EQUIPMENT ID NUMBER(S) EQUIPMENT DESCRIPTION EQPT CODE SYSTEM ID. PLANT NO.
LAYOUT DRAWING NUMBER REV. NO. PURCHASE ORDER NUMBER EC / PMCC / MCC NO.
SCHEDULED INSPECTION DATE & TIME ACTUAL INSPECTION DATE & TIME QUANTITY INSP. MH's SPENT TRAVEL TIME
SAUDI ARAMCO USE ONLY
SAUDI ARAMCO TIP NUMBER SAUDI ARAMCO ACTIVITY NUMBER WORK PERMIT REQUIRED?
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Interior plastering with gypsum plaster or cement plaster shall not be less
than three coats when applied over metal lath or wire fabric lath SAES-M-100
A1
and shall not be less than two coats when applied over concrete or Sec. D
masonry base materials. (1997 UBC, Sec. 2507.1)
Gypsum plaster shall not be applied directly to fiber insulation board and
SAES-M-100
A2 cement plaster shall not be applied directly to gypsum lath, gypsum
Sec. D
masonry, or gypsum plaster. (1997 UBC, Sec. 2507.1)
Two coat gypsum plaster shall be applied so that the first coat is brought
out to grounds and straightened to a true surface, leaving a rough
SAES-M-100
A7 surface for the finish coat and permitted to dry before the finish coat is
Sec. D
applied. The second coat is similarly applied.
(1997 UBC, Sec. 2507.3.2)
The finish coat shall be applied with sufficient pressure to bond, 1.6mm
SAES-M-100
A8 (1/16") minimum thickness after the second base coat has dried.
Sec. D
(1997 UBC, Sec. 2507.3.2)
The first two coats of cement plaster shall be applied as required for
gypsum plaster except that each coat will be allowed 24 hours of moist
curing between coats; Moist curing shall not be required where job and SAES-M-100
A9
weather conditions are favorable to the retention of moisture in the Sec. D
cement plaster for the full 24 hours curing time.
(1997 UBC, Sec. 2507.3.3)
Page 1 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Gypsum Wall Board System Plastering, Finishing and Final
SAIC-M-1039 18-May-05 Civil
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
Exterior cement plaster shall not be less than 3 coats applied over metal
SAES-M-100
A11 lath or wire lath and 2 coats applied over masonry, concrete or gypsum
Sec. D
backing board. (1997 UBC, Sec. 2508.1)
Dash bond coats, when applied, shall be a part of the total cement SAES-M-100
A16
plaster thickness noted on IFC Drawings. (1997 UBC, Sec. 2508.8) Sec. D
B Final Inspection
Interior gypsum wallboard single-layer fire rated assemblies shall have all
SAES-M-100
B1 joints taped and plastered before application of decorative surface
Sec. D
treatments. (1997 UBC, Sec. 2511.5)
The finished plaster shall bring the surface out to the required
SAES-M-100
B5 dimensions, straightened to a true surface as required by the IFC
Sec. D
Drawings. (1997 UBC, Sec. 2507.3.2)
REMARKS:
Page 2 of 4
SAUDI ARAMCO ID/PID - 18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Gypsum Wall Board System Plastering, Finishing and Final
SAIC-M-1039 18-May-05 Civil
Inspection
PROJECT TITLE WBS / BI / JO NUMBER CONTRACTOR / SUBCONTRACTOR
ITEM
ACCEPTANCE CRITERIA REFERENCE PASS FAIL N/A RE-INSP DATE
No.
REFERENCE DOCUMENTS:
1- SAES-M-100 -- Saudi Aramco Building Code, 31 August 2002
2- 1997 UBC -- Uniform Building Code, 01 January 1997
Page 3 of 4
SAUDI ARAMCO ID/PID -18-MAY-05 - REV 0 (Standards Cutoff - August 2004)
SAIC NUMBER DATE APPROVED QR NUMBER
SAUDI ARAMCO INSPECTION CHECKLIST
Gypsum Wall Board System Plastering, Finishing and Final
SAIC-M-1039 18-May-05 CIVIL-
Inspection
Attachment 1
Re-Instatement Punch List Form SATR NUMBER DATE APPROVED DISCIPLINE