Vous êtes sur la page 1sur 6

DESIGN OF EARTHING SYSTEM FOR GRID STATIONS AND

PROBLEMS ASSOCIATED WITH REMEDIAL MEASURES


Prof. Dr. Suhail Aftab Qureshi*, Farhan Mahmood* *

Abstract: The earthing system of a grid station is of the utmost importance, primarily to
ensure electrical safety for persons working within or near the substation and also to limit any
electrical interference with third-party equipment to acceptable values. Adequate forethought
can help prevent unwanted surprises and avoid unnecessary and sometimes retrospective
expenditure to achieve an adequate earth grid impedance value. This paper reviews earthing
practices with special reference to safety and also provides guidance and information
pertinent to safe earthing practices in A.C Grid stations design.

1. Introduction lighting or fault current will choose to flow


down that path in preference to any other
Earthing means a conducting connection, allowing the current to be conducted safely
whether intentional or accidental, by which to and dissipated in the earth. [1,3].
an electric circuit or equipment is
connected to the earth or some conducting 2. Basic Considerations for Design
body of relatively large extent that serves Earthing System
in place of the earth". [1] This is achieved
by electrically connecting the respective Table 1 highlights the possible
parts in an installation to some systems of aspects of designing the earthing system
electrical conductor or electrode placed in
and recommended materials, which are
intimate contact with the soil some
used in earthing design.
distance below the ground level. [6]

The function of an earthing system for an Table:1 Recommended Materials


electrical installation can be split into three Recommended Material
broad bands, BS No
in process
Ingots for cast components
• To limit the potential of any part of
an installation to a pre-determine
value with respect to the general Leaded gun metal BS 1400
mass of earth. Aluminium silicone bronze BS 1400
• To permit the flow of current to Aluminium Alloy BS 1490
earth so that the protective Cast iron BS 1452
equipment has time to operate and Forgings and stampings (hot or cold
thus isolate the faulty circuit in the formed)
event of fault. Copper BS 2872
• To ensure that, if a fault occurs, Navel brass BS 2872
non-current carrying metal work Aluminium BS 1474
associated with the equipment Steel BS 970
does not attain a dangerous Bar, Rods and Tubes (For Machined
potential with respect to the components fittings)
general mass of earth.
Hard drawn copper BS 2874
Annealed copper BS 2874
The earthing system should possess low
Copper Silicon BS 2874
electrical resistance between the electrode
and earth. The lower earth electrode Phoshor Bronze BS 2874
resistance, the more likely the Aluminium Bronze BS 2871
_________________________________________ Aluminium BS 1471
Naval Brass BS 2874
*. Department of Electrical Engineering Steel (General use) BS 970
* *. University of Engineering and Technology, Steel (Galvanizing) BS 970
Lahore

26
The major components used for the considerable. In winter season the earth
designing earth system are, freezes to a considerable depth below the
surface, below 320 F the water in the soil
Major components
freezes and thus causes tremendous
increase in the temperature coefficient of
resistivity for soil. So, the coefficient is
Bonding to prevent Earth termination Down conductors Air termination
side flashing Network Network negative when temperature goes down,
then resistivity rises and resistance of
earth connection is increased.
Deep driven Parallel earth Radial strip Solid plates Reinforcing bars
earth electrode rod electrodes electrode or mat in foundation as 4.4. Effect of Size of Electrode
netural earth
Underground
Pipe network A very little change in resistance would
result by using large diameter electrodes.
3. Basic Design Requirements
4.5. Effect of Voltage Gradient
• No earth plate should be less than 2ft
× 2ft in area and 1/8 inch for copper, The resistance is not affected by the
so the plate are buried at least one foot voltage gradient, unless it exceeds a
below the permanent level. critical value. This value will vary with the
• If lower resistance is required for an nature of soil but it is of the order of few
installation, more than two plates are kilovolts per cm. The earthing system is
connected in parallel keeping each normally designed to keep the gradient
plate at least 10 feet away from each well below these critical values.
other.
• If electrical apparatus is present, then 4.6. Effect of Current Magnitude
at least two plates are buried at
maximum distance which is never less It has been found that high currents are
than 10 feet [1,6], not of sufficient magnitude to result in
extremely high voltage gradient.
4. Effect on Different Parameters
4.7. Tolerable Limits of Body Current
4.1 Effect of Soil on Resistance
The magnitude and duration of the current
The resistance of the ground connection conducted through a human body at 50 or
depends upon the soil surrounding the 60 Hz should be less than to cause
electrode. The chemical ingredients and ventricular fibrillation. Much higher
the amount of moisture in the soil currents can be tolerated without causing
determine the electrical conductance of fibrillation if the duration is very short.
soil. The resistance varies inversely as the 99.5% of all the human beings could
cross section and within a few feet from withstand current, without fibrillation given
the electrode where the conducting path is by the equation.
small.
Ik = 0.116 (1)
4.2 Effect of Moisture on Soil √t
where
A variation in the moisture of soil will make Ik = rms current through a body in amperes
a difference in the effectiveness of ground t = time duration of shock in seconds
connection with the electrode.
5. Design Procedure of Earthing
4.3. Effect of Temperature
The step-by-step procedure of designing
The variation in soil resistivity with the earthing system is as follows,
temperature for red clay soil having
moisture contents of 18.6% is quite
27
5.1. Investigation of Soil Characteristics
R= ......................(3)
4r
Investigation of station site will normally
Where
include at least a determination of the
R = Station resistance in ohms
general soil composition. The resistivity of
ρ = Average earthing resistivity in ohm-
the soil is measured by the formula
meters
2π AR
r = Radius of a circle having the same
= .....................(2) area of
2A 2A
i+ − the designed grid
A2 + 4 B 2 4 A2 + 4 B 2
It can also be written as
Where ρ = resistivity of soil in ohm-meters

