Académique Documents
Professionnel Documents
Culture Documents
T
he use of DC/AC inverters in distributed generation (DG) II. PRESENTATION OF THE CONTROL SCHEMES
systems, as the “front-end” converters of DG units, is The control scheme of the inverter may be considered as a
gradually becoming the norm. Such inverters, either single cascade of two independent controllers, where the external
or three-phase designs, are almost universally of the voltage- controller of the output power generates the reference currents
source type. Although current and voltage control schemes are to be tracked by the internal current controller, which
possible and implementable, the current control principle is constitutes the pulse generator for the inverter switches. These
generally preferred for its excellent dynamic characteristics two controllers are presented in more detail in the following
and its inherent over-current limitation capabilities. When Subsections II.A and II.B.
current control is used, the inverter output currents are
measured and compared with reference signals, the errors A. Current controller
being used as an input to the PWM modulator, which provides The methods used for pulse generation in a VSI, can be
the inverter switching signals. divided in two major classes, depending of the utilization or
Several methods have been proposed in the literature for the not of a carrier signal (usually a triangular waveform). In this
control of such inverters, ([1]-[5]). The strategies presented in paper, one representative method of each class is selected,
[1] are used for rectifier operation. In [2] and [3] an LCL filter namely the hysteresis current control, as a carrier-less closed-
is proposed for the connection of the inverter to the grid, loop method, and the PI-current control (known also as ramp-
which enhances the performance of the inverter but increases comparison), as a carrier-based current regulator. Block
considerably the complexity of the control scheme. In [4] and diagrams for these methods are shown in Fig. 1.
[5] the control strategies are applied in motor control and The characteristics of the hysteretic current controller,
optimized and sophisticated techniques are presented. shown in Fig. 1(a), are well-known ([4],[5]). Its main
This paper focuses on simple control schemes, suitable for advantage is the simplicity of implementation and its
three-phase voltage-source current-controlled inverters of DG robustness, while a number of important disadvantages also
units, such as small wind turbines, photovoltaics, fuel-cells exist, including: (a) the current is not strictly limited within
etc. the hysteresis band, (b) the switching frequency is not fixed,
increasing excessively for low filter inductance values and
F. N. Gakis and S. A. Papathanassiou are with the School of Electrical and small hysteresis bands and (c) the harmonic spectrum contains
Computer Engineering, National Technical University of Athens (NTUA), 9 subharmonic and interharmonic components (Fig. 2(a)).
Iroon Polytechniou st., 15780 Athens, Greece (e-mail: st@power.ece.ntua.gr).
P_737 2
The problem of the variable switching frequency, related to The regulators used in both methods (hysteresis or PI type)
the absence of a carrier signal, is overcome using the PI regulate the phase currents transformed to a dq0 reference
current control scheme of Fig. 1(b), where the output of the PI frame [8], either the stationary frame (ω = 0) , or the
controllers act as reference signals, compared to the triangular synchronous, rotating at the electrical frequency ωe of the
carrier to determine the switching of the inverter. In this way, terminal voltage. In the latter case, synchronization of the
the switching frequency is fixed (equal to the frequency of the reference frame to the grid voltage is achieved by a suitable
triangular carrier) and as a result, the harmonics in the inverter PLL method. Notably, for a three-wire connection, no zero-
output current appear as sidebands, centered around the sequence component exists in the output currents.
switching frequency and its multiples (Fig. 2(b)). When hysteresis current control is used, the choice of
reference frame is of no practical significance. However,
ω =0 ω =0
id when the PI current control scheme is adopted, the stationary
- reference frame is not preferred, because of the steady-state
+
abc
id* dq
3φ ia amplitude and phase errors introduced by the PI regulators. In
VSI GRID contrast, when currents are transformed to the synchronous
ib
abc dq reference frame, becoming dc signals (under balanced
+
* - ic sinusoidal conditions and perfect synchronization), the PI
iq iq regulators achieve zero steady-state error ([9]).
In general, the PI regulators must provide stable and fast
(a) response characteristics to the system. To assist in the
selection of the regulator parameters and to provide some
ω = ωe insight in the control characteristics of the system, a linearized
id ω = ωe Synchr .
model of the inverter and its controller is used, as shown in
+- dq abc
Fig. 3. G cabc (s ) is the transfer function of the PI regulator in
* ia
i d
3φ
GRID abc coordinates ([9]). k ∆ = υ dc / 2V∆ , where υ dc is the dc
VSI ib dq
abc
+
ic voltage and V∆ the amplitude of the triangular carrier. υ i ,
* -
i q iq υ g are the phase voltages of inverter and grid respectively.
