Vous êtes sur la page 1sur 27

SIPROTEC 7SJ600

Numerical Overcurrent, Motor


and Overload Relay

Protection Systems
Catalog
LSA 2.1.15 ⋅ 1997
SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay

n Feeder protection
n Optional auto-reclosing Protection systems
n Transformer protection Page

n Motor protection
n Busbar protection Description 2 and 3

n Trip coil monitor


n Metering Tripping characteristics 4 to 6

n Event log
n Fault recorder Functions 7 to 11

n Self diagnostics
LSA2-001f.tif
Typical application 11
n Remote communication Typical elementary
diagrams 12 to 13

Scope of functions 14

Fig. 1
SIPROTEC 7SJ600 Technical data 15 to 19
numerical overcurrent,
motor and overload relay

Selection and
ordering data 20
Fig. 2
Typical applications
Trip Circuit diagram 21 to 23
Dimension drawings

Not contained
in 7SJ600
Protection functions
Trip Recloser
Blocking I>>

50 I>>, I>>> Instantaneous


Busbar overcurrent

Trip Trip 50N IE>> Instantaneous


ground overcurrent
51 I>t, Ip Time overcurrent
Pickup

51N IE>t, IEp Time ground


Recloser overcurrent
46 I2>>t, I2>t Negative sequence

49 ϑ>t Overload protection

79M Multishot reclosing


Pickup

 Siemens AG 1997

Siemens LSA 2.1.15 ⋅ 1997 1


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Description

Wide range of applications


The SIPROTEC 7SJ600 is a nu-
merical overcurrent relay
which, in addition to its prima-
ry use in radial distribution pow-
er systems and motor protec-
tion, can also be employed as
backup for feeder, transformer
and generator differential pro-
tection.
The SIPROTEC 7SJ600 provi-
des definite-time and inverse-
time overcurrent protection
along with overload and unba-
lanced load protection for a
very comprehensive relay
package. In this way, equip-

LSA2002f.eps
LSA2006f.eps
ment such as motors can be
protected against asymmetric
and excessive loading. Asym-
metric short-circuits whose cur-
rents can be smaller than the
largest possible load currents Fig. 3 Fig. 4
Front view of the Rear view of the
or phase interruptions are relia- 7SJ600 flush 7SJ600 surface
bly detected. mounting case mounting case

Construction
The relay contains all the Improved measurement Circuit-breaker / For easy commissioning the
components needed for technique Trip contact testing status of each binary input, re-
The SIPROTEC 7SJ600 relay The trip and reclose command lay or LED can be displayed
• acquisition and evaluation of
operates fully numerical with contacts can be activated via via HMI or DIGSI program.
measured values
• operation and display (local
enhanced algorithms. Due to the keyboard or through the
HMI) the numerical processing of RS485 interface. This facili-
measured values, the influ- tates testing of the trip and
• output of signals and trip
ence of higher-frequency tran- close circuits during commis-
commands sient phenomena and tran- sioning without the need for
• input and evaluation of bina- sient DC components is additional test equipment.
ry signals largely suppressed.
• data transmission (RS485)
• auxiliary voltage supply
Programmable inputs and
Continuous self-monitoring outputs
The nominal CT currents app-
lied to the SIPROTEC 7SJ600 The hardware and software in Up to 10 different functions
can be 1 A or 5 A. the SIPROTEC 7SJ600 relay can be activated by each bina-
This is selectable via a jumper are continuously self-monito- ry input via a form “a”(NO) or
inside the relay. red. This ensures a very high “b”(NC) contact
level of availability and redu- Up to 20 internal events can
Two different cases are ces the need for routine test-
available. The flush-mounting activate each signal or trip re-
ing. lay.
version has terminals accessi-
ble from the rear. The surface-
mounting version has termi-
nals accessible from the front.

2 Siemens LSA 2.1.15 ⋅ 1997


Serial data transmission
The SIPROTEC 7SJ600 is fit-
ted with an RS485 port. A PC Opt↔RS485 Protection Protection Protection
RS232↔RS485 relay 1 relay 2 relay 32
can be connected via this port Converter 7SJ600 7SJ600 7SJ600
to ease setup of the relay using
DIGSI. This program, which runs
under MSWINDOWS, can also Terminating
be used to evaluate up to 8 resistor
oscillographic fault records, 8 120 Ω
(cable-
fault logs and 1 event log con- dependent)
taining up to 30 events. The or
SIPROTEC 7SJ600 can be hook- Fig. 5
Wiring,
ed up to a PC or substation communi-
automation system. (IEC 870-5) cation

Convenient setting
The menu driven HMI or con-
nected PC is used for setting
parameters. These parameters
are stored in a non-volatile me-
mory so that the settings are
retained even if the supply volt-
age is cut off.

Oscillographic fault record-


ing of up to 8 records
(5 seconds maximum)
The “Fault recording” function
is used to record the phase cur-
rents in the event of a power
system fault. Either pickup,
tripping or binary input can be
selected to trigger waveform
capture. The maximum length
of a record can be program-
med. The recorded traces of
the phase and ground currents
and pickup and drop-off of in-
ternal events can be transmit-
ted to a PC for convenient ana- Fig. 6
lysis using DIGRA. Settings
windows

Event logging with time


stamp
The SIPROTEC 7SJ600 relay
supplies detailed data for the
analysis of faults and for check-
ing on operating conditions
• Fault Logs
The last 8 fault record logs
can always be displayed. If a
new fault occurs, the oldest
will be overwritten. These
logs give a detailed descrip-
tion of the fault in the power
system and the reaction of
the SIPROTEC 7SJ600, with
1ms resolution. Each record
is time stamped and assigned
a sequential number to easily
associate it with the corre-
sponding waveform capture.
• Event Log (operational an-
nunciation) This log records
up to 30 internal events in
the relay with 1ms resoluti-
on. These events include set-
ting changes and resets to
the relay, binary input activity Fig. 7
Analog and
and other relay internal activi- binary traces
ties.