R = resistance in ohms obtained by =


R + ..............................(4)
dividing the voltage between the potential 4r L
probes with current
A = distance between the adjacent Where
electrodes in meters L = Total length of the buried conductor in
B = depth of electrode in meters meters
Note that the second term of this equation
When B < A, then the above equation has the total length of buried conductor in
becomes meters and L reaches to infinity.
Resistivity ρ = 2πAR
7. Calculation of Maximum Grid
5.2. Determination of Maximum Earth Potential Rise
Fault Current
The resistance of the mat is calculated as
Following steps are performed to calculate the maximum rise in potential above
the maximum earth fault current remote earth so that
E=IR
 Determine which of the possible type
of ground fault will result in the Where
greatest flow of current between the
ground grid and surrounding earth. E = Maximum rise in grid potential in volts
 Determine the maximum symmetrical I = Maximum short circuit current in grid in
rms value of earthing fault current amperes
flowing between the station grounds R = Grounding grid resistance in ohms
and surrounding earth by short circuit
study. 8. Calculation of Step Voltage
 Apply a correction factor where
appropriate to allow for future It is the potential difference shunted by the
increase in fault current due to body and limited to the maximum value
expansion of the system. between two accessible points on the
ground separated by a distance one
6. Resistance Calculation of meter. It can be calculated by the
Earthing equation,
E= KKi. . I .....................(5)
It is not necessary to know the
step L
exact value of resistance but rather to Where
know whether it is the order of 1 ohm to K = Correction factor
1000 ohms. The resistance of driven Ki = Irregularities factor
electrode is not to exceed 25 ohms. I = Fault current in amperes
So the earthing resistance can be L = Total length of buried conductors in
calculated as, meters
ρ = Ground resistivity in ohm-meters

