Académique Documents
Professionnel Documents
Culture Documents
R.C.C
R.C.C.B.s fourfour-pole LEXIC
PAGES
Symbol :
Pollution degree :
.2
Technology :
Product range :
Rated current :
25 / 32 / 40 / 63 / 80 A
Sensitivity :
Type :
. Uimp = 6 kV
. 400 V ~ - 50/60 Hz
. - 25C / + 40C
Insulation voltage :
. Ui = 500 V
Operation at 400Hz :
. Do not operate
Dielectric strength :
. 2000 V 50 Hz
Insulation resistance :
. 2 M
Updated : 05/09/06
Created : 05/09/06
1/8
R.C.C
R.C.C.B.s fourfour-pole LEXIC
(continued)
(continued)
. By device loaded at In
In
25 A
40 A
63 A
80 A
30 mA 25 and 40 A Type A
and AC
All others :
11 W
24 W
--------36.5 W
--------50 W
8.5 W
14.5 W
0.38 kg
Volume
Packaging
0.7 dm3
par 1
type
U mini
U maxi
30 mA
all
195 V *
440 V
100 mA
all
230 V
440 V
300 mA
A / AC
215 V
440 V
300 mA
230 V
440 V
300 mA
Hpi / G
190 V *
440 V
500 mA
A / AC
295 V
440 V
500 mA
230 V
440 V
500 mA
Hpi / G
210 V
440 V
Protection degree :
Updated : 05/09/06
Created : 05/09/06
2/8
R.C.C
R.C.C.B.s fourfour-pole LEXIC
1. ELECTRICAL
ELECTRICAL AND MECHANICAL CHARACTERISTICS
(continued)
IN
OUT
Mecanism lock
Plug-in
Contacts
Handle
Test bottom
Polarized relay with shield plate
Core subassembly
Terminals
Updated : 05/09/06
Created : 05/09/06
3/8
R.C.C
R.C.C.B.s fourfour-pole LEXIC
2. INSTALLATION
2. INSTALLATION (continued)
Fixing :
installation software:
software:
. XL PRO
Supply :
Auxiliaries clipped
clipped on the leftleft-hand side of the R.C.C.B.s
R.C.C.B.s
Auxiliaries list :
Connection :
Signalisation auxiliaries:
auxiliaries:
Tightening torque :
Wire :
Without ferrule
Rigid cables
With ferrule
ou
1 x 0,75 35 mm
1 x 0,75 25 mm
2 x 0,75 16 mm
Wiring accessories :
Sealing
Sealing :
Locking :
ou
Tools required :
Control auxiliaries :
3. STANDARDS
1 x 0,75 50 mm
2 x 0,75 16 mm
Flexible cables
4. RESPECT OF ENVIRONMENT
ENVIRONMENT
Compliance with European Union Rules :
Plastic material :
Packaging :
Marking :
Updated : 05/09/06
Created : 05/09/06
4/8
R.C.C
R.C.C.B.s fourfour-pole LEXIC
5. OVERALL DIMENSIONS
45mm
83mm
93mm
70mm
44mm
60mm
76mm
71.2mm
6. MARKING
Front face marking : by permanent pad printing.
Im =5 00A
400 V
I m =1000A
I n=0,03 A
10000
TEST
30mA
Frquent
Frequently
Updated : 05/09/06
Created : 05/09/06
5/8
R.C.C
R.C.C.B.s fourfour-pole LEXIC
8. ASSOCIATION
ASSOCIATION WITH UPSTREAM PROTECTION
Protection
Protection against shortshort-circuits :
. 400/415 V three phases + neutral network : Maximum value of short-circuit withstand of R.C.C.B.s in terms of associated protection
downstream
R.C.C.B
upstream
M.C.B.
DX
DX-h
DX-L
DPX 125
25 A
10 kA
20 kA
50 kA
25 kA
32 / 40 A
10 kA
15 kA
50 kA
25 kA
63 A
10 kA
12.5 kA
50 kA
25 kA
80 A
10 kA
12.5 kA
50 kA
25 kA
downstream
upstream
R.C.C.B
gG FUSE
Rated current
25 A
40 A
63 A
80 A
25 A
100 kA
100 kA
50 kA
15 kA
32 / 40 A
100 kA
100 kA
50 kA
15 kA
63 A
100 kA
100 kA
50 kA
15 kA
80 A
100 kA
100 kA
50 kA
15 kA
Updated : 05/09/06
Created : 05/09/06
6/8
R.C.C
R.C.C.B.s fourfour-pole LEXIC
TYPE AC
1
T (s)
0.5
30 mA
100
100 mA
300 mA
500
500 mA
0.1
Type S
0.05
Type G
Type Standard
0.01
100
101
102
Updated : 05/09/06
103
I (mA)
104
Created : 05/09/06
7/8
R.C.C
R.C.C.B.s fourfour-pole LEXIC
LEXIC
9. RESIDUAL CURRENT
CURRENT TRIPPING CURVES (continued)
Curve of tripping time in terms of residual current
TYPE A
1
T (s)
0.5
100
100 mA
300 mA
500
500 mA
0.1
30 mA
Type S
0.05
Type Hpi
Type Standard
0.01
100
101
102
Updated : 05/09/06
103
I (mA)
104
Created : 05/09/06
8/8
9/8