EPI2-MAN-652NA-OM1
I/O Module
User’s Manual
Note:
Tyco Valves & Controls has taken every care in collecting and verifying the documentation
contained in this Instruction and Operating Manual.
The information herein contained is reserved property of Tyco Valves & Controls.
INDEX
INSTALLATION
To install the OM1 into the actuator, proceed as follows:
The OM1 option kit consists of the following parts:
- OM1 modulating input/output module
- 3 metal spacers (models 006 and 013 only)
- 4 screws
- 1 flat cable with connectors
Fig. 2 Fig. 3
¾ Pull out the 4 black cables (already installed in the base ¾ Remove the local mechanical indicator by pulling
actuator) (fig. 4) upward (fig. 5)
Fig. 4 Fig. 5
¾ Connect the flat ribbon cable to connector J9 on the OM1 card to connector J8 on the logic card in the actuator
(Figures 6 and 7)
Connector J9
Connector J8
Fig. 6 Fig. 7
¾ Connect the 8-pin connector to connector ¾ Connect the 4-pin white connector to connector J2 on
J3 on the OM1 card (figure 8) the OM1 card (figure 9).
8-pin 4-pin
connector connector
Fig. 8 Fig. 9
¾ Connect the 2-pin connector to connector J7 on the ¾ Connect the 3-pin connector to connector J6 on the
OM1 card (figure 10). OM1 card (figure 11)
3-pin
connector
2-pin
connector
Fig. 10 Fig 11
¾ Install the three metal spacers (Models E006 and E013 only)
¾ Place the OM1 card onto the supports (fig 12)
Fig. 12
¾ Install the four screws, as shown in the pictures below, to mount the OM1 card to the logic card:
OM1 configuration and setup is done using the controls on the card. To access these controls, the actuator cover must be
removed. (Please follow instructions in MAN 652NA or MAN 652NA_SG.)
Important:
Please note that the settings may be performed in any order.
OM1 settings are changed using the following controls, see fig. 19:
SW2
Red
LED
SW4
SW3
SW8
SW7
SW9
SW6
SW1
Fig. 19
Default Value
No. Function SW8 SW7 SW9
1 Relay AUX1 0 0 to 9 - 0%
2 Relay AUX2 1 0 to 9 - 25%
3 Relay AUX3 2 0 to 9 - 75%
4 Relay AUX4 3 0 to 9 - 100%
0 (stay-put)
5 Fail position on loss of signal 5 1 (fully open) - Stay-put
2 (fully closed)
6 Dead band 6 0 to 9 - 0.5%
0 = break
7 Relays AUX1-AUX3 7 -
1 = make Break
0 = break
8 Relays AUX2-AUX4 8 -
1 = make Make
0 = OFF
9 Blinker (motor running) 9
1 = ON 0 OFF
Retransmission Signal 0 = dir.
10 9
(direct or reverse) 1 = rev. 1 Direct
Retransmission Signal 2 = Current
11 9 1 Current
Current or Voltage 3 = Voltage
0 = dir.
12 Direct or Reverse acting 9
1 = rev. 2 Direct
0 = OFF
13 Positioner ON or OFF 9
1 = ON 3 OFF
0 = OFF
14 Command Signal 4 – 20 mA 9
1 = ON 4 ON
0 = OFF
15 Command Signal 0-10 Vdc 9
1 = ON 5 OFF
Important:
Note that the default setting for the Positioner function is OFF. To enable,
the setting must be changed to ON. See item 13 in the table above.
SW5
SW3
Fig. 20
Output signal selection of 4-20 mA or 0-10 Vdc is done using switches SW1 and SW6. Output setting is 4-20 mA by default.
Output 4-20 mA
To select an output of 4-20 mA:
SW1_1 = ON
SW1_2 = OFF
SW1_3 = OFF SW1
SW1_4 = ON
SW6 = OFF
Impedance = 250 Ohm
Fig. 21
- Relay AUX1 Setting: - Relay AUX2 Setting: - Relay Aux3 Setting: - Relay Aux4 Setting:
Relay 3 Relay 4 Relay 5 Relay 6
SW8 SW7 Action SW8 SW7 Action SW8 SW7 Action SW8 SW7 Action
0 0 Inactive 1 0 Inactive 2 0 Inactive 3 0 Inactive
0 1 0% 1 1 0% 2 1 0% 3 1 0%
0 2 12.5% 1 2 12.5% 2 2 12.5% 3 2 12.5%
0 3 25% 1 3 25% 2 3 25% 3 3 25%
0 4 37.5% 1 4 37.5% 2 4 37.5% 3 4 37.5%
0 5 50% 1 5 50% 2 5 50% 3 5 50%
0 6 62.5% 1 6 62.5% 2 6 62.5% 3 6 62.5%
0 7 75% 1 7 75% 2 7 75% 3 7 75%
0 8 87.5% 1 8 87.5% 2 8 87.5% 3 8 87.5%
0 9 100% 1 9 100% 2 9 100% 3 9 100%
Dead band
SW8 SW7 Setting (%)
6 0 0.3
6 1 0.4
6 2 0.5
6 3 0.6
6 4 0.7
6 5 0.8
6 6 0.9
6 7 1.0
6 8 1.5
6 9 2.0
The monitor relay contacts can be set to make or break by soldering the pins of connection J1.
J1
3
2
1
Default setting: with pins 2 and 3 soldered together, the monitor relay contact operates as follows:
- Contact closed in normal condition with relay energized, relay de-energizes and the contact opens to signal an alarm
condition.
If the application requires the contact to “make” for an alarm condition, de-solder pins 2-3 and solder pins 1-2 of connection
J1.