Siemens LSA 2.1.15 ⋅ 1997 3


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Tripping characteristics

Inverse-time characteristics
With regard to the inverse-
time overcurrent protection
function, the tripping time de-
pends on the magnitude of
the current (see Figs. 8 to 19).
The following tripping charac-
teristics are available:
Inverse-time characteristics in
accordance with ANSI/IEEE:
• inverse
• short inverse
• long inverse
• moderately inverse
• very inverse
• extremely inverse
• definite inverse
• I squared T ç
Fig. 8
Inverse

è
Fig. 9
Short inverse

F 8.9341 I F 0.2663 I
t= GG 2.0938 + 0.17966JJ ⋅ D t= GG 12969 + 0.03393JJ ⋅ D
H e I Ip j − 1 K H e pj K
.
I I − 1

• t = tripping time in s
• I = measured current
• Ip = parameterizable
threshold value
0.1 to 4 I/IN
• D = time multiplier

ç
Fig. 10
Long inverse

Note for Figs. 8, 10, 13 to 15:


è
Fig. 11
Equations valid from Moderately inverse
1.1 to 20 for I/Ip

F 5.6143 I F 0.0103 I
t =G JJ ⋅ D GG 0.02 + 0.0228JJ ⋅ D
GH e I I j − 1
p
+ 218592
.
K
t=
H e I Ip j − 1 K

4 Siemens LSA 2.1.15 ⋅ 1997


ç
Fig. 12
Very inverse

è
Fig. 13
Extremely inverse

F 3.922 I F 5.64 I
t= GG 2 + 0.0982JJ ⋅ D t= GG 2 + 0.02434JJ ⋅ D
H e I Ip j − 1 K H e I Ip j − 1 K

ç
Fig. 14
Definite inverse

è
Fig. 15
I squared T

F 0.4797 I
t= GG 15625 + 0.21359JJ ⋅ D t=
50.7 ⋅ D + 1014
.
eH I Ip j . − 1 K eI I j
p
2

Siemens LSA 2.1.15 ⋅ 1997 5


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Tripping characteristics

Inverse-time characteristics
(51, 51N)
Characteristics of the inverse-
time overcurrent curves in ac-
cordance with IEC 255-3:

• inverse
• very inverse
• extremely inverse
• long inverse

ç
• t = tripping time in s Fig. 16
Inverse
• I = measured current
• Ip = pickup value 0.1 to 4 I/IN
• Tp = time multiplier è
Fig. 17
Very inverse

0.14 13.5
t= ⋅Tp t= ⋅Tp
e I Ip j 0.02
e j
I Ip − 1

ç
Fig. 18
Extremely
inverse

Note for Figs. 16 to 19: è


Equations valid from 1.1 to 20 Fig. 19
for I/Ip Long inverse

80 120
t= ⋅Tp t= ⋅Tp
e I Ip j
2
−1 e j
I Ip − 1

6 Siemens LSA 2.1.15 ⋅ 1997


Definite-time characteristics
The definite-time overcurrent
Delay
function is based on phase-se-
lective measurement of the
three phase currents.
The earth (ground) current IE
(Gnd) is calculated from the
three line currents IL1 (A),
IL2 (B), and IL3 (C). Alternatively,
IE (Gnd) can be connected to
the relay in place of IL2 (B) and
the relay will then calculate
IL2 (B).
The definite-time overcurrent
protection for the 3 phase cur-
rents has a low-set overcur-
rent element (I>), a high-set
overcurrent element (I>>) and Fig. 20
an instantaneous-tripping ele- Definite-time
ment (I>>>). Intentional trip overcurrent characteristic
delays can be parameterized
from 0.00 to 60.00 seconds for
the low-set and high-set over-
current elements. The instanta-
neous zone I>>> trips without
any intentional delay.
Tripping characteristic
The definite-time overcurrent
protection for the earth
(ground) current has a low-set
overcurrent element (I>), and
a high-set overcurrent element
(I>>). Intentional trip delays
can be parameterized from Fig. 21
0.00 to 60.00 seconds. Characteristic of the
negative sequence
protection function
Negative sequence overcur-
rent protection (I2>>, I2>/ 46
Unbalanced-load
protection)
The negative sequence over-
current protection has the task IStart = start-up current
of detecting a phase interrup- of the motor
t
tion or unbalanced load. IStart max = maximum per-
missible starting
This function is especially use- time
ful for motors since negative Ipick-up = pick-up setting of
sequence currents cause im- function
permissible overheating of the
rotor.
Furthermore, low level single-
phase and two-phase short-cir-
tStart max
cuits (such as faults beyond a
transformer) as well as phase Fig. 22
interruptions can be detected. Characteristic of
• I2 = negative phase- start-up monitor Ipick-up IStart I
sequence current
• TI2 = tripping time

Locked-rotor protection The tripping time depends on where


The start-up monitor protects the current. It is determined in • tTRIP = tripping time
the motor against excessively accordance with the following
• IStart = start-up current
long start-ing. This can occur, equation:
F I I ⋅t
of the motor
for example, if the rotor is blok-
ked, if excessive voltage dips
occur when the motor is swit-
tTRIP = GH I JK
Start

rms
Startmax
• TStartmax = maximum
permissible
starting time
ched on or if excessive load tor-
• Irms = actual current
ques occur.
flowing

Siemens LSA 2.1.15 ⋅ 1997 7


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Tripping characteristics

Thermal overload protection


(49)
The thermal overload protec-
tion func-tion provides tripping
or alarm-ing based on a ther-
mal model calculated from
phase currents.
Thermal overload protection
without preload
For thermal overload protec-
tion without consideration of
the preload current, the follow-
ing tripping characteristic app-
lies only when
I ≥ 1.1 ⋅ IL
For different thermal time con-
stants TL, the tripping time t is
calculated in accordance with
the following equation:

35
t= ⋅TL
FII 2

GH I JK
L
−1

The reset threshold is above


1.03125 ⋅ I/IN
Fig. 23
Thermal overload protection Tripping characteristics
with preload of thermal overload
for complete memory
The thermal overload protec- without previous load and
tion with consideration of pre- at 90 % of previous load
load current constantly upda-
tes the thermal model calcula-
tion regardless of the
magnitude of the phase cur-
rents. The tripping time t is
calculated in accordance with
the following tripping charac-
teristic (complete memory in
accordance with IEC 255-8).