Inherent assumptions in this representation are the following:
(b)
Fig. 1. Block diagram of (a) Hysteresis and (b) PI current control scheme for a (a) the variation of the dc-voltage is negligible and its value is
grid-connected three-phase VSI. sufficiently high to prevent saturation of the current controller,
(b) the inverter control loop dynamics are much slower than
the switching frequency, (c) the electrical system is balanced
and (d) the regulation in each phase is independent of the
other phases.
υg
υi - 1
i *
+ abc
G (s) k∆ +
R f + sL f
c
-
PI regulator VSI Filter
i
(a)
B. Output power and dc voltage controller
The current controller of the previous section ensures that
the output currents track the reference values, generated by an
additional external control loop, which performs the output
power regulation (active and reactive power). Regulating the
active power permits also the implementation of a controller
for the input dc voltage of the inverter.
Two alternative implementations of this concept are shown
in Fig. 4. In both cases an external dc current regulator
(typically a PI controller) is used, which provides either the
(b) current magnitude reference (Fig. 4(a)) or the active output
Fig. 2. Harmonic spectrum of inverter output current for (a) Hysteresis power set point (Fig. 4(b)). There follows the generation of
(hysteresis band ±5%) and (b) PI Current Control (carrier frequency
10 kHz). THD<5% in both methods. the reference currents, which need to be synchronized to the
P_737 3
grid voltage. In Fig. 4(a) this is performed using the measured For the external dc voltage regulator a PI controller is used,
grid voltage as a template sine wave, incorporating a desired but other types are also possible (such as P, PID or Fuzzy). As
phase shift angle φ* , using the following expressions ([10]): in the previous section, the PI regulator parameters are
3 I* υc −υb selected using a linearized model of each system, as shown in
i a* = υ a cos ϕ + sin ϕ * ,
*
∆υ dc
Xk V2 S S
X k ( p .u .) = = N2 k = N (4)
F (s ) Z base V N S N Sk
(a) where SN is the nominal power of inverter and S k is the grid
υ dc ∆i s short circuit power. Therefore current harmonics are reduced
∆υ dc
* ∆P * +
at weak grids, but the resulting voltage distortion will
- Gcdq (s )
+
- increase.
∆υ dc In case of varying grid frequency, the synchronization of
F (s )
the reference frame to the grid voltage will inevitably be
imperfect ([12]) and the dq signals will as low-frequency
(b) (instead of dc) components. However, the PI regulators (Fig.
Fig. 5. Block diagrams of the control systems of Fig. 4.
1(b)) can handle such components and therefore, after the
P_737 4
Fig. 10: Inverter output current and dc voltage response to a step increase of
the input source power (100%).
(a)
(b)
Fig. 9: Harmonic spectra of (a) non-sinusoidal grid voltage with the maximum
values of harmonics according to IEC 61000-3-6 and (b) resulting inverter Fig. 11: Inverter output currents and dc voltage response to a 30%
output current. symmetrical three-phase voltage sag.
Grid Comments
Low THDi. Low order harmonics
strong
absent if VSI in the linear range
The weaker the grid, the more
Balanced weak distorted the PPC voltage and the
Sinusoidal less distorted the output current
No undesirable phase shift,
variable
even if synchronization to
frequency
grid voltage not perfect
Unbalanced Low order harmonics appear in
Nonsinusoidal output current and dc voltage
→ ∆ P = υ dc ∆ i s + i s ∆ υ dc − C υ dc d ∆ υ dc
Power Electronic Converters in Polluted and Variable-Frequency
*
Environments’, IEEE Transactions on Power Systems, Vol. 19, No. 3,
dt August 2004
[13] L. Moran, P. D. Ziogas, G. Joos ‘Design Aspects of Synchronous PWM
→
L
∆ P = υ dc ∆ i s + i s ∆ υ dc − sC υ dc ∆ υ dc
*
Rectifier-Inverter Systems under Unbalanced Input Voltage Conditions’,
→ F (s) = ∆ υ dc 1 (11)
IEEE Transactions on Industry Applications, Vol. 28, No. 6,
= November/December 1992
υ dc ∆ i s − ∆ P *
sC υ dc − i s