie n c y o f 9 6 %
D is t r ib u t io n S t e p - d o w n t o a le v e l o f 1 1 / 3 3 k V .
S t a t io n η 6 E n v is a g e d lo s s e s 0 .5 % o r e ffic ie n c y o f 9 9 .5 %
P r im a r y D is t r ib u t io n is fin a l lin k t o e n d u s e r a t 1 1 / 3 3 k V .
D is t r ib u t io n η 7 E n v is a g e d lo s s e s m a x im u m 5 % o f e ffic ie n c y o f 9 5 %
T h e c a s c a d e e ffic ie n c y in t h e T & D s ys t e m fr o m o u t p u t o f t h e p o w e r p la n t t o t h e e n d u s e
is 8 7 % ( i.e . 0 .9 9 5 x 0 .9 9 x 0 .9 7 5 x 0 .9 6 x 0 .9 9 .5 x 0 .9 5 = 8 7 % )
11 KV/440V
Transformer
Transformer .Effi.98-99.5%
ELECTRICAL
M
Sub-station Dist. loss
1 -6%
Feeders,
M M M M C Capacitors
Distribution
C
Panels
C
Motors
Effi.85-96%
MECHANICAL
FANS & BLOWERS PUMPS R & AC COMPRESSORS LIGHTING, HEATING LOAD
• Primary coil is connected to the power source and the secondary coil
connects to the load.
• The turn’s ratio is the ratio between the number of turns on the primary to
the turns on the secondary
• The secondary voltage is equal to the primary voltage times the turn’s ratio
For a load of 1500 KVA the plant has installed three numbers of 1000 KVA
transformers. The No load loss is 2.8 KW and the full load loss 11.88 KW. Estimate
the total loss with 3 transformers in operation and 2 transformers in operation.
a) 2 transformers in operation :
b) 3 transformers in operation :
No load loss = 3 x 2.8 = 8.4 KW
Load loss = 3 x (500)2 x 11.88 = 8.91 KW
(1000)
Example:
For a 1100 KVA set, at 800 KW loading, and with 480oC exhaust gas temperature,
the waste heat potential works out to:
If the normal load is 60%, the flue gas parameters for waste heat
recovery unit would be 320oC inlet temperature, 180oC outlet
temperature and 27180 kgs/Hour gas flow.
At 90% loading, however, values would be 355oC and 32,400
kgs/Hour, respectively.
Central Pulp & Paper Research Institute, Saharanpur
Energy Saving Measures for DG Sets
a) Ensure steady load conditions on the DG set, and provide cold, dust free
air at intake
b) Improve air filtration.
c) Ensure fuel oil storage, handling and preparation as per manufacturers’
guidelines/oil company data.
d) Consider fuel oil additives
e) Calibrate fuel injection pumps frequently.
f) Ensure compliance with maintenance checklist.
g) Ensure steady load conditions, avoiding fluctuations, imbalance in
phases, harmonic loads.
h) For base load operation, consider waste heat recovery system steam
generation or vapour absorption system adoption.
i) Consider partial use of biomass gas for generation. Ensure tar removal
from the gas for improving availability of the engine in the long run.
j) Consider parallel operation among the DG sets for improved loading .
Carryout regular field trials to monitor DG set performance, and
maintenance planning as per requirements.
Central Pulp & Paper Research Institute, Saharanpur
Pumps and Pumping Systems
COUPLING 2% LOSS
PUMPS
24% LOSS
VALVES
9% LOSS
PIPES
11% LOSS
System
70 m 82%
A
50 m
Full open valve
42 m
System Curves
Head
Meters
Static Operating Points
Head
300 m3/hr 500 m3/hr
3
Flow (m /hr)
70 m Partially B 82%
closed valve
A
50 m
Full open valve
42 m
System Curves C
Head
Meters
Static Operating Points
Head
300 m3/hr 500 m3/hr
3
Flow (m /hr)
14.8 kW
N = No. of stages
K = Ratio of specific heats (1.35 for air)
Ps = suction pressure in kg/cm2
Pd = Discharge pressure in kg/cm2
Q = Actual air flow (m3/min.)
Actual kW = √ 3 V I × PF as measured
Every 40C rise in inlet air temperature results in a higher energy consumption by 1 % to
achieve equivalent output. Hence, cool air intake leads to a more efficient compression.
It can be seen from the table that an increase of 5.50C in the inlet to the second stage
results in a 2 % increase in the specific energy consumption. Use of cold water
reduces power consumption.
P2 − P1 V
Actual Free air discharge Q= × NM 3 / Min.
P0 T
Where
P2 = Final pressure after filling (kg/cm2 a)
P1 = Initial pressure (kg/cm2a) after bleeding
P0 = Atmospheric Pressure (kg/cm2 a)
V = Storage volume in m3 which includes receiver,
after cooler, and delivery piping
T = Time take to build up pressure to P2 in minutes