Subject: Quotation For RO Based Water Treatment Plant. (250 lph SS)

Dear Sir,

With reference to above subject, herewith we are submitting our competitive price of Reverse Osmosis water treatment plant for your requirement.

SALIENT FEATURES OF RO SYSTEM

We have made a hard and sincere effort to incorporate our past experience in our offer which has made it elaborate and comprehensive. We have incorporated several worldclass renowned equipment / instruments that are time tested. Almost care is taken for selection of proper material of construction for each component in M-Tech mineral R.O System. This is so because we believe that appropriate selection of material is vital in such a sophisticated system.

Enjoys full technical back up from the world leader in global water treatment field, some of which are listed below:-

USA make for their thin film composite, polyamide, spiral wound Reverse Osmosis Membranes in India. SS vertical pump are for their high capacity multi-stage, vertical, centrifugal pumps, which are dedicated to handle one fluid i.e., water. Accurate Dosing Pumps. Structural FRP vessels are for sand filter, Carbon filter and softener. M/s Filtra is for their wide range of Multi Port Valve.

2 |Page

Features Of Reverse Osmosis Membrane :

1.

All these Membranes are made up of World Class State of Art Technologies. We preferred it for its reliability and consistent performance. Excellent silica rejection. Low operating pressure reduces power cost. Low operation and maintenance cost compared to other conventional systems Supplied by others. Resistant to Bacteria / Biological attack. Excellent product water quality having TDS less than 100. Low membrane replacement cost due to longer life span. Consistent & reliable performance avoids any accidental shut down of the system hence eliminates probable production losses. They manufacture specially for the water application. Inner surface prevents the microbiological growth to occur.

2. 3. 4. 5 6. 7. 8.

These are self lubricating pumps and require vertically no attendance and dont require oil chamber and replacement of the oil/oil seal on regular intervals. less stress on the moving parts of the pump compared to others. Very less noise levels. Smooth and trouble free operation. The pumps are fitted with a motor with reinforced bearings. All materials used in pump manufacturing are having WRC approval.

3 |Page

PLC Controls And Instrumentation:

Start Raw Water Pump The PLC will check the Level of dosing tank, if level is OK then start special anti Scalant dosing system. PLC check the low suction pressure (Low pressure switch) at the inlet of High Pressure Pump, pump will start if it is ok. High pressure switch provided after the high pressure pump will make the pump trip if it is beyond the set point limit. Flow meters indicate the Flow Of Raw Water which is continuously used as a Raw Water in the RO system and also shows the flow of the treated water and also the reject water. Pressure Gauges at various levels showing the pressure at the mounted points.

After Sales Service.

Mineral Technologies

Team of experienced fitters, welders, electricians technicians and engineers To repair any equipment, pumps, electrical and Instrumentation of system.

we are having a considerable inventory in stock for almost all the related equipments, components, spares and parts available round the clock.

4 |Page

Rich Experienced Engineers in RO are available immediately to solve any problem and for effective troubleshooting. We take Annual Maintenance Contract after the end of the warranty period if required which comprises of fixed periodic visits of our service team to service and carried out replacement.

BASIS OF DESIGN AND TREATMENT SCHEME

PLANT INTRODUCTION: The proposed Water Treatment scheme is designed to produce product water at the flow rate of 250 LPH based on Reverse Osmosis Technology.

1.2

RAW WATER ANALYSIS (ASSUMPTED):

We have designed the proposed Water Treatment System based on following Water Analysis,

Sr. No. 1 2 3 4 5 6 7

Parameter Total Dissolved Solids Turbidity SDI Heavy metals Organics And Bacteria Oil And Grease Residual Chlorine

Analysis Value. 1000 ppm (Max.) <1 NTU <4 NIL NIL NIL NIL

5 |Page

8 9 10 11

Temperature ( C ) Color Odor BOD & COD

< 40. Color Less Odor Less NIL

1.3

END WATER QUALITY: TDS < 50 ppm. 6-7 Nil. Nil.

pH Turbidity Color

1.4

RO PLANT OPERATING CONDITION:

Sr. No. 1 2 3 4

Parameter Feed Flow Rate. Product Flow Rate Reject Flow Rate. Recovery.

