Académique Documents
Professionnel Documents
Culture Documents
Qs
QL
27200
27200
2346
680
156
300
345
435
312.5
312.5
2550
33889.5 27947.5
QT
54400
2346
680
156
300
780
625
2550
61837
Qs
1 refrigerador de 2 puertas
1 bao mara caliente
1 chichera
1 freezer pequeo
2 lmparas de 4 tubos (75 watts c/tubo)
2 personas
1 mquina expendedora de soda
5083
26765
1094.2
1251.2
2550
690
156
37589.4
QL
QT
5083
35000
1094.2
1251.2
2550
870
1560
156
9105 46694.4
8235
COMEDOR
Btu/hr
EQUIPOS
1 microondas
2 fuentes de agua
84 personas
10 lmparas de 4 tubos (75 watts c/tubo)
Qs
5222.4
6000
21420
12750
45392.4
QL
QT
5222.4
6000
27300
48720
12750
27300 72692.4
OFICINA 1
Btu/hr
EQUIPOS
Qs
1 monitor y 1 CPU
1 impresora
1 sumadora
2 lmparas de 4 tubos (75 watts c/tubo)
2 personas
QL
3060
163.2
24.48
2550
460 380
6257.68 380
QT
3060
163.2
24.48
2550
840
6637.68
OFICINA 2
Btu/hr
EQUIPOS
Qs
1 monitor y 1 CPU
1 fax
1 impresora
1 sumadora
1 lmparas de 4 tubos (75 watts c/tubo)
1 persona
QL
3060
326.4
163.2
24.48
1275
230 190
5079.08 190
QT
3060
326.4
163.2
24.48
1275
420
5269.08
OFICINA 3
Btu/hr
EQUIPOS
2 monitores y 2 CPU
1 impresora
1 mquina de escribir elctrica
conexin en red
1 sumadora
2 lmparas de 4 tubos (75 watts c/tubo)
3 personas
Qs
QL
6120
408
126.48
391.68
24.48
2550
690 570
10310.64 570
QT
6120
408
126.48
391.68
24.48
2550
1260
10880.64
Qs
QL
QT
1275
230 190
1505 190
1275
420
1695
DEPOSITO 1
Btu/hr
EQUIPOS
1 lmparas de 4 tubos (75 watts c/tubo)
1 persona
1 sumadora
Qs
QL
QT
1275
230 190
24.48
1529.48 190
1275
420
24.48
1719.48
DEPOSITO 2
Btu/hr
EQUIPOS
2 lmparas de 4 tubos (75 watts c/tubo)
1 persona
Qs
QL
2550
230 190
2780 190
QT
2550
420
2970
Q= UxAxDTCEc
DTCEc = [(DTCE LM)*K + (78 tR) + (to 85)]*f
-Pared Norte
U = 0.263; A= 662.08 ft2, to = 83 F
DTCE = 19 F, LM = -3, K = f = 1, tR = 75 F
DTCEc = 17 F
QT = (0.263)(662.08 ft2)(17 F)
QT = 2960.16 Btu/hr
-Pared Sur
U = 0.263; A= 594.1 ft2, to = 83 F
DTCEc = 10 F
QT = (0.263)(594.1 ft2)(10 F)
QT = 1562.48 Btu/hr
-Pared Este
U = 0.263; A= 476.16 ft2, to = 83 F
DTCE = 36 F, LM = -1, K = f = 1, tR = 75 F
DTCEc = 36 F
QT = (0.263)(476.16 ft2)(36 F)
QT = 4508.28 Btu/hr
-Pared Oeste
U = 0.263; A= 545.2 ft2, to = 83 F
DTCE = 28 F, LM = -1, K = f = 1, tR = 75 F
DTCEc = 28 F
QT = (0.263)(545.2 ft2)(28 F)
QT = 4014.85 Btu/hr
CUARTO DE HIELO:
Tabla A-8: U = 1.04; A= 22 ft2, to = 83 F
Tabla 6.5: DTCE = 13.5, tR = 75 F
DTCEc = DTCE + (78 tR) + (to 85)
DTCEc = 13.5 + (78 75) + (83 85)
DTCEc = 14.5 F