F I I 2 − F Ipre I 2
GH k ⋅ IN JK GH k ⋅ IN JK
t = t ⋅ ln
F I I2 −1
GH k ⋅ IN JK
• t = tripping time after
beginning of the thermal
overload
• τ = 35.5 x TL
• Ipre = pre-load current
• TL = time multiplier
• I = overload current
• k = k factor (in accordance
with IEC 255-8)
• ln = natural logarithm
(See Fig. 23)

8 Siemens LSA 2.1.15 ⋅ 1997


Applications

3-pole multishot automatic


reclosing (AR, 79)
(see Fig. 25) (optional)
Automatic reclosing (AR) en-
ables 3-phase auto-reclosing of
a feeder which has previously Recloser
been disconnected by time-
overcurrent protection
(I>, I>>, I>>>, Ip, IE>, IE>>, Busbar
IEp/50, 51, 50N, 51N).
The SIPROTEC 7SJ600 allows Trip
up to 9 reclosing shots. The
first four dead times can be
set individually. Reclosing can
be blocked or initiated by a bi-
nary input or internally. After
the first trip in a reclosing se-
quence, the high-set instanta- Recloser
neous elements (I>>>, I>>,
IE>>) are blocked. This is used Fig. 24
for fuse saving applications Feeder protection Typical feeder
and other similar transient
schemes using simple overcur-
rent relays instead of fuses.
The low-set definite-time
(I>, IE>) and the inverse-time These elements trip These elements trip
Busbar faster than the fuses. slower than the fuses.
(Ip, IEp) overcurrent elements They are blocked after They allow the fuse to blow
remain operative during the en- the first reclosing cycle after the first reclosing cycle
tire sequence. Trip

Recloser

Typical feeder

Fig. 25 Fuse is saved during arcing faults, but


Automatic reclosing blows after the first unsuccesful reclosing
with fuse saving scheme cycle to clear permanent faults

Busbar

Trip Transformer stand-by protection

Typical feeder
Fig. 26
Transformer Unbalanced
backup protection faults

Siemens LSA 2.1.15 ⋅ 1997 9


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Applications

Cold load pickup (see Fig. 28)


By means of a binary input
which can be wired from a ma-
nual close contact, it is possi- Busbar
ble to switch the overcurrent
pickup settings to less sensi- Trip
tive settings for a program-
mable amount of time. After
the set time has expired, the
pickup settings automatically
return to their original setting.
This can compensate for initial
inrush when energizing a cir-
cuit without compromising the Typical feeder
sensitivity of the overcurrent
elements during steady state
conditions.

Left/Right rotation (5144 > rev PhR)


Fig. 27
Motor protection

Trip

Binary input
(1727 > c/o)
Trip
Desensetize during inrush

Busbar

Trip

Typical feeder

Binary
input
(1727 > c/o)
Fig. 28
Cold load pickup
(Timer controlled
setting group)

Busbar

Trip (high speed dead fault clearance)

Feeder grounded

Fig. 29 Manual close


Switch-onto-fault (356 > m close) 200 ms
protection Typical feeder

10 Siemens LSA 2.1.15 ⋅ 1997


Applications

Busbar protection
(Reverse interlocking)
Reverse interlock principle in-
volves the blocking of the high-
speed overcurrent protection Clears faults Backup for
on the supply feeder, to the at the busbar feeder relays
TI>> = 50 msec TI> = 300 msec
auxiliary bus, if any of the load Power flow
feeder overcurrent relays are
in pickup. If a fault is not pre-
sent on any of the associated
load feeders, the supply’s high- Block 50, I>>, I>>> elements
speed overcurrent protection Bus relay 1 trips for
will not be blocked, providing faults on location A
reliable protection for bus 7SJ600
Busbar
faults. Relay 1 Feeder relays
In this manner, selective high- t1 = 0 msec
speed overcurrent relaying can
be applied to the supply and
load feeders to provide coordi- Feeder relay 2 will not trip
for faults on location B
nated bus protection. The re-
lays, through contact input and Pickup
output interconnection, can dis-
criminate and operate selec-
tively for various types of
faults and locations, tripping 7SJ600
only the affected parts of the Typical feeder Relay 2 Feeder relays
system. t1 = 0 msec

Feeder relay 3 trips for


Trip circuit monitor faults on location B while
(see Fig. 31) blocking bus relay 1
One or two binary inputs can Pickup
be used for the trip circuit mon-
itoring.
7SJ600
Relay 3

Fig. 30
Busbar protection
(Reserve interlocking)

VCV

Trip
Bl 1 circuit
7SJ600 faulty
or any TCo
protective
relay

R
CLOSE TRIP

Aux 1 Aux 2 TCo Trip contact of the 7SJ600s


52a 52b
BI Binary input of the 7SJ600
TC TC Trip coil
CB
Aux Circuit-breaker auxiliary
52 contact
R Equivalent resistor
Vcv Control voltage
CB Circuit-breaker

Fig. 31
Trip-circuit monitor
with one binary input1)

1) Example with 2 binary inputs,


see manual for the 7SJ600.

Siemens LSA 2.1.15 ⋅ 1997 11


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Typical schematic diagrams

AC schematics
(optional connections)
• measured
IL1 (A), IL3 (C), IE (Gnd)
• calculated
IL2 (B)

Fig. 32
Three CT circuit with
measurement of the earth
(ground) current

• measured
IL1 (A), IL2 (B), IL3 (C)

Fig. 33
Two CT circuit only for
isolated or
resonant-earthed
(grounded) power systems

Fig. 34
Sensitive earth-fault
protection
(three times increased
sensitivity)

12 Siemens LSA 2.1.15 ⋅ 1997


AC schematics
(standard connection)
• measured
IL1 (A), IL2 (B), IL3 (C)
• calculated
IE (Gnd)

Fig. 35
Three CT circuit with
measurement of the
phase currents

Fig. 36
Serial port

DC schematics

Power-
supply
BI1 BI2 BI3

LED* Trip
Reset I>> Alarm*
Other Manual*
protecti- Close
on

Fig. 37
DC schematics

* Factory settings

Siemens LSA 2.1.15 ⋅ 1997 13


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Scope of functions

Multiple applications
• Feeder protection, overhead
line cable protection CLOSE
• Motor protection (overload
and short-circuit protection) TRIP
• Transformer protection (main
or backup protection, over-
load protection) Phase Earth (ground)
• Generator protection (backup
protection) AR
• Busbar protection (reverse 50HS
interlocking)
Cost effective 50(51) 50N(51N)
• Less wiring: one relay - many

