Preface
In an attempt t o make the power industry more effective, a new

t r e n d in electric power production has witnessed intense development during recent years, that of energy storage. Several options have been considered for this purpose, one of t h e m being the battery energy storage system. B o t h classical lead-acid batteries, as well as new advanced types of batteries are being used. A number of demonstration battery energy storage plants and facilities have been designed and built, and are now subjected t o testing. I t has become general practice for experts in the power industry, and battery researchers and manufacturers t o meet at j o i n t conferences t o exchange information and opinions o n the problems of energy storage. It is now opportune t o siirrimarize the results and experiences so far acquired in t l i e design arid utilization of battery energy storage systems. In 1954, Elsevier in Amsterdam issued the book entitled Power Sources for Electric Vehicles edited by B.D. M c N i c o l and D.A..J. Rand, which presented a comprehensive survey o f the curM o t o r car transport i s being increasingly adopted, since it is an important and indispensable element of the n o r m a l functioning of every modern social community. I t has, however, a serious environmental impact in t h a t it causes considerable air pollution in large cities and densely populated areas. Development and large-scale commercialization o f electric vehicles has become oiie of the greatest challenges o f the late 2 0 t h cen-

rent knowledge in the field.

tury. However, the electrocliemica1 power sources used for propulsion of these vehicles cannot yet meet the challenge. Annual international

conferences o n t h e problems of electrochemical power sources show that more effort is being placed o n broad-spectrum investigations in t h e field. Accumulated theoretical knowledge and practical experience o n battery energy storage systems for electric vehicle applications should now be analyzed and evaluated. T h e Regional Office for Science and Technology for Europe (ROSSE) at the U n i t e d Nations Educational, Scientific and Cultural Organization (UNESCO) entrusted us w i t h the task of carrying out
an overview of the current status and future perspectives of battery

energy storage systems for applications in the power industry and in transport, w i t h the purpose of attracting wider public attention t o t h e problems of these systems. T h e current status and the problems confronting battery energy storage systems for the power industry are presented by Prof. D r S c i . D. Pavlov, and for electric vehicle applications, by

Dr. G. Papazov. The English version of the text was provided by Mrs. M. Gerganska. All three of us work at the Central Laboratory
of Electrochemical Power Sources, Bulgarian Academy of Sciences, Sofia, Bulgaria. If we have achieved, even in part, the aims envisioned by

UNESCO for this book, and i f our efforts contribute, though modestly, t o the development of battery energy storage systems, we w i l l
be most satisfied.

D. Pavlov, G. Papazov, M. Gerganska


May 1991, Sofia, Bulgaria

11

Contents

Preface

................................................

Chapter 1
BATTERY ENERGY S T O R A G E S Y S T E M S F O R THE POWER I N D U S T R Y
1 Introduction ....................................... . 1.1. The four basic elements of every national electric
power system

1 1
3 3

.........................................

1.2. Power industry and i t s problems ........................ 1.2.1. Energy, power and response t i m e . . . . . . . . . . . . . . . . . . 1.2.2. Quality of energy supply systems . . . . . . . . . . . . . . . . . 1.2.3. Ecological problems and the development of power industry ................................
2

5
6 7 8 9
11 13

Electric energy storage

...........................

2.1. Pumped Hydroelectric Energy Storage Systems (PHESS) . . 2.2. Compressed-Air Energy Storage Systems (CAESS) ....... 2.3. Superconducting Magnetic Energy Storage Systems (SMESS) ............................................. 2.4. Battery Energy Storage Systems (BECS) . . . . . . . . . . . . . . . .

2.4.1. T h e revival of battery energy storage systems . . . . . . 13 2.4.2. Basic principles of battery operation . . . . . . . . . . . . . . . 15 2.4.3. Some advantages of battery energy storage systems 15 2.5. Choosing the right option for electric energy storage . . . . . . 17

111

...

2.4.2. Basic principles of battery operation

. . . . . . . . . . . . . . . 15

2.4.3. Some advantages of battery energy storage systems

. 15

2.5. Choosing the right option for electric energy storage . . . . . . 17

Batteries for energy storage .in operation and under development ................................

19

3.1. Development projects for battery energy storage systems . . 19 3.2. Sodium/Sulfur Batteries

...............................

20

3.2.1. Principles of cell operation ....................... 3.2.2. Design of sodium/sulfur cells

20
23

.....................

3.2.3. Specification and test results for battery modules and pilot plant of the Japanese Moonlight Project 3.3. Zinc/Bromine Batteries

24
28

................................

3.3.1. Reactions and principles of cell design arid operation 28 3.3.2. Chemistry and electrochemistry of the zinc/bromine cell ............................................ 3.3.3. Battery system design

31 33

...........................

3.3.4. Characteristics of zinc/bromirie batteries 3.4. Zinc/Chlorine batteries

. . . . . . . . . . . 33
37

................................

3.4.1. Fundamentals of zinc/chlorine batteries 3.4.2. Battery design

. . . . . . . . . . . . 37
39 40

..................................

3.4.3. Battery characteristics

...........................

iv

5.2. Lead-acid b a t t e r y energy storage systems (LABESS) in operation by 1990 throughout the world . . . . . . . . . . . . . . . 63

Lead-acid battery energy storage systems for load levelling ...................................... 6.1. System structure ......................................
6

67 67 68 68 69 76 78 78 79

6.2. Chino 10 hgW/40 MWh lead-acid battery energy storage


systein

6.2.1. 6.2.2. 6.2.3. 6.2.4. 6.2.5. 6.2.6.

............................................... .................................... T h e b a t t e r y ..................................... Power conditioning system ....................... Facility monitoring and control system ............ Equipment energy losses ......................... Economics of Chino LABES Plant . . . . . . . . . . . . . . . .
Plant layout

7 . L A B E S S for instantaneous (spinning) reserve


and frequency control applications

..............

7.1. Island networks ....................................... 7.2. T h e BEWAG 8.5/17MW Lead-Acid B a t t e r y Energy Storage Plant .........................................
7.2.1. System frequency response having given rise t o the construction of the BEWAG LABES plant 7.2.2. System design and characteristics

80 80 81

. . . . . 81 . . . . . . . . . . . . . . . . . 82

Lead-acid battery energy storage systems for peak shaving ....................................... 8.1. What i s peak shaving? .................................

86 86

8.2. Johnson Controls 300 1<W/600 1Wh LABES Facility . . . . . . 88 8.3. Lead-acid battery energy storage systems in t h e railway transport network ..................................... 91

9. Valve-regulated lead-acid b a t t e r i e s f o r b a t t e r y
e n e r g y storage systems

. . . . . . . .. . . . . . . . . . . . . . . . .. . 94 .. . . . . . . . . . . 96

10. S t r a t e g i c advantages of BES systems


References

.... . .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98

Chapter 2
ENERGY S T O R A G E S Y S T E M S F O R ELECTRIC
VEHICLES

1. M o t o r vehicles and e n v i r o n m e n t a l p o l l u t i o n

. . . 103

2.

Specification of e n e r g y storage systems f o r e l e c t r i c vehicles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106 C h a r g e a n d capacity o f b a t t e r i e s f o r e l e c t r i c vehicles .. ..... .... .. .. ... . ... .. . ... .. ... . . . . . . .. .. . 122 T y p e s o f cycles o f e l e c t r i c vehicle b a t t e r i e s

3.

4. 5.

. . . . 128

R e q u i r e m e n t s t o t h e c o n s t r u c t i o n and m a n u f a c t u r i n g t e c h n o l o g y o f b a t t e r i e s f o r EV e n e r g y storage systems ................................... 139 Specification o f o p e r a t i n g e n e r g y storage systems f o r e l e c t r i c vehicles . .. , . . . . . . .... . .. .. .. 1.12

6.

7 . L y r i c a l epilogue
References
vi

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 144
145

. . , . . . . .. .. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Chapter 1

BATTERY ENERGY STORAGE S Y S T E M S FOR THE POWER INDUSTRY


D. PAVLOV

1. Introduction
1.1. T h e four basic elements o f every national electric
power system
Production of electric energy is the basic pillar for n o r m a l functioning of every modern social community and a guarantee for i t s progress. It is organized in an electric power system comprising three basic elements: a) Electric power and energy generating utilities, i.e. electric power plants: thermal power plants fired by coal or nuclear fuel, gasfired steam plants, oil- or gas-fired combustion turbines, hydroelectric plants, etc. b) Electric power distributing systems including transformer facilities, transmission trunk lines and distribution lines t o every customer. c) Consumers of electric power and energy. These are users in industrial, transport, agricultural and telecommunication contexts, and people in their day-to-day life, administrative buildings, etc. T h e electric power produced by the generating utilities is delivered through t h e transmission/distribution system t o the consumers for utilization. The consumers demand for electric power varies cyclically during day and night, as well as w i t h i n t h e week and the seasons.

Demand. T h i s is the rate at which electric energy is delivered t o t h e consumer, measured in kW (kilowatts) integrated over a specific time interval (15 min) [l].
Figure 1 shows an example of a daily customer demand profile.

A baseload level o f demand is introduced. The power capacity for meeting this demand level is generated and maintairied by thermal
power plants fired by low-cost fuels such as coal or nuclear fuel. To be economically effective, baseload generating units should operate at a minimum capacity of 500-1000 MW and under constant load.
I

. . , , ,

5 ' 7 ' 9 ' 1 1 ' i 3 ' 1 ' ' 1 7 ' 1 9 21 Hour of day
mGas steam

23

DCoal

@Gas turbine

Bottery

Fig. 1. Example of customer energy demand curve for a working day

[il.

D u r i n g the night (hours O t o 6), the demand decreases t o about 15-30% below t h e baseload level. The daytime demand is significantly higher than the baseload level. I t is served by gas-fired steam plants. They burn natural gas or o i l which are more expensive fuels than coal. There are two peaks in the daytime demand profile related t o the increased energy consumption for the transportation of people from home t o the working place and back, as well as for increased household needs. Peak power is generated by gas-fired turbines utilizing relatively expensive fuel, and also by hydroelectric

power plants. T h e r a t i o of actual t o peak power demand over a given period is called load factor. There is an intrinsic contradiction in each power supply system between producers and consumers of electricity. T o b e efficient, power plants should operate at constant load. T h e customers demand, o n the other hand, undergoes cyclic fluctuations. T h i s leads t o inefficient utilization of t h e generating capacities. A possible sol u t i o n t o this problem is the involvement of a new element in the energy system.
Electric energy storage. At night, when energy demand is low, generated electric energy is stored in appropriate facilities, and is delivered t o meet peak-hour demands during the day. Thus, low-cost fuel power plants work at maximum load during the night and store

the generated energy t o sell it at increased cost during peak demand periods. The introduction of this f o u r t h element in the electric power
system makes i t s operation more efficient. T h i s n o t o n l y brings about considerable savings of expensive fuels such as gas and oil, but also improves t h e load factor of the power generating facilities.

1.2. Power i n d u s t r y and i t s problems

1.2.1. Energy, power and response time


I t has been established t h a t the different forms o f m o t i o n (mechanical , thermal, electromagnetic , gravitational, chemical, etc.) are
converted i n t o one another following definite quantitative ratios. T o allow measuring of the various forms of m o t i o n by a unified measuring unit, the term energy has been introduced. T h e electrical energy is determined f r o m the product of the voltage and the quantity of charge that passes through an electrical device (load). T h e work done per unit t i m e is called power. T h e electrical power is determined f r o m the product of voltage and current.

In thermal power stations, the chemical energy accumulated in coal, crude o i l or natural gas is transformed by burning (oxidat i o n o f t h e hydrocarbons) i n t o heat (high-temperature, high-pressure
steam), which sets in m o t i o n a turbine, whereby the thermal energy is transformed i n t o mechanical. T h e turbine shaft is connected t o the shaft of an electric generator. On rotation, this common shaft drives the r o t o r of the generator as a result of which the mechanical energy is converted i n t o electrical energy. It is evident that, t o obtain elect r i c a l energy f r o m coal, several processes of energy conversion have t o occur. In an electrochemical power source, a battery in particular, this energy transformation path is much shorter. In this case, through electrochemical reactions o f oxidation and reduction proceeding o n the surface of t h e t w o electrodes, the chemical energy is directly transformed i n t o electrical power. Conversion o f one type of energy i n t o another requires a certain t i m e period. T h e time needed for an energy-generating system t o change i t s power f r o m a value (A) t o another value (B) is called
response (transition) time (Fig. 2 ) .

/
ition time

i
_J

Time

Fig. 2. Power curve showing t h e change of power from level A t o level B.

A thermal power plant needs tens of minutes t o change f r o m one power level t o another, while for a battery, the response time is of the order of millionths of a second. For a n energy utility t o meet a l l load fluctuations, it should dispose of a system of power plants with various response times ranging f r o m milliseconds t o hours.
1.2.2. Quality of energy supply systems
T h e quality o f an electric power supply is determined by the available reserve capacity at the energy utility. Figure 3 illustrates the distribution of the electric-system capacity expressed by a typical weekly load curve of an electric utility.
100
2.

Generation for load No storage)

Baseload

Mon

Tue Wed! Thul Fri 1 Sat

Sun

1
I
IReserve

Generation for load WHh storage) Mon I Tue I Wed I Thu I Fri I Sat I Sun

Baseiood energy to S i O M g t Peaking energy from storage

Fig. 3. T y p i c a l w e e k l y load c u r v e for an electric utility

[il.

T h e energy system should have 15-20% of reserve power available t o b e able t o meet any customer demand. I f there is n o or insufficient reserve capacity and the load level exceeds the power generation level,

a decline in voltage at the consumer side w i l l appear which would upset the n o r m a l operation of the users machines and electrical devices or even cause them t o fail. For this reason it is essential for t h e n o r m a l functioning and development of each social community t o have reliable national and local electric power systems w i t h capacities exceeding the actual energy demand by at least 15%. Unfortunately, however, o n l y r i c h and advanced modern countries possess such high-grade energy systems. T h e power systems of most countries in the world have capacities t h a t only j u s t meet their energy demands, and in some cases are simply inadequate. T h i s hunger for electricity is very often a l i m i t i n g factor for the economical and social development o f a country.

1.2.3.

Ecological problems and the development of power

indus t r y

T h e electric energy needs of the population, industry, agriculture, transport, etc. increase every year, and the claims for high-quality electric power become ever more demanding in relation t o the i n creasing automation and computerization of the national economy. Previously, these needs were met by expanding the capacities of all types of electric power generating facilities. Operation of these facilities, however, is based o n the combustion of coal, o i l and gas, which i s accompanied by harmful gas emissions of COZ, SO2 and others. T h e increased content of SO2 in the atmosphere has led t o the format i o n of acid rains causing enormous damage t o the agricultural crops and the forests. T h e accumulated CO2 in the air might b r i n g about considerable climatic changes b o t h o n a regional and global scale (the so-called greenhouse effect). Thus the rapid development of power industry has added comfort t o society and i t s individuals, but it has posed very serious ecological problems of a national, regional

and global nature. In response t o these processes, various organi6

zations and social movements are being founded whose activities of environmental control and protest actions begin t o have a significant impact o n the policy of state governments and of companies engaged
in electric power production.

The efforts of these movements, com-

bined w i t h the wisdom of a number o f state governments, have led t o the adoption o f dead-line terms for decreasing the harmful gm contents in the atmosphere, especially those of SO:! and COL, in order
t o restrict possible environmental damage. Solutions are being sought in several directions: First, in reducing SO2 emissions by building up special facilities at electric power plants for purification of exhaust gases. T h i s method has an undoubtedly beneficial effect o n the environmental aspect of electric energy production, but it involves rather expensive, complicated and n o t fully efficient procedures leading t o increase in energy and power costs. Second, in building up a system of energy storage plants which haw a considerable impact o n the efficiency of energy utilities as well as significant cost benefits. Third, in t h c sphere of electric power consumption, a l l technological processes of m a j o r energy consumers have been revised w i t h regard t o power consumption, and the most energy-consuming procedures replaced by new technologies w i t h lower power demands.

The basic problems and the development trends o f energy storage w i l l be discussed in the chapters t o follow.

2. Electric energy storage


During the last few decades, several options for electric energy
storage have been devised. Many countries have started programs aimed at development of energy storage technologies. T h e basic principles of some of these options, that have found successful application, w i l l be outlined below.

2.1.

P u m p e d Hydroelectric Energy Storage Systems

(PHESS)
Figure 4 presents the schematic of such a system.

Fig. 4. Schematic of a Pumped Hydroelectric Energy Storage System.

These energy storage units require two large water reservoirs located at different heights, so that water fall is possible. D u r i n g periods of low demand, t h e excess power is utilized t o pump water f r o m the lower reservoir and transfer it t o t h e upper one. At peak demand periods, the pumped storage plant acts as a hydroelectric power plant thus adding capacity t o the energy system. T h i s storing option is cost-effective i f used only 5 t o 8 hours in the peaking range. I t s response t i m e is of the order of 5 t o 10 minutes. T h e above energy storage technology has been in use for over 50 years now. At present, there are about 35 pumped storage plants in operation a l l over the world w i t h a t o t a l capacity of 25,000 MW. T h i s energy storage option i s most appropriate for countries w i t h mountainous relief. Construction of these plants requires f r o m 8 t o 10 years and is often associated w i t h considerable environmental im-

pact. Pumped hydroelectric energy storage systems are cost-effective i f they are designed for power units of over 1000 MW. In Italy, for example, pumped storage plants supply 14% of the net power capacity. In Japan, they amount t o about 10% o f t h e national net capacity, while for France, Germany and the UK, this figure is 6%, and 3% for the USA. At the moment, more than 200 pumped storage plants are under construction worldwide. Consequently, by the beginning o f the next century, this energy storage o p t i o n w i l l become an i m p o r t a n t element of many national electric power systems.

2.2.Compressed-Air Energy Storage Systems (CAESS)

A compressed-air storage plant uses inexpensive off-peak energy


t o drive the motor of a compressor for compressing air that is stored
in a salt cavern located deep underground or in large hard r o c k caverns. D u r i n g peak demand periods, gradual release of pressure i s performed and the air coming up t o the surface i s heated by burn-

i n g o i l or gas, and is then expanded through expansion turbines that drive the r o t o r of an electric current generator. Compressor m o t o r and generator are combined in one machine. During air compression, t h e rnotor/generator i s connected t o the compressor and decoupled f r o m the turbine. During electric current generation, the motor/generator is disconnected f r o m the compressor and coupled t o the turbine. Compressed-air storage units burn only one third of the fuel used by conventional combustion turbines t o produce the same amount o f electricity. T h i s leads t o a two-third reduction in the environmental pollution caused by the combustion process of turbines which are usually located in urban areas. Ways have been sought for optimization of the system operation, such as return of the heat released during air compression back t o the energy system. T h i s energy storage option is cost-effective i f operated at a power above 25 MW.

For every hour of electric current generation, 1.7 k i of air compression


are needed. The response t i m e is about 10 minutes. Efficiency of air

compression is 65-75%. T h e starting period is 20 t o 30 minutes. As rcgards the security aspects, measures should b e provided against leakage of compressed air. T h e service life o f air-compressed storage plants is about 30 years.

A block diagram of such a system is presented in Fig. 5.

Fig. 5. Block diagram of a Compressed-Air Energy Storage System [2].

Compressed-air storage technology was first devised in Germany, and since 1978 a 290 MW, four-hour capacity unit has been in operation in Huntorf. The plant uses two salt caverns, and storage efficiency of over 80% is reported. T h e cost of unit power is about 425 $ kW-. A 30-year operational life of the plant is expected. Commercial operation of the German CAES plant has shown that this type of energy storage option i s sufficiently reliable.

10

Compressed-air storage plants have a negligible environmental impact, and can be built w i t h i n 2 t o 5 years. They arc: fit,ted w i t h modified combustion turbines of routine production. T h i s technology can find application only in countries w i t h n a t u r a l deep underground, h a r d rock or salt caverns. At present, several demonstration compressed-air energy storage plants are being built: in the USA, Alabama (110 MW, 26-hour capacity), in the USSR (1050 MW, 10-hour capacity, thrce-unit plant w i t h salt, cavern storage), in Israel (300 h'lW, l o - h o u r capacity, threeunit plant), etc. T h e Italian conipany ENEL has st,arted construction of modular mini-units of 25 and 50 MW, arid 10-hour capacity, using aquifer storage.

2.3. Superconducting Magnetic Energy Storage System (SMESS)


There i s a theoretical and a technical option t o store electrical energy as such, w i t h o u t converting it i n t o other forms. T h i s is possible owing t o the ability of some substances t o become superconducting at extremely low temperatures. Because of the conductor's electrical resistance at anibient temperature, p a r t of the electrical energy is lost in t h e f o r m o f heat emission (joule losses). These losses can be compensated by adding new quantities of electricity t o the power supply network. At extremely low temperatures, some alloys and ceramic materials achieve superconducting properties, i.e. they lose t h e i r electrical resistance. W h e n direct current is fed i n t o an electric circuit o f superconductors, the current w i l l circulate endlessly along the closed r i n g w i t h o u t energy losses. W h e n an energy demand appears, t h e requested electrical power can be drawn f r o m t h a t closed ring. Large-scale investigations are presently being performed aimed at devising a technology for the production of superconducting magnetic

11

Fig. 6. Schematic of a Superconducting Magnetic Energy Storage

System [2]. energy storage plants. A block diagram of such a plant is presented

in Fig. 6. T h e heart of this storage system is the electromagnetic superconducting coil. T h e latter operates o n direct current. Charging o f the electromagnetic coil w i t h electricity f r o m the ac generating utility is accomplished via a two-way converter. A refrigeration system maintains the temperature of the electromagnetic coil at a very low fixed value. Operation of the electromagnetic coil, converter and refrigerator is monitored and controlled by a controller. Such an energy storage plant should be sited near a substation where the transformer converts the high voltage energy f r o m the utility network t o appropriate low voltage power. T h e response time of this type of storage system for switching between charging and discharging is about 20 milliseconds. The ac-ac efficiency is 90% or more. T h e experimental SMES systems so far set up operate at extremely low temperatures -269C (4 K), the temperature of liquid helium) and the coil-wire used i s made of NbTi and NbSn alloys.

12

With the discovery of ceramic high-temperature semiconductors, it


can be expected that superconducting magnetic storage plants w i l l be constructed that are capable of operating at the temperature of liquid nitrogen (-196C). Since the technology for liquid nitrogen production is well advanced and cost-effective, t h e expenses for construction and maintena.nce o f the refrigeration system will b e reduced significantly. The current density in superconductive wires m a y reach extremely high values as t h e conductor exerts n o electrical resistance

leading t o joule losses. T h i s allows the wire cross-section t o be decreased more than five times w i t h respect t o copper wires used at ambient temperature. T h i s w i l l change substantially the existing classical electric power system. In Japan, an energy storage project is being developed k n o w n as the Moonlight Project. The power of the Japanese superconducting magnetic storage system is 1000 MW, energy density is 12 Wh kg-, storage efficiency SO-SO%, storage utilization rate approx. 75%. T h e system w i l l be used for daily and weekly energy storage. Underground bed rocks are required for construction of this system. Location possibilities are restrictcd, because antimagnetic measures are needed for environmental protection. Protect i o n against superconductive material degradation is also necessary.

A 10 MW, two-hour capacity SMESC pilot plant has been developed in the USA. T h e refrigeration system is based o n liquid helium.

2.4. B a t t e r y Energy Storage Systems ( B E S S )

2.4.1. The revival of battery energy storage systems

At t h e beginning o f this century, electric power supply for industrial and domestic needs was provided by dc generators arid battery facilities operating under floating charge conditions. D u r i n g this pe13

riod, batteries proved t o be a diverse and flexible means of solving the load factor problem. During the 1930s, an expansion of ac technologies for electric power generation, transmission and distribution applications was noted and, very soon, the dc battery system was abandoned and hence also t h e storage of energy as an element of t h e power system.