Value. 1000 LPH 250 LPH 500 LPH 40 - 45 %

1.5

Treatment Scheme.

Sr. No.
6 |Page

Description

1 2 3 4 5 6

Raw Water Pump Sand Filter carbon filter Anti Scaling Dosing System. ( for more then 1000 ppm TDS) Micron Cartridge Filter ( 20 Micron & 5 Micron ) High pressure Pump

The End Water quality shall be achieved subjected to:

1)

Feed quality is same as specified in your enquiry. In case of any change in the quality of raw water, the same may have an implication on the operating parameters and End- water quality of the system.

2) 3)

Feed limiting condition mentioned in our offer is strictly maintained. Operation of Water treatment plant is strictly followed in totality as per our operating manual & instructions. 250 SS

TECHNICAL SPECIFICATION

7 |Page

MODEL :RO 250 SS

CAPACITY : 250 LPH

SPECIFICATION: Sr. No. mp Description 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. Specification Nos.

Skeed...........................................................SS..........................1 Pressure Sand + carbon Filter ....................FRP 10 X 54......1 Multi Porte Valve ......................................1 ..........................1 20 Micron Sediment Pre-filter....................20 X 2................1 5 Micron Sediment Pre-filter......................20 X 2................1 central vertical pump..................................CRI/NANFANG...1 Reverse Osmosis Element (Imported)........ HYDRONAUTICS/DOW.........................................................1 .................................................................... Pressure Vessel for Membrane Elements...SS...........................1 Digital Control Panel with Ameter ,Voltmeter, Indicators, On Off switch...................1 Low Pressure & High Level Switch for Automatic control.................................Imported...............1 Pressure Gauge Meter.................................Glycerin Fluid.......2 Pressure Control ValveSpring System......................................1

11. 12.

Dimension Weight Power Consumption

(LxWxH Approx.) (Kg. Approx.) (H.P.)

: 100x19x54 : 400 : 3 (H.P.)

Oem price : 85,000/8 |Page

m.r.p price : 1,25,000/INSTRUMENTATION:

Flow Indicators

Quantity Type Maximum Op. Temp. Measuring Points

: : : :

2 Nos. Float Type Panel Mounted. 40 Degree Centigrade. 1) RO Module Product Flow 2) RO Module Reject Flow

Pressure Gauges Quantity Range Location : : : 2 Nos. 0-20 Kg / Cm2. 1) RO Module Inlet. 2) RO Module Reject Flow.

High Pressure Switch And Low Pressure Switch Quantity Location : : One Nos. Before & after High Pressure Pump. Reject Water Line 1 No

Pressure Control Valve Location Nos.

9 |Page

Make E

Spring System USA.

Digital Control Panel With meter, Voltmeter m indicators, On off Switch

PIPE LINE

: UPVC PIPE LINE FROM SAND FILTER TO

HIGH PRESSURE PUMP. PIPE LINE FROM HIGH PRESSURE PUMP TO END POINT.

SCHEDULE OF EXCLUSIONS AND TERMINATION

SCHEDULE OF EXCLUSION: 1. All Civil Works such as plant foundation of the equipments,

10 | P a g e

2. 3. 4. 5. 6. 7.

Mass concreting etc. Supply of power to Motors, regeneration chemicals for trial run and commissioning. Laboratory testing facility, Instruments and reagents. Lubricants, oil and Greece as and when required. Raw water storage tank and Raw Water Pump. All equipments, works and services not specifically mentioned in our proposal. Storage and site security.

TERMINATION POINTS: 1. 2. 3. 4. Suction Of Raw Water Pump.(feed water pump) Permeate / Reject Out Let of Reverse Osmosis System. Outlet of Final Polishing Cartridge Filter. Overflow or drain pipe work of all vessels.

11 | P a g e

5.

Power control termination at High pressure pump, RO Product / Raw water transfer pump.

Terms & Conditions : 1. 2. 3. 4. 5. VAT 5 % for Gujarat.. Against C Form 2%. (taxes extra applicable) Octroi and freight extra as applicable. Payment: 50% as advance, 50% at the time of inspection by the client at our factory before delivery of plant Delivery: 2 to 3 weeks after confirmation of purchase order along with advance. Validity: This quotation valid for 30 days.