Further 7SJ600 units


functions 51(50) 51N(50N)
• Reliable and available, inter-
nal hardware and software
monitoring, current transfor-
mer monitoring, trip-circuit 51 51N
monitoring
• Reduced testing due to self Over- 49
diagnostics and numerical load
technology
• “Easy” commissioning
• Simplified parameterization
and fault analysis using Win- Serial RS485 port
dows-based DIGSI program
• Remote communication (via
modem)
Additional functions
• Protection
− automatic reclosing
(AR, 79) or PC
− cold load pickup
− trip circuit monitoring
• Metering functions or
PC
− currents
− thermal model (49)
• Fault recording
− status indications
− event log
− fault log records
− waveform capture/fault ana-
lysis
Parallel running functions
Overcurrent protection
• Definite-time overcurrent pro-
tection (up to three zones)
− phase currents IL1 (A), IL2
(B), IL3 (C)
I>>>, I>>, I> (50)
− earth (ground) current IE
(Gnd) (50N) IE>>, IE>
• Inverse-time overcurrent pro-
tection (51, 51N)
− IEC
inverse
very inverse
extremely inverse
long inverse Fig. 38
Scope of functions *Automatic reclosing (AR, 79) (optional)
− ANSI/IEEE
inverse
long inverse − I squared T • Negative sequence overcurrent pro-
moderately inverse tection (46, unbalanced load) (2 zones)
very inverse − phase currents IL1 (A), IL2 (B), IL3 (C) Ip
• Thermal overload protection (49)
extremely inverse − earth (ground) current IE, IEp
• Locked-rotor protection

14 Siemens LSA 2.1.15 ⋅ 1997


Technical Data

CT circuits Rated current IN 1 A or 5 A


Rated frequency fN 50 Hz/60 Hz (selectable)
Overload capability current path
Thermal (rms) 100 x IN for ≤ 1s
30 x IN for ≤ 10s
4 x IN continuous
Dynamic (pulse current) 250 x IN one half cycle
Power consumption
Current input at IN = 1 A < 0.1 VA
at IN = 5 A < 0.2 VA
Power supply via integrated Rated auxiliary voltage Vaux /permissible variations 24/48 V DC/19 to 58 V DC
DC/DC converter 60/110/125 V DC/48 to 150 V DC
220/250 V DC/176 to 300 V DC
115 V AC/88 to 133 V AC
230 V AC/176 to 265 V AC
Superimposed AC voltage,
peak to peak
at rated voltage ≤ 12%
at limits of admissible voltage ≤ 6%
Power consumption
Quiescent Approx. 2 W
Energized Approx. 4 W
Bridging time during failure/
short-circuit of auxiliary voltage ≥ 50 ms at Vaux ≥ 110 V DC
≥ 20 ms at Vaux ≥ 24 V DC
Binary inputs Number 3 (marshallable)
Operating voltage 24 to 250 V DC
Current consumption, independent of Approx. 2.5 mA
operating voltage
Pick-up threshold, reconnectable by
solder bridges
Rated aux. voltage
24/48/60 V DC Vpick-up ≥ 17 V DC
Vdrop-off < 8 V DC
110/125/220/250 V DC Vpick-up ≥ 74 V DC
Vdrop-off < 45 V DC
Signal contacts Signal/alarm relays 2 (marshallable)
Contacts per relay 1 CO
Switching capacity
Make 1000 W / VA
Break 30 W / VA
Switching voltage 250 V
Permissible current 5A
Heavy-duty (command) contacts Trip relays, number 2
Contacts per relay 2 NO
Switching capacity
Make 1000 W / VA
Break 30 W / VA
Switching voltage 250 V
Permissible current
Continuous 5A
For 0.5s 30 A
Serial interface, isolated Standard RS485
Test voltage 2.8 kV DC for 1 min
Connection Data cable at housing terminals, two data
wires, one frame reference, for connection of
a personal computer or similar; core pairs with
individual and common screening, screen
must be earthed (grounded), communication
possible via modem
Transmission speed As delivered 9600 Baud
min. 1200 Baud,
max. 19200 Baud

Siemens LSA 2.1.15 ⋅ 1997 15


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Technical Data

Design Housing 7XP20 For dimensions refer to dimension drawings


Weight
Flush mounting /cubicle mounting Approx. 4 kg
Surface mounting Approx. 4.5 kg
Degree of protection acc. to EN 60529
Housing IP51
Terminals IP21
Insulation tests Standards IEC 255-5, ANSI/IEEE C37.90.0
High-voltage test (routine test)
Except DC voltage supply input and RS485 2 kV (rms), 50 Hz
Only DC voltage supply input and RS485 2.8 kV DC
Impulse voltage test (type test) 5 kV ( peak), 1.2/50 µs,
all circuits, class III 0.5 J, 3 positive and 3 negative shots at
intervals of 5 s
EMC tests, immunity Standards IEC 255-6; IEC 255-22 (product standard)
(type tests) EN 50082-2 (generic standard),
DIN VDE 0435 Part 303
High-frequency test 2.5 kV (peak), 1 MHz, τ=15 µs,
IEC 255-22-1 class III 400 shots/s, duration 2 s
Electrostatic discharge IEC 255-22-2 class III 4 kV/6 kV contact discharge,
and EN 61000-4-2 class III 8 kV air discharge, both polarities,
150 pF, Ri=330 Ω
Radio-frequency electromagnetic field
Non-modulated, IEC 255-22-3 (report) class III 10 V/m, 27 to 500 MHz
Amplitude modulated, IEC 1000-4-3, class III 10 V/m, 80 to 1000 MHz,
80% AM, 1 kHz
Pulse modulated, IEC1000-4-3 10 V/m, 900 MHz, repetition frequency
class III 200 Hz, duty cycle 50%
Fast transients 2 kV, 5/50 ns, 5 kHz, burst length 15 ms,
IEC 255-22-4 and IEC 1000-4-4, class III repetition rate 300 ms, both polarities,
Ri = 50Ω, duration 1 min
Conducted disturbances induced by radio-frequency fields, 10 V, 150 kHz to 80 MHz,
amplitude modulated IEC 1000-4-6, class III 80% AM, 1 kHz
Power frequency magnetic field 30 A/m continuous, 50 Hz
IEC 1000-4-8, class IV 300 A/m for 3 s, 50 Hz
IEC 255-6 0.5 mT; 50 Hz
Oscillatory surge withstand capability ANSI/IEEE C37.90.1 2.5 kV to 3 kV (peak), 1 MHz to 1.5 MHz,
(common mode) decaying oscillation,50 shots per s,
duration 2 s, Ri = 150 Ω to 200 Ω
Fast transient surge withstand capability 4 kV to 5 kV, 10/150 ns, 50 shots per s, both
ANSI/IEEE C37.90.1 (commom mode) polarities, duration 2 s, Ri = 80 Ω
Radiated electromagnetic interference 10 to 20 V/m, 25 to 1000 MHz,
ANSI/IEEE C37.90.2 amplitude and pulse modulated
High-frequency test 2.5 kV (peak, alternating polarity), 100 kHz,
Document 17C (SEC) 102 1 MHz, 10 MHz and 50 MHz,
decaying oscillation,Ri = 50 Ω
EMC tests, emission Standard EN 50081-* (generic standard)
(type tests) Conducted interference voltage, aux. voltage 150 kHz to 30 MHz
CISPR 22, EN 55022, DIN VDE 0878 Part 22,
limit value class B
Interference field strength CISPR 11, 30 to 1000 MHz
EN 55011, DIN VDE 0875 Part 11, limit value class A
Climatic stress tests Recommended temperature
during service - 5° C to + 55° C (25° F to 131° F),
> 55° C decreased display contrast
Permissible temperature
during service - 20° C to + 70° C (- 4° F to 158° F)
during storage - 25° C to + 55° C (-13° F to 131° F)
during transport - 25° C to + 70° C (- 13° F to 158° F)
(Storage and transport with standard works packaging)
Permissible humidity Mean value per year ≤ 75% relative humidity,
on 30 days per year 95%relative humidity,
condensation not permissible