In the 1960s, a powerful reliable and cost-effective static rectifier was devised. Nuclear power plants were equipped w i t h large
stand-by lead-acid battery storage facilities ensuring their reliability by supplying reserve power and energy. N e w and innovative elect r i c power applications in industry and every-day life brought about radical changes in the profile of the daily, weekly and seasonal de-

m a n d ciirves. To enhance the operational efficiency of electric power utilities, energy storage units were introduced. At first, pumped hydroelectric energy storage plants were used for t h a t purpose, and later, the old lead-acid battery storage systems were revived. T h e y were based o n t o t a l l y new conversion, management and control technologies. A t t h e end of the 1970s, for the first time, BEWAG-AG decided t o install the B a t t e r y Storage Facility in West Berlin under a test program in order t o collect the necessary operational and technical information. I t started operation in July 1981. Within the Moonlight energy storage project, a 1 MW/4 MWh load-levelling battery plant started operation in 1986 in Tatsumi, Japan. In July 1988, t h e largest battery plant for load-levelling (10 MW/ 40 MWh) was set in operation in the USA, at Chino, California. Since then, many technologically advanced countries throughout tlie w o r l d have started large-scale research and test programs aimed at the introduction of battery energy storage systems in their national ccoiioinies and public services.

14

2.4.2. Basic principles of battery operation

When t w o appropriately chosen electrodes are immersed in the


respective electrolyte and a direct electric current f r o m a n external source flows between them, electrochemical reactions proceed o n the electrode surfaces during which inactive substances are transformed i n t o electrochemically active ones. This process is called charging of t h e electrochemical power source or t h e battery. As a result of these reactions, electrical energy is converted to chemical and an electromotive force is created between the two electrodes. When the electrodes are interconnected v i a a load, under the action of this electromotive force, electrocheniical reactions proceed o n the electrode surfaces in an opposite direction t o the reactions during charge. T h i s process of current generation is called discharge. T h e

battery can endure thousands of charge-discharge cycles. However, parallel t o the reversible processes of charge and discharge, certain
low rate irreversible processes also take place that limit batt,ery cycle

life.
D u r i n g off-peak periods, the battery is charged f r o m the electric power utility via a converter. The latter converts the alternating current i n t o dc. During discharge, the direct current generated in the battery is transformed by t h e converter iiit,o alternating current and the latter i s delivered through the tramfornier t o the utility for meeting energy demands. Operation o f t h e converter arid the battery
are monitored and controlled by a controller,

2.4.3. Some advantages of battery energy storage systems


In t h e process of developnient of the new generation of BEC systems, lead-a,cid batteries were widely used, which allowed t h e latter to exhibit a number of useful advantages leading to significant cost beneits. The following ecoiioniical features of lead-acid battery storage systems were demonstrated.

15

a) Modular design. Construction of BES plants is realized on a modular basis, i.e. through connecting of the individual b a t t e r y cells, in parallel and/or in series, various configurations could b e obtained

for any desired voltage, power or ampere-hour capacity. This allows BESS construction t o b e accomplished in stages according t o demand needs. b) Short construction terms. All BESS elements are produced at the factories w i t h i n a few months only and then the actual building of t h e BES plant i s reduced t o installing, assembling and testing of these elements in a working system. c) Small environmental impact. Battery energy storage systems are basically closed systems. No other materials are consumed except water, and hence n o air and environmental pollution is caused. T h e y are quiet and can be located near, and even in, housing c i t y areas. d) H i g h level of recycling of the materials employed a the n batteries. At the end of a battery's service life, many of t h e materials used for i t s manufacture can b e regenerated.
F r o m the above, it follows t h a t the revival of BES systems during the 1980s i s a normal process based o n the rapid progress of electric power industry. To b e economically effective, BES systems should meet t h e following challenging performance requirements:

30 years of service life o 75% ac-ac efficiency o Unit power cost about 400-700 $ kW-' e 5 hour discharge.
o

Many projects are being implemented at present worldwide aimed at achieving the above parameters.

16

2.5. Choosing t h e right option for electric energy storage


W h e n deciding o n the type of off-peak energy storage system t o adopt, the following considerations should be taken i n t o account:
o profile o f t h e 24-hour
o available budget
0

demand cyclogram and i t s possibilities

national topographical peculiarities o environmental aspects and limitations. According t o a n EPRI investigation, there are a great number of hard rock caverns in the USA, which suggests dominating importance of off-peak energy storage through compressed-air storage plants. Second in importance are battery energy storage systems, and pumped hydroelectric storage facilities come third.
In Italy, owing t o i t s pronounced mountainous relief, pumped hydroelectric energy storage systems have proved t o be most costeffective, and hence this country, together w i t h Japan, occupy t h e leading positions in the construction of this type of storage plant o n

a worldwide basis.

EPRI in the USA have carried o u t an analysis of the economics of the various options for energy storage. T h e results of these evaluations are summarized in Table 1.

An analysis of the results indicates that battery storage systems and superconducting magnetic storage systems are more appropriate for use when there are peak demands w i t h a duration of 2 t o

3 hours. P u m p e d hydroelectric storage plants and compressed-air storage systems may cover efficiently peak power demand needs of up to 10 hours. T h e y can also function as intermediate load power
systerns.

17

Table 1. Estimated costs for energy storage technologies [2]


~ ~

Technology

Power Energy Hours of Total related related storage cost $ k W - ' $kWh-' $ kW-' Small module (25-50 M W ) Large module (110-220 MW) Conventional (500-1500 M W ) Underground (2000 M W ) Lead-acid (10 M W ) Advanced (10 M W )

Compressed-air

575 415
1000

5
1

10
10

625
425 1100

Pumped hydro electric

10 45 170
1 O0

10
10

1040 125 125 150

1490 635 425 975

Battery

3 3 3

Supereconducting (Target) magnetic (1000 MW)

275

T h e unit power costs are highest for pumped hydroelectric plants, owing t o the large capital costs for construction of the facilities. With regard t o the unit energy storage costs, this type of storage option is considerably cost-effective. Total costs ($ kW-') for compressed-air and battery storage units show similar values. T h e above rating of the various energy storage options will, o f course, vary for the various countries, depending o n their specific economic and technological conditions and requirements.

18

3 . Batteries for energy storage t i o n and under development

in opera-

3.1. Development projects for battery energy storage systems


T h e Moonlight Project is the nickname of an RSrD prograin for energy storage in Japan. T h e nanie nioonlight was selected t o imply the analogy between the nioon that does n o t sliine with i t s o w n light but reflects the suns light, arid the energy storage batteries that do n o t generate their o w n energy but dispatch the stored electric power produced by another source. T h e Moonlight Project includes six progranis, one o f which is the Advanced B a t t e r y Electric Power Storage Systeni. Sonie o f the basic functions o f this system will b e discussed below. T h e Electric Power Research Institute in t h e USA lias beeii carrying out research and developirieiit activities within the Energy Storage Program since 1972. T h e profirani incliirlcs dcvclopIricrit o f leadacid and advanced batteries. Both programs are haced o n almost t h e sanie electrochemical systems. First, the lead-acid battery has been chosen as a basic chemical power source commercially available. R&D activities are aiming at adapting, b o t h f r o m a constructional arid technological p o i n t o f view, this 100-year o l d battery t o t h e requirements o f energy storage. Second, new electrochemical power sources aie being investigated and developed, such as: sodium/sulfur, zinc/chloride, zinc/broniide and redox/Aow batteries. Japans project i s targeted at devising a demonstrational model of a battery energy storage system with t h e following parameters:
o power o u t p u t

o charge t i m e o

1 MW 8h discharge t i m e 8 h
~

19

o overall energy efficiency o service life


~

min. 70% (at ac input/output) min. 10years (2000 cycles)


-

Batteries should conform t o all environmental standards [4]. Analogous specifications have been adopted by the American 10 MW demonstration battery storage plant. Several demonstration and testing battery storage facilities using lead-acid batteries have been built and are in operation in other countries in the world. T h e testing results of these units will be discussed later. The basic properties and characteristics o f the socalled advanced batteries w i l l be described first.

3 . 2 . Sodium/Sulfur b a t t e r i e s

3.2.1. Principles of cell operation

The sodium/sulfur cell consists of a negative electrode (cathode) of molten sodium (Na) and a positive electrode (anode) of molten
sulfur separatkd by a beta-alumina (P-Al20,) ceramic ion-conductive membrane. T h r o u g h this membrarie, only sodium ions can pass, but A block diagram of a sodium/sulfur cell is given in Fig. 7.
not electrons or sulfur ions.

Sodium

Ij-oiumino

Sodium polysulfide

NO

S.NOS, (X.3i5)

Fig. 7. Block diagram of a sodium/siilfur celi [5].

20

The reactions that proceed in the c e l l can be expressed by the


following ecpiation:
Discharge

2Na+2S

+
Charge

Na&

( x = 3-5)

D u r i n g discharge, metallic sodium of the negative electrode is ion-

ized t o positive sodium ions (Nat) and electrons are released. The sodium ions pass through the beta-alumina membrane and reach the positive sulfur electrode. The electrons released o n the negative electrode flow through an external circuit, pass through a load whereby certain useful electric work i s done, and reach t h e sulfur electrode. There, they are bonded t o the sulfur atoms and f o r m sulfur ions (S2-). These react, w i t h the sodium ions giving sodium polysulfide

(NazS,). There i s a voltage of 2 V between the sodium and the sulfur electrodes. Under the act,ion of this electromotive force, the above
reactions procecd and electrons move f r o m the sodium t o the sulfur electrode doing some work. During charge, reverse processes take place. In this case, electric energy shoiild he introduced i n t o the cell t o enable proceeding of the reverse processcs. Under the action of an external \-oltage applied t o the cell, electrons f r o m t h e polysulfide electrode move back, through

t h e external circuit, t o the sodium electrode. As a result, the sulfur


ions of the polysulfide molecule (Y) are transformed i n t o sulfur atoms, and the released Na+ ions pass through the beta-alumina membrane and are bonded t o the electrons forming sodium atoms.

For the battery t o operate, a temperature o f about 350C should be maintained. In this way, b o t h sodium and sulfur are kept in the

liquid state and the resistance of the beta-alumina membrane is very


low. Figure 8 shows the voltage curves during charge and discharge of the battery, as a function o f the composition of sodium polysulfide.

21

0 i O 2 0 3 0 0 4 0 5 0 7 0 8 0 9 0 1 0 0
S
Discharge composition, O/. Na253

Fig. 8. Cell voltage us. sodium polysulfide composition during charge and

discharge [6]. T h e voltage characteristics depend on the temperatiire and t h e composition of sodium polysulfide. Figure 9 illiistra2tc:s tlic changcs in the open circuit voltage as a function of anodc coinpositioii.

300'C
A
0

330T 360.C 390'C

0.60 0.65 0.70 0.75 0.80 0.85 0.90 Anode composition (mole ratio of sulfur)

0.95

Fig. 9. Open circuit voltage as a f i i n r t i o i i of molar r a t i o of s i i l f u r iiis o d i u m

polysulfide [5].

22

W h e n the molar r a t i o of sulfur t o polysulfide falls below 0.7, the cell voltage begins t o decline. T h e sodium/sulfur battery i s hermetically sealed and completely maintenance-free. There are n o side reactions during charging and discharging. I t is free o f self-discharge. T h e state of charge can be easily monitored by measuring the amounts o f electricity (Ah) charged and discharged.

3.2.2. Design of sodium/sulfur cells


Schematic of a sodium/sulfur cell is given in Fig. 10.

A
r

ss
*

N . l

Insulolion ring (olumina ceramics)

Anode cose iron 1 Anode (sulfur. graphite (el t )

Solid electrolyte tube (cilumino ceramics)

-Colhode ( sod ium , metollic liber)

L C o t h o d e tube (copper)

1
Fig. 10. Principal design of sodiurn/sulfur unit cell [5]

T h e beta-alumina membrane is a cylindrical t u b e w i t h a b o t t o m at one end. Sodium is filled inside this tube, and sulfur and sodium

23

polysulfide in a metal cylindrical case outside t l i c tiihc. At the upper opening o f the beta-alumina tube, the anodc, the cathode and the metallic case are connected arid welded t,ogct,lic,r with insiilat-

ing ceramics in between. A graphite niat is i n s e r k d in t l i c anodic space aimed at improving sulfur and polysulfide clcctric conductiw ity, whilst in the cathodic space, a stainless steel fibcr is placed t o conduct the current. T h i s fiber retains sodium and is also i i i k n d e d t o prevent release o f sodium in the everit of brcakagc of the betaalumina tube, thus having an iinportant safety role. T l i e nieta1 case surface i s plated with chroniiuni t o prevent corrosion i i i i d c r tlie action
o f sulfur and sodium polysulfide. Na/S cells are arranged in a tlierrnoinsulatcd c a e with a iiiaiiitained constant temperature o f 350C. Before operation, the batt,ery is pre-heated gradually t o 350C, arid only after that does tlie normal operation of charging and discharging start. Further heating by the heaters is barely needed since the h t t e r y gciierates r c x t i o n heat.

3.2.3. Specification and test results for battery modules and


p i l o t plant o f t h e Japanese Moonlight Project

A 50 k W / 4 0 0 kWh sodium/sulfiir battery module has been produced by the YUASA company in Japan. T h e o u t p u t capacity of the plant is 8000 kW1i (1000 kWh x 8 hours). Output voltage i s 1000 V dc, o u t p u t current 1011 A dc. T h e technical results f r o m testing o f various configurations of the above battery t y p e are summarized in Table 2. T h e sodium/sulfur bat,tery plant is located at the Tatsumi substation 77 close to t h e Tatsiimi lead-acid battery energy storage test plant. By the end o f 1990, the 1 M W / 8 MWh sodium/sulfur pil o t plant was half completed and operation of 500 1iW o u t p u t was started in November 1990.

24

Table 2. Technical results from testing of a sodium/sulfur battery produced by YUASA Battery Co. Ltd.

10 kW class p i l o t modules [7]

Energy density

- per -per

footprint volume - per weight

Starting time Stopping t i m e Response t o load change Discharge 6 h overall eff. 4 h overall efT. Voltage variation - on charging on discharging Energy consumption in standing hot standing - cold standing
~ ~ ~ ~

52.4 kWh m-2 26.8 kWh m-3 42.6 Wh kg-' 1s 1s 10% 1.2 ins-'
76.S% 73.6%

11.8% 4.2% 19.4% day-' 0%: day-'

50 kW class battery modules [SI

Voltage Current
output

Capacity Current density Electrode area Module composition External dimensions Energy efficiency ac-ac Energy density per weight - per volume - per footprint
~

200 v 250 A 50 kW 400 kW11 50.5 m.4 an-' 495 cm2 (7s x lop) x 1Gs = 1120 cells Width = 2.5 m Length = 2.3 m Height = 2.8 m Weight = 12.8 t 76.6% 31.1 Wli kg-' 17.5 1tWh mP3 48.5 kWh in-'

25

Table 2. (Continued)
1 M W class pilot plant [8]

Beta-alumina tubes: outer diameter length weight beta-alumina doped w i t h Li20 specific resistivity tube resistivity fracture strength Capacity of the cell Battery output capacity Output voltage Current ac-dc converter Conversion efficiency Output transformer Number of cells Building area Charge/discharge efficiencies dc-dc efficiency (including aux. power consumption) ac-ac efficiency

68 mm 450 mm 3.6 kg

< 4.5 R c m at 350C 8 m > 200 MPa > 300 Ah 8 MWh (1 MW - 8 h) ac 6.6 kW dc 1.0 kV dc 1 kA self-commutated 1200 kVA up t o 96% ac reactor 240 kVA 26,880 cells 800 m2 (total for 2 floors) approx. 87%
86%

approx. 76%

The batteries for this project were made by YUACA Battery Co. L t d . in collaboration w i t h NGK Spark P l u g Co. L t d . The power
conditioning system was manufactured by Toshiba Corporation. Figure 11 shows a birds-eye view of a 1 MW sodium/sulfur pilot plant consisting of twenty 50 kW battery modules. Sodium/sulfur batteries have high charge and discharge efficiencies w i t h no loss of energy during storage. The batteries are compact

w i t h high storage energy density. Individual Na/C batteries subjected t o testing have undergone 1500 cycles already.

26

Environmental proieciion equiprneni

Machinery room

Fig. 11. Birds-eye view of 1 MW sodium/sulfur pilot, plant [7].

Basic trends in the design of Na/S batteries are targeted at optimization of specific energy and efficiency, and at preventing reactant leakage f r o m t h e cells. Safety is the key t o practical use of these batteries and o f course t o extending their life, too. Whether or not this type of battery w i l l h o l d an i m p o r t a n t posit i o n in the energy storage system, w i l l depend on i t s service life, o n the competitive power of i t s price t o that of the lead-acid battery, o n t h e simplicity and cost-effectiveness of i t s production technology yielding reliability of the end product, and easy and inexpensive operation and maintenance of the battery. These are all questions that await answers in the near future.

27

3.3. Zinc/Bromine batteries

3.3.1. Reactions and principles of cell design and operation


D u r i n g the Franco-Prussian war, French balloonists flying over the Prussian lines illuminated their maps by means of strange primi t i v e static batteries containing zinc and bromine. T h i s i s the first k n o w n historical evidence of the invention and practical use of a zinc/halogen battery. I t should be recalled that the lead-acid battery was also devised by a Frenchman. I t would b e fair t o say that during the last century, France was a pioneer in the discovery and development of new electrochemical power sources. Early zinc/bromine batteries had probably proved inefficient in performance and maintenance, and were therefore forgotten until the 1970s. As a result of the A r a b o i l embargo, interest in electrochemical power sources increased greatly worldwide, and t h e question of devising new advanced battery systems gained momentum. Zito, Magnetti-Marelli and E x ~ o rResearch and Engineering (ER&E) were attracted by the i high electromotive force provided by Zn/Br batteries and started design and development work o n this t y p e of battery. MagnettiMarelli developed an electrolyte circulating battery design, whereby the performance of b o t h the zinc and the bromine electrodes was enhanced. ER&E combined the ideas of circulating electrolytes, liquid bromine complexing agents and the use o f low-cost conductive plastic electrodes. At first, 20 t o 60 kWh batteries for e!ectric vehicles were manufactured and, o n testing, these showed encouraging performance parameters. Later on, zinc/bromine batteries were also developed for load-levelling applications. Operation of Zn/Br systems is based o n the following reactions:

ne
Brz+

Zn2++
T- -L 2e-

2e-

2Br-

external circuit

28

W h e n the reactions proceed in t h e direction from l e f t t o right, b a t t e r y discharge occurs, whilst in t h e reverse direction, charging of t h e b a t t e r y i s accomplished. T h e theoretical electromotive force of this battery i s 1.83 V, but since complexing agents are involved, t h e open circuit ce11 voltage is lower, namely 1.76 V. T h e theoretical energy density i s 436 Wh kg-', while t h e practical one is only 65 Wh kg-'. O t h e r characteristics are: p e a k power 95 W kg-', d e p t h of discharge loo%, and energy efficiency 60-65% [9]. T h e zinc/bromine b a t t e r y operates at ambient temperature. Although i t is an electrochemical system using aqueous electrolyte, no decomposition of water is observed during charge. T h i s system faced a serious problem related t o t h e rapid selfdischarge caused by t h e p r o p e r t y of bromine to dissolve readily in zinc bromide electrolytes and to diffuse t o t h e zinc electrode osidizing it. To avoid t h i s process, it was necessary to remove b r o m i n e from t h e zinc electrode, and t o divide t h e anodic and cathodic sections of t h e cell by a separator. Thus, a cell design \vas developed in which t h e bromine compartment of t h e cell was connected by nieans o f a t u b e t o a storage compartment for collecting t h e evolved bromine. T h e electrolyte, forced by a pump, circulated between the electrodes and t h e storage compartment. T h i s design principle lias l e d t o a significant decrease in b a t t e r y self-discharge, but lias n o t eliniiiiated

it completely. A schematic of the zinc/bromine system i s 1)reseIited in Fig. 12. A t o m i c bromine formed on t h e electrode i s indicated by t h e dots in t h e figure. T h i s t y p e of b a t t e r y construction has solved anotlicr p r o b l e m of zinc/bromine batteries as well. that of t h e zinc electrode. In the early static battery design, zinc deposited on t l i e clectrode iii t h e form of non-uniform dendritic plating. Dendrites s o n i d m e s grew across to t h e bromine electrode aiid caused short circuits in t h e cells. By introducing electrolyte circulation also in t l i e zinc half-cell, t l i e zinc deposit, formed over the electrode surface duriiig charge, becaine

29

more u n i f o r m and shortages were eliminated. Complete discharge is required for every charge-discharge cycle t o equalize the zinc distrib u t i o n over t h e negative electrode surface.
Cathode loop
Anode loop

Zn deposit

Fig. 12. Schematic of

circulating electrolyte Zn/Br battery [9].

T h e double circulation loop battery design also proved beneficial for the thermal management of the cell. In static zinc/bromine batteries, the reaction heat was accumulated in the cell. With t h e introduction of electrolyte circulation, the temperature of the electrolyte becomes controllable and thermal homogeneity of the whole electrochemical system can be achieved. Circulating electrolyte batteries require various auxiliaries t o cont r o l battery operation. Obviously, their efficiency will influence the power consumption for actual cell operation and hence affect overall battery efficiency. T h e power of an electrochemical power source is, as a rule, proportional t o the electrodes surface area, while i t s capacity is determined

by the amount of active materials that takes part in the electrochemical processes. T h r o u g h the adoption of the bromine circulation loop and the storage compartment, the quantity of this active mass com-

30

ponent grows significantly. T h e zinc circulation loop also increases the volume of t h e electrolyte and hence the quantity of zinc ions. a Nevertheless, zinc h s remained the capacity limiting active material. Batteries designed for high-power applications comprise a large number of zinc electrodes with relatively thin zinc p l a t i n g deposited o n their surface. W h e n high battery capacity is needed, the thickness of the Zn electrodes is increased. T h e cathodic half-cell is divided f r o m the anodic one by means of a microporous polyethylene separator with pore radius smaller t h a n

1 pm. Such separators are commercially available and are widely used in lead-acid battery manufacture. T h e separator displays barrier properties w i t h respect t o bromine diffusion, but it is permeable for the solution ions that carry the electric charges between the two
electrode sections of the cell. Bromine is a strong metal-corrosive agent. Consequently, the

problem of material resistance t o oxidation is of primary importance for this battery. Fortunately, most o f the commercially available

and relatively low-cost plastic and carbon materials meet the above requirements, which w i l l make t h e large-scale production of these batteries feasible and cost-effective f r o m an engineering point of view.
However, improvement of the overall battery construction reliability

is necessary t o eliminate a l l hazards of explosion or bromine leakage in the atmosphere.

3.3.2. Chemistry and electrochemistry of the zinc/bromine cell


D u r i n g charge of the zinc/bromine cell, bromine evolved at t h e electrode associates w i t h the bromide ions and dissolves easily in the solution of zinc bromide:

nBr2+ Br-

BrGn+l)

(where n = 1,2 or 3)

31

Trihromitle ions (Br:) are formed first, then pentabromide (Br;) and eventually heptabromide (Br;). When the concentration of bromine rises significantly, it is evolved as a separate liquid phase collected in a special bromine storage compartment. In spite of this, however, bromine concentration in the solution remains relatively h i g h and hence considerable self-discharge proceeds.

A second nieans of bromine storage has also been applied, i.e. as


a complexed form. In this case, complexing agents are added t o the

electrolyte, t h a t react w i t h bromine forming a separate phase which i s collected through precipitation in the storage reservoir. Various complexing agents have been used, e.g. quaternary ammonium ions, n-ethyl, n-methyl-morpholinium bromide oil, etc. A possible electrolyte composition of a discharged zinc/bromine cell is: zinc bromide

3 M, quaternary ammonium bromide 1 M, KC1 4 M as supporting electrolyte [g].


D u r i n g discharge of the zinc/bromine cell, the valve between the
Br2 complex storage department and the circulation loop is opened.

Brz complex is mixed w i t h the solution in the circulation stream and


i s p u m p e d t o the bromine electrode where i t is reduced t o bromine

ions. At the other electrode, zinc is oxidized t o zinc ions. These react w i t h the bromine ions forming zinc bromide. These processes are accompanied by release of the electrical energy accumulated by the cell during charging. T h e charge/discharge voItage characteristics o f the cell are shown in Fig. 13. During charge, a slight linear increase in cell voltage i s observed. D u r i n g discharge, the voltage decreases very slowly at the beginning, and as a result of complete exhaustion of the zinc resources, the cell voltage drops rapidly at the end of discharge. Coulombic efficiency o f the zinc/bromine c e l l is about 80% (i.e. 20% is inefficient). T h e inefficiency is mainly due t o electrode self-discharge. Other sources o f inefficiency are the energy losses for driving the

32

electrolyte pumps, as well as for supplying power t o t h e b a t t e r y cont r o l and management system and t o i t s microprocessor.

Discharge
L

60

120
Tlme. min

I80

U0

Fig. 13. Charge/discharge curves for

zinc/broniine c e l l [9].

3.3.3. Battery system design


ZincJbromine batteries have been designed in two niodifications, w i t h monopolar and w i t h bipolar electrodes. These two battery designs are shown in Fig. 14.
Bipolar orrongement Electrolyte
t -

Monopolor orrangements Manifold Eledrdyte

O E 2E3E4ESE

t t t t t t

EMF olong m n i f o I d = ( n - l ) E . where n = No, of cells ond E = call voltogc

EMF olong monifoid O os all electrodes


of the some polarity ore connecled

Fig. 14. Bipolar and monopolar stack designs for Zn/Br systems

[lo]
33

In t h e monopolar version, there are separate positive and negative

electrodes, and all monopolar electrodes are connected in parallel. Ii i t h i s way, high battery power and low voltage are achieved. T h e bipolar battery design uses electrodes which have one zinc and one bromine side. These bipolar electrodes are connected in series, only the end electrodes being monopolar. Cell-to-cell current flows f r o m the entire electrode surface and is carried through i t s thickness. T h e o u t p u t is h i g h voltage and low current.
In energy storage batteries, a definite number of cells with bipolar electrodes are arranged in series. These strings are connected in parallel forming a module w i t h the desired voltage, capacity and power.

3.3.4. Characteristics of zinc/bromine batteries


Table 3 presents the specifications of a 10 ltW/SO 1tWh battery used for testing. T h i s is a reduced-size model of the 50 k W / 4 0 0 kWh battery module for the 1 MW p i l o t plant wliose parameters

and testing results are also given in the table. These batteries were developed by Meidensha Electric Manufacturing Co. Ltd. in Japan within the framework of the Moonlight Project.
T h e 1 MW battery energy storage plant is installed o n the premises of the Imajuku Substation in the Western part o f Fukuoka City. I t was constructed f r o m November 1989 through September

1990. Operation tests started in December 1990 and will continue till M a r c h 1992. T h i s i s the largest Zn/Br battery in the world.
Interesting and useful testing results are expected.

34

Table 3. R esul t s from testing of Zn/Br battery modules produced by M e i densha Electric Manufacturing Co., Ltd, Japan. T h e t e s t s were performed
at t h e Government Industrial Research I n s t i t u t e ,

Osaka [7].

10 kW battery [7]

Configuration

Unit cells

Open c i r c u i t voltage
Maximum charging voltage

Charging power Discharging power


Energy density
- per
~

footprint per volume - p e r weight Dimensions - width - depth - height Starting time 1 s Self-discharge rate 7.4% 1 s Stopping t i m e Change time charge-discharge 1 s Change t i m e discharge-charge 1 s Response to load change 10% 0.9 m s Discharge - 6 h capable eff. 68.3% - 4 h capable eff. 66.5% Voltage variation - on charging 19.9% - on discharge 15.5% 0% Energy consumption in standing Test cycle life appr. 550 cycles End of battery life was due t o carbon plastic electrode degradation

(24 cells in series x 3 series in parallel) x 4 in parallel = 360 1600 cm2 x 13 mA cm-' 1.67 V x 166 Ah18 h 43.8 V 50.0 V 12.7 kW 10.0 kW 33.6 kWh m-' 14.9 kWh m-3 29.1 Wh kg-' 1.37 m 1.59 m 1.67 m

35

Table 3. (Continued)
50 kW class battery module [8]

Voltage
Current Output power

100 v

Capacity
Module configuration

External dimensions

width height

- length
~

Weight

Energy efficiency ac-ac Energy density - per footprint per volume - p e r weight
~

500 h 50 kW 400 kWh (30 cells in series x 24 series in parallel) x 2 in series = 1440 cells 3.9 m 1.6 m 3.1 m 16 tons 73.2% 63.1 kWh m-2 20.7 kWh mP3 25.0 Wh kg-'

I m a j u k u Energy Storage Test Z n / B r Plant

[SI
~

Output capacity Output voltage


current

ac

ac-dc converter Output transformer Number of batteries Number of ceils

4.4 MWh ( 1 M W 4 h) 6.6 kV; dc 1.1k V dc 1 k A self-commutated 1000 kVA self-cooling 1200 kVA 24 submodules (series) 30 cells (scrics) x 24 stacks (parallel) x 24 submodules (series) = 17,280 cells 23 kW 8 tons 1630 mm 1520 mm 3150 mm 735 m2

Submodule battery
output power

weight
dimensions
- width - depth - height

Building area

36

3.4. Ziric/Chlorine batteries 3.4.1. Fundamentals of zinc/chlorine batteries


T h e electrochemical reactions o n which operation of this t y p e of battery is based are as follows:

Z n e Zn2++ T-L

2e-

external circuit

C12+

2e-F=+

2C1-

D u r i n g battery discharge, the above reactions proceed f r o m left t o right, and in the opposite direction during charge. T h e theoretical voltage o f the Zn/Cl- cell is 2.12 V. It is higher than that of the Zn/Br cell. Since n o complexing agents are used, the open circuit voltage of the Zn/ClL cell has a value equal t o the theoretical one. T h e theoretical energy density is 465 Wh kg-' against 60 t o 80 Wh kg-' in the practical circuit depending o n cell design. T h e d e p t h of discharge i s 96% [9]. Zn/C12 batt,eries are similar t o Zn/Br ones. However, bromine and chlorine differ in chemical and physical properties. At ambient temperature, chlorine is gaseous, while bromine is a reddish-brown liquid. Consequently, different methods for storage of the t w o halogens in the cell reservoirs should be used. T h i s leads t o substantial differences in design of the t w o types of zinc/halogen cells. Chlorine is slightly soluble in zinc chloride solutions. For this reason, during charge, chlorine is evolved in the f o r m o f bubbles that leave the electrolyte forming a gaseous phase. T h i s gas should b e collected and stored in an appropriate manner, t o b e fed back i n t o the solution and reduced t o chlorine ions at the electrode, when elect r i c current is delivered by the battery. So far, there have been t w o methods for chlorine storage in use. In the first method, chlorine is compressed until liquefication and is stored as liquid chlorine at pressures of 70-80 psig. W h e n electric current is to be generated by the

37

'u
E
.-

2.18 v

5 40--- ~ ~ L c E 2 - - ~ jg 2010(

1 7 - - 7\ -- ?
40
cm-2
FUII

1 1.75v cut aff voltoge


pwer
coulmblc Usable
I l

- 2.4 2.0 - -1.6 u


-1.2

--cl8 %

20

Charge
( 1 1 1 1

coubmk+ Discharge
I l I I I

- 0.4

T h e cell is charged at a voltage of 2.25 V. During discharge, the cell voltage is kept at the 1.9 V level for a long period of time. T h e discharge is carried down t o a cut-off voltage of 1.75 V. Voltaic efficiency is about 88%. Voltage losses are primarily due t o poor electrolyte conductivity between the electrodes. Coulombic efficiency is about 87%, capacity losses being due primarily t o the self-discharge caused by chlorine diffusion towards t h e zinc electrode. As a rule, n o separator is used in this type of battery. The n e t electrochemical efficiency is decreased, because part of the energy is utilized for supplying power t o the auxiliaries: gas and electrolyte pumps, the inert rejection system, the hydrogen recombination system and the cooling system

38

3.4.2. B a t t e r y design

EDAs (Energy Development Association, USA) Zn/Clp battery


design [5] is based o n the use of graphite electrodes, a single chlorine circulating loop and cooling of the electrolyte and t h e gaseous phase t o f o r m C12(H20),. A schematic of E D A s Zn/C11 battery is shown in Fig. 16.

e I

heat exchanger

Fig. 16. Schematic of t l i e c i r c u l a t i n g zinc/chlorine b a t t e r y [9].

T h e battery is composed of an electrochemical module (electrode stack) and electrolyte of zinc chloride solution w i t h added potass i u m chloride ( t o improve electrolyte conductivity). Using tubes and pumps, an electrolyte circulation loop is formed. Zinc is deposited o n the cathode. For a uniform plating t o be formed, the current density should be in t h e range f r o m 20 t o 45 mA crnp2, and zinc loading between 90-300 mAh crnv2. Chlorine evolved o n the anode is removed f r o m the stack and pumped i n t o the hydrate storage reservoir. To allow formation of chlorine hydrate, prior t o mixing with chlorine the electrolyte is cooled by a refrigeration system. In the hydrate reservoir, an ice-lile slurry o f chlorine hydrate is stored.

39

D u r i n g battery discharge, the cooled hydrate slurry froiri t l i e storc is passed through a heat exchanger, where chlorine liydrntc i s tlcconiposed. T h e chlorine-rich stream is then pumped t o the anode wliere chlorine is reduced to chloride. On the negative electrode, zinc is osidized t o zinc ions that react w i t h chloride ions giving zinc cliloride. In the course of these processesi the electrical energy stored during charge i s liberated, i.e. doing work. T h e chlorine electrode i s made of a porous graphite material. I t s surface is activated. T h e chlorine-containing solution passes through the pores of t h e graphite electrode, whereby chlorine is transformed t o chloride ions ( flow-through electrode). (In t l i e zinc/bromine cell, the bromine electrode i s of the flow-by type.) T h e rate of the chlorine-rich electrolyte stream deterniines the rate of battery discharge. Self-discharge of the zinc/chlorine battery i s caused 1)y t h e react i o n between zinc and chlorine. Electrolyte circulatioii aims at faster removal of chlorine f r o m the electrode st,acli and hencc rcdiiciiig the self-discharge. Zinc/chlorine batteries tend t o release hydrogen, because they operate w i t h acidic solutions. Zinc corrodes in acidic electrolytes evolving hydrogen. This hydrogen should be bonded t o chlorine, v i a ultraviolet irradiation, for example. In this way, potential hazards of explosions in the chlorine storage reservoir are avoided. Zinc/chlorine battery design is usually based o n bipolar electrode stacks.

3.4.3. B a t t e r y characteristics
Design and development of a zinc/chlorine battery associated with the Energy Storage Project in Japan was carried o u t by the Furukawa Electric Co. Ltd. T h i s company has developed 1, 10 and

40

50 kW battery configurations. The test results for 1 kW and 10 kW


b a t t e r y modules, before completion of t h e cycle life tests, are presented in Table 4. A f t e r a critical analysis of the technological, performance and economical parameters of the above b a t t e r y modules, further development of zinc/chlorine batteries was interrupted. T h i s t y p e of b a t t e r y poses serious environmental hazards since chlorine is a toxic

gas.
T a b l e 4. Some results f r o m testing o f 1 kW and 10 kW Zn/Clz b a t t e r y m o d u l e s p r o d u c e d by Furukawa E l e c t r i c Co. Ltd. T h e tests were p e r f o r m e d at t h e G o v e r n m e n t I n d u s t r i a l Research I n s t i t u t e , Osaka [7].

1 kW battery

Configuration

30 cells in series x

Unit c e l l - voltage
- capacity

2 series in p a r a l l e l 2.0 v

O p e n c i r c u i t voltage

Charging p o w e r
D i s c h a r g i n g p o w e r (8 h rate) C o u l o m b i c efficiency V o l t a i c efficiency E n e r g y efficiency Self-discharge r a t e
~

75 Ah16 h r a t e 63.0 V 1.41 kW 1.01 kW 84.0%


83.0%

70.5-76% 71.1% 68.7% 3.4% 67.9%


4.5%

initial energy efficiency

a f t e r t w o weeks self-discharge r a t e
- after

f o u r weeks

self-discharge r a t e

41

Table 4. (Continued)
10 kW battery

Module

Unit ceiis

Open circuit voltage


Maximum charging voltage

Charging power Discharging power (8 h) Energy efficiency - overall efficiency - coulombic efficiency - voltage efficiency - aux. power efficiency Energy density - per footprint - p e r volume - per weight Self-discharge rate Starting t i m e Stopping time Change time charge-discharge Change time discharge-charge Response t o load change Discharge - 6h capable eff. - 4 h capable eff. Voltage variation - o n charging - o n discharging Energy consumption on standing - hot standing - cold standing

(24 cells in series x 2 series in parallel) x 2 in parallel = 96 2800 cm2 x 22 mA 1.95 V x 495 Ah18 h 50.9 V 60.0 V 14.9 kW 11.6 kW
65.7% 86.5% 90.2% 93.4% 33.6 kWh m-2 14.9 kWh m-3 29.1 Wh kg-' 4.5% 2 min
1 s

2 min 77 min 10% 0.9 ms-' 60.5% 60.6% 7.5% 24.5%


0.7% 0%

42

4. Lead-acid batteries
4.1. Some history
In 1860, Gaston Plante presented t o the French Academy o f Sciences a 9-cell battery (composed of lead and lead dioxide electrodes

immersed in H2S04 solution and separated by rubber tapes) and a rep o r t entitled Nouvelle pile secondaire d une grande puissance. T h i s report was the birth certificate o f the lead-acid storage battery. (Dune grande puissance - what wisdom and foresight shown by Plante so many years ago! Today, over 400 m i l l i o n cars worldwide have engines driven by high-power lead-acid batteries. D u r i n g t h e period 1880--1900, lead-acid batteries found their first practical application in the early power stations. T h e y were used as a stand-by source of energy and power. With the progress of indust,ry and of dc-electroenergetics, production and usage of leadacid b a t k r i c s as energy storage facilities gained increasing popularity t o reach, in 1930, large-scale commercialization. In most towns in Germany, such as Berlin, Munich, Hamburg, Leipzig, Stuttgard and Bremen, large lead-acid battery storage facilities were in operation. T h e largest battery storage unit was in Berlin. It h a d a capacity of 66,500 1iWh a,nd was capable of delivering 186 MW of electric power w i t h i n 30 minutes. T h e c i t y of Chicago was supplied w i t h electricity

by dc generators and large leacl-acid batteries owned by the Common Wealth Edison Company. With the development of ac technologies for electric power generation and distribution in t h e 1930s, the dc battery system was abandoned, t o b e revived again during the 1980s. At present, a number of lead-acid battery energy storage facilities in various countries worldwide are under construction or in the
demonstration and/or actual operation stage. W e w i l l discuss the technical and economical aspects of lead-acid battery energy storage

43

technologies in the n e x t sections o n the basis of knowledge, experience and information obtained so far.

4.2. Electrochemistry of the lead-acid battery


T h e basic reactions that proceed in the lead-acid battery and determine i t s electromotive force (emf) are:

+
-

PbOz

+ 2H+ + HzS04 + 2e- +PbS04 + 2 H z 0


T P L
+- external circuit

Pb+H,SO,

PbS04+2Ht+2e-

These reactions together w i t h the corresponding charge/discharge curves of the cell are presented in Fig. 17.
DISCHARGE e-

. f- - ' + j

CHARGE
+ Z

Recti1ier

Positive plate

Negalive plate

7
I= 3.2 A

2.m
O

io
Time. h

20

io
Time, h

20

Fig. 17. A scheme of t h e charge and discharge reactions proceeding in t h e


lead-acid cell and t h e corresponding voltage transients.

44

Calciilatcd tlicrrriod~namically, voltage between t h e lead sulthe fate and t l i e lead dioxide electrodes in the cell i s 2.040 V, but the open circuit voltage i s iisually taken as 2.0 V (rated voltage). T h e tlieoretical specific energy of the cell is 170.2 Wh kg-. To transf o r m the lead-acid cell i n t o a practical power source, several design requirements must b e rnet. Lead and lead dioxide active materials are b o t h porous. Part o f the active mass acts as a conductive sl<elet,on, and another part (30 t o 55%) participates in the reactions leading t o generation and acciiiiiiilatioii of cncrgy. T h e active materials are fixed in lead-based grids that are chemically resistant t o H2SOS solution. T h e positive and ncga2tive plates are separated by microporous separators that arc iori-permeable and chemically resistant t o H2S04, 0 2 and HL. T h e cell iises approximately 36% H2S04 solution as electrolyte. T h e positive aiitl iiegative plates are interconnected in s e m i - blocks with terniinal posts protriidirig f r o m the cell. T h e plates of the lead and the lead dioxitle seini-bloclis together with the separators and the electrolyte hetween thein f o r m the active block. In it, all processes occur, eiicrgy i s accumulated and electric ciirreiit i s generated during discharge. Ahove the active block, there is a space containing a certain amoiiiit of HLSO4 soliition (upper reservoir). Below t l i e active block, another free space is available where t h e shedded active niass is collected t o avoid short-circuits between t h e plates.

At t l i e end o f charging, decomposition of water takes place and


H 2

and

0 2

gases are evolved.

T h e cell i s provided with a valve

as an outlet for these gases. Since gas evolution i s associated with

water consurnption, an equivalent amount of water m u s t be added periodically t o the cell iii order t o maintain the required electrolyte conccritratjioii. Water is added through t h e outlet. T h e cells are mounted in a plastic container fitted with a cover. T h e cells are joined
in series with lead connectors that may b e situated over t h e cover, or pass through the cell partitions ( through-the-wall arrangement).

45

T h e construction of a coiiventional present-day SLI l m t t c r y i s shown in Fig. 18.


Terminai posts
Iniercell
Post stmp

comedor

Fig. 18. Exploded drawing of a pasted-plate lead-acid battery.

4.3. Electrical characteristics of lead-acid batteries


Discharge curves. When electric current flows through the cell, t h e close circuit voltage depends o n b o t h the direction and magnitude o f the current, and o n cell temperature. Figure 19 presents a set of discharge voltage curves for a 12 V/100 Ah battery at 25C for
various discharge currents. Discharge proceeds w i t h i n a given period of time, after which t h e voltage begins t o decrease rapidly. Since deep discharges have an adverse effect u p o n battery performance, a limit is set for t h e endof-discharge voltage (U, final or cut-off voltage). When the time of discharge is between 1 and 20 hours, U, = 1.75 V. For shorter discharges, U, = 1 V. The mean discharge voltage (Ud) i s shown w i t h a dotted line. T h i s value is used for the calculation of battery
~

energy and power.

46

4lo A

528A 1 2
4

6 8 1 12 14 16 1 20 22 24 26 28 30 0 8 Time, min
a 12 V/100

Fig. 19. Discharge voltage curves for


battery [12].

Ah (22 h rate) s t a r t e r

Capacity. T h e capacity ( C d ) of a b a t t e r y is determined by the quantity o f electricity that can be delivered during discharge at constant current until the final discharge voltage is reached. T h e t i m e ( t ) needed for reaching the final discharge voltage i s marked o n the abscissa and is known as the rate of discharge. International and domestic standards require the capacity t o be determined by a discharge w i t h a current at which t h e battery reaches U, = 1.75 V at 20C after 20 or 5 h (C20 or CS). T h i s capacity is k n o w n as the rated capacity. Under n o r m a l operating conditions, the battery should n o t be discharged beyond 80% of the rated capacity. T h i s capacity is k n o w n as working capacity. T h e relationship between capacity and discharge current i s expressed by the empirical equation formulated by Peukert in 1898 and widely accepted:

where

K and n are constants. According t o Peukert, n = 1.30,

while K depends on the temperature, t h e HzS04 concentration and t h e design of the battery.

47

12V11OOAh SLI battery

I I I

I I I

I l I

h 20minlOrnin 5 min

lmin
I

O ~ l O O 2 O O 300

400

6001.A

Rate o discharge (1) or current (I1

Fig. 20.

C a p a c i t y 'us.

discharge c u r r e n t ( I ) discharge r a t e (t) of a or

12 V/100 Ah s t a r t e r b a t t e r y [13].

T h e relationship between capacity and current is shown in Fig. 20.

Energy. T h e energy (Ed) delivered by the battery during discharge under constant current conditions is equal t o the product of the mean voltage of the battery multiplied by i t s capacity. Figure
21 presents the dependence of energy and mean voltage o n discharge current. When the discharge current increases, the energy delivered by the battery is decreased. Therefore, in battery energy storage plants, discharge of batteries should be carried o u t w i t h moderate currents, i.e. 3-10 h discharge rate. T h e delivered energy under routine operation is usually 80% of the rated value.
Power. T h e power of a battery is the energy delivered per unit time. T h e value per unit weight or volume is k n o w n as specific power of the battery. Figure 22 presents the power us. current dependence. W h e n the current increases, power is also augmented. Therefore, in order t o deliver h i g h power, batteries are designed t o be discharged at heavy currents. As the capacity decreases w i t h increase of current, the discharge time will decrease rapidly.

48

1 2 V I Kx) Ah SLI battery

20h 20minX)min Smin


I
I I I I

Imin
I

Current, A

Fig. 21. (a) Average discharge voltage vs. discharge c u r r e n t ; (b) energy vs.
discharge c u r r e n t for a 12 V/100 Ah b a t t e r y [13].

100 200 300

400

Kx)

Current, A

Fig. 22. P o w e r vs. discharge c u r r e n t of a 12 V/100 Ah s t a r t e r b a t t e r y [13].

49

T h e service life o f a battery is the number of charge/discharge cycles obtained during laboratory bench tests. T h e battery must attain a given number of cycles before i t s capacity is reduced t o 80% of the rated value. T h e real life o f a battery may be longer or shorter t h a n that experienced under laboratory conditions. During practical use, the battery is subjected t o other life-limiting factors that are n o t taken i n t o consideration in the laboratory tests. Current test procedures are aimed at maximum simulation of real operating conditions.

Cycle life.

4.4. Charging characteristics

That p a r t of the current utilized for the formation o f lead and lead dioxide during battery charge i s called charge acceptance. T h e remaining current is consumed for water decomposition. Figure 23 shows the charge acceptance of a battery vs. i t s state-of-charge.

20

5 0

20

40

60

Charge Rated capacity

; ,

80

loo120

Fig. 23. Charge acceptance of a t r a c t i o n b a t t e r y ws. i t s state-of-charge


at 30C [14].

T h e data show that almost the entire amount o f charging elect r i c i t y is used for the transformation of PbS04 t o Pb and PbOz until a 60~75% state-of-charge is reached. At this stage o f battery charg-

50

ing with a current of 0.1 A per Ah, the cell voltage reaches 2.35 V and gas evolution starts. After that, water decomposition proceeds
simultaneously w i t h the charging reactions. T h e charge acceptance is gradually and continuously reduced. Cell voltage is increased f r o m 2.35 t o 2.50 V. T h e cell is completely charged. During the next charging stage, water decomposition and self-discharge are t h e m a i n processes that take place. The battery is overcharged. These stages can be clearly identified by galvanostatically charg-

ing a b a t t e r y which has previously been subjected t o three different depths of discharge (50, 75 and 100% DOD). After these discharges, t h e efficient charge stage acquires three different durations. Figure 24 shows the changes in cell voltage during charge. T h e charging current
was 0.1 A per Ah.
2.8 - 50 per cent
75 per cent

20

dischorqed Time

Fig. 24. Changes in celi voltage d u r i n g charge, f o l l o w i n g three discharge


runs t o different depths [15].

T h e gas evolution voltage is 2.35-2.40 V per cell at 75% state-ofcharge. T h e following parameters are used t o define charging regimes: o I n i t i a l and final charging voltage (2.1 t o 2.4-2.7 V per cell). o I n i t i a l gas evolution voltage (2.35 t o 2.40 V per cell). o Charging current during the efficient charge stage (0.3 t o

0.1 A Ah-' or

I c h = 30-10%

C, A).
51

o Current at the beginning of gas evolution

(I:h 0.07 A Ah-' =


I!h

or
c 5

I h 7% C A). , = 5
o

Final charging current (ICh = 0.01-0.03 A Ah-' or

= 1-3%

A).
o Upper charge temperature limit

(45-50'C).

T h e duration o f charge must be short, the energy and power efficiencies must attain maximum values, the irreversible processes in the active masses and the grids must n o t be enhanced, thus ensuring long service life of the battery. There are several charging regimes in use for energy storage plant batteries which meet the above requirements: a) controlled currentvoltage charging method, b) tapered charging method, and c) pulsed charging m e t h o d [13]. T h e specific charging method for each battery is usually prescribed by the battery manufacturer.

4.5. Effect o f electrolyte stratification

During discharge, the concentration of the acid in the cell decreases, and during charge it increases. Concentration gradients are formed in the cell between the solution above the active block and that between the plates. T h e formation of concentration gradients in the active block of a 400 Ah battery was studied during cycling w i t h 169 mA Ah-' at 100% DOD until a cut-off voltage of 1.7 V/cell was reached [16]. Figure 25 shows the concentration changes during four
consecutive cycles at a charge/discharge r a t i o of 1.02. Stratification of the acid is enhanced as the number of cycles is increased. This indicates that the concentration changes accumulate

during cycling. The difference between t h e acid concentration at the


t o p and the b o t t o n i of the active block was used as a measure for the extent of stratification. In the above studies this reached 0.15 sg. 52

Charge time. h

Fig. 25. E l e c t r o l y t e s t r a t i f i c a t i o n measured during b a t t e r y charging t o 2%


overcharge and a f t e r 100% DOD [16].

As HzS04 is an active material, stratification w i l l affect c e l l capacity. It has been established that the capacity decreases by l% for each 0.01 sg unit of stratification. T h i s capacity loss depends on the DOD and the charge/discharge ratio. With increase in overcharge, t h e extent of stratification (and hence the capacity loss) i s diminished. To eliminate fully t h e capacity losses due t o strat'ification,

the battery should be subjected t o 15% overcharge. Since the active block is a compact assembly, during overcharge the evolved gas will exert a pumping action which w i l l transfer the dense acid at the lower half of the active block t o the top, thus enhancing t h e equalization of the acid concentration. Intensified gas evolution, however, w i l l lead t o greater water consumption and hence heavier battery maintenance, on the one hand, and w i l l increase the corrosion of the positive grids, o n the other hand. That is w h y the use o f devices for forced electrolyte circulation is recommended. These are usu-

ally small air-lift pumps t h a t let an air flow i n t o the cell to stir the electrolyte throughout the charge cycle.

53

4.6. Charge-discharge energy efficiency


Figure 26 presents a typical charge-discharge curve for a lead-acid cell. T h e quantity o f electricity consumed for charging i s about 15% greater than that o f the discharge.

Charge or discharge
F i g . 26.

Dependence of t h e cell p o t e n t i a l o n t h e state-of-charge or

discharge [17].

Since the charge and discharge were conducted at the same current, the difference AE, between the areas situated below the charge and discharge curves gives the energy losses. To improve the energy efficiency, this area

AE, should be made as small as possible. T h i s

can be achieved by reducing t h e polarization o f the positive and negative battery plates and decreasing the ohmic drop in the electrolyte (separator) during charge and discharge as well as by decreasing the duration of overcharge. T h e highest energy losses are related t o battery overcharge. If the latter is eliminated, however, t h e process of conversion of lead sulfate t o lead and lead dioxide w i l l n o t proceed fully and the battery will b e gradually sulfated. Besides, a stratification of the electrolyte occurs also leading t o battery capacity drop.

54

Investigations have been conducted w i t h cells whose electrolyte hac been agitated using a special device for admitting air t o stir the electrolyte. T h i s device is shown in Fig. 27. Air

II

Fig. 27. Electrolyte agitator [17]

In this device, air i s introduced by a blower i n t o the inner t u b e of a double-wall cylinder f r o m the top. T h i s air l i f t s t h e electrolyte,
while ascending as bubbles, through the gap between the inner and outer tubes. T h e electrolyte is sucked f r o m a hole at the lower part of the outer tube and ejected f r o m a hole at the upper part o f the same tube. T h e obtained results have shown that: first, battery charge w i t h o u t overcharge is possible whereby no plate sulfatization proceeds when the electrolyte is stirred thoroughly t o prevent stratification; second, an equalizing charge w i t h 25% overcharge should be performed after every 30 cycles t o prevent coarsening of the lead sulfate crystals accumulated in the plates.

55

Figure 18 presents the capacity/cycle number dependences for a 200 Ah battery subjected t o 100% charge w i t h o u t electrolyte stirring, 120% charge w i t h o u t external agitation but w i t h intense gas evolution stirring the electrolyte, and finally w i t h outer electrolyte agitation and equalizing overcharges conducted after every 30 cycles.

U < LO-

agitation)

Cycies
Fig. 28. Influence of overcharge and electrolyte s t i r r i n g o n cycle l i f e [17].

As can be seen from the figure, when lead-acid batteries are subjected t o charge-discharge cycling w i t h 100% state-of-charge and electrolyte stirring t o prevent stratification, and equalizing charges are carried out periodically, corrosion of the grids and softening of
the active materials can be strongly suppressed and life performance markedly improved. Under the above conditions, n o t only is the life of the battery extended, but i t s charge-discharge energy efficiency is improved as well.

56

4.7. Methods for reducing water losses


Maintenance o f lead-acid batteries consists primarily in periodical refilling the cells w i t h water. Water is lost f r o m lead-acid batteries through the following processes:
e Electrolysis of water during overcharge o f t h e battery
o Self-discharge under open-circuit conditions

o Evaporation

of water

Manual filling up o f the cells t o a constant electrolyte level is very laborious and time-consuming, especially in a b a t t e r y energy storage plant. Therefore, m a j o r challenges in battery servicing are t o find a way t o reduce water losses and t o replace manual refill methods. T h e following methods have been proposed:
a) Single-point (common point) watering. T h i s system i s used for fill up of conventional batteries w i t h excess electrolyte above the active block, i.e. flooded batteries. In these batteries, a water addition system is fitted t h a t can automatically adjust the electrolyte

level in each cell o f the battery. This watering system comprises: devices t o monitor the level of the electrolyte in the cells and t o stop the flow of water when t h e electrolyte reaches a previously adjusted level;
a device for escape of evolved oxygen and hydrogen gases f r o m

the ce ll t o eliminate explosion hazards. Finally, the design should avoid electrical shorting between the cells through the common filling system. These systems have found wide application in stand-by energy facilities for power plants, post offices, cultural and commercial centers using stand-by lead-acid batteries. A common p o i n t r e f i l l system is utilized in many battery energy storage plants. Operating experience of batteries w i t h the above r e f i l l system in various modifications has shown that it is n o t always sufficiently reliable and safe.

57

b) Catalytic plug recombination of hydrogen and oxygen. Designed t o recombine hydrogen and oxygen t o water that is brought
back i n t o the cell. Instead of a cell valve, a catalytic plug i s included

that enables the following reactions t o proceed:

2H2

+ O2

2H2OVapOUr

H~Ovapour+ HZOiiqui

+114 kcal +9.7 kcal

T h e first reaction requires a stoichiometric ratio between the evolved H and 0 2 , and is accompanied by the release of a great 2 amount o f heat. T h e latter causes the cell temperature t o rise as a result of which the reaction rate is increased. If left uncontrolled, this could lead t o an explosion. Various designs of catalytic plugs have been used t o avoid this hazard. Metals f r o m the platinum group are used as catalysts for the recombination. Carbon, alumina or asbestos wool are usually used as catalyst carriers. T h e m a j o r disadvantage o f this water recycling m e t h o d is the high price o f the catalyst materials, which h s rea stricted large-scale application of the method. c) Closed oxygen and hydrogen cycles. During charge-discharge operation, hydrogen and oxygen are often evolved in nonstoichiometric amounts. That is w h y the efficiency of the catalytic plug i s reduced. A method has been proposed suggesting that t w o

auxiliary catalytic electrodes are fitted in the cells. T h e y are presented in Figure 29. On one auxiliary electrode, the reaction of oxygen reduction t o

OH- ions proceeds. For this purpose, the oxygen electrode is connected through an appropriate diode t o the lead electrode of the cell
(Fig. 29a). On the other catalytic electrode, hydrogen is oxidized t o hydrogen ions (Fig. 29b). T o ensure the right potential for the electrochemical reaction of hydrogen oxidation, the hydrogen electrode is connected through a proper electronic device (diode and resistor) to

58

p 2 m

Pb

Pb02

Pb

Fig. 29. Schematic o f cells with auxiliary electrodes

[is].

the lead dioxide electrode of the cell. T h e reactions proceeding at the t w o auxiliary electrodes are catalyzed by metals f r o m the platinum group. T h i s makes the m e t h o d very expensive and hence i t s applicat i o n is strongly restricted. It has recently been found that tungsten carbide displays similar catalytic properties t o those o f platinum w i t h respect t o hydrogen and oxygen reactions [19]. Consequently, interest
in this method has increased of late.

d) Valve-regulated recombinant lead-acid batteries. charge, the following reactions take place in the cell:
positive plates negative plates

During

+ 2H20 +PbO2 + 2H+ + H2S04 + 2e;O2 + 2H+ + 2ePbS04 + 2H+ + 2e- +Pb + H2S04 2H+ + 2eH 2
PbS04 HzO

Figure 30 shows the relationship between the charge acceptance o f positive and negative plates and the time of charge.
20 2.6
2.4

2
c
I

22 2 .o

Chorge tlrne, h

Fig. 30.

C h a r g e acceptance of p o s i t i v e and negative p l a t e s at 40C

v s t i m e [2O]. u.

When the positive plate reaches a 60--70% state-of-charge, a reaction o f oxygen evolution starts and i t s rate is increased w i t h time.
T h i s leads t o an equivalent decrease in positive plate charge acceptance. T h e negative plate is charged w i t h 100% charge acceptance until about 95% state-of-charge. After t h a t , hydrogen evolution starts. T h i s difference in the behaviour of the H and 0 2 reactions has 2 been exploited in the oxygen cycle. Oxygen evolved first, is brought t o the negative plate, where it oxidizes the lead in the grid. Thus, on t h e one hand, the negative plate is kept discharged and hence evolution of hydrogen is prevented, and o n the other hand, oxygen itself reacts in the cell. T h e basic problem w i t h this t y p e of oxygen cycle battery was t o prevent oxygen f r o m being lost f r o m the active block. A solution was found in immobilizing the H2S04 electrolyte between the plates. T h i s was achieved by:

60

o Using gelled electrolyte. T h e cracks formed in t h e gel act as channels for the transport of oxygen. T h i s technology was devised by the German company Sonnenschein for small lead-acid batteries

(several Ah), and then further developed for large stationary batteries [21]. T h e U company .Johnson Controls Inc. lias enhanced this S technology [22,23] and is now manufacturing gelled-electrolyte batteries for b o t h traction and stationary applications, and for energy storage systems as well.
o

Using absorptive glass m a t separators. T h e electrolyte in

t h i s case i s absorbed by the glass fibre mat that has t h e property o f absorbing H2S04and water, and adsorbing oxygen. Oxygen is retained in the glass mat separator and flows f r o m the positive t o the negative plate, while H2S04and water participate in the reactions in the cell. Gates in the USA [24,25] and IUASA in Japan [25] were the first t o employ this technology in small batteries, and later in stationary batteries. N o w these batteries are under large-scale tests for energy storage applications.

The problem of oxygen retention between the plates lias found an adequate technical solution, but even so, over time, ccrtain amounts
of hydrogen are evolved at a l o w rate, which accumulate above the electrode stacks in the cells. T o avoid explosion, a valve is fitted t h a t lets the gas out and controls the pressure in the cell. These batteries are maintenance-free and are called valve-regulated batteries.

61

5 . Lead-acid batteries in the battery energy


storage system ( B E S S )
Functions of lead-acid battery energy storage systems
After the revival of interest in energy storage systems, the first batteries t o be used for that purpose were flooded lead-acid batteries of the traction/industrial type. Early battery storage plants were installed for demonstration purposes t o validate the feasibility of design, investment , operational and maintenance costs of the system; t o demonstrate operational and economic benefits; t o establish BESS applications w i t h higher efficiency; and t o test feasibility of BES systems w i t h power utilities. Technical, technological and economical information has been gathered over 2-3 years. Analysis of the testing results of these demonstration BES plants shows that battery energy storage systems can improve the operational efficiency and the cost-effectiveness of the electric power system by providing the following functions. a) Load-levelling: off-peak battery charging and on-peak discharging, which leads first t o improvement o f the load factor of baseload generating units, and second t o reduction of energy costs by storing cheap energy at night and selling it at higher cost during the

5.1.

daytime peak demand hours.

b) Peak-shaving: Often m a j o r utility customers need instantaneous delivery of peak electric power for meeting technological needs.
T h e lead-acid battery, owing t o i t s low internal resistance and very short response time, i s capable of dispatching considerable power w i t h i n several milliseconds. Through charging of the battery f r o m the energy utility, electric power is concentrated in the battery. T h i s power can be delivered through high-current discharge of the battery (Fig. 23) when a high peak demand appears. T h i s method of energy storage allows electric utilities t o save capital investments for

62

expansion of the generating facilities and, on the other hand, offers utility customers the cost benefit of reducing their expenses for peak demand charges. c) Load-following: When the energy demand exceeds the local electric system power level, the voltage o f the system begins t o decline. T h e battery storage unit takes over part of the load by discharging electricity, thus enhancing the stability of the power supply. d) Frequency control and spinning reserve: To ensure n o r m a l operation of the customers' electrical devices and machines, stable ac frequency should be provided. Overloading of the electric power system may cause the frequency of the supplied current t o fluctuate. Storage batteries may play the role of spinning reserve and, through discharging, compensate for such frequency distortions and thus maintain the frequency of the local power system w i t h i n the desired limits.

'
Utility lines charging (off p e a k )
r--,---

Battery dixhorgi ng (on p k )

-- 1

Fig. 31. Schematic of a customer-owned LABESS

[il.
63

Some of the operational LABES systems are listed in Table 5.


Table 5. L A B E S systems in operation by 1990 t h r o u g h o u t t h e world [27]. Company
Utility operated

Size

In service

Application

B e r l i n e r Kraft und L i c h t (BEWAG), Berlin, FRG


Kansai E l e c t r i c Power Co. Ltd Tatsumi, Japan

1 7 MW 14 MWh

1986 1986

frequency regul. spinning reserve demonstration multi-purpose t e s t program demonstration multi-purpose test program

1 MW 4 MWh

S o u t h e r n C a l i f o r n i a E d i s o n Co. Chino, CA, U S A

10 MW 40 MWh

1988

Customer operated

Elektrizittswerk Hammermiihle Selters, FRG H a g e n Battcric AG Socst, FRG Crescent El ect r i c Membership C o r p o r a t i o n Statesville, NC, U S A D e l c o Remy. Division of General M o t o r s M u n c i e , IN, USA
Vaal Reefs Exploration and M i n i n g Co. South Africa
Johnson Controls, I n c .

400 kW 400 kWh 500 kW 7 MWh 500 kW 500 kWh

1980

load-levelling peak-shaving load-levelling peak-shaving


load-levelling peak-shaving

1986 1987

300 kW
600 kWh 4 MW

1987

peak-shaving

1989

peak-shaving
emergency power

7 MWh
300 kW
600 kWh 1989

H u m b o l d t Foundry M i l w a u k e e , WI, USA

peak-shaving load-levelling

64

T h e table shows that when battery storage plants (LABESP) are installed at the side of the electric power generating utilities, they have a power of over 1 MW. T h e power of lead-acid b a t t c r y storage facilities (LABESF) at the customer side is of the order of 300 t o 500 kW. T h e only exception is the L A B E S facility in South A f r i c a which n o t only serves for peak-shaving purposes, but also for emergency power supply. Customer operated lead-acid battery storage facilities are utilized primarily for peak-shaving and load-levelling. All thcse applications

bring immediate financial profits t o the customers, and make theni


less dependent o n the power supply utilities in peak deniand periods. T h u s sufficient stability of the technological processes i s guaranteed. T h e use of lead-acid battery storage plants by electric power generating utilities is aimed n o t only at levelling the electric loads, but also at improving the quality of t h e energy delivered by the utilities t o the customers. LABES systems can function a spinning reserves; ? . provide instantaneous fast power reserve; regulate frequency, voltage damp-out, subsynchronous oscillations and other system instabilities. W h i c h option t o choose for BEC plant location - before or after the meter? I f the power demand is n o t very h i g h and a number of customers could be grouped o n a territorial principle, siting LABES plants o n the utility side of the meter is advisable. T h e storage unit should be installed close t o the substation at i t s low-voltage stage. LABESP capacity should be properly rated t o meet the local peak power demand. For m a j o r energy consumers having high peak power demands, e.g. commuter railroads and stations, metropolitan t r a i n or subway systems, foundries, large administrative or commercial centers, etc., it would be more cost-effective and associated w i t h smaller power losses t o install the LABEC facility o n the customer side of t h e meter. 65

Battery charging could be accomplished at any off-peak intervals

during the day and the night. Spindler [ l ] has performed a cost analysis o f the utilization of LABEC plants by m a j o r electric power consumers in the USA. T h e
investment pay back periods have also been estimated. T h e obtained results are summarized in Table 6.
T a b l e 6. E c o n o m i c analysis of selected cases of LABESS a p p l i c a t i o n o n t h e customer side [il.' Customer / Application

D e m a n d Converter B a t t e r y size size charge MW/ac $ kW-' MWh/ac

Capital Payback
cost

$M
2.48 1.46 0.53 0.56 0.32

period years

Commuter railroad Steel m a n u f a c t u r e C o p p e r alloys plant T r u c k part plant Chemical manufacture


~ ~~~ ~ ~ ~~

16.24 11.88 13.50 13.82 9.87

5.8 3.5 0.9 0.5 0.4

5.6 2.3 0.7 0.7 0.5

2.2

3.5 3.5 4.3


6.2

Based o n a b a t t e r y cost o f 260 $ kWh-', converters at 130 $ kW-', and balance of plant, 140 $ kWh-I, o p e r a t i n g 250 days yr-l.

It can be seen that with commuter and metropolitan railroads, as well as steel and alloys production using electric furnaces, customer LABEC plant construction is economically effective. In b o t h cases, applied before or after the meter, battery energy storage brings significant profits t o the electric utility company.

66

6 . . Lead-acid battery energy storage systems for load-levelling


6.1. System structure
T h i s consists o f the following basic components:
0

lead-acid battery (converter, transformer, dc and ac switchgear)

o ac/dc power conversion system

o facility monitoring and control system.

T h e electric energy i s supplied by a utility distribution network t h r o u g h an ac switchgear t o the high-to-low-voltage transformer. T h e n an ac-dc converter follows. T h r o u g h a dc switchgear, the current is fed i n t o the battery t o charge it. Operation of all these LABES plant components is managed by a monitoring and control system. During battery discharge, direct current is generated which passes through a dc-ac converter and is then delivered t o the customers to meet their demand, or after increasing i t s voltage in a transformer, is fed back i n t o the utility distribution line. Figure 32 gives a schematic o f a lead-acid battery energy storage system.
Facility monitoring

dc
-I-

1-

oc

Charge Discharge

F i g . 32. Schematic of electric utility b a t t e r y energy storage s y s t e m

[il.
67

T h e battery energy storage plant is located near a substation o f t h e power supply system, after the transformer, and serves the substation local area. This is the case of LABES plant before the meter. T h e basic components of the system are discussed below. The system design, properties and parameters can be best described if based o n a real operating energy storage system. L e t us take for example the worlds largest, up t o now, lead-acid battery energy storage system in Chino, California, U S A .

6.2. Chino 10 M W / 4 0 MWh lead-acid battery energy storage system

6.2.1. Plant layout


Figure 33 presents a floor plan of t h e battery energy storage plant.

Demineralized

Fig. 33. General arrangement of LABES plant at Southern California Edison Chino Substation [28].

68

T h e Chino LABES plant is sited 50 miles east of Los Angcles, in the vicinity of the Chino 220 kV Substation of the Southern California Edison Company. The Electric Power Research I n s t i t u t e (EPRI) and the International Lead-Zinc Research Organization I n c . (ILZRO) are project participants. T h e plant consists of two large parallel buildings housing the batteries. Between them is the common converter/control building and related facilities. In the immediate proximity, there is a 12 kV ac switch rack. T h e system supplies 10 MW of power in four hours or 40 MWh of energy, enough t o meet t h e needs of 5000 customers.

6.2.2. The battery


T h e Exide Corporation has supplied the b a t t e r y which comprises 8256 individual cells, specially designed for deep-discharge capability.

Exide has warranted the life of the cells for a minimum of 2000 cycles, or eight years before battery replacement becomes necessary. Argonne National Laboratory has tested these batteries and found that they could endure more t h a n 4000 cycles [29].
T h e battery unit operates at nominal voltage o f 2000 V, generated by strings of 1032 cells connected in series. During charge and discharge, the battery and the strings change their voltage in

the range f r o m 1750 t o 2800 V. The charge rates first step is usually 4000 A, followed by a constant voltage period and finally by the third step overcharge rate of 1000 A. The nominal daily voltage cut-off is
1800 V based o n 1.75 V per cell. T h e battery delivers 50 MWh eriergy at a maximum 10.5 MW power for 5 h during daily discharge at 80% DOD, and 40 MWh at 10 MW power for 4 h at 80% DOD.

Six t o 10 hours nightly recharge is performed. Turn-around battery dc-to-dc energy efficiency is 78%.

69

T h e specified battery characteristics are presented in Table 7.


T a b l e 7. C h i n o L A B E S plant B a t t e r y specification requirements [29].

R a t e d discharge requirement - energy o u t p u t (MWh) - power (MW) - t i m e t o 1.75 V (h) N o m i n a l voltage O p e r a t i n g range N o r m a l daily c u t - o f f voltage B a t t e r y has 1032 cells in series s t r i n g B a t t e r y l i f e (80% DOD)

100% DOD 80% DOD 65.8 52.7 10.5 10.5 6.5 5.0 2000 v f r o m 1750 t o 2800 V 1800 V 8 years = 2000 cycles 6-10 h 78% 75% 32-1 17F
SbH3 5~10-~ 3~10-~ 34 19

Daily recharge
O v e r a l l energy efficiency - ceii dc t o dc -battery O p e r a t i n g t e m p e r a t u r e range S t i b i n e & arsine gas emissions:

ASH^
2x104
1.1 10-~ x

P e a k flow Daily (8 h) T o t a l p e r day T o t a l annual

SCFM SCFM
g

lb

0.77 0.42

T h e cell is an Exide special design hybrid construction w i t h PbSbAs positive grids and PbCa negative ones. T h e positive active material has a low density and contains anti-shedding additives, yielding a high active mass utilization coefficient. T h e negative active mass contains a long-life expander composition and h s h i g h density. a T h e cell design features are presented in Table 8. Figure 34 shows the changes in cell voltage during battery discharge with various discharge currents. Three cut-off voltages are given in the figure.

70

T a b l e 8. C e l l design features [29]. R a t e d capacity (I= 650 A, 5 h t o 1.75 V) Energy output P o s i t i v e plates (17.3 x 13.7 x 0.33) grid a l l o y Negative plates (17.3 x 13.7 x 0.21) grid a l l o y C e l l cover m a t e r i a l Cell jar material Sediment space Separator s y s t e m ( o n positives) - absorber mat - retainer - separator A c i d specific g r a v i t y (top-of-charge) Terminal posts - design: l o w t o r q u e maintenance Post-to-cover seal Cover-to-jar seal 3250 Ah

6.2 kWh 17
Pb-Sb 18

Pb-Ca PVC SAN


1.3
non-woven glass p e r f o r a t e d PVC niicroporous r u b b e r 1.28-1.29 l e a d p l a t e d copper slide-lockTM s t r u c t u r a l adhesive

1.75 V

l.m 1.600
1.500
2000A M O A
I I

1.67 V 1.60 v
520A 650 A
I

\
220A

380 A
I I I I I I

1 0

1 2 14 lime, h

1 6

Is

20

2 2 :

Fig. 34. I n i t i a l celi voltage transients at discharge [29].

On the basis of these curves the dependences of mean voltage,


capacity, energy and power o n the rate of discharge were plotted. T h e y are presented in Fig. 35.

1.0

l
I

'

'

2 4

6
I

8 10 12 14 16 18 2 0 . h

C.
Ah 4400 -

795590

390

1.A

210

E.

P.

4000

8 7
6 ti0 I , A 5 8 1 12 1 16 18 20 t . h 0 4

3600 3200 -

,jkW1
?IS.

2800 I 1 4

75590

390

Fig. 35. M e a n voltage, capacity, energy and power

t h e r a t e of discharge.

Increasing the discharge current, the average voltage i s only slightly changed until the 4-hour rate of discharge, and decreases rapidly thereafter. T h i s has allowed successful employment of the b a t t e r y for 4-hour discharge applications. Up t o the sixth hour, the slope of curves P, E and C is roughly constant and it changes after

that.
T h e internal ohmic resistance of the battery has been determined (using the A V / A I method) t o be 0.025 ohms during the 10 MW

72

discharge. Average resistance of the string has been measured as 0.20 ohms at full state-of-charge, which means that t h e internal resistance o f the cells is 194 micrq-ohms [30].

A certain number of cells have been subjected t o tests o f 2 cycles per day at 40 f 5C. Over 4 years, the cells have undergone more than 2300 cycles at 80% DOD and are s t i l l in good health. T h e cells are organized in a battery as follows: 6 cells are assembled in a 12 V module with an energy of 36 kWh. A schematic of
this module is given in Fig. 36.
,Hold
&un b r k

Fig. 36. Drawing of a battery module [29].

44 modules (264 cells) form a row. Four rows separated by foot aisles f o r m a string. The battery has 8 strings and 1376 modules or 8256 cells housed in t w o battery rooms [29]. 73

The large number of cells in the battery create non-homogeneous conditions in the parallel strings. Depending o n the ohmic resistance of each string, different currents will flow through the different strings. W i t h o u t equal sharing of current, over a large number of cycles, the state-of-charge of the cells in some of the strings may become considerably lower t h a n that of the other cells. T h i s could lead t o reversal of the cells during discharge and early cell failure. To prevent such processes, the difference in state-of-charge o f the cells must be monitored and controlled. Duringthe initial operation of the Chino BES system, a difference of about 12% was found between the individual strings, while after 350 cycles this difference diminished t o about 4% [31]. Table 9 lists the accessories of each cell.

T a b l e 9. Load-levelling b a t t e r y accessories [29].

Location

1. A u t o m a t i c w a t e r i n g valve s t i b i n e l a n i n e trap flame arrester

each c e l l

2. 3. 4. 5. 6.

Air lift pump


Electrolyte withdrawal tube Thermocouple well A c i d level i n d i c a t o r I n t e r c e l l connectors

each cell each cell

0.5% of cells
each cell l e a d p l a t e d copper t w o per post expanded p l a s t i c t u b e a r o u n d each t w o i n t e r c e l l connectors minimum 2 each 4/0 2000 V

7. H i g h voltage protectors

8. I n t e r m o d u l e cables 9. Lugs o n cables

410 l o n g b a r r e l compression t y p e 2000 V r a t i n g

74

T h e positive plate grid alloy contains As and Sb. T h e grids corrode, and As and S are oxidized and dissolved in the HzS04 elecb trolyte. These ions are then deposited o n the negative plates, and when the potential becomes more negative than a certain value, As and Sb f o r m AsH3 (arsine) and SbH3 (stibine) gases, respectively. Since these gases are toxic, they should be retained in the cell. T h i s is accomplished by means o f an arsine and stibine trap. T h e latter comprises activated chemically treated carbon and absorbs 98% of the stibine and arsine emissions f r o m the cell for 2-3 years of service life. T h e trap can be replaced after that. Since oxygen and hydrogen are accumulated above the active block in t h e cell, t o avoid explosion, a ceramic flame arrestor i s used, sized for a maximum overcharge current of 200 A per cell [29].

A l i m i t e d number of battery modules are watered simultaneously when the battery is o n open circuit after the full charge. Water purity
is controlled t o a specific resistivity n o t less than 2 x Each cell is fitted with an acid level indicator.

l o 6 o h m cm.

Table 10 presents a summary of the materials needed for battery manufact ure. Table 10. Materials for 10 MW/40 MWh Chino LABESP [30].

1. Lead 2. Copper (intercells and parts) 3. Steel (racks and trays) 4. Plastic (SAN, PVC, PP) 5. Sulfuric.acid (1.285 sg) 6. Microporous separator 7. Bolts, intercells, racks, trays 8. Cable (4/0)

tons metric tons metric tons m e t r i c tons metric tons EA EA FT


metric

1560 30

153
90

480 280,704 139,600 6,048

75

Maintenance and monitoring of the battery is the most labourconsuming i t e m o f the LABESP operation and maintenance. T w o full-time battery electricians w i t h part-time support personnel areneeded t o provide proper maintenance of t h e battery. T h e m a j o r time-consuming procedures are watering of the battery, cell cleaning and performance monitoring. For watering of the cells, approximately 6500 gallons of demineralized water are needed every 30 cycles. Cell cleaning takes about 4.5 man-weeks and i s done every six months. D a i l y monitoring of the voltage, current and capacity o n a string-by-string basis is performed f r o m the control room. T h e most i m p o r t a n t performance parameter is the end-of-discharge voltage of each cell. By means of an infrared camera, w a r m cells are detected during the end of discharge that denote possible weak cells. The electrolyte temperature is determined o n the basis of a number of selected cells. During i t s operation for over t w o years now, the battery system has displayed stable and reliable performance parameters close t o the rated values [30].

6.2.3. Power conditioning system


T h e power conditioning system has been designed by EPRI and nanufactured by the General Electric Company. It is the interface between the Edison grid and the battery. T h e power conditioning system converts the 12 kV/60 Hz ac f r o m the grid t o 2000 V direct current required for battery charge and vice versa when the battery discharges electricity t o the Edison grid. Figure 37 shows a block diagram of the power conditioning system and associated equipment. T h e converter can function independently as a synchronous generator to maintain unity power factor. T h e converter is a seifcommutated, Gate-Turn-off voltage source, stepped-wave design w i t h a response time of 16 milliseconds. It consists of three sixpulse three-phase converter bridges connected in series o n the ac side

76

utility BrE!!w

411

fOrmW

GTC

T
T
GTC

Breaker?
I LI I
1 1

Fllter cap

1 -&k*
,

-3
Inverter control

5 battery strings

I I

Table 11. Major power conditioning system characteristics [32]. Power - real reactive Efficiency Harmonic voltage Ripple voltage dc t o battery Response Voltage input range - nominal
~

10 MW, charge/discharge 10 MVA, leading/lagging 97% one way 3% total, 1.5% any single frequency 1.5% R M S voltage 16 ms 2.112 VdC 2.860 Vdc 1.750 V d c

- max

- min

77

T h e dc entrance equipment consists of t w o 3000 A, 3000 V dc high-speed breakers, dc no-load break battery string connectors, fuses, and disconnect switches. The ac entrance equipment includes 12 kV vacuum switchgear, single-phase transformers, three-phase neutral transformer, filter capacitors, surge arresters and ac protect i o n relays. T h e control system o f the converter is a microprocessorbased interface w i t h pre-programmed algorithms for charging and discharging operations. T h e control system communicates w i t h the facility monitoring and facility control system [32-341.

6.2.4. Facility m o n i t o r i n g and control system

The microprocessor-based control system provides complete facility supervisory control and data acquisition. It is pre-programmed w i t h a typical load curve for automatic control of the battery discharge rate, but can be modified readily t o allow for different discharge patterns. Reactive power output is also programmed i n t o the system. T h e data acquisition system records data o n facility operations t o allow analysis of the performance and economics of

the system. Analog inputs are scanned at one-second intervals and stored in the data acquisition system in predefined intervals of one, ten or sixty seconds. A microcomputer is also connected t o the data highway access f r o m a remote computer located at the Edison m a i n office [32-341.

6.2.5. Equipment energy losses


T h e distribution of plant losses f r o m all sources for an average cycle is presented in Fig. 38. The energy losses in the battery represent about 10 MWh per cycle or 61% of the t o t a l losses. T h e inefficiency of the Power Conditioning System accounts for 12% (2 MWh per cycle). Auxiliary power consumption accounts for the remaining 27% (4 MWh per

78

Total Losses L16.SMWh

Fig. 38. Distribution of equipment losses in Chino plant [31] cycle). T h e t o t a l energy input, o n a daily basis, is 58.6 MWh and the useful energy o u t p u t i s 42.1 MWh o n average. B a t t e r y systeni efficiency is a function of operating parameters such as overcharge, rate of discharge, etc. [31].

6.2.6. Economics of Chino LABES Plant

The t o t a l cost of the Chino LABES Plant i s about $ 13,560,000


or 1,350 $ kW-'. T h e distribution of these costs in various items i s presented in Table 12.
Table 12. Chino LABES s y s t e m costs [35].
Item

Cost, $ kW-'

10 MW lead-acid battery Power conditioning s y s t e m Balance of plant Plant site and tie-ins Engineering and management Tax, escalation, and contingency

600 190 325 52


76

103 Total: 1,356

79

I t is expected that w i t h mature technologies, the cost per unit kW generated by subsequent plants of that kind will fall t o $ 600-700. Chino battery energy storage system is operating at 75% overall

efficiency (ac-ac). T h i s storage system has been designed for demonstration purposes and has been initially intended for load-levelling applications, as a large active store of energy. That is w h y it has been designed for a h i g h Ah capacity, 40150 MWh at a power of

10 MW. Later on, other applications o f the system, requiring higher power, have also been tested and demonstrated.

7 . LABESP for instantaneous (spinning) reserve and frequency control applications


7.1. Island networks
Small energy supply systems, also called island networks, have serious problems w i t h the quality of the delivered energy and i t s cost. Energy generating facilities willing t o reduce t h e price of the electric energy must use large generator plants. A sudden outage o f such a big generating unit, however, would cause great problems t o the energy network operator. Besides, when a large industrial consumer switches o n or off his load (which might comprise for example 5% of the current system load), this would induce considerable frequency deviations in the whole power supply system. That is why an island network must maintain a significant amount of reserve power which can b e activated at h i g h speed for load-frequency control. Why frequency control? When a debalance occurs between the generated power level and the load, the system frequency is changed. Hence the quality of the delivered electric energy is determined by the frequency deviations. T h e latter should n o t exceed f 0 . 2 Hz. For Europe, 5 0 f 0 . 2 Hz.

80

7.2. The BEWAG 8.5/17 M W lead-acid battery energy


storage plant

7.2.1. System frequency response having given rise t o t h e construction of the BEWAG LABES plant

Figure 39 represents the system frequency response of a West European grid system w i t h a load of about 150,000 MW.

In case of outage of the 1200 MW or 2500 MW units, the system frequency decreases. In the latter case, a frequency deviation of more than -0.2 Hz appears, and the system immediately activates i t s spinning reserve. T h e generated power is increased and the frequency is brought back w i t h i n t h e required limits.
-Outage of o 1200 MW unit Outage 01 2500

M w

P
F

BEWAG island system

1 0

K t, s

25

Fig. 39.

S y s t e m frequency response after unit outages in different grid

systems [33].

That was n o t the case w i t h the West Berlin power supply system, which was a typical example of an island network. At a n outage of
146 MW, frequency deviations reached up to IM H z . In order t o h o l d
the energy system frequency within the range of 5 0 f 0 . 2 Hz, i t was 81

n o t enough t o have considerable reserve power generators available, but they also had t o respond very quickly t o the demand changes. T h i s could b e achieved if the power gradient o f the generating systems was higher t h a n 5-10 MW s-'. That meant that t h e power system should comprise generating units with a response t i m e of the order of milliseconds. Lead-acid batteries display such a response time. With t h e purpose of improving the spinning reserve and frequency control of i t s energy network, the Berliner Kraft und Licht Company (BEWAG) built up a battery energy storage plant based o n highpower lead-acid batteries. T h i s BES plant was first intended for demonstration purposes. In 1981 it started operation as a 24 kW test facility, and after a 3-year test period during which encouraging positive results were obtained, BEWAG decided in 1984 t o install a full-scale 8.5/17 MW demonstration plant in the power station Steglitz in West Berlin. Construction of the plant was completed for 18 months, and in 1986 actual operation started. T h e BES plant was used t o replace a turbo-generator set. Power

of the BES plant was 3 3 . 5 MW against f 7 . 5 MW o f the turbogenerator. However, BESP power gradient (minimum 5 MW s-l) was much higher than that of the turbo-generator (which could reach maximiim 4.5 MW s-l).

7.2.2. System design and characteristics

A block diagram of the BEWAG BES plant is given in Fig. 40.


T h e battery energy storage system is connected t o a 30 kV electrical network. T h e plant has two identical six-pulse inverters w i t h 8.5 MW each. The second inverter path operates as reserve for the first in the frequency control function, and provides additionally an instant reserve of a t o t a l of 17 MW power [33]. In order t o obtain a construction easy t o handle and maintain, six-pulse converter bridges 82

3 0 k V Steglitz Gr.B

8
Central dispatching room

Fig. 40. Block diagram of BEWAG 8.5/17 MW lead-acid battery energy storage system [33]. are used w i t h o n l y one thyristor per string. Thyristors have maximum power (12-pulse unit) of 8.5 MW and a rated dc voltage of

1200 V. T h i s design meets the safety regulations well [36].

The battery i s designed t o exhibit a very l o w internal resistance


and a short response time, t o be able t o serve as instant power reserve.
I t must deliver, under the worst operating conditions, i t s maximum

power of 8.5 MW for a period of at least 30 minutes.

83

T h e battery consists of 12 parallel strings of 590 cells each or a t o t a l number of 7080 cells. T h e battery comprises 1416 modules of 5 cells each housed in a common polypropylene container
- monoblock

module. T h e container and t h e polypropylene lid are heat sealed in place. In order t o reduce the resistance o f the connectors, the cells are connected in series in the monoblock through the cell partitions. Low-antimony tubular positive plates are used. To improve the negative grid conductivity, it i s made of expanded lead-plated copper mesh after Hagens technology. Air lift pumps are provided in each cell t o stir the electrolyte and prevent it f r o m starving during operation. Refilling of the battery is accomplished automatically by a common watering system. Each cell is provided w i t h a water-filling valve. Since high currents flow through the cells and a considerable amount of heat is released, each cell is equipped w i t h a heat exchanger which is accessible through the central cell vent. In some of the cells, there are thermometers and specific density probes. Figure 41 presents a two-day load-frequency response curve of the BEWAG LABES plant.

x)

15 2 0 2 5 3 0 3 5 4 0 4 5 Time, h

F i g . 41. T y p i c a l o p e r a t i o n o f test facility, c o m p r i s i n g t w o days o f loadfrequency-control o p e r a t i o n w i t h a subsequent constant-current constantp o t e n t i a l charge

[il.

84

T h e battery i s permanently connected t o the system and monitors load fluctuations. W h e n t h e frequency begins t o decrease, t h e b a t t e r y discharges power t o t h e systeni, and vice versa, when t h e frequency exceeds t h e upper limit, t h e battery charges. T h e fluctuations in charge and discharge currents are given in t h e figure. These changes affect t h e state-of-charge of t h e battery w h i c h is presented in Fig. 41a. T h e battery i s r a t e d in such a way that load fluctuations would not cause i t s state-of-charge to fall below 50% of t h e noniinal capacity. Normally, the b a t t e r y operates at 70% state-of-charge. With t h e introduction of t h e BEWAG LABES plant, previous frequency deviations of more than f 0 . 2 Hz have been halved owing t o t h e excellent dynamic response of the lead-acid b a t t e r y energy storage system. T h e frequency control function of t l i e b a t t e r y is accomplished in a severe operating mode. On calculating t h e quantity of electricity passing through t h e cells during t h e intermittent charge-discharge cycles, it tiirns out that t h e capacity turnover for a 24-hour period i s as high as three times t h e battery capacity [37]. T h e energy efficiency of t h e battery is about 7%,, but nevertheless there i s t h e tendency t o b a t t e r y overheating in warm weather w h i c h necessitates restriction of t h e battery inaximum power [37]. T h e battery has also been used as an instantaneous reserve in reference t o a steam storage system. A comparison of results has shown clearly t h e superiority of t h e LABES system. B a t t e r y maintenance comprises automatic fill 1 1 of tlie cells 1 weekly. T h e LABES plant operates unmanned under remote ~ 0 x 1 trol from the power station control room.

85

8 . Lead-acid battery energy storage systems


for peak-shaving
8.1. W h a t i s peak-shaving?

At railway stations, there are usually one or t w o short intervals during t h e day when several trains depart simultaneously. T h i s creates an extremely high peak power demand. Furthermore, in alloy
production plants employing electric furnaces t o melt t h e alloy components, high power needs may also occur for short periods of time. Since alloy production is performed in batch mode, t h e above h i g h energy demand usually appears only two or three times a day. There are indeed many manufacturing technologies displaying similar power demand curves w i t h several daily or weekly peaks, w i t h energy needs fluctuating w i t h i n their normal l i m i t s during the rest of the time. T h e electric utility customer pays t o the power supply company two basic types of energy rates: o for claimed peak demand o for actually consumed energy. Despite the short duration of peak load periods, the customer must pay for the claimed peak power demand, because the latter is related t o the size and t h e power of the generating plant, and the capacity of the transniission and distribution lines. These, for their part, are associated w i t h the amount of capital invested. Often peak demand charges are close t o the charges paid for actually consumed energy. In this case, a lead-acid battery energy storage system can b e installed t o take over the supply of peak power, and hence the customer w i l l claim only his baseload power needs t o the energy

utility company. T h e battery of this system, charged with electricity from the utility, accumulates electric power which w i l l then be used for shaving of peak loads. LABES facilities respond instantaneously t o load fluctuations. That is why they are most appropriate for

86

tliesc purposcs. Besidcs, when installed in immediate p r o x i m i t y t o the consunicr, power losses are minimized. Figure 32 shows t h e peak-shaving profile for a commuter railroad substation w i t h integrated LABES system
6OC
Commuter rai Iroad peaking

&OC

200

z
C O

6 a
- 20c
Charge

- coo
I

I
L

I 1 12 16 Clock lime. hours

Fig. 42. Peak-shaving profile f o r a c o m m u t e r railroad substation.

T h e LABES facility manages the peak loads occurring when trains pass along the railroad segment served by the substation] and is then charged t o replenish t h e amount of energy w i t h d r a w n irrespective of the t i m e of day. As clearly shown by the data in Table 5, LABES systems are used increasingly for peak-shaving applications throughout the world. The test results of LABES facilities are so encouraging, and t h e interest in t h e m so great, that commercial production o f such facilities can b e expected t o begin in the near future.

87

8.2. Johnson Controls 300 kW/SOO kWh LABES facility


Johnson Controls I n c . (USA) is a large producer of industrial energy management and lead-acid battery systems. T h e company h s designed and const,ructed a 300 kW LABES facility based o n a valve-regulated lead-acid (VRLA) cells used for the first t i m e in this application. T h e system was intended for peak-shaving and installed
at their Humboldt brass foundry for purely demonstration purposes.

T h e design and layout of the facility are presented in Fig. 43.


aL disconnect

22 feet

Fig. 43. Schematic of LABES facility [38].

T h e battery consists of 6 V/180 Ah building blocks. Fifteen inoiiobloclts are connected in parallel t o give 6 V/2700 Ah modules. Lead-coated copper busbars are used t o connect the lead-coated copper cell terminals. T h i s results in low battery resistance. Each niodule is fitted w i t h an internal air manifold t o provide cooling or

heating. An energy management system monitors and controls the state of each module. T h e battery i s assembled f r o m 64 modules ensuring 384 V and 2700 Ah at &hour discharge [38,39]. Table 13 gives a summary o f the basic characteristics of the battery.

T a b l e 13. VRLA b a t t e r y at Johnson C o n t r o l s H u m b o l d t brass f o u n d r y [38, 391.

B a t t e r y rating Depth-of-discharge Discharge range

2 h at 300 kW

End o f charge
GC6-1500D gel cells M o d u l e s (64) F o r c e d air cooling

60% 360 t o 320 V 460 V


192

G V, 1500 Ah 4 x 1.5 HP

T h e power conditioning systcm is of a diial-bridge six-pulse l i n e commutated design. The system has a noniinal 384 V dc bus voltage and a 480 V ac three-phase inpiit. It operates in a constant-power mode under the management of the control systcni. I n i t i a l battery charge is performed at constant power, and a constant-volt,age mode is applied for final charging. During peak-shaving (battery discharge), the power converter operates in a controlled-power mode under direction of the control system [38]. T h e static power converter i s housed in one cabinet w i t h talie

bridge and firing circuitry, power factor correction capacitors and the harmonic indicator. The entire LABES facility is under the coilt r o l of a JCI DCC 8500 energy management systcni. Only monthly
inspections of t h e system are needed, because i t operates fully automatically [38].

89

Figure 44 presents the daily power profile with and without t h e LABES facility.

200 O

12 Real time. h

I I

I
I

18

Wiih IABES iocility

12

I8

24

R e a l lime. h

Fig. 44. Daily power consumption of t h e foundry without (a) and with (b)
t h e LABES facility [38].

The good peak-shaving capabilities of the LABES system are obvious. Normal foundry baseload is 1100 kW. At alloy melting, 4-5 discrete power peaks occur of about 1600 kW. The power utility
rate structure includes a monthly peak power demand charge. In-

90

stalling the LABES facility, the m o n t h l y peak demand was reduced by 300 kW. T h e utility demand charge is about 8 $ kW-'. (In most industrial regions in the USA, the rate is 10 $ kW-'). A few years

of service o n l y are enough for the facility to become profitable [40]. Of course, the assessment of the economical benefits o f t h i s system can be performed based o n the peak power rates which differ for the different countries and regions of the world.

8.3. Lead-acid battery energy storage systems in the railway transport network
In San Diego (USA), an Exide 200 kW traction type gelledelectrolyte battery i s under construction in a light r a i l transit system t o meet peak power demand during morning and evening commuter r u s h hours. T h e battery is produced using Aat positive plates w i t h low-antimony grids. I t w i l l operate in a 2-hour discharge mode at 80% DOD and w i l l have a capacity of 1620 Ah (8 h rate). T h i s facility i s designed for purely demonstration purposes: t o determine technical parameters and economical benefits. I f these prove good enough, the remaining railway substations w i l l also be equipped w i t h similar LABES facilities. T h e latter w i l l be installed o n the customer side of the meter at the 600 V rectifier interface [27]. T h e public transportation system (PTS) in a given c i t y is always in competition w i t h individual transportation. I t has been established t h a t the attractiveness of a PTS is affected by two m a j o r system characteristics: travelling t i m e and frequency of trains run-

ning [41]. B o t h are acsociated w i t h high power demands. Figure 45 presents a typical train current-velocity-time diagram of a subway car. During acceleration periods, a h i g h power rate is needed. The running train represents a storage system for kinetic energy. A considerable part of this kinetic energy can be recuperated.

91

O F
- 0.50
energy

Fig. 45. Current-velocity-time diagram [41].

T h e B e r l i n subway system (100 km) has a t o t a l power demand of about 60 MW. Since 1982, BVG has been using t w i n cars w i t h onboard power converters t o transform the dc current t o ac energy and feed three-phase asynchronous motors. On braking of the r a i l cars, the ac energy is converted i n t o dc one and is fed back t o the network
again. It has been established that one rail car only regenerates about 50% of the acceleration energy. Since there are many rail cars o n the line, at a certain moment they may regenerate such a great aniount of braking energy, which niay create very high voltage in the conductors. To avoid this, much of the braking energy has t o be damped in braking resistors.

I f however BES facilities are installed at the substations, they can


store about 20% of the braking energy, which could then be utilized for meeting p a r t of the accelerating energy needs [42]. A model block diagram of such a substation is presented in Fig. 46.

For o p t i m u m energy recuperation, German experts recommend that storage should be as close as possible t o the energy source [35].

92

O.

Fig. 46. A m o d e l of t h e BES facility at t h e subway s u b s t a t i o n [42]. T h i s can b e achieved i f bat.tery storage facilities are dispersed to a great number of stops and are connected t o t h e d c busbar line. T h e use of braking energy recuperation may lead first' to reduction of t h e unit size of t h e rectifier stations since t h e acceleration power can partially b e supplied by battery storage systems. Secondly, BES facilities serve also as emergency power sources. In t h e case of failure

of t h e public supply network, t h e dispersed LABES systems on t h e dc busbar lines provide emergency power and trains can leave t h e
t u n n e l and stop at t h e n e x t subway station. T h e b a t t e r y i s connected in parallel t o t h e rectifier and acts as a voltage buffer. T h e share of current provided by t h e b a t t e r y depends on t h e ratio between t h e internal resistances of t h e rectifier and t h e battery. Since battery resistance varies depending on t h e stateof-charge and t h e cycle life, sophisticated management and control i s necessary t o guarantee reliable operation of t h e battery for this specific electric transport application.

93

9.

Valve-regulated lead-acid batteries for b a t t e r y energy storage systems

Valve-regulated lead-acid batteries (VRLA) are maintenancefree, which makes them especially suitable for battery energy storage. T h e y w i l l reduce significantly operation and maintenance costs of BES systems, and thus improve their competitiveness w i t h other energy storage options. On the other hand, they w i l l consolidate the positions of lead-acid batteries in this business field as compared t o other electrochemical power sources. The first VRLA batteries were employed by Johnson Controls
I n c . in their 300 k W / 6 0 0 kWh BES facility. These batteries used gelled electrolyte and displayed very good performance during their three years of service. T h i s stimulated the wider application of these

batteries. At present, two types of VRLA batteries are under test, batteries w i t h gelled electrolyte and those w i t h adsorbed glass mat. Since convection o f the electrolyte in VRLA batteries is strongly

inhibited, and n o forced circulation is possible, two m a j o r problems arise during battery operation which are inter-related:
a) Electrolyte immobilization creates, even though slowly, a nonhomogeneous and uncontrolled concentration distribution of electrolyte w i t h i n the active block. Since H2S04 is an active material, a non-uniform distribution of reaction rates in this block occurs. T h i s affects battery capacity and cycle life. In order t o reduce or totally

eliminate this adverse effect, a special charging mode has been introduced, and an equalizing long charge is carried o u t at the end of each week.

b) T h e non-uniform reaction rate distribution and the immobilization of the electrolyte in the active block b r i n g about a thermal non-homogeneity in the cells, and impede the dissipation o f heat
during high-power battery operation.

Possible solutions t o the above defects are sought in cell construction modifications. Smaller size and height o f the cells are recommended for high-current operating modes. Special requirements are claimed t o the charging mode and the thermal management of the battery.
In addition t o the irreversible processes typical for flooded lead-

acid cells (grid corrosion, active mass shedding, sulfatization, shortcircuits, etc.), another process also occurs in VRLA batteries, d r y i n g o u t of the cell. What is more, this process can proceed first, especially

on valve failure or excessive over-charge, and limit battery life.


Assembling of VRLA cells in a battery i s often accomplished by vertical stacking, which saves floor space and facilitates battery thermal management blowing air i n t o the cells.

All these problems are in the process of being solved, but even at this stage, VRLA batteries are preferred by a number of energy producers and consumers. In San Diego, an Exide traction type gelled
electrolyte battery has been installed in a light rail transit system. At the Plasma Physics Laboratory in Princeton, a 15 MW/5 MWh LABES plant is t o use VRLA batteries. Sonnenschein has requested the introduction of i t s VRLA batteries in traction service. Highperformance Hagen VRLA batteries are in stand-by service. YUASA describes i t s 3000 Ah VRLA battery for stationary service. The Japanese Storage B a t t e r y Company is also very active in this field.

Rand and Baldsing [43] have reported encouraging performance results o f gelled-electrolyte cells employed for remote-area power suppiy duties. An ever-more pronounced tendency is observed in the w o r l d battery industry for utilization of VRLA batteries for deep cycling in BES systems. T h i s would allow construction of unmanned maintenance-free BES facilities managed by remote control systems.

95

10. Strategic advantages o f B E S systems


T h e implementation of BES systems in the power industry offers the following m a j o r benefits and advantages:
Load-levelling (energy storage).

Considerable cost-effective

benefits are provided by utilizing low-cost energy f r o m the baseload generating utilities for meeting expensive peak energy demands.
D y n a m i c power response. T h i s is due t o the high operating flexibility and very short response t i m e provided by lead-acid battery plants. These plants are capable of supplying electric power for frequency control and instantaneous power reserve, and can be used

for peak-shavirig as well. All these functions provide dynamic power benefits resulting in improved quality of the energy delivered. Strategic advantages. These are more general in nature and have their impact o n environmental protection, efficiency of power transmission and distribution networks, and economy as a whole. These benefits cannot be directly measured but can be estimated by mathematical calculation and modelling. T h e i r importance is becoming increasingly evident [44]. Some o f these advantages w i l l be discussed below. It is general practice t o locate baseload power plants burning coal or nuclear fuel away f r o m populated centers. In this way the pollutants, dust, CO1, CO? and NO, emitted as a result o f the combustion process reach the populated areas in strongly reduced concentrations. I t is economically effective t o build peak power plants w i t h oil/gas-fired combustion turbines w i t h i n the boundaries of populated centers. In this case, however, harmful emissions f r o m these power plants w i l l cause considerable environmental pollution of the neighboring towns. LABES plants themselves are clean and quiet.

The o n l y environmental impacts of these plants are related t o the baseload generating units that supply the charging power. LABES
plants provide pronounced environmental benefits as compared t o combustion turbine peak plants.

96

W h e n BES plants are installed at t h e utility distribution substation, or BES facilities are located in the vicinity o f the consumer, transmission and distribution losses are significantly reduced and the stability of the network is improved. As is known, energy losses are proportional t o the current squared, and hence by decreasing and equalizing the current, these losses will be reduced. Additionally, by shaving t h e peak load transmitted, BESP allow deferral of capital costs for the construction o f new transmission and distribution capacities. Finally, power stability in t h e transition and distribution network is improved considerably owing t o the short response time o f BEC plants. In general, greater benefits will be achieved if BES plants are located close t o the loads, charging generators are more distant f o r m t h e load than BES plants, the difference between the on-peak and off-peak loads is high, and the transmission system is heavily loaded [44]. BES plants or facilities are m u c h easier t o site at any p o i n t in the populated centers than combustion turbine facilities. T h e costs of o i l and gas fuels used by peak power generation plants depend o n political, economical and other factors, a n d are very unstable. When combustion turbines are replaced by BES plants this instability of energy costs i s strongly reduced or eliminated, which i s a strong financial benefit. Another iniportant cost benefit is provided by the modular design of BES plants. B a t t e r y units are comprised of small modules allowing any load increase t o be met quickly and fully by installing additional modules w i t h i n a very short time.
So far, only a small number of BES systems have been constructed throughout the world and these are mostly in the demonstration

stage. T h e full range of benefits provided by BEC systems in the energetics have n o t yet been completely studied. But even at this i n i t i a l stage of demonstration tests and experimental operation, BES systems have shown promising performance and w i l l obviously become an important element of the modern power supply system.

97

Acknowledgements
T h e author would like t o acknowledge the kind assistance o f Dr.

W.C. Spindler, consultant t o ILZRO, USA, and Dr. S. Takahashi from the Government Industrial Research Institute in Osaka, Japan, in providing the necessary literature, and also for helpful discussions o n the problems of battery energy storage systems.

References
1. W.C. Spindler, Why Lead-Acid Batteries for Energy Storage, International Lead Zinc Research Organization (ILZRO) Project LE-363,

1989. 2. EPRI 1989.


3.
~

Energy Storage: How t h e New Options Stack up. Brochure,

Japan Industrial Technology Association. The Moonlight Project DeNew Technologies for Energy Conservation. veloping Brochure. 1989.
M. Tada, T. Sakamoto, T. Tanaka, H. Yamamoto, Y. Sera, T. Nakayama, Outline of the New Facilities of Tatsumi Electric Energy Storage System Test Plant, 2nd Int. Conf. Batteries for Utility Energy Storage, New Port Beach, California, 1989. M. Tada, E. Furune, T. Tanaka, T. Sakamoto, T. Oota, Y. Sera, T. Nakayama, Monitor and Control System to the New Facilities of Tats u m i Electric Energy Storage System Test Plant, 2nd Int. Conf. Batteries for Utility Energy Storage, New Port Beach, California, 1989.

4.

5.

98

6.

J.L. Sudworth, T h e Sodium Sulfur Battery (J.L. Sudworth, A.R. Tiller, eds.), Chapman and Hall, London, 1985, p.9.

7.

N. Itoh, T. Nakayama, T.Hiramatsu, S.Takahashi, R&D Evaluation on Energy Storage Batteries for Power Systems in Japan, R e p o r t NEDO-OS-8801, Government Industrial Research Institute, Osaka,
Japan.

8. S. Fucuta, T. Hirabayaski, K. Satoh, H. Satoh, Proc. 3rd Int. Conf. Batteries for Utility Energy Storage NEDO, EPHI, BEWAG, Kobe, Japan, 1991, p. 49. 9.
R.J. Bellows, P.G. Grimes, Zinc/Halogen Battery, in Power Sources for Electric Vehicles (B.D. McNicol, D.A.J. Rand, eds.), Elsevier, Amsterdam, 1984, p. 621.

10. D.A.J. Rand, Overview of Performances of Candidate Battery Systems, in Power Sources for E l e c t r i c Vehicles (B.D. McNicol, D.A.J. Rand, eds.), Elsevier, Amsterdam, 1984, p. 721.
11. P. Symons, C. Warde, P. Carr, Development of t h e Zinc/Chlorine Battery for Utility Applications, Part 1-4, EPRI EM-1051 (Project 226-3), 1979.

12. M. Barak, Electrochemical Power Sources, Peter Peregrinius, Stevenage, 1980, p. 251.
13. D. Pavlov, in Power Sources for Electric Vehicles (B.D. McNicol, D.A.J. Rand, eds.), Elsevier, Amsterdam, 1984, p. 111.

14. P. Montalenti, Report 6, 1982. 15. G. Smith, 1964, p. 252.

in Power

Sources 9

(J. Thomson,

ed.),

Storage Batteries,

2nd Ed.,

Pitman, London,

16. W.G. Sunu, B.W. Burrows, Power Sources 8 (J. Thomson, ed.), Academic Press, 1981, p. 601.

99

17. I<. Takahashi, M. Shiomi, T. Funato, M. Tsubota, Proc. 3rd Int. Conf. Batteries for Utility Energy Storage NEDO, EPRI, BEWAG, Kobe, Japan, 1991, p. 187. Ruetchi, 18. P. 4 (1966) 383.
J.B.

Ockermann,

Electrochem. Technol.,

19. D. Pavlov, T . Vitanov, I . Nikolov, V. Nikolova, G. Papazov, K. Petrov, US Patent 4, 925, 746 (1989). 20.
K. Peters, A.I. Harrison, W.H. Durant, Power Sources 2 (D.H.Collins, ed.), Pergamon Press, Oxford, 1968, p. 1. H. Tuphorn in Advances in Lead-Acid Ba tte ri e s (K.R. Bullock and D.Pavlov, eds.), T h e Electrochem. Soc. Inc., Pennington, NJ, USA,

21.

1984, vol. 84-14, p. 441. 22.


K.R. Bullock, B.K. Mahato, G.H. Brilmyer, G.L. Wierschem, ibid,
p. 451.

23.

B.IC Mahato, K.R. Bullock, Progress in Batteries and Solar Cells, 6

(1987) 136. 24. Energy


Denver,
cells, Technical Leaflet

20 M3/77, Gates Energy Products,

USA, 1977.

25. R.F. Nelson, Proc. 4th Int. ILZRO Lead-Acid Battery Seminar, San Francisco, CA, USA, 1990, p. 31. 26.
K. Okada, in Rechargeable Batteries in Japan (Y. Miyake and A. Kozawa, eds.), JEC Press Inc., 1977, p. 291.

27. G.M. Cook, W.C. Spindler, J. Power Sources, 33 (1991) 145. 28. 29.
D. Morris, EPRI Journal, March issue, 1988, p. 1.

A.M. Chreitzberg, F.L. Tarantino, I.C. Baeringen, Design of a 10 MW/50 MWh Lead-Acid Load-Levelling Battery, Int. Conf. Batteries for Utility Energy Storage, Berlin, 1987.

30.

G.D. Rodriguez, W.C. Spindler, D.S. Carr, Operating t h e Worlds Largest Lead-Acid Battery Energy Storage System, Proc. 4th Int. ILZRO Lead-Acid Battery Seminar, San Francisco, CA, USA, 1990.

31. S. Eckroad, Proc. 3rd Int. Conf. Batteries for Utility Energy Storage NEDO, EPRI, BEWAG, Kobe, Japan, 1991, p. 269. 32. G.D. Rodriguez, W.C. Spindler, Operating t h e Worlds Largest LeadLong Beach Acid Battery Energy Storage System, 4th ABC CSU Conf., 1989.
~

33. H. Dominik, B. Voigt, Applications and Economics of Battery Energy Storage Systems, Abstract 14, Lead Battery Power for t h e 90s Conf., Paris, 1988. 34. G.D. Rodriguez, Edison Embarks on Another F i r s t : The Chino 10 MW Battery Energy Storage Project, Research Newsletter, 16 (3) (1987) 1. 35. D.S. Carr, Lead-Acid Battery in U S E l e c t r i c a l Load-Levelling Applications, Abstract 16, Lead Battery Power for the 90s Conf., Paris, 1988. 36. P. Berger, K.G. Kramer, W.Naser, R.Saupe, T h e BEWAG 8.5/17 MW Battery Energy Storage Demonstration Plant, Int.. Corif. Batteries for Utility Energy Storage, Berlin, 1987 (BEWAG-EPRI-NEDO).
37.

K.G. Kramer, BEWAG Plan Berlins New System, Batteries International, l(4) (1990) 32.

38. R. Hamann, R. Scarvaci, G. Brilmyer, ILZRO Lead-Acid Battery Seminar, Orlando, Florida, LEA, 1989. 38. G. H. Brilmyer, Batteries International, 1 (4) (1990) 36. 39. W.C. Spindler, Industrial Applications of Large Lead-Acid Batteries for Emergency and Peak Power Demand. World Lead-Zinc-Tin Syniposium 90, Anaheim, CA, 1990.

101

41.

K.G. Kramer, B.Voight, Proc. 3rd 1nt.Conf. Batteries for Utility Energy Storage NEDO, EPRI, BEWAG, Kobe, Japan, 1991, p. 519. B. Voight, T. Mierke, H.J. Hinrichs, Batteries International, 1 (4) (1990) 18. D.A.J. Rand, W.G.A. Baldsing, J. Power Sources,
23 (1988) 233.

42.

43.

44.

R.B. Shainker, Proc. 3rd Int. Conf. Batteries for Utility Energy Storage (BEWAG-EPRI-NEDO), Kobe, Japan, 1991, p. 519.

102

Chapter 2 ENERGY STORAGE S Y S T E M S FOR ELECTRIC VEHICLES

G. PAPAZOV

1. M o t o r vehicles and environmental pollution


O w i n g t o the continuous development of h u m a n society and rapid technological progress, m a n k i n d is now faced w i t h a crucial problem whose solution w i l l determine i t s future. T h i s problem is the environmental p o l l u t i o n caused by human activities. E r i c h Sauer

[il

illustrates the impact of industry and transport on the environment in terms of harmful gas emissions measured in Germany in 1980

(Table 1).
Table 1. Harmful gas emissions in Germany
Type of pollutant Industry min. taons

[il
%
44 56 32 48
1.5
Total mln. tons

%
56 44 68 52 98.5 95.5

Transport min. tons

CH ,, CO NO2
Pb

so2
dust

1.02 5.7 1.56 0.0032 4.04 0.478

0.8 7.3 1.4


0.003

1.82 13.00 2.96


0.0062 4.1

0.06 0.022

4.5

0.5

A number of modern internal combustion engined (ICE) vehicles


use appropriate catalytic cartridges that improve fuel combustion, or

103

employ lead-free petrol fuels. Table 2 presents quantitative comparative data on t h e adverse emissions released p e r kilometer both with and without catalysts [l].
T a b l e 2. Specific gas emissions of ICE vehicles
~

[il.
With catalyst
g km-'

Type of p o l l u t a n t

W i t h o u t catalyst g km-'

CnHm CO NOz Pb

2.253 22.999 3.264


0.010

0.28 2.2 0.66


0.0

so2
dust

0.039 0.035

0.039 0.042

Despite the ten-fold decrease in the quantity o f some pollutants, the amount of harmful exhaust gas emissions f r o m cars o n a worldwide basis i s measured in millions of tons. T h e above tables d o not include data o n carbon dioxide which i s t h e end-product o f fuel conibiistion. T h i s COL is accumulated in t h e atmosphere contributing t o the so-called "greenhouse effect", i.e. temperature increase. T h e data presented in Table 2 are average values for the various

gas emissions. These emissions differ in magnitude at different hours,


b o t h daytime and nighttime (Fig. l ) , being largest during the day w h e n urban traffic is most intense [l]. T h e exhaust gas emission depends also o n the travel speed o f the

ICE vehicle and this relationship is illustrated in Fig. 2 [ l ] . Evolution of harmful gases (except for KOz) is reduced increasing
t h e travel speed. M o s t of t h e t i m e a car is used in urban conditions: for driving t o w o r k and b x k home, for shopping, during leisure time, etc. City driving means travelling at a low speed with frequent halts

104

Fig. 1. 24-hour dist,ribution of gas emissions [l].

Fig. 2. Dependence of gas emission o n vehicle speed [l]

and starts and low operational engine speed, which, according t o t h e


above-mentioned data, is associated w i t h a several-fold increase of the harmful gas emissions in populated regions. In other words, environmental pollution caused by the transport i s n o t uniformly distributed over the earths surface. I t is greatest in areas with considerable con-

105

centrations of human masses. Thus, the ecological problem related t o the noxious gas emission f r o m transport vehicles is n o t so much a problem of the environment, but rather a problem of people's health and of the genetic stock of mankind. Bearing in mind that motor vehicles release millions of tons of harmful gases daily, t h i s problem acquires crucial importance and i t s solution becomes a question of the survival of our civilization. At the present moment, large-scale introduction of electric vehicles i s one of the basic ways of reducing the environmental impact of noxious gases and noise. I f 7,000,000 ICE automobiles are replaced by electric vehicles, p e t r o l consumption w i l l decrease by about 3.5%, the amount of toxic gas emissions w i l l be reduced by 20-30%, and the noise level in the cities w i l l decline significantly [2].

2. Specification o f energy storage systems for electric vehicles


T h e t e r m electric vehicle indicates any rail-less, autonomous vehicle, independent of external systems, and driven by the energy generated by an electrochemical power source. We can regard as ancestor of the modern electric vehicle the transp o r t vehicle devised by the Americans Devenpator and Page in 1837 [3]. Literature data evidence the invention of another electric vehicle by Robert Davidson f r o m Scotland in the same year [4]. In 1897, a number of electric-driven taxi cabs were o n the road in London. A record r u n n i n g speed of 63.3 km h-' was achieved by an electric car in 1898, and only a year later, in France, a battery-driven car reached

the then unthinkable speed of 106 km h-l. T h e first Russian elect r i c vehicle appeared also in 1899. 6000 electric vehicles were built
in the USA in 1912. T h e basic characteristics, given in averaged

values, of the battery-driven cars produced in 1923 are as follows: payload 200-250 kg, range between battery charges 50-80 km, speed

106

20-35 kin h-, battery energy 10-18 kWh at a b a t t e r y weight of about 750-780 kg [3]. After the 1920s, electric vehicles began t o lose their positions in the competition w i t h ICE automobiles. In the mid-60s, however, owing t o the Oil Crisis, interest in electric driven transport vehicles was revived. In the course of t h e numerous development and demonstration progranis that followed, the electric car exhibited i t s basic disadvantages associated niairily w i t h the chemical power source used for energy generation. T h e reduced petrol costs at the beginning of the 1980s once again caused interest in the electric vehicles t o decline, and a number of developnient and improvement projects in this field t o be interrupted. By t h e end of the decade, however, the attent i o n of automobile users and producers towards the electric-driven car marked a certain rise again. Accounting for the fact that o i l resources are finite, environmental pollution is largely caused by the exhaust emissions of internal combustion engines, and electric energy generated by thermal, water and nuclear power stations cannot be used directly for automobile propulsion, it becomes evident that the future belongs t o electric vehicles driven by electrochemical power sources.

What are motor vehicles utilized for o n a worldwide basis, and how? According t o E. Sauers investigations [il, average distance the run by a motor car varies w i t h mission. T h i s is illustrated in Table 3 which gives d a t a (measured for 1975) about the diverse-task range
distribution of automobiles. T h e data show that, except for the holiday journeys, the average range of a single travel is less than 20 km. 94.5% of the yearly distance run is comprised of such short-range travels. T h e longrange journey (650 km) for holidays accounts for o n l y 5.5% o f the t o t a l travelling distance during the year. K n o w i n g the frequency of the various range travels, it turns o u t that 90% of al1 travels are at a distance below 25 km. On the other hand, all above-mentioned

107

T a b l e 3. T r a v e l mission and range d i s t r i b u t i o n Travel mission professional educational business shopping leisure time holidays

[il.
Single t r a v e l range, km

% of t h e y e a r l y
distance range

23.9 3.4 24.9 11.3 31.0 5.5

11.1

13.7 18.0 7.2 15.7 685.4

trips, w i t h the exception of the holiday journey, are accomplished in

urban conditions, i.e. at a limited speed of up t o 60 km h-'. T h e above data refer t o Germany. For other countries, there might be some specific features in the utilization of motor vehicles, but these deviations f r o m the above average values are unlikely t o be so significant as t o impose substantial changes o n the overall picture. It can thus be assumed that a car performs t w o trips daily at an average distance of 16.7 km each and an average speed of up t o 60 km h-l. T h e da.ily distance run is 33.4 km or 12,200 krn per year, which may be considered as o p t i m u m utilization of the vehicle What is the energy needed t o ensure this optimal usage of the automobile? Table 4 presents data o n the basic power characteristics o f some types o f motor cars [1,5]. T h e energy consumption of a V W - G o l f CitySTROMers electric vehicle for a range of 100 km is presented in Table 5 [l]. other types of electric vehicles, the energy demand For varies f r o m 30 t o 50 k W h / 1 0 0 km [3,6]. T h e first question is which type of power source is capable of supplying this energy? A summary of the basic performance characteristics of various electrochemical power sources i s presented in Table 6.

[il.

108

T a b l e 4. Power characteristics o f several a u t o m o b i l e types. Characteristics Peugeot 205


Maximum power, kW R a t e d power, kW

Automobile type C i t r o e n C15

VW-Golf

18.5 12.7

23.0 16.0

24.0

12.0

T a b l e 5. E n e r g y c o n s u m p t i o n p e r 100 km of t r a v e l l i n g range. Speed, km h-' Energy, kWh/100 km 50

21.5

70 27.6

c i t y driving

30.0

T a b l e 6. B a s i c performance characteristics of various types o f batteries. Electrochemical p o w e r source Specific energy Wh kg-' Specific power W kg-' Cycle life

References

Improved Pb/acid Gelled P b / a c i d Golf t r a c t i o n P b / a c i d Tubular P b / a c i d

37 26 30 34.3 37.7 55 70 40 55 52 106 72 175 60

105 95 96
108

176 318 323

161 161 161 161 161 I61 161 161 171

EV-5T HED-88 Ni/Zn Ni/Zn


Ni/Fe Ni/Fe

112 218
~

> 850 > 100


195
-

163
-

> 650
~

Ni/Cd
Allair

Zn/Br Na/S
Li/MoSz

200 6.5 20
-

1200
~

250
-

[lo1

181 11 9

[71
11 11

208

500

109

Figure 3 illustrates the basic power and energy parameters of some o f t h e above-mentioned electrochemical power sources [3]. I t can be seen that non-aqueous-electrolyte batteries ( l i t h i u m and sodium/sulfur cells) show considerably higher energy performances

than aqueous-electrolyte power sources. As t o the latter, it is evident that alkaline nickel cells have better energy capacity than lead-acid storage batteries.

1 0

1 0

20

3 0 4 0 5 0 7 0 i o o

Specific pciwer, W kg-'

Fig. 3. Power and energy characteristics of several t y p e s of batteries.

T h e energy needed for electric vehicle propulsion depends o n the car weight and the travelling range, and it can be determined from the following equation:

110

(1 )

E=KGL

where E is the energy delivered by the power source measured in Wh, K i s the specific energy needed for transportation of 1 kg o f weight at a distance of 1 km measured in Wh kg-' km-'. When all side factors of travelling, e d friction, aerodynamic drag, etc., are taken i n t o consideration, t h e value of K i s estimated at 0.120.15 Wh kg-' km-' [3]. G is the weight of the vehicle in kg, and L i s the distance range in km. Thus, for a 1600 kg electric vehicle t o cover a distance of 100 km, 24 kWh of energy will b e required supplied by an electrochemical power source. The t o t a l power delivered by the storage b a t t e r y is utilized for vehicle acceleration, and for overcoming friction and aerodynamic drag. Besides, additional power i s also needed t o compensate for the energy losses during conversion o f the electrical t o mechanical energy (efficiency ca. 0.7), and also during transmission of this mechanical energy t o the car wheels (efficiency ca. 0.95). W h e n operated in urban driving conditions, the maximum power of an electric vehicle is about 17-19 W kg-', and the average power at constant speed i s about 12-13 W kg-' [5]. Let us assume that a 4-seat electric car needs an average power of 20 kW and an energy of 30 kWh for covering a road distance o f 100 km. Using the data presented in Table 6 we could calculate t h e weight of t h e various batteries that could supply t h e power needed for this 100 kni range of the vehicle. The results obtained are summarized in Table 7. I s is evident f r o m the d a t a in the table, t h a t battery weight cornprises a considerable p a r t (25 t o 50%)
of the t o t a l car weight. For comparison, i t can be pointed o u t that the energy needed for covering t h e same travelling range of 100 krn

could be supplied by aboiit 3 k g of gasoline w i t h specific energy of 11,600 Wh kg-' [3].

111

Table 7. Calculated battery weight, needed for 100 km travelling range.

T y p e of power
source

Battery weight

kg

Improved Pb/acid Gelled Pb/acid Golf traction Pb/acid Tubular Pb/acid

810 1154 1000 875 796 545 750 577 283 417 500

EV-5T HED-88 Ni/Zn


Ni/Fe
Ni/Cd Al/air Zn/Br

Li/MoSz

T h e range of the electric vehicle, according t o eqn (l), depends o n the energy capacity of the power source, and the car weight. K n o w i n g that the energy of the power source can be expressed by the specific energy W (Wh kg-') and the battery weight M (kg), the range of the electric vehicle w i t h o u t charging of the battery can be determined f r o m eyn (2):

L,-

WM KG

T h e range is directly proportional t o the specific energy and the weight of the battery, and inversely dependent o n the car weight.

A graphic representation of this dependence for a 1200 kg electric vehicle (excluding battery weight and including 320 kg payload) using
112

lead-acid batteries (W = 30 Wh kg-') of various b a t t e r y weight, is given in Fig. 4.

3oom

700

900

il00

Battery weight, kg

Fig. 4. Dependence of electric vehicle r a n g e on b a t t e r y weight.

It i s evident that t h e greater the battery weight, the longer the range between battery charges. With increasing the weight of t h e battery, however, the t o t a l car weight is also increased, which, according t o eqn (2), w i l l shorten the travelling range. I t should also be noted, here, that increasing the t o t a l car weight leads t o reducing the relative share of the payload transported by the vehicle. Using this formula, we can determine the maximum theoretical range of a b a t t e r y driven electric vehicle. That is, the distance covered by the vehicle when M = G,i.e. when only the battery i s being transported, the remaining car weight being negligible. T h e obtained values for the maximum theoretical range for various types of electrochemical power sources w i t h K = 0.15 Wh kg-' km-' are presented in Table 8. As evident f r o m the table, the m a x i m u m theoretical range of an electric vehicle driven by various types of power sources varies w i t h i n the l i m i t s 200-400 km, except .for the Al/air and Na/C batteries which provide for longer ranges. The actual range, of course, is twice

113

Table 8. Calculated maximum range for various types of batteries. Type of power source Specific energy Maximum range

Wh kg-'
Improved Pb/acid Gelled Pblacid

km

Golf traction Pb/acid


Tubular Pb/acid EV-5T

37 26 30 34.3 37.7 55 70
40

247 173 200 229 251 367 467 267 367 347 707 480 1167
400

HED-88
Ni/Zn Ni/Zn Ni/Fe
Ni/Fe
Ni/Cd Allair

55
52
106

Zn/Br Na/S Li/MoSz

72 175
60

t o four times smaller than t h e theoretical one, because the vehicle h s a a considerable gross weight, o n the one hand, and should transport maximum payload, o n the other hand. Hence, the problem of the o p t i m u m ratio between the battery and vehicle weight arises. I f this relation is determined o n the basis of the existing operational electric vehicles, it w i l l show t h a t the power source weight accounts for 25-

40% of the gross car weight. In this case, the actual travelling range of the vehicle is respectively 25 t o 40% o f the theoretical one. When discussing the energy performance of electric vehicles, the
problem of o p t i m u m energy utilization should also be given consideration. Thus, for example, the efficiency of internal combustion en-

114

gines is about 25--30'% [ 3 ] . wliich means that from t l i c 11,600 Wli kg-' specific energy of gasoline only about 3500 Wli kg-' arc u t i l i z e d for vehicle propulsion. T h e operating efficiency of electric trwctiori systems is much higher rcaching up t,o 85% [ 3 ] . Beside tlicw iicgligiblc energy losses, electric traction systems allow easy and snioot,li regulation and control of t h e travelling speed. Sonic dynamic parameters of the electric vehicles are also w o r t h discussing hcrc, c.g. maximum speed and acceleration rate (Table 9), that are determined by the energy characteristics of the battery.
T a b l e 9. Some d y n a m i c parameters of electric vehicles. Electric vehicle Peugeot 205 Citroen C15 VW-Golf ErAZ-3732 VA Z -2801 M a x . speed T i m e for accclcrating
f r o m O t o 50 km lip', c

References

km h-'
100 80 100 60 -

11.6 11.6 13.0


-

151

Pl I1 1
[31

lLO*

131

* (0-60 km h-I)

By their dynamic parameters, electric vehicles are considerably


inferior t o ICEVs. On the other hand, being designed for predominant c i t y driving, electric vehicles show adequate speed and acceleration performances t h a t meet the requirements set by the conditions of operation. These facts are of utmost importance in assessing the prospects for future EV development. T h e second crucial problem t h a t needs adequate solution i s the problem of battery charging. The fuel in the tank of an ICE vehicle supplies useful power for a travelling range o f about 500-600 krn and refuelling at t h e petrol station takes only a couple of minutes.

115

Charging of the electric vehicle battery usually requires several hours, and t l i c duration of charging is often twice or three times longer than t h e discharge period, i.e. the t i n i e of utilization o f the car. T h i s results in a cyclic profile of operation o f the electric vehicle, the time of rcst being much longcr than the driving time. It has been suggested that, similar to petrol stations, battery charging stations should be

built along the motor roads, where discharged electric vehicle batteries would be l r f t for charging and replaced by ready-for-use charged ones. This idea is hardly feasible, because, o n the one hand, it presupposes unification of all EV power sources used, i.e. employment of t h e same type of battery by all electric vehicles, and, o n the other
liaiid, the nuniber of batteries needed w i l l be at least three times the iiumber of electric vehicles o n the road.

On the basis of the &ta given in Table 3, the average daily


range [l], the distance covered without battery charge, and the cyclic mode of EV utilization, it can be concluded that electric vehicles can meet all travelling requirements, except the long range of the holiday travel. The elcctric vehicle is used for the purposes outlined in Table 3 usually during the day, so charging of i t s battery could be performed at night, when the car i s at rest. As regards l o n g distance trips, public transport such as trains, buses or airplanes, could be used in these cases. T h e problem of the restricted freedom and m o b i l i t y asso-

ciated w i t h the use of public transport could be easily solved first by


employing petrol-engined automobiles for long-distance travel, and
later by combining the use o f public transport for long-range trips

and rent-a-car electric vehicles for local transportation.


T h e third problem w i t h electric vehicle efficiency is related t o the life of the battery used for propulsion. I f the day-night cycle mode of the electric vehicle is assumed, then the b a t t e r y should endure

365 cycles per year. T h e data f r o m Table 6 show that only Ni/Cd,

116

Ni/Fe and tubular Pb/acid batteries can ensure 2-3 years of vehicle operation without battery change.

And last but not least in importance i s t h e problem of battery


cost. There are two aspects of this problem. T h e first refers t o t h e cost of t h e battery as related t o t h e cost of t h e electric vehicle without battery. T h u s for example, t h e ,4g/zi1 battery has a liigli specific energy (120 Wh kg-') ensuring a travelling range of 300 krri,

but i t s price would b e about 100,000 roubles, while t l i c vehicle's price


without battery would be about 10,000 roubles [3]. That is the I(~asoii why t h e Ag/Zn battery, in spite of i t s liigli energy perforrriaiice, i s
excluded f r o m t h e list of candida.tes for EV powcr sources. T h e second aspect of t h e bat tcry cost proi>leiii i s rclatcd to t,lic total lifetime energy cost, of t l i c battery, in other words t,lic> cricrgy cost 1)cr 1Wh or per 1 lim. Unfortunately, it i s \-cry difficult to nialie a precise energy cost assessment since a great part of t l i c elcctroclieniical p o w e r sources are still in t h e prototype phase of devclopmciit a i i c i have no specified market price. On t h e other hand, prices of coiiiiiiercially available batteries vary coiisiderahly for thc various coiiiitrics. T h i s i s well illustrated by t l i c data presentccl in Talilcs 10 and 11 bc~low, giving the costs per 1 kWh of energy arid 1 kni of range for severai types of electrochemical powcr sources.
T a b l e 10. Specific energy costs for sornc t y p e s of b a t t e r i e s .

Type of
battery

c o s t , 11s $ per 1 kW1i per 1 lai

Rcfcrciicrs

Pb/acid Ni/Cd
Molicel

0.387'
0.263* 1.220*

0.116

Pl
[SI

0.079 0.366

[ill

* Data calculated for energy c o n s i i m p t i o i i of 0.30 k W 1 i km-'.


ll

T h e costs (in roubles) per 1 kWh of energy delivered by batteries produced in t h e USSR are given in Table 11 [3].
T a b l e 11. Specific energy costs of some R u s s i a n batteries.
Type

C o s t p e r 1 kWh, roubles

Versus P b / a c i d cost

Pb/acid Ni/Cd
Ni/Fe

O. 02-0.04

1.o
10.0

0.2-0.4 0.04-0.06
0.1-0.2 0. 1550.30

N i /Zi i Ni/Hi
Pb02/Hz Zn/Br Na/S

2.0 5.0 1.o


5.0

0.02-0.04

o. 1 o. 1

5.0

In spite of t h e incomplete and sometimes contradictory data available, it i s generally accepted that lead-acid and t o some extent Ni/Fe batteries are m o s t cost-effective for electric vehicle propulsion. Though there is a certain bias for one or t h e other t y p e of power source among experts in the field, t h e most appropriate battery t y p e
for electric vehicle application has not been found yet. Despite t h e numerous design improvements, lead-acid batteries s t i l l remain heavy
systems with ratlier low energy performance; alkaline batteries are ratlier expensive; N i / F e batteries need improvement of cell cooling (by electrolyte circulation, for example); Ni/Zn batteries have very short cycle life; there are a number of unsolved design and technological problenis with high-temperature cells (Na/S); fuel-cells employing platiiiuni metals as catalysts are characterized by high weight

and large volume, short cycle life and complicated operation; Zn/Br
cells require a coniplex system for operation monitoring and control, and morcovcr bromine is toxic and hence special safety measures

are needed; the exotic metal/hydrogen batteries face t h e problems

of self-discharge and safety [3]. T h i s short overview o f deficiencies


of the various types of electrochemical power sources does n o t mean

that investigators have given up the idea o f finding at least t h e best,

if n o t the ideal, suitable power source for electric vehicle propulsion.


Research activities are being carried o u t with increasing intensity, every research team having i t s own favourite t y p e o f battery. Thus, for example, investigations in France are concentrated o n Ni/Cd, Ni/Zn and Ni/Fe cells; Japanese researchers pay greater attention t o Na/S and Zn/Br; R&D efforts in the USA are devoted m a i n l y t o fuel cells, A l / a i r and Na/S batteries; lithium batteries are the basic subject o f investigations in Canada; the basic target o f R&D activities in Germany and England are Na/S batteries, etc. There is one comm o n feature uniting all research centers, however, and that i s t h a t all of t h e m show a marked preference t o t h e lead-acid battery as their favourite electrochemical power source or as a reference stan-

dard. China [12] and I n d i a [13] have also initiated programs for the
development o f lead-acid battery driven electric vehicles. Consultants f r o m the US Department of Energy [14] have evaluated 24 types of batteries lead-acid; alkaline; ambient-temperature Li; flow and metal/air; high-temperature batteries, etc. T h e assessment was based o n designed power packs for an Improved Dual~

Shaft Electric Propulsion (IDSEP) Van. The technical requirements of the battery were as follows:
o max. weight

o max. volume

min. power min. energy o min. system voltage o min. life


0 0

700 kg 600 1 55 1iW 21 1 h ; W 120 V 500 cycles

119

T h e criteria for battery evaluation included:


O

cost

o performance - energy vus. power, power 'us.


0

DOD

cycle life
~

o safety

effects of normal and abnormal battery operation on

passengers and public safety


o abuse resistance effects of overcharge, overdischarge, singlecell failure, shock and vibration o dc-dc efficiency
~

0 environmental impact - issues in battery manufacture, operat i o n and control o use of critical resources - use of i m p o r t makerials 0 user issues - type, frequency, and complexity of routine maint eriance

The results f r o m the performed analysis are illustrated in Fig. 5 showing the suitability/techiiical risk relationship for 12 battery
types applicable t o the IDSEP van [14].

As suitable "low-risk? battery types are assessed technologically mature power sources in iarge-scale production. Examples are the Ni/Fc batteries produced by Eagle-Picher Inc.; sealed leadacid batteries (Electrosource Inc., Concorde) and Na/S batteries (BBC/Powerplex Technologies Inc., Chloride Silent Power Limited). T h e group of "medium-risk" technologies include Zn/Br and flowthrough lead-acid batteries developed by Johnson Controls Inc., Li/FeS technology pursued by G o u l d I n c . and Electrofuel M a n ufacturing Co., Fe/air of Westinghouse Electric Corporation, and Na/metal chloride systems developed j o i n t l y by Beta K&D Ltd. and Harwcll Laboratorics.

T h e highest technical r i s k i s associated w i t h prototype batteries developed at universities and/or national laboratories, but s t i l l lacki20

Lorv risk

I Medium risk I High risk

Technical risk

Fig. 5. Risk/suitahiiity relationship for battery technologies [i-i]. i n g a mature manufacturing technology. Examples of such battery technologies are the Li/FeSz battery developed by the Argonne National Laboratory, Lawrence Berkeley Laboratorys Zn/air project,

and the bipolar lead-acid batteries designed by Ensi Inc. and the Jet
Propulsion Laboratory. T h e general conclusion from this assessment is that there is n o

ideal battery technology for electric vehicle applications, and further research activities should be directed mainly at iniprovernent o f the above-mentioned battery types. Other problems concerning electric vehicle utilization are general issues relevant for all types o f automobiles, i.e. t h e issue of energy (fuel) economy, which can be reduced to considerable decrease in car weight and improvement of i t s aerodynamic shape. T h e problem of ICE t o electric vehicle conversion should also b e mentioned here. T h e simple conversion of a petrol-driven car t o an electric vehicle using the same basic construction would give a transport vehicle

121

w i t h poor user performance. Thus, for example, a 4 t o 5 seat car w i t h high speed and practically u n l i m i t e d range would be converted i n t o a two-seat electric vehicle w i t h l i m i t e d driving speed and l i m i t e d range. It has been suggested [3] t h a t the design o f new constructions for electric vehicles is imperative. This, however, would slow down

and complicate the process of transition f r o m ICE t o battery driven


vehicles.

3. C h a r g e and capacity o f batteries for elect r i c vehicles


Charging of batteries is accomplished by l e t t i n g electric current f r o m an external power source flow t o each battery cell. T h e charge current should guarantee complete charging of the individual battery plates, equal state-of-charge of all battery cells or modules, and adequate gas evolution at the end of charge ensuring proper stirring of the electrolyte. T h e charge current is the most i m p o r t a n t parameter in the process o f battery charging. It is well k n o w n that i f lead-acid batteries are charged at a h i g h rate ( w i t h a high charge current), their cycle

life is shortened. At the battery Technology Center of the M e l l o n I n stitute, USA [15], the effect o f charging current o n the performance parameters o f the Golf-car batteries has been investigated. T h e results obtained are presented in Fig. 6. W h e n high-rate charge is performed (50 A), battery capacity increases rapidly during the first 20 cycles, but the service life of these batteries is t h e shortest. The end of battery cycle life in this case is determined by corrosion of the positive battery plates. At very low charge currents (12 A), the battery does n o t reach i t s maximum capacity and has a short cycle life owing t o sulfatization of the plates. It turned o u t that t h e o p t i m u m charging current ensuring maximum cycle life of the battery is the current corresponding t o the 5-hour

122

loo

150 Life, cycles

200

n o

Fig. 6. Dependence of cycle life on c h a r g i n g r a t e (151

charge cycle. In this case, shedding o f the positive active mass is the life limiting factor. A p p l y i n g constant-current charging modes does n o t seem t o be the most appropriate method for charging of batteries. Battery charge should be performed at maximum charge acceptance, avoiding unacceptable temperature rise and minimizing gas evolution. For electric vehicle applications, particularly, the following t w o charging modes are recommended [4]: a) Controlled I / V charging method. In this method, charging is carried o u t under constant-current conditions during the efficient stage, followed by a cross-over t o constant-voltage conditions when a defined voltage is reached (Fig. 7).

123

$:rq-J
Current

2 3 Hours

u 2.4

= 2.2
2.01 O
I 1
I I 2 3 Hours

Fig. 7 . B a t te r y charge u n d e r controlled I / V c o n d i t i o n s [4]

The value of the cell voltage i s selected t o give slight gas evolution and t o enable the battery t o be charged w i t h i n a short time period.
b) Tapered charging method. In this method, the ma'timum charging current is l i m i t e d by the cell voltage (Fig. 8).

A linear relationship is used provided t h e following conditions are satisfied: (a) the charging unit must be able t o provide the
maximum current at a c e l l voltage 2.1 V, and to reduce this t o a

defined value on reaching 2.6 V per cell at the end of charge; and (b) at a voltage of 2.5 V, t h e current must n o t exceed 8.33% Cg. Under these conditions, the rate of gas evolution w i l l n o t surpass the permissible limit, and n o damage w i l l be caused t o the battery. Batteries for electric vehicle propulsion consist of a large number
of battery cells or modules connected in series. Each cell or mod-

ule has i t s o w n internal impedance different f r o m that of other cells

124

7.0

k 5 1 0
I

Chorger oulpul

2.0

Amperes per 1OOAh CCIpOCly

-20.:
-15
-10

x
u
$

f 8

s s

-5
2 .o
O
I
I

0 5

6 Hours

1 0 1 7

Fig. 8.

(a) haximum current at the output of t h e taper charger us. c e l l

voltage; (b) Cell voltage and charging current 71s. t i m e [A].

and modules, which determines the nori-uriifurm distribution of the charge voltage among the cells. This i s of n o importance at the beginning of charge, but near t h e end of charge, some of the cells will reach t,he water decomposition voltage more quickly and hence gas evolution will start in them, while the process of charging will continue in the remaining cells. In this case, a sniall increase in voltage will cause a considerable increase in gassing and, accordingly, t h e energy consumption will grow significantly. Scientists at the University of Alabama at Huntsville [15] have devised an average voltage based control system. A microprocessor measures the voltage differences between the individual cells (modules) and controls t h e charge current so as to prevent reaching the gas evolution voltage in any of

125

the cells. In this way a better balance of charge is achieved between the cells and hence better performance characteristics of the battery are yielded. T h i s voltage control allows reduction o f the energy consumption and this in turn reduces the cost per km distance range of the electric vehicle. F r o m the above, i t becomes clear that charging of batteries for electric vehicles cannot be carried o u t w i t h ordinary charging devices. M o d e r n chargers should be programmable, w i t h built-in m i c r o p r e cessors and various sensors t o allow o p t i m u m charging depending o n the instant state o f the battery. T h i s is especially important for maintenance-free batteries. The charger should possibly be i n stalled in the electric vehicle itself, which would allow recharging of the battery at any point of i t s route, provided there is power supply available. T h i s battery charger is n o t t o o heavy, about 20 kg against 1600 kg vehicle weight [l], would n o t degrade i t s performance and parameters. One way of shortening the charging t i m e may be the so-called fast battery-to-battery charge [16]. In this case, a stationary battery pack, which has been previously recharged at a l o w rate, is used as the source of electrical energy for a rapid charge of the vehicle battery. Charging takes about 20 min when the source battery has a voltage 20% higher than the rated value. For this type of fast battery-tobattery charge, 25530% more energy is needed than for the normal fast battery charge.

In the West German M a n n B u s program [15], the so-called bibberonnage charging cycles have been demonstrated. W h i l e waiting at the bus stop for passengers t o get on, a quick high-current charging pulse is passed t o the battery of the electric driven bus. In this way, partial charging of the battery is achieved, and i t s distance range is extended. According t o the test results obtained, the batteries of the
electric bus have performed well even after a hundred thousand bibberonnage charging cycles. T h e effect o f these strong current pulses o n battery life has n o t yet been fully elucidated.

126

Bozek et al. [17] have determined the effect of pulsed discharge o n the specific energy and power of a battery (Fig. 9). It was found

that pulsed discharge l i m i t s the energy provided by the battery at


l o w specific power.

i r

40

I
L

Ha

._
c

U ._

rl)

20

IO

specific e n e r g y , Wh kg-

Fig. 9. Energy and power delivered by a lead-acid battery during pulseand constant-current discharge [4]. Analyses of the performance of lead-acid batteries as energy source for electric vehicles have shown that the primary factor responsible for t h e decline of battery parameters and for t h e end of b a t t e r y service life are the heavy, though short-term, peak power loads it is subjected to during high acceleration driving (on starting and overtaking). It is considered t h a t charging methods, duration of rest periods, etc., do not have such an impact o n battery cycle life

[is].
127

There are contradictory data about the effect of temperature on battery cycle life [19, 201. i t i s generally accepted however that bat-

k r y failure depends on t h e temperature conditions of service. So b a t t e r y failure at l o w temperature operation i s due both to irreversible sulfatization of a few positive plates and t o morphological changes in t h e positive active mass. At high temperature, t h e failu r e i s associated with negative plate deterioration and positive grid corrosion [ X I ] . A s t o the decline in negative plate capacity during cycling, it i s assumed that t h e basic reason for t h i s is passivation of t h e plate

[21]. Continuous refinement of t h e grain structure of t h e PbS04 cryst,als with cycling, worsening of the contact between t h e particles of t h e negative active mass, and impeded electrolyte diffusion are also factors causing the plate capacity to decrease.

4.Types o f cycles o f electric vehicle batteries


T h e energy performance of an electrochemical power source depends on a number of factors among which discharge current, temperature and riiimber of charge-discharge cycles are of primary importaiice. Figure 10 shows t h e capacity curve of a lead-acid battery as a function of discharge current and temperature

[il.

It i s evident f r o m t h e figure that t h e higher t h e discharge current and t h e lower t h e t,emperature, t h e smaller t h e amount, of energy delivered by t h e battery.

In electric vehicle applications, batteries operate under complex temperature conditions. Owing to the high discharge and charge currents, considerable amounts o f Joule heat are released. Conventional b a t t e r y constructions, as a rule, hamper emission of t h i s heat i n t o t h e atmosphere, and hence t h e temperature of t h e cells may rise t o unacceptable levels. On the other hand, low b a t t e r y temperatures lead t o a sharp decrease in energy performance. T h i s calls for t h e need for an adequate heating system that would provide p r e h e a t i n g of t h e battery a,t low surrounding temperatures,

128

Fig. 10. Dependence of b a t t e r y c a p a c i t y o11 discharge c u r r e n t and ternperature

[il.

and cooling of t h e cells t o prevent overheating as well as t o allow utilization o f t h e released heat (during charge and discharge) for warming of t h e car interior during winter. A fairly sophisticated syst e m of t h i s kind has been dcveloped for t h e VW-Golf CityCTROMers
electric car

[il.

T h e dynamic characteristics of t h e electric vehicle are determined by t h e power performance of t h e battery used for propulsion. Power

output depends on t h e state of discharge of t h e battery arid usually degrades rapidly near t h e end of battery cycle life.
Figure 11 illustrates t h e dependence o f t h e battery specific power on t h e d e p t h of discharge (DOD) [22].

As seen in t h e figure, an abrupt decline in b a t t e r y specific power


i s observed beyond 50% DOD. T h i s complex multi-factor dependence of b a t t e r y energy and power performance on t h e one hand, and t h e diverse road and c i t y

driving conditions of t h e electric vehicle on t h e other hand, make

129

M1 0 O

I I I

0 2 0 4 0 6 0 8 0 1 0 0 Depth of discharge, */.

F i g . 11. Specific power vs. d e p t h of discharge

characterization o f the system electric vehicle/battery extremely difficult. Worldwide there is n o unified standard for testing o f batteries for electric vehicle applications. A wide spectrum o f test profiles are in use, from simple constant current discharge, through velocity profile,

up t o the fairly complicated real-world driving profiles. Some of these test procedures are aimed at characterizing the battery as a power source, arid other tests attempt t o determine battery behaviour under conditions as close as possible t o real traffic. T h e former test profiles, oriented t o specifying battery parameters] are similar t o traction battery test procedures and hence will n o t be discussed here. As t o the second category of test profiles, targeted at determining the battery behaviour during EV operation] four testing standards w i l l be described here - the US standard SAE J 227a1 C [3,23], the European test cycle ECE [1,23], the Simplified Federal Urban Driving Schedule (SFUDS 79) [24], and t h e Electric Vehicle Battery Test Cycle (EVBTC) [23].
130

T h e first t w o test procedures, SAE J 227a, C (Fig. 12) and ECE (Fig. 13) have been developed o n the basis of the so-called velocity profile.

Time, s

Fig. 12. SAE J 227a, C v e l o c i t y p r o f i l e [3].

Time. s

Fig. 13. ECE v e l o c i t y p r o f i l e

[il.

T h e above test procedure is based o n the dynamics of electric vehicle velocity including starting, accelerating up t o a definite speed, cruise-driving at t h i s speed for a certain period of time, decelerat-

ing, at a definite rate, t o zero velocity, and standstill period. In

131

SAE J 227a, C, one such test cycle is adopted with acceleration rate of 0.74 m s - ~ , speed of 50 km h-', deceleration rate at braking 1.23 m s - ~and overall duration of the test cycle 80 s [3]. T h e

ECE test standard envisages three test cycles w i t h more complex


variations of speed and acceieration. For the sake o f simplicity, only t h e maximum speeds of the three test cycles w i l l b e mentioned here. These are resp. 15, 32 and 50 km h-' [23]. Test procedures based o n velocity profiles are relatively simple

and easy t o implement, because they are reduced t o driving the vehicle at a definite speed. These tests can be regarded as oriented t o t h e vehicle as a system in m o t i o n rather than t o the system vehicle/battery. On the basis of t h e results obtained f r o m these tests,

it is very difficult t o compare various types of electrochemical power sources for EV applications, especially so i f the tests are performed
on different cars.

A summary of the specific power characteristics determined v i a these tests is presented in Fig. 14 for SAE J 227a, C, and Fig. 15 for ECE [23].

O Time.s

Fig. 14. SAE J 227a, C battery power profile [23]

132

3
Tlme. s

Fig. 15. ECE battery power profile [23].

It can be seen that these characteristics are rather complex, especially in Fig. 15, which makes interpretation and analysis of results
w i t h respect t o battery performance very difficult. W h e n in operation, t h e electric vehicle requires a definite power level irrespective o f the instantaneous state of the power source. B a t tery power can b e determined by measuring t h e current at constant battery voltage. Voltage Characteristics, however, depend o n a number of factors, e.g. battery type, depth of discharge, number of cycles, temperature, etc., and hence, current profiles cannot characterize

fully the dynamic performance of the electric vehicle. Thus, for example, at constant power battery discharge, near the end of discharge
when the voltage is low, the discharge current grows considerably, i.e. the battery is subjected t o more severe operating conditions as compared t o those at constant-current discharge. Under these more severe conditions, the battery capacity is reduced and hence also i t s energy output. However, these conditions are closer t o the real driving situation.

133

An example of a power profile test of an electric vehicle i s the Simplified Federal Urban Driving Schedule (SFUDS 79) illustrated
in Fig. 16 [23,24]. Figure 17 gives the driving speed according t o

SFUDS 79.
-780
2

rn

? 60

[
U

40

< 20
& O

- 20

60

120

180uom360
Time, s

Fig. 16. SFUDS 79 battery power p r o f i l e [24].

lime, s

Fig. 17. SFUDS 79 velocity p r o f i l e [24].

In most general terms, t h e above test profile consists of five power pulses distributed in time so as t o ensure four starts and four stops of the vehicle. Overall duration of the cycle is 360 s and the distance covered i s 3100 m.
134

All the above outlined test procedures (Figs. 14, 15 and 16) include the so-called regenerative braking effect consisting essentially in the ability of the electric motor t o act as a generator of electricity o n vehicle braking (movement w i t h negative acceleration), and the utilization of t h e generated energy for charging of the battery.
In the above-mentioned figures, the energy used for battery charge is indicated w i t h a negative sign. Including regenerative braking in the test cycle w i l l increase battery capacity or, t o b e more precise, recover part of the energy delivered by the battery. On the other hand, however, strict standardization o f this t y p e of charge is n o t possible, because the features of regenerative braking differ considerably for the different types of vehicles. For these reasons, regenerative braking should b e excluded f r o m EV test schedules [23], but it m a y and should be utilized in actual vehicle operation, since electric regeneration increases the mileage of the electric vehicle between t w o full charges of the battery w i t h 18-25% [24]. W h e n regenerative braking is used, however, the charging pulses should be restricted t o current values that allow efficient charging w i t h o u t posing a threat t o battery life.

Urban driving of an electric vehicle can be characterized w i t h respect t o energy demands as follows: o n starting, when rapid acceleration should be achieved, t h e power demand is very high; then a period of constant speed cruise follows and the respective power demand is low; this speed is then maintained until the next stop. Based o n this simplified driving profile representation, t h e Electric Vehicle B a t t e r y Test Cycle (EVBTC) has been developed [23], presented in Fig. 18.
T h i s test cycle comprises two power pulse steps w i t h o u t regenerative braking. Overall duration of t h e cycle i s 100 seconds. T h e spectrum of speed characteristics covered by the EVBTC is presented in Fig. 19. It is seen that this test procedure is performed w i t h i n a fairly wide bandwidth of speeds including starting and braking, as well as driving at varying speed w i t h o u t stopping.

135

Time, s

Fig. 18. EVBTC battery power p r o f i l e (231

Tim. s

Fig. 19. EVBTC vehicle speed characteristics [23].

T h e degree of compliance between the above test cycles and the real urban driving conditions has been examined using a CityS T R O M e r (VW-Golf) electric vehicle as a reference [23]. T h e results obtained are presented in Fig. 20 and Table 12.

136

_.......... .,

Urban driving (recorded)


S E J n?a. C

_____ ECE

SFUDS

--- EVBTC

20

40 60 Cumulative time, ' / e


8s.

1 I

Fig. 20. Specific battery power

cumulative time for various test profiles

in comparison t o urban driving [23].

Table 12. Characteristics of various t,est cycles 1231.


Test

Average power W kg-'

Required max. power W kg-'

Standstill period

Degree of compliance

%
100 90 85 85 95

Urban driving, recorded SAE J 227a, C ECE SFUDS 79 EVBTC

15.5
11.1 9.0

53 60
43

30 53
44

11.8 15.6

79 50

42 30

137

T h e above comparative results show that, in all characteristics, the EVBTC test procedure reflects real EV operation in urban driving conditions w i t h a highest degree of accuracy. A m a j o r advantage of EVBTC is t h a t it yields reproducible and comparable informat i o n o n energy utilization and lifetime, irrespective o f the type and size of battery system used. The fairly complex and diverse conditions o f real EV operation require constant battery monitoring and control. The latter should perform the following functions: provide information about t h e state-of-charge, respectively o f discharge, of the battery and about the remaining driving range until full battery discharge; indicate near end of discharge; signal and prevent battery f r o m operation under abnormal conditions; prevent overpolarization of individual cells; indicate excessive temperature rise; ensure proper and complete battery charging; monitor gas evolution; prevent dangerous pressure rise in the cells, etc. These complex monitoring and control functions cannot be accomplished only by voltage, current and temperature measurements. A number of sensors are needed as well as a microprocessor t o collect and process the acquired information, compare the obtained results w i t h the normal EV operation data, signal or interrupt vehicle operation at noted discrepancy between the specified and the measured values of the parameters under test. Such a sophisticated multifunction control system is n o t available yet, but would probably be developed when large-scale product i o n of electric vehicles commences. Since electric vehicles operate under considerable current loads, reliability of cabling and terminal connections is of utmost importance. Mis-rated and over-long electric conductors, and poor contacts w i t h the power source and the consumer, may lead t o considerable power losses and hence impair electric vehicle performance. These electrical contacts should, therefore, be periodically checked or included in the control system.

138

R e q u i r e m e n t s of t h e construction and m a n u f a c t u r i n g technology o f b a t t e r i e s for EV energy storage systems

5.

A s a rule, lead-acid batteries used for electric vehicle propulsion have a modular construction. These modules are usually 6 V tract i o n batteries consisting of three storage cells housed in a plastic case w i t h a common cover, and intercell through-the-wall connectors. T h i s battery design yields a relatively h i g h specific power out-

put (30-35 Wh kg-'). Chloride Silent Power [6] has developed an advanced tubular plate lead-acid battery w i t h h i g h specific energy (37.7 Wh kg-') and specific power (112 W kg-').. T h e capacity of the modular battery is 167 Ah at unit module weight of 32 kg. Utilization of non-hermetic electrochemical power sources with aqueous electrolytes (e.g. lead-acid and alkaline batteries) requires constant monitoring of the electrolyte level in each battery cell and replenishment w i t h distilled water when necessary. Filling up is one of the maintenance procedures most often underestimated and neglected by drivers, and leads t o drying of individual battery cells and hence shortening of battery cycle life. T o prevent this, single point watering systems have been developed [6] for monitoring electrolyte levels and refilling w i t h water when needed. On.charging of aqueous electrolyte batteries, evolution of hydrogen and oxygen occurs. These two gases f o r m an explosive mixture which requires special safety measures t o prevent explosion of the vehicle. There are two possible solutions t o this problem. First, by designing a common gas vent system t o collect all gases released from the individual cells, and l e t t h e m o u t i n t o the atmosphere. T h i s gas vent system can be combined w i t h the refill and cooling battery systems, an approach adopted by U n i o n Globe Co., in the USA [3]. Second, by the introduction of maintenance-free batteries w h i c h are of special interest for electric vehicle propulsion applications. These

139

batteries utilize lead-calcium alloys and fumed silica gelled electrolyte or glass mat separators immobilized electrolyte. An oxygen cycle is employed w i t h these batteries t o stop the electrolysis of water and the evolution of oxygen and hydrogen. A s evidenced by a number of investigations, hydrogen gassing cannot b e completely eliminated in maintenance-free lead-acid batteries, i.e. these batteries cannot be sealed. They are usually equipped w i t h a safety valve that controls the pressure in the cells, and when the pressure rises, the valve is opened and the accumulated gases are released f r o m the cell. The use o f a restricted amount of electrolyte, however, decreases battery energy performance slightly. Thus, a gelled-electrolyte battery developed for the VW Rabbit Sedan [6] has a specific energy of 26 Wh kg-' and specific power of 95 W kg-'. T h e m a j o r advantages of the maintenance-free batteries are [6]: 0 n o battery watering or checking of electrolyte level required (this saves 1 hour per 100 km for each vehicle oprated); o greatly reduced hazard of hydrogen explosion; o reduced energy consumption because of less requirement for overcharge; a reduced maintenance of t h e battery ventilation system; o improved cold weather performance displayed by sealed batteries.

During battery operation, electrolyte density undergoes cyclic changes resulting in i t s stratification, the denser electrolyte flowing
d o w n t o the b o t t o m part of the plates and the lighter one floating over it. T h e electrochemical activity of the cells and their capacity t o accumulate energy are higher in their upper parts than in the lower ones. At the b o t t o m of the cells, where the acid concentrat i o n i s highest, full charging o f the plates is impeded, they undergo sulfatization which in turn decreases battery capacity. T h i s capacity loss i s about 1% for each 0.01 g cmP3 difference between t h e acid concentration at the t o p and at the b o t t o m o f the cell [25).

140

Various methods for destratification of the electrolyte have been developed. T h e simplest consists in provoking intense gassing at the end of battery charge t o stir the electrolyte. T h i s can b e achieved by applying an appropriate current or by adding high-current pulses t o the charging current. T h i s method, however, turned out t o lack efficiency. I t cannot be applied t o maintenance-free batteries. Mechanical stirring o f the electrolyte, n o t related t o the charging current, has proved t o be most effective. T h i s method has been implemented successfully by Johnson Controls Inc., in the USA, where an electrolyk circulation system has been developed [26]. T h i s system uses a small, b l o w molded, insert pump w i t h n o moving parts, which i s designed t o maximize reliability and heat-sealed i n t o each ce11 of the battery module as part of the final assembly operation. During cycling, a low-pressure air pulse o f predetermined volume i s forced i n t o the insert pump, collecting higher density electrolyte f r o m the b o t t o m of the cell stack and dispersing it across the top of the cell. On the basis of the above electrolyte circulation system, a lightweight container and a single point watering system, an Improved State of the Art

(ISOA) lead-acid battery has been developed [27]. The results f r o m testing of the battery are presented in Table 13.
T a b l e 13. Performance of lead-acid batteries for EV Performance parameter Specific energy (Wh kg-') P o s i t i v e active mass u t i l i z a t i o n - (Ah kg-')
-

Golf car b a t t e r y (1978)

ISOA EV-3000

FFLA

23 63.9 28.5 250'

42 72.7 32.4 508'

52.4 126.7 56.5 130"

Cycle life

* based o n SFUDS 79 ** based on 80% DOD c y c l i n g

141

T h e ISOA battery showed a 46% higher specific energy and 80% longer cycle life t h a n the conventional lead-acid battery. Besides, the ISOA battery offered the advantages of reduced overcharge and water addition requirements, and improved system thermal management. In the ISOA battery, simple circulation o f the electrolyte between the plates and the separators is achieved w i t h o u t affecting the active mass. By forcing the electrolyte i n t o the electrodes, more active material sites w i l l be accessed, which w i l l result in enhanced active material utilization and improved system specific energy. Johnson Controls Inc. have developed such a battery system, called the FFLA (Forced F l o w Lead-Acid) battery [Z']. The demonstrated performance results of this battery are given in Table 13. I t can be seen

that the specific energy and the active mass utilization of the FFLA battery are considerably higher than those of the ISOA system. From the data presented in Table 13, it is difficult t o predict the life span of these batteries. It can be expected however that their cycle life w i l l be significantly reduced through mechanical deterioration of the active mass caused by forcing the electrolyte i n t o the electrodes. T h e relative complexity of the system including battery, pumps and electrolyte circulation tubes should also be given consideration.

6 . Specification o f operating energy storage systems for electric vehicles


Classification of electric vehicles is very difficult, because on the road electric vehicles are mostly demonstration prototypes employing various power sources w i t h different design and dynamic performance parameters. T h i s is well illustrated in Table 14 presenting comparative d a t a for several EV types. Despite the fact that many of the problems facing electric vehicles are n o t solved yet, a l o t of countries are planning t o start large-scde

142

rn

I m 2 -m Z 8

I
I i

* iO l
Hl I I
m
O
01 01

o * m m m t -

I
I N

cu

5
3

ci

*
3 u ? d i3

e
-t
?-

a
4 L-

143

production o f these vehicles. In the USA, design and development o f an electric G - V a n is planned, driven by Chloride tubular lead-acid batteries [25]. Peugeot intends t o manufacture an electric car com-

mercially using Ni/Cd batteries. In Switzerland, a number of manufacturers and importers have capitalized o n high-profile EV races and exhibits. A purpose-designed postal van has been brought up t o the production stage in Finland. In the UK, W and E Electric Vehicles has developed and implemented a standard E V conversion package which can convert any internal combustion engined vehicle t o electric power. Fifteen electric vehicles t o o k p a r t in the demonstration The Twelve Electric Hours of Bruges, Belgium, t o show that electric vehicles could be a solution for urban traffic related problems [29].

7. Lyrical epilogue
L o o k around, dear reader! You w i l l see many, many cars that have occupied the streets, and even the sidewalks, of all big cities in the world. Their powerful engines of 40-60-100 and more kilowatts allow them t o whizz past at a reckless speed. But, instead, most often y o u w i l l see them creeping one after the other in hundreds, entrapped in the next traffic jam. If you look inside the car, y o u w i l l see a SINGLE self-satisfied or more often extremely nervous person. W h a t a wasteful and irrational world we are living in! A world conscious only o f i t s present self, w i t h n o thought for i t s tomorrow.

And this tomorrow is in our hands: we are obliged t o think about the future and t o safeguard it for our children and for generations t o come. We must give up this madness of driving super-powerful cars,
and our only salvation is the small, lightweight, two-seater, noiseless, environmentally safe and cheap ELECTRIC VEHICLE.

144

References:

1.

E. Sauer, Elektroauto, Verlag TU\. Rheinland, Kln, 1985.


Anon. Electric Vehicle Prog. 10 (1988) 3

2. 3.

V.A. Shtetin, U.J. Mortowskij, B.I. Tsenter, W.A. Bogomazov, Elektromobil: Technika i Ekonomika, (V.V. Burkov, ed.) Leningrad 1987 (in Russian). A. Aldous, in Power Sources for Electric Vehicles (B.D. M c N i c o l and D.A.J. Rand, Eds.) Elsevier, Amsterdam, 1984, p.47. C.P. Peyriere, Proc. 9th Int. Electric Vehicle Symp., EVS88- P16, Toronto, Canada, 1988.
K.F. Barber, S.K. Takagishi, ibid. EVS88-073.

4.

6.
7.

A. de Guilbert, ibid. EVS88-Pl5. C. Madery, J.L. Liska, ibid. EVS88-051. N.P. Fitzpatrick, D.S. Strong, ibid. EVS88-001.
H. Nakao, Y. Suzuki, M. Okawa, ibid. EVS88-042. L.B. Taylor, D.T. Fouchard, ibid. EVS88-023. F.E. Zhao, Y.Y. Hu, Electric Vehicle Develop., 8 (1989) 21 K.R. Ramachandran, S.C. Chopra, Proc. I L Z I C Silver Jubilee Conf. Pb, Zn and Cd into t h e gos, New Delhi, 1988, p.2.

8. 9. 10.
11.

12. 13.

14.

E.Z. Ratner, G.L. Henriksen, C.J. Warde, Proc. 9th Intl. Electric Vehicle Symp., EVS88-011, Toronto, Canada, 1988. W.J. Dippold, ibid. EVS88-022.

15.

16.

H.P. Schoner, L.L. Ogborn, J. Power Sources, 21 (1987) 91.

145

17.

J. M. Bozek, J.J. Smithrick, R.L. Cataldo, J.G. Ewashinka, E V 80, Report No. 8014, Electric Vehicle Council, Washington, 1980.
Expo

18.

J.

Lee,

J.F.

Miller,

C.C. Christianson,

J. Power Sources,

24 (1988) 215.

19.

M. Peohler, H.A. Kiehne, Die. Antrzebsbatterie, VDI-Verlag, VARTA,


Hannover,

1980, p.7.

20.

D.C. Constable, J.R. Gardner, E;. Harris, R.J. Hill, D.A.J. Rand, L.B. Zalcman, J. Electroanal. C'hem., 168 (1984) 395. C.P. Wales, S.M. Caulder, A.C. Simon, J. Electrochem. Soc., 128 (1981) 236. W.C. Spindler, R.L. Driggans, C.C. Christianson, Proc. 9th Int. Elect r i c Vehicle Symp.. EVS88-032, Toronto, Canada, 1988.
F.H. Klein, U. Wagner, ibid. EVS88-077.

21.

22.

23.
24.

G.H. Cole, ibid. EVS88-078. W.G. Sunu, B.W. Burrows, in Power Sources 8 (J. Thompson, ed.), Academic Press, 1981, p.601. U Patent 4 221 847. S M.G. Andrew, P.A. Budney, J.L. Heder, Proc. 9th Int. Electric Vehicle Symp., EVS88-002, Toronto, Canada, 1988.
Anon. Electric Vehicle Anon. Electric Vehicle
PTOgT.,

25.

26. 27.

28. 29. 30.

12 (1990) 1.

PTOgT.,

11 (1989) 1.

J. Angelis, D. Sedgwick, Proc. 9th Int. Electric Vehicle Symp., EVS88-009, Toronto, Canada, 1988.

ISSUED WITHIN THE SAME SERIES:

Technical Report No. 1: &tate of Research and Future Trends in Energy Storage Materials: Solid State lonics and Related Devices.. Technical Report No. 2: <<Aperu rsultats et des persdes pectives des recherches scientifiques et mdicales en vue de la prvention et du traitement du SIDAV. TeXHLlW?cKLlfi AOKJlaA N 2: 0630p pe3yilbTaTOB M ie pC ie KT M B Hay Hb IX Mefl M 4 M HC K MX M C C J l el l AoeaHMR no npeAoTspatqeHMto M neqeHMto CnuiAAB. Technical Report No. 3: Report of the Working Party on Brain Drain Issues in Europe,,. Technical Report No. 4: <<Report the Advanced Seminar of on Economic and Legal Aspects of Pollution Abatement Strategies in Europe.. Technical Report No. 5: Conference on Clean Coal Technologies)). Technical Report No. 6: Proceedings of the International Symposium on Virology, Immunology and Society..

Finito di stampare ne1 mese di novembre del 1991 press0 la Tipo- Litografia Armena di San Lazzaro - Venezia