28
9. Touch Voltage 10.3 Arcing

The potential difference that appears from Arcing in earthing system may be due to
hand contact to feet contact is termed as the following reasons,
touch potential. It is calculated by the
equation, • The grid station earthing resistance
is approximately 2 ohm. If the
(h 2 + x 2 )( D + x 2 ) 1 2 D + x 3D + x resistance of the earthing is
=Etouch [ 1 ln + I
2 hdD 2 π ln( 2 D )( 3d )...].. L ....(6)
increased, then during the flow of
fault current, arcing may result.
Where
X = Horizontal distance on the surface of • If the two different earthing
earth conductors have different ohmic
from the buried conductor in meters. value, then during fault condition,
d = diameter of buried conductor in meters very heavy current will flow
towards the lower resistance
9.1 Calculation of Mesh Voltage conductor, which can produce
arcing in the system.
Mesh Voltage is determined by the
expression, 10.4 Effect of Failure of Earthing
=
Emesh KmKi. . I ...................(7) on Grid Station Equipment
L
In the neutral of power transformer, if the
Where Km = constant which is the effect of
failure of earthing occurs, then voltage of
number of parallel conductors buried
2
transformer winding will rise which causes
1 ln ( D ) + 1 ln[( 3 )( 5 )( 7 ) + .....]....(8)
Km = failure of installation. During the fault,
2π 16hd π 4 0 0
heavy current flows and this heavy current
will not pass through the neutral of the
10. Causes and Effects of Failure of earthing system but keeps on circulating in
Earthing and Remedial the transformer winding producing
Measures excessive thermodynamic stress. This will
result in the deformation of the core and
Following are the causes and effects of damages the winding. Therefore, the body
failure of earthing system, of the transformer is earthed at least two
diagonally different conducting points. If
10.1 Corrosion the earth of transformer body is open
having high value of resistance greater
Earthing conductor, rod, electrode plates than 2ohm, then the transformer bushing
and their joints are buried under the provides the protection.
ground where water logging. Under the
ground, salinity badly affects the 10.5 Effect on Lightning Arrestor
termination and produce oxide compound
at the joint and electrode which can cause Lightning arrestors are installed at every
damage to the equipment. grid station for safety against lightning
strokes but it is always earthed. The
10.2 Improper Material Loose lightning stokes are diverted through a
Connections non-linear resistance connected with
ground. However, if earth is disconnected
If the material is not used as per due to any fault, then the lighting stroke
specification, the earth resistance will not be grounded. This will cause heavy
increases and will resist the flow of fault heating in the non-linear resistance that
current. This badly affects the can damage the arrestor.
performance of the equipment.

29
10.6 Effect on Instrument • The termination joints of the
Transformers metallic body should be inspected
regularly and tightened every time.
Potential transformer is a step down
transformer. One terminal of potential • The neutral point of the transformer
transformer is connected with line voltage should be earthed separately with
and other terminal is solidly grounded. If insulated copper conductor from
the potential transformer is opened due to the bushing to avoid contact with
any fault, then the line voltage will appear transformer body.
on the neutral terminal and insulation is
damaged. This will damage the potential • Earth testing should be carried out
transformer. regularly and compared with last
result.
A current is a step up transformer. The
secondary side of current transformer is • Lighting arrestors should be
earthed. If the earthing connection gets earthed with insulated conductor.
open, then high voltage will appear on the
secondary winding. This can damage the 12. Conclusions
insulation of secondary winding and
destroy the current transformer. Frequency of accidents from ground fault
gradients has been limited by low
11. Remedial Measures probability of coincidence of all the
adverse factors required. Never the less,
Following remedial measures are taken to one fatal accident, which could be
achieve proper ohmic resistance prevented, is too many. Precise
according to standard specification. calculation in this field is seldom
attainable.
• Soil conditioning agents are
introduced into ground to reduce Field measurements of local potentials,
the soil resistivity and also to when the ground system is loaded with
reduce earth resistance. relatively high-test current are quite
conclusive, but too expensive for routine
• In order to avoid corrosion effect, application. It is hoped, however that the
the earthing material should be material here presented may help
galvanized and standard copper engineers to avoid both the more
conductor as per standard dangerous situations, on the one hand and
specification may be used. extreme over design on the other.

• All joints should be cad welded REFERENCE


used, then minimum corrosion
occurs. [1] IEEE guide for safety in sub station
grounding, Edition 1976.
• Loose connections should be [2] IEEE guide for safety in AC sub
avoided. station, Edition 1985.
[3] A course in electrical power by P.V
• When digging in grid station yard Gutta, US Bhatnagar & M. Lsoni.
with respect to proper layout of [4] Grid station operation by Pak.
earth mesh, proper route for fresh German Co-operation (GTZ)
excavation should be selected. Gmbh.
[5] Furse, Earthing and lighting
• All the metallic parts of grid station protection. Consultant handbook.
should be solidly earthed at least [6] Earthing resistivity manual, Soil
two points through standard copper test, Inc. Evanston, IIIinois 60202
conductor to mesh. USA.

30
[7] Present-day practices in grounding (Committee report) A.IEE technical
of transmission system by wood paper.
ruff and stone (committee report) [10] Guide for safety in alternating-
A.IEEE transaction April 1923 current substation grounding A.IEE
[8] General consideration is grounding March 1961.
the neutral of power system by H.H [11] Grounding principles and practice
Dewey, A.IEE transaction April special report from electrical
1923. engineering June 1915.
[9] Present-Day, grounding practices [12] An American National standard
on power system-third A.IEE, IEEE Guide for safety in A.C
report on system grounding Substation grounding.

31

Vous aimerez peut-être aussi