16 Siemens LSA 2.1.15 ⋅ 1997


Mechanical stress tests Standards Acc. to IEC 255-21and IEC 68-2
Vibration and shock during Vibration Sinusoidal 10 to 60 Hz: ± 0.035 mm amplitude,
operation IEC 255-21-1, class1 60 to 150 Hz: 0.5 g acceleration
IEC 68-2-6 Sweep rate 1 octave/min
20 cycles in 3 orthogonal axes
Shock Half sine, acceleration 5 g , duration 11 ms,
IEC 255-21-2, class 1 3 shocks in each direction of 3 orthogonal axes
Seismic vibration Sinusoidal
IEC 255-21-3, class 1, 1 to 8Hz: ± 3.5 mm amplitude (horizontal axis)
IEC 68-3-3 1 to 8 Hz: ± 1.5 mm amplitude (vertical axis)
8 to 35 Hz: 1 g acceleration (horizontal axis)
8 to 35 Hz: 0.5 g acceleration (vertical axis)
Sweep rate 1 octave/min
1 cycle in 3 orthogonal axes
Vibration and shock during trans- Vibration Sinusoidal
port IEC 255-21-1, class 2 5 Hz to 8 Hz: ± 7.5 mm amplitude;
IEC 68-2-6 8Hz to 150 Hz: 2 g acceleration
Sweep rate 1 octave/min
20 cycles in 3 orthogonal axes
Shock Half sine, acceleration 15 g ,
IEC 255-21-2, class 1 duration 11 ms,
IEC 68-2-27 3 shocks in each direction of 3 orthogonal axes
Continuous shock Half sine, acceleration 10 g
IEC 255-21-2, class 1 duration 16 ms, 1000 shocks in each direction
IEC 68-2-27 of 3 orthogonal axes
Definite-time overcurrent protec- Setting range/steps
tion (50, 50N) Overcurrent pick-up phase I> I/IN = 0.1 to 25.0 (steps 0.1), or ∞
earth IE> = 0.1 to 25.0 (steps 0.1), or ∞
phase I>> I/IN = 0.1 to 25.0 (steps 0.1, or ∞
earth IE>> = 0.1 to 25.0 (steps 0.1), or ∞
phase I>>> I/IN = 0.3 to 12.5 (steps 0.1, or ∞
Delay times T for I>, IE>, I>> and IE>> 0.00 s to 60.00 s (steps 0.01 s)
The set times are pure delay times
Pick-up times
I>, I>>, IE>, IE>>
at 2 x setting value, without meas. repetition Approx. 35 ms
at 2 x setting value, with meas. repetition Approx. 55 ms
pick-up times for I>>> at 2 x setting value Approx. 20 ms
Reset times
I>, I>>, I>>>, IE>, IE>> Approx. 65 ms at 50 Hz
Approx. 95 ms at 60 Hz
Reset ratios Approx. 0.95
Overshot time Approx. 55 ms
Tolerances
Pick-up values I>, I>>, I>>>, IE>, IE>> 5% of setting value
Delay times T 1% of setting value or 10 ms
Influence variables
Auxiliary voltage in range 0.8 ≤ Vaux /VauxN ≤ 1.2 ≤1%
Temperature in range 0° C ≤ Θamb ≤ 40° C ≤ 0.5 %/10 K
(32° F ≤ Θamb ≤ 104° F)
Frequency in range 0.98 ≤ f/fN ≤ 1.02 ≤ 1.5 %
Frequency in range 0.95 ≤ f/fN ≤ 1.05 ≤ 2.5 %
Harmonics
up to 10% of 3rd harmonic ≤1%
up to 10% of 5th harmonic ≤1%
Inverse-time overcurrent protec- Setting range/steps
tion (51/51N) Overcurrent pick-up phase Ip I/IN = 0.1 to 4.0 (steps 0.1)
earth IEp = 0.1 to 4.0 (steps 0.1)
Time multiplier for Ip, IEp Tp (IEC charac.) 0.05 to 3.20 s
D (ANSI charac.) 0.5 to 15.0 s
Overcurrent pick-up phase I>> I/IN = 0.1 to 25.0 (steps 0.1), or ∞
phase I>>> =0.3 to 12.5 (steps 0.1), or ∞
Delay time T for I>>, IE>> 0.00 s to 60.00 s
Pick-up threshold Approx. 1.1 x Ip
Drop-off threshold Approx. 1.03 x Ip
Drop-off time Approx. 50 ms at 50 Hz
Approx. 60 ms at 60 Hz
Tolerances
Pick-up values 5%
Delay time for 1 ≤ I/Ip ≤ 20 and 5 % of theoretical value
0.5 ≤ I/IN ≤ 24 ± 2 % current tolerance;
at least 30 ms