Qv.K. = (1.04)(22 ft2)(14.5 F)
Qv.K. = 331.76 Btu/hr
DE
VENTANAS
COMEDOR:
Tabla A-8: U = 1.04; A1 = 154 ft2, to = 83 F
Tabla 6.5: DTCE = 13.5, tR = 75 F
DTCEc = DTCE + (78 tR) + (to 85)
DTCEc = 13.5 + (78 75) + (83 85)
DTCEc = 14.5 F
Qv.1. = (1.04)(154 ft2)(14.5 F)
Qv.c. = 2322.32 Btu/hr
OFICINA 1:
Tabla A-8: U = 1.04; A= 11 ft2, to = 83 F
Tabla 6.5: DTCE = 13.5, tR = 75 F
DTCEc = DTCE + (78 tR) + (to 85)
DTCEc = 13.5 + (78 75) + (83 85)
DTCEc = 14.5 F
Qv.OF.1. = (1.04)(11 ft2)(14.5 F)
Qv.OF.1. = 165.88 Btu/hr
OFICINA 2:
Tabla A-8: U = 1.04; A= 11 ft2, to = 83 F
Tabla 6.5: DTCE = 13.5, tR = 75 F
DTCEc = DTCE + (78 tR) + (to 85)
DTCEc = 13.5 + (78 75) + (83 85)
DTCEc = 14.5 F
Qv.OF.2. = (1.04)(11 ft2)(14.5 F)
Qv.OF.2. = 165.88 Btu/hr
OFICINA 3:
Tabla A-8: U = 1.04; A= 22 ft2, to = 83 F
Tabla 6.5: DTCE = 13.5, tR = 75 F
DTCEc = DTCE + (78 tR) + (to 85)
DTCEc = 13.5 + (78 75) + (83 85)
DTCEc = 14.5 F
Qv.OF.3. = (1.04)(22 ft2)(14.5 F)
Qv.OF.3. = 331.76 Btu/hr
A= 22 ft2
A= 22 ft2
COMEDOR:
-Ventana Oeste:
Tabla 6.6: FGCS = 241 Btu/hr.ft2;
Tabla 6.7: CS = 0.55
Tabla 6.8: FCE = 0.72
QO = (241)(88 ft2)(0.55)(0.72)
QO. = 8398.37 Btu/hr
A= 88 ft2
- Ventana Este
Tabla 6.6: FGCS = 241 Btu/hr.ft2;
A= 66 ft2
OFICINA 1:
Tabla 6.6: FGCS = 241 Btu/hr.ft2;
A= 11 ft2
OFICINA 2:
Tabla 6.6: FGCS = 37 Btu/hr.ft2;
Tabla 6.7: CS = 0.55
Tabla 6.8: FCE = 0.82
Q = (37)(11 ft2)(0.55)(0.82)
Q. = 183.56 Btu/hr
A= 11 ft2
OFICINA 3:
Tabla 6.6: FGCS = 37 Btu/hr.ft2;
A= 22 ft2
REA DE SERVIR:
U = 0.47; A= 20.7 ft2, to = 83 F, DT = 10 F
Q = (0.47)(20.7 ft2)(10 F)
Q. = 97.29 Btu/hr
COMEDOR:
U = 0.47; A= 37 ft2 * 2 PUERTAS, to = 83 F, DT = 10 F
Q. = 591.26 Btu/hr
3360CFM
A/A
3
CAFETERIA
HR = 50 %
BS = 75 F
3360CFM
CFM 3 =
203748.06 BTU/HR
= 9261.3 CFM
1.1 x 20
(3360)(92) + (5901.3)(75) = 81 F
9261.3
BS3 = 55 F
REA DE SERVIR:
Q = 601.22 BTU/HR
COMEDOR:
Q = QE + QO = 2453.73 BTU/HR + 2409.21 BTU/HR
Q = 4862.93 BTU/HR
OFICINA 1:
Q = 918.40 BTU/HR
OFICINA 2:
Q = QE + QN = 568.08 BTU/HR + 314.58 BTU/HR
Q = 882.66 BTU/HR
OFICINA 3:
Q = 265.40 BTU/HR
DEPSITO 2:
Q = 2429.36 BTU/HR + 1159.39 BTU/HR
Q = 3588.75 BTU/HR
A = 129.15 ft2
Q = 938.66 BTU/HR
REA DE SERVIR:
A = 204.43 ft2
Q = 1485.77 BTU/HR
COMEDOR:
A = 2271.54 ft2
Q = 16509.53 BTU/HR
OFICINA 1:
A = 168.80 ft2
Q = 1226.80 BTU/HR
OFICINA 2:
A = 76.28 ft2
Q = 554.37 BTU/HR
OFICINA 3:
A = 106.79 ft2
Q = 776.11 BTU/HR
DEPSITO 1:
A = 160 ft2
Q = 1162.88 BTU/HR
DEPSITO 2:
A = 554.69 ft2
Q = 4031.44 BTU/HR