Siemens LSA 2.1.15 ⋅ 1997 17


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Technical Data

Inverse-time overcurrent protec- Influence variables


tion (51/51N) (cont’ d) Auxiliary voltage in range
0.8 ≤ Vaux/VauxN ≤ 1.2 ≤1%
Temperature in range
-5° C ≤ Θamb ≤ 40° C ≤ 0.5 %/10 K
-32° F ≤ Θamb ≤ 104° F
Frequency in range
0.95 ≤ f/fN ≤ 1.05 ≤ 8 % referred to theoretical time value
Negative sequence overcurrent Setting range/steps
protection (46) Tripping stage I2> in steps of 1% 8 % to 80 % of IN
I2>> in steps of 1% 8 % to 80 % of IN
Time delays T(I2>), T(I2>>) in steps of 0.01s) 0.00 s to 60.00 s
Lower function limit at least one phase current ≥ 0.1 x IN
Pick-up times
Tripping stage I2>, tripping stage I2>> at fN = 50 Hz 60 Hz
but with currents I/IN>1.5 (overcurrent case) approx. 60 ms 75 ms
or negative-sequence current < (set value +0.1 x IN) approx. 200 ms 310 ms
Reset times at fN = 50 Hz 60 Hz
Tripping stage I2>, tripping stage I2>> approx. 35 ms 42 ms
Reset ratios
Tripping stage I2>, tripping stage I2>> Approx. 0.95 to 0.01 x IN
Tolerances
Pick-up values I2>, I2>> current I/IN ≤ 1.5 ± 1 % of IN ± 5 % of set value
current I/IN > 1.5 ± 5 % of IN ± 5 % of set value
Stage delay times ± 1 % but min. 10 ms
Influence variables
Auxiliary DC voltage in range
0.8 ≤Vaux /VauxN ≤ 1.2 ≤1%
Temperature in range -
-5° C ≤ Θamb ≤ +40° C ≤ 0.5%/10K
-32° F ≤ Θamb ≤ +104° F
Frequency
in range 0.98 ≤ f/fN ≤ 1.02 ≤ 1% of IN
in range 0.95 ≤ f/fN ≤ 1.05 ≤ 5% of IN
Auto-reclosing (option) Number of possible shots 1 up to 9
(79) Auto-reclose modes 3-pole
Dead times for 1st to 3rd shot 0.05 s to 1800.00 s (steps 0.01 s)
for 4th and any further shot 0.05 s to 1800.00 s (steps 0.01 s)
Reclaim time after successful AR 0.05 s to 320.00 s (steps 0.01 s)
Lock-out time after unsuccessful AR 0.05 s to 320.00 s (steps 0.01 s)
Reclaim time after manual close 0.50 s to 320.00 s (steps 0.01 s)
Duration of RECLOSE command 0.01s to 60.00 s (steps 0.01 s)
Thermal overload protection with Setting ranges
memory (49) Factor k according to IEC 255-8 0.40 to 2.00 (steps 0.01)
(total memory according to IEC 255-8) Thermal time constant τth 1.0 to 999.9 min (steps 0.1 min)
Thermal warning stage Θalarm/Θtrip 50 to 99% referred to trip temperature rise
(steps 1%)
Prolongation factor at motor stand-still kτ 1.00 to 10.00 (steps 0.01)

Trip time characteristic see page 8


Reset ratios
Θ/Θtrip Reset below 0.99 Θalarm
Θ/Θalarm Approx. 0.99
Tolerances
referring to k ⋅ IN ± 5 % (class 5 % acc. to IEC 255-8)
referring to trip time ± 5 % ± 2 s (class 5 % acc. to IEC 255-8)
Influence variables referred to k ⋅ IN
Auxiliary DC voltage in the range of ≤1%
0.8 < Vaux / VauxN < 1.2
Temperature in the range of ≤ 0.5 % / 10 K
-5° C < Θamb < +40° C
-32°F≤ Θamb ≤ +104° F
Frequency in the range of 0.95 < f / fN < 1.05 ≤1%

18 Siemens LSA 2.1.15 ⋅ 1997


Thermal overload protection Pick-up value IL / IN 0.4 to 4.0 (steps 0.1)
(cont’d) without memory Time multiplier tL (= t6 -time) 1.0 to 120.0 s (steps 0,1 s)
Tripping characteristic see page 8
Reset ratio I/IL Approx. 0.94
Tolerances
referring to pick-up threshold 1.1 IL ± 5%
referring to trip time ± 5% ± 2 s
Influence variables
Auxiliary DC voltage in the range of 0.8 < Vaux / VauxN < 1.2 <1%
Temperature in the range of -5° C < Θamb < +40° C < 0.5 %/10 K
Frequency in the range of 0.95 < f/fN < 1.05 <1%
Start-up monitor Setting ranges
Motor protection Permissible start-up current IStart / IN 0.4 to 20.0 (steps 0.1)
Permissible start-up time tStart 1.0 to 360.0 s (steps 0.1 s)

FI I 2

Tripping characteristic t= GH I JK
Start

rms
⋅t for Irms > IStart

Reset ratio Irms / IStart Approx. 0.94


Tolerances
Pick-up value 5%
Delay time 5% of setting value or 330 ms
Fault recording Measured values IL1, IL2, IL3
Start signal Trip, start release, binary input
Recording duration 5000 ms
Additional functions Operational value measurements
Operational current values IL1, IL2, IL3
Measurement range 0% to 240% IN
Tolerance 3% of rated value
Thermal overload values
Calculated temperature rise Θ/Θtrip
Measurement range 0% to 300%
Tolerance 5% referred to Θtrip
Fault event data storage Storage of annunciations of the last 3 faults
Time assignment
Resolution for operational annunciations 1s
Resolution for fault event annunciations 1 ms
Max. time deviation 0.01 %
Data storage for fault recording max. 8 fault events
Total storage time (fault detection or trip command = 0 ms) max. 5 s, selectable pre-trigger and
post-fault time
Max. storage period per fault event Tmax 0.30 to 5.00 s (steps 0.01 s)
Pre-trigger time Tpre 0.05 to 0.50 s (steps 0.01s)
Post-fault time Tpost 0.05 to 0.50 s (steps 0.01 s)
Sampling rate 1 instantaneous value per ms at 50 Hz
1 instantaneous value per 0.83 ms at 60 Hz
Trip circuit monitor with one or two binary inputs
Circuit-breaker trip test with live trip or trip/reclose cycle
(models with auto-reclose)
CE conformity, regulations The product meets the stipulations of the guideline of the council
of the European Communities for harmonization of the legal
requirements of the member states on electro-magnetic
compatibility (EMC guideline 89/336/EEC).
The product conforms with the international standard of the
IEC 255 series and the German national standard
DIN VDE 57 435,Part 303.The unit has been developed and
manufactured for use in industrial areas in accordance with the
EMC standard. The unit has not been designed for use in living
quarters as defined in standard EN 50081.
This conformity is the result of a test that was performed by
Siemens AG in accordance with article 10 of the guideline and
the EN 50081-2 and EN 50082-2 basic specifications.

Siemens LSA 2.1.15 ⋅ 1997 19


SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Selection and ordering data

Designation Order No.

7SJ600 numerical overcurrent, motor and overload relay 7SJ600


▲ ▲ ▲
¨ – ▲¨ ¨ A▲¨0 – ¨ DA0
Binary input voltage 24 to 250 V DC
with isolated RS485 port
Rated current at 50/60 Hz
1A 1
5A 5

Rated power supply voltage


24, 48 V DC 2
60, 110, 125 V DC 4
220, 250 V DC, 115 V AC 5
230 V AC 6

Housing
Surface mounting B
Flush mounting/cubicle mounting E

Languages
English, German, Spanish, French 0

Auto-reclosing (option)
without 0
with 1

Accessories
Communication cable (copper)
between PC (9-pole socket) and converter/protection device 7XV5100- 2

Converter V.24 - RS485


with communication cable for the 7SJ600
numerical overcurrent, Motor and overload relay
Length 1 m (3 ft)
PC adapter
with power supply unit 230 V AC 7XV5700 - 0AA00
with power supply unit 110 V AC 7XV5700 - 1AA00

Converter full-duplex
Fibre-optic cable - RS485 7XV5600 - 0AA00
with built-in power supply unit
Auxiliary voltage 24 to 250 V DC and 110/230 V AC

Manual 7SJ600
German C53000 - G1100 - C106-3
English - G1176 - C106-2
French - G1177 - C106-1
Spanish - G1178 - C106-1

1)
DIGSI-LIGHT protection software
Parameterizing and operating software for the 7SJ600
protection unit without graphical evaluation program
Requirements: MS WINDOWS 3.1 or higher
German 7XS5120 - 0AA0
English - 1AA0
French - 2AA0
Spanish - 4AA0

1)
DIGRA graphical evaluation program for DIGSI-LIGHT
For visualization of fault recording, in conjunction
with DIGSI-LIGHT protection software for 7SJ600
Requirements:
MS WINDOWS 3.1 or higher
In addition we offer: German 7XS5130 - 0AA0
SIPROTEC 7SJ601 English - 1AA0
(Reduced version of the SIPROTEC
7SJ600 protection device) French - 2AA0
See Catalog LSA 2.1.16 Spanish - 4AA0
Order No.:
E50001-K5712-A261-A1-7600
Sample order
7SJ6001-4EA00-1DA0 7SJ600 1A, 60-125V,
1) Contained in the full version of flush mounting, ARC
DIGSI
German 7XS5020-0AA00 7XV5700-0AA00 Converter RS485-RS232
English 7XS5020-1AA00 C53000-G1176-C106 Manual, English
French 7XS5020-2AA00 7XS5120-1AA0 DIGSI Light English
Italian 7XS5020-3AA00
Spanish 7XS5020-4AA00

20 Siemens LSA 2.1.15 ⋅ 1997


Version for surface-mounting

Fig. 39
Version for flush / cubicle mounting

Trip relay
Circuit diagram

Tripping of def.-time overcur. prot. I>> (phases)


(grounded)
(grounded) K1: Tripping of def.-time overcur. prot. I> (phases)

INPUT K2: Tripping of def.-time overcur. prot. I> (ground)


Reset LED displays

connection circuit diagram for the 7SJ600


-BI1

numerical overcurrent, motor and overload relay


Block time overcurrent protection
-BI2

ALARM contacts
Manual Close
M1: Ready (“Life-contact”)
-BI3

Power supply
M2: Pickup

Siemens LSA 2.1.15 ⋅ 1997


21
SIPROTEC 7SJ600 (Version V2.1)
Numerical Overcurrent, Motor and Overload Relay
Terminals

Wire size Fittings Order No. Order No.


(manufacturer) (Siemens)
Contacts 1 to 6
Ring-cable lugs Crimp spring contacts1) from Grote & Hartmann (type DFK 2)
d1 = 6 mm (0.24 in) 0,5 to 1 mm2 3000 units 26456.331.042 W53073-A2508-C1
one-sided locating spring
Wmax. = 13 mm (0.51 in) 1,5 to 2,5 mm2 2500 units 26457.331.042 W53073-A2509-C1
one-sided locating spring
Wire size
2,7 to 6,6 mm2 2,5 to 4 mm2 2000 units 26473.331.042 W53073-A2510-C1
(AWG 12 to 10) double-sided locating spring
Contacts 7 to 31
Ring-cable lugs Crimp spring contacts1) from Weidmüller
d1 = 4 mm (0.2 in) 0,5 to 1mm 2 3000 units 162 552 W73073-A2502-C1
1,5 to 2,5 mm2 2500 units 162 550 W73073-A2503-C1
Wmax. = 9 mm (0.36 in)

Wire size
1 to 2,6 mm2
(AWG 16 to 14)
1) Only for panel mounting

22 Siemens LSA 2.1.15 ⋅ 1997


Dimension drawings in mm (inch)

For panel surface mounting, terminals on the side (7XP20 housing)

Terminal for
earth (ground)

Side
Front view
view

“A” View

For flush mounting, terminals on the rear (7XP20 housing)

Assembly plate

∅5 (0.2)

Terminal

Side View from


view the rear

Panel cutout

Siemens LSA 2.1.15 ⋅ 1997 23


Catalog Index

Catalog Index of the Power Transmission Distribution Group

Title Designation Order No.

Measurement and Recording Systems


Fault Recorder OSCILLOSTORE SR 10.1 E50001-K4010-A101-A1-7600

Numerical Protective Relaying


7SJ41 Definite-Time Overcurrent Protection Relay LSA 2.1.10 E50001-K5712-A201-A2-7600
7SJ511 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.3 E50001-K5712-A131-A3-7600
7SJ512 Numerical Overcurrent-Time Protection (Version V3) LSA 2.1.4 E50001-K5712-A141-A3-7600
7SJ531 Numerical Overcurrent Protection Relay LSA 2.1.9 E50001-K5712-A191-A3-7600
7SJ551 Multi-Function Protection Relay LSA 2.4.2 E50001-K5742-A121-A2-7600
7SJ600 SIPROTEC Overcurrent, Motor and Overload Protection LSA 2.1.15 E50001-K5712-A251-A2-7600
7SJ601 SIPROTEC Overcurrent Protection LSA 2.1.16 E50001-K5712-A261-A1-7600
7SA511 Line Protection Relay (Version V3) LSA 2.1.11 E50001-K5712-A211-A2-7600
7SA513 Line Protection Relay (Version V3) LSA 2.1.12 E50001-K5712-A221-A1-7600
3VU13 Miniature Circuit-Breaker LSA 2.1.8 E50001-K5712-A181-A1-7600
7SD502 Line Differential Protection with Two Pilot Wires LSA 2.2.1 E50001-K5722-A111-A2-7600
7SD503 Line Differential Protection with Three Pilot Wires LSA 2.2.2 E50001-K5722-A121-A2-7600
7SD511/512 Current Comparison Protection Relay (Version V3)
for Overhead Lines and Cables LSA 2.2.3 E50001-K5722-A131-A2-7600
7UT512/513 Differential Protection Relay (Version V3)
for Transformers, Generators and Motors LSA 2.2.4 E50001-K5722-A141-A2-7600
7SS5 Station Protection LSA 2.2.5 E50001-K5722-A151-A2-7600
Auxiliary Current Transformers 4AM50, 4AM51, 4AM52
and Isolating Transformers 7XR95 LSA 2.2.6 E50001-K5722-A161-A1-7600
7SN71 Transient Earth-Fault Relay LSA 2.3.2 E50001-K5732-A121-A1-7600
7VC1637 Earth-Leakage Monitor LSA 2.3.4 E50001-K5732-A141-A1-7600
7UM511 Generator Protection Relay (Version V3) LSA 2.5.2 E50001-K5752-A121-A2-7600
7UM512 Generator Protection Relay (Version V3) LSA 2.5.3 E50001-K5752-A131-A2-7600
7UM515 Generator Protection Relay (Version V3) LSA 2.5.4 E50001-K5752-A141-A2-7600
7VE51 Synchronizing Unit LSA 2.5.7 E50001-K5752-A171-A1-7600
7VK512 Numerical Auto-Reclose/Check-Synchronism Relay LSA 2.7.3 E50001-K5772-A131-A1-7600
Test Switch 7XV72 R 2.20 E50001-K4502-A301-A1-7600
7VP151 Three-Phase Portable Test Set (Omicron CMC56) LSA 2.6.1 E50001-K5762-A111-A2-7600
Centralized and Remote Control of Siemens Protection Relays (Overview)* LSA 2.8.1 E50001-K5782-A111-A1-7600
Operating and Analysis Software DIGSI V3* LSA 2.8.2 E50001-K5782-A121-A1-7600

Substation Control and Protection


Input/Output Unit 6MB522 LSA 1.1.1 E50001-K5701-A111-A4-7600
Input/Output Unit 6MB523 LSA 1.1.2 E50001-K5701-A121-A2-7600
6MB511/6MB512 Substation Master Unit 7SW511/7SW512 Relay Data Concentrator LSA 1.1.3 E50001-K5701-A131-A2-7600
6MB520/6MB521 Input/Output Units LSA 1.1.4 E50001-K5701-A141-A1-7600
6MB513/514 Compact Control Master Unit and Relay Data Concentrator LSA 1.1.6 E50001-K5701-A161-A1-7600
6MB5510 Station Control Unit LSA 1.2.1 E50001-K5701-A211-A2-7600
6MB552 Compact Remote Terminal Unit LSA 1.2.2 E50001-K5701-A221-A1-7600
6MB5530-0 Minicompact Remote Terminal Unit LSA 1.2.3 E50001-K5701-A231-A1-7600
6MB5530-1 Minicompact Remote Terminal Unit for Cable Shield Communication LSA 1.2.4 E50001-K5701-A241-A1-7600
6MB5540 SINAUT LSA COMPACT Remote Terminal Unit LSA 1.2.5 E50001-K5701-A251-A1-7600
6MB5515 Station Control Unit LSA 1.2.6 E50001-K5701-A261-A1-7600
Control in SINAUT LSA Substation Control and Protection LSA 1.4.1 E50001-K5701-A411-A1-7600
Status Indications in SINAUT LSA Substation Control and Protection LSA 1.4.2 E50001-K5701-A421-A1-7600
Analog Values in SINAUT LSA Substation Control and Protection LSA 1.4.3 E50001-K5701-A431-A1-7600
Metering in SINAUT LSA Substation Control and Protection LSA 1.4.4 E50001-K5701-A441-A1-7600
Voltage Control with Input/Output Units 6MB520/6MB521 LSA 1.4.5 E50001-K5701-A451-A1-7600
Network Synchronization with Input/Output Units 6MB520/521 LSA 1.4.6 E50001-K5701-A461-A1-7600
Operation with Two Control Master Units LSA 1.4.7 E50001-K5701-A471-A1-7600
Node Functions in SINAUT LSA Substation Control and Protection LSA 1.4.8 E50001-K5701-A481-A1-7600
System Management with the SINAUT LSA Substation Control and Protection System LSA 1.4.9 E50001-K5701-A491-A1-7600
LSADIAG - Testing and Diagnostics System for SINAUT LSA LSA 1.5.2 E50001-K5701-A521-A1-7600
Substation Control and Protection
LSACONTROL - Control and Monitoring LSA 1.5.3 E50001-K5701-A531-A1-7600
LSAPROCESS - Process Information Analysis LSA 1.5.5 E50001-K5701-A551-A1-7600
LSA 678 Standard Cubicle LSA 1.6.1 E50001-K5701-A611-A1-7600

* Information on additional equipment for 7SJ600/601

Responsible for
Technical contents: Hans Heining-Triebs
Siemens AG, EV S V13, Nürnberg
General editing: Claudia Kühn-Sutiono
Siemens AG EV BK T, Erlangen

24 Siemens LSA 2.1.15 ⋅ 1997


Conditions of Sale and Delivery ⋅ Export Regulations
Trademarks ⋅ Dimensions
Conditions of Sale and Delivery

Subject to the
General Conditions of Supply The technical data, dimensions
and Delivery and weights are subject to
for Products and Services of change unless otherwise stated
the Electrical and Electronic on the individual pages of this
Industry and to any other catalog.
conditions agreed upon with The illustrations are for
the recipients of catalogs. reference only.
We reserve the right to adjust
the prices and shall charge the
price applying on the date of
delivery. En 1.91a

Export Regulations Trademarks Dimensions

In accordance with the present An export licence may how- All product designations used All dimensions in this catalog
provisions of the German Ex- ever be required due to country- are trademarks or product are given in mm (inch).
port List and the US Commercial specific application and final names of Siemens AG or of
Control List, export licences are destination of the products. other
not required for the products Relevant are the export crite- suppliers.
listed in this catalog. ria stated in the delivery note
and in the invoice subject to a
possible export and reexport li-
cence.
Subject to change without no-
tice.

Siemens online!

The Power Transmission and Distri-


bution Group can also be found in
the Internet:
http://www.ev.siemens.de

Order No.: E50001-K5712-A251-A2-7600


Printed in Germany
KG K 0697 6.0 24 EN321542 U0564
Your Siemens representative

Bereich
Energieübertragung und -verteilung
Geschäftsgebiet Sekundärsysteme
Postfach 4806
D-90026 Nürnberg

Siemens Aktiengesellschaft Order No.: E50001-K5712-A251-A2-7600

Vous aimerez peut